36C25221Q0667 0001.docx
DOCX document 26 KB Posted
- Attached to
- N030--REPLACE TWO (2) POWER DISTRIBUTION UNITS Federal contract opportunity
- Solicitation number
- 36C25221Q0667
About this file
This document is an amendment to a solicitation for the replacement of two power distribution units at a Veterans Affairs medical center. The solicitation requests the contractor provide all labor, materials, tools, and equipment necessary to replace the two PDUs located in Building 111 on the campus. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12 is the contracting agency. The amendment provides answers to questions submitted by interested offerors regarding load breakers, dual feeds allowing replacement of one unit at a time, and whether temporary power or generators would be required. Reuse of existing conduit and wiring is permitted where feasible for the new equipment. The solicitation close remains May 20, 2021 at 9:00 AM local time.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S06 ATTACHMENT - PDU block Diagram.pdf | ||
| ATTACHMENT B - VA NOTICE OF LIMITATIONS ON SUBCONTRACTING FORM.docx | DOCX document | |
| 36C25221Q0667.docx | DOCX document | |
| ATTACHMENT A - PHOTOS of PDUs.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7.
ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF
PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE
OF YOUR
ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERE
D CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES
SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR
OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendmen t, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED
STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF
CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF
SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) 05-17-2021 695-21-3-6023-2044 36C252 Department of Veterans Affairs Great Lakes Acquisition Center (GLAC) 115 S 84th Street, Suite 101 Milwaukee WI 53214-1476 36C252 Department of Veterans Affairs Great Lakes Acquisition Center (GLAC) 115 S 84th Street, Suite 101 Milwaukee WI 53214-1476 To all Offerors/Bidders
36C25221Q0667 05-17-2021
X X
X REFERENCE SOLICITATION 36C25221Q0667 FOR REPLACEMENT OF TWO (2) POWER DISTRIBUTION UNITS AT CLEMENT ZABLOCKI VA MEDICAL CENTER AND AMEND TO REFLECT THE FOLLOWING: Provide answers to questions submitted by interested Offerors (see page and attachment Solicitation close remains MAY 20, 2021 AT 9:00 AM LOCAL.
All other terms and conditions of solicitation remain the same.
CC: Contract File Susan Pasholk Contracting Officer
1. Please provide an electrical single line diagram / electrical riser for this system, showing the utility source input and UPS/PDU connected loads Line diagram is not available. Please see Attachment – PDU Block Diagram.
2. Please provide quantity and sizes for the output load breakers in the PDU sections A/C Input breaker 225a/208v – Sub-feed output breaker 225a/208v – Q1 UPS Input 600a/208v Q2 Maintenance bypass breaker 600a/208v Q3 UPS Output breaker 600a/208v. In PDU 2 there are (3) single pole 20a breakers and (6) 3 pole 20a breakers. PDU 1 has no 20a single or 3 pole breakers in the back just PDU 2. Pictures attached that shows (5) breakers that are input/output in each PDU listed in beginning of this answer.
3. Are all loads dual fed, which would allow us to replace (1) UPS/PDU at a time without a long term outage to downstream loads?
Yes, there is a transfer switch in the 3rd floor IRM room that will allow loads from both PDU’s be transferred from one to another so that one can be down at a time for maintenance/replacement.
4. Will any temporary power feeds or temporary generators be required to be provided by the contractor during this work?
No, there should be no temporary feeds or generators needed for replacement of PDU’s.
5. Are we re-using existing conduit and wiring, where feasible, with the new equipment?
Yes, we will allow re-use of any existing conduit or feeds and wiring where possible.
File details come from the government source that posted it. Updated .