DESCRIPTION
The Fireye® BurnerLogix™ System is a microprocessor based burner management control system designed to provide the proper burner sequencing, ignition and flame monitoring protection on auto-matically ignited oil, gas, and combination fuel burners. In conjunction with limit and operating con-trols, it programs the burner/blower motor, ignition and fuel valves to provide for proper and safe burner operation. Through SMART LED’S, the control provides current operating status and lockout information in the event of a safety shutdown. Optional VFD and LCD displays are available that may be either plugged in or mounted remotely to give full language descriptors of current status and diagnostic lockout information. Refer to BurnerLogix PROGRAMMER SELECTION later in this document for the various combinations of programmer and display modules.
A complete BurnerLogix system includes the YB110 (YB230) chassis equipped with the type of flame amplifier required for the application, appropriate flame detector, plug-in programmer mod-ule, wiring base and optional alpha-numeric display. Interchangeable programmer modules allow for complete versatility in selection of function, timing and flame failure response times.
The optional alpha-numeric display is made up of 2 lines by 16 characters per line and is available in either vacuum fluorescent or liquid crystal formats. The advantage of VFD is high brightness and extended temperature range to –40°F. Both displays contain a fully functional keypad allowing the user to easily scroll through the various menus to view the current operating status, review program-mer configuration, and lockout history. When mounted remotely, the displays provide NEMA
4x(IP66) protection. An advantage of the BurnerLogix control family is the ability to set many of the operating parameters associated with proper and reliable burner operation allowing inventory of var-ious programmer types to be kept to a minimum.
The YB110 (YB230) is a chassis/flame amplifier module complete with mounting screws and blank display module. The display module (BLV512 or BLL510), if required, must be ordered separately.
Interchangeable YP programmer modules allow for complete versatility in selection of control func-tion, timing, and flame scanning means. Functions such as pre-purge time, recycling or non-recy-cling interlocks, high fire proving interlock, and trial for ignition timing of the pilot and main flame are determined by the programmer module. The BurnerLogix system can be used with ultra-violet, auto-check infrared, flame rod, self-check ultra-violet flame scanners or direct coupled integrated scanners by choosing the proper chassis/flame amplifier module.
YB110/YB230 FIREYE®
BurnerLogiX™
MICROPROCESSOR-BASED
INTEGRATED BURNER
MANAGEMENT CONTROL
BL-1001
MAY 4, 2011
APPROVED
Wiring bases for the BurnerLogix control are available pre-wired with 4 foot lead wires color coded and marked for easy installation or with an integral terminal block capable of a accepting up to 2 X
14 AWG wires. The wiring base terminal block is available with knockouts for conduit or open ended for cabinet mounting. The pigtail wiring base is 4" X 5" and the terminal block wiring base is
4" X 7".
Additional functions of the BurnerLogix system include:
• A non-volatile memory which allows the control to remember its history and present position even when power is interrupted.
• A consistent flame signal read-out via display module or 4-20 mA output.
• Read-out of main fuel operational hours and complete cycles via display module.
• Modbus communications via RS485 multi-drop link.
• Proof of fuel valve closure during off cycle.
• Burn-in time of program parameters occurs after 8 hours of main valve on time.
• A run/check switch which allows the operator to stop the program sequence in any of four different positions (Purge, PTFI, MTFI or Auto).
• Remote Display mounting with NEMA 4 protection.
• Remote Reset.
• Programmable communication baud rate allows for DCS compatibility.
• Keypad selectable language readout.
• Revert to pilot can increase burner turn down.
• Additional terminals provided for applications requiring additional inputs and outputs.
WARNING: This equipment is a Class B digital apparatus which complies with the Radio
Interference Regulations, CRC c.1374.
CAUTION: While programmers are mechanically interchangeable in that they mate with a common chassis/amplifier module, you should select the correct model for your application.
Inappropriate application of a control could result in an unsafe condition hazardous to life and property. Selection of a control for a particular application should be made by a compe-tent professional, such as a boiler/burner service technician licensed by a state or other gov-ernment agency.
TABLE OF CONTENTS
BURNERLOGIX SPECIFICATIONS
PART NUMBERS AND APPROVALS
ORDERING INFORMATION
INSTALLATION PROCEDURE
WIRING BASE
PTFI*MTFI TIMINGS
LED INDICATOR LIGHTS
REPLACEABLE FUSE
DESCRIPTION OF FUNCTIONS OF OPERATING CONTROLS
SETTING PROGRAMMER PARAMETERS
KEYPAD DESCRIPTION
PROGRAM SET UP SUB-MENU
TO VIEW AND MODIFY A PROGRAMMABLE PARAMETER
FLAME SCANNERS
INSTALLATION - UV SCANNERS
OPERATION — 45UV5 & 55UV5 SELF-CHECKING UV SCANNER
WIRING - UV SCANNERS
INSTALLATION—INFRARED SCANNER TYPE 48PT2
OPERATION - IR LEARN
INSTALLATION - 69ND1 FLAME ROD
INSTALLATION - 85 SERIES PHOENIX SCANNER
INSTALLATION - 95 SERIES INSIGHT SCANNERS
SYSTEM INFO SUB-MENU
SYSTEM OPERATION
YP100 OPERATING SEQUENCE
START-UP (NORMAL CYCLE)
YP200 OPERATING SEQUENCE
YP300 OPERATING SEQUENCE
YP138 PROGRAMMER
LOCKOUTS
SAFETY SHUTDOWN
DIAGNOSTIC MESSAGES
RESETTING THE CONTROL
LOCKOUT CODES
LOCKOUT HISTORY SUB-MENU
COMMUNICATIONS
MESSAGE FORMAT
MODBUS MESSAGE TABLE
INPUTS
OUTPUTS
EXPLANATION OF LOGSTAT
BURNERLOGIX MESSAGES
INTERLOCK ANNUNCIATOR
OPERATIONAL FEATURES
4-20 mA TEST JACKS
CHECK-RUN SWITCH
OPERATIONAL TEST
TEST CHECKOUT PROCEDURES
SUGGESTED GROUNDING RULES
MAINTENANCE
BURNERLOGIX SPECIFICATIONS
Supply Voltage:
YB110 120 VAC (+10%, -15%) 50/60 Hz
YB230 230 VAC (+10%, -15%) 50/60 Hz
Power Consumption:
25 VA
Temperature Rating:
-40°C (-40°F) to +60°C (140°F)
Protection Category:
YB110 (YB230) control NEMA 1 (IP01)
Display, remote mounted NEMA 4X (IP66)
Unit Dimensions:
Wiring base 60-2810-1 - 4.0" (101 mm) W x 5.0" (127mm) H
Wiring base 60-2812-1, 60-2814-1 - 4.0" (101 mm) W x 7.0" (178 mm) H
Shipping Weight:
YB110 (YB230) Approx. 3.2 lbs. (1.45kg)
OPERATING TEMPERATURE LIMITS
CONTROL MAXIMUM MINIMUM
YB110, YB230 140°F 60°C -40°F -40°C
YP Programmers 140°F 60°C -40°F -40°C
BLV512, VFD Display 140°F 60°C -40°F -40°C
BLL510, LCD Display 140°F 60°C -4°F -20°C
Scanner UV1A, UV2, UV8A, UV90, 45UV3 200°F 93°C -40°F -40°C
45UV5-1005, 45UV5-1105
45UV5-1007, 45UV5-1009
55UV5-1007, 55UV5-1009
200°F 93°C -40°F -40°C
48PT2 140°F 60°C -40°F -40°C
Flame Rod (Tip 2460°F) 1500°F 816°C -40°F -40°C
Humidity: 90% R.H. (Non-condensing)
Phoenix 85 Series 150°F 65°C -40°F -40°C
InSight 95 Series 150°F 65°C -40°F -40°C
LOAD RATINGS:
Combination of fuel and igniter terminals
Composition of each combination
Maximum connected load not to exceed 2000 VA
ELECTRICAL RATINGS
VA ratings (not specified as pilot duty) permit the connection of transformers and similar devices whose inrush current is approximately the same as their running current.
VA Pilot Duty ratings permit the connection of relays, solenoid valves, lamps, etc. whose total oper-ating load does not exceed the published rating and whose total inrush current does not exceed 10 times the rating.
Running and locked rotor ratings are intended for motors. VA and VA Pilot Duty loads may be added to a motor load provided the total load does not exceed the published rating.
Terminal Typical Load A. Maximum Rating @120V-50/60 Hz
B. Maximum Rating @230V-50/60 Hz
C. Alternate Rating
M Burner/Blower Motor 9.8 F.L.A. * 58 L.R.A.
4.0 F.L.A. *
20 L.R.A.
240 VA Pilot Duty (Motor Starter Coil)
10-11-12-X Modulator 125 VA Pilot Duty
A Alarm 50 VA Pilot Duty
Terminal ratings may be selected from either column A or C for 120 VAC or from either column B or C for 30 VAC:
(select the rating from the column which best applies to the connected load on that terminal).
* F.L.A. = full load amps; L.R.A = locked rotor amps
Combination No. Pilot Fuel Trm 6
Main Trm 7
Ignition Trm 5
Delayed Valve Trm W
1 C E No Load No Load
2 B E No Load No Load
3 No Load E No Load B
4 E E A No Load
5 No Load E A E
6 D E A No Load
7 D D A D
8 No Load D A No Load
A B C D E
4.5A Ignition
@120 VAC
50 VA Pilot Duty plus 4.5A ignition@
120 VAC
180 VA Ignition plus motor valves with: 660 VA inrush, 360 VA open, 250 VA hold.
2A Pilot Duty
@120 VAC
65 VA Pilot Duty plus
Motor valves with:
3850 VA inrush, 700
VA open 250 VA hold.2.2A Ignition
@230 VAC
50 VA Pilot Duty plus 2.2A ignition
@230 VAC
1A Pilot Duty
@230 VAC
APPROVALS
Underwriters Laboratories Inc.:
MCCZ File MP1537
Controls, Primary Safety - Listed
MCCZ2 File MP1537
Controls, Primary Safety - Component
MCCZ7 File MP1537
Controls, Primary Safety Certified for Canada
MCCZ8 File MP1537
Controls, Primary Safety Certified for Canada - Component
Factory Mutual: Approved
Acceptable by: Industrial Risk Insurers (I.R.I.)
CE:
Gas Appliances
Gas Appliance Directive: 90/396/EEC
Low Voltage Directive: 73/23/EEC
EMC Directive: 89/336/EEC
GASTEC: 0063BT1754
(EN298, 2003; EN230, 2005)
DVGW: Reg. No. NG-2510BT0347
DIN-CERTCO: Reg. No. 5F233/08
CAUTION: Published load ratings assume that no contact be required to handle inrush cur-rent more often than once in 15 seconds. The use of control switches, solenoid, relays, etc.
which chatter will lead to premature failure. It is important to run through a test operation
(with fuel shut off) following the tripping of a circuit breaker, a blown fuse, or any known instance of chattering of any external current consuming devices.
WARNING: This equipment generates and can radiate radio frequency energy, and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference in which case the user, at his own expense, will be required to take whatever measures which may be required to correct the interference.
PART NUMBERS AND APPROVALS
Table 1: Agency Approvals
BurnerLogix Chassis/Flame Amp. Module
YB110UV X X X X X X
YB110UVSC X X X X X X
YB110IR X X X X X X
YB110IR2 X X X X X X
YB110FR X X X X X X
YB110DC X X X X X X
YB230UV X X X X
YB230UVSC X X X X
YB230IR X X X X
YB230IR2 X X X X
YB230FR X X X X
YB230DC X X X X
BurnerLogix Programmer Module
YP100 X X X
YP102 X X X
YP138 X X X
YP118 X X X
YP183 X X X
YP200 X X X
YP202 X X X
YP300 X X X
YP302 X X X
YP113 X X X X X X
YP115 X X X X X X
BurnerLogix Displays
BLV512 X X X X X X
BLL510 X X X X X X
BurnerLogix Wiring Bases
60-2810-1 X X X X X
60-2812-1 X X X X X
60-2814-1 X X X X X
X = CERTIFICATION IN HAND
APPROVED
APPLICABLE BULLETINS
ORDERING INFORMATION
Programmers, Non-recycle Operation
YP-1001Programmers, Recycle Operation
Programmers, Non-modulating
Displays BD-5001
Wiring base installation, 60-2810-1 133-676
Wiring base installation, 60-2812-1 133-677
Wiring base installation, 60-2814-1 133-677
BurnerLogix Chassis/Flame Amplifier Module
YB110UV 120 VAC input with UV non self-check amplifier
YB110UVSC 120 VAC input with UV self-check amplifier
YB110IR 120 VAC input with IR auto-check amplifier
YB110IR2 120 VAC input with IR auto-check amplifier (special application only -consult factory)
YB110FR 120 VAC input with flame rectification amplifier
YB110DC 120 VAC input with direct coupled amplifier
YB230UV 230 VAC input with UV non self-check amplifier
YB230UVSC 230 VAC input with UV self-check amplifier
YB230IR 230 VAC input with IR auto-check amplifier
YB230IR2 230 VAC input with IR auto check (special application only-consult factory)
YB230FR 230VAC input with flame rectification amplifier
YB230DC 230VAC input with direct coupled amplifier
BurnerLogix Programmer Modules
YP100 Keypad selectable parameters, non-recycle operation, modulation, open damper proving, 4 second FFRT
YP102 Keypad selectable parameters, non-recycle operation, modulation, open damper proving, 2 second FFRT
YP138 Keypad selectable parameters, non-recycle operation, modulation, open damper proving, indefinite pilot hold, revert to pilot from auto, 4 second FFRT
YP118 Keypad selectable parameters, non-recycle operation, modulation, open damper proving, indefinite pilot hold, revert to pilot from auto, 1 second FFRT
YP183 Same as YP138, terminal W used for purge complete, no voltage on 21 to move to pilot, no voltage on 16 to move to main.
YP200 Keypad selectable parameters, recycle operation, modulation, 4 second FFRT
WARNING: This equipment generates and can radiate radio frequency energy, and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference in which case the user, at his own expense, will be required to take whatever measures which may be required to correct the interference.
Note: All programmers: when used with the YB110DC or YB230DC, the FFRT is 0.2 seconds
YP202 Keypad selectable parameters, recycle operation, modulation, 2 second FFRT
YP300 Keypad selectable parameters, recycle operation, low fire start, early spark termination, 4 second FFRT
YP302 Keypad selectable parameters, recycle operation, low fire start, early spark termination, 2 second FFRT
YP113 Keypad selectable parameters, non-recycle operation, modulation, open damper proving, 1 second FFRT
YP115 Keypad selectable parameters, non-recycle operation, modulation, open damper proving, 1 second FFRT
BurnerLogix Displays
BLV512 Display, 2 line X 16 characters, VFD, with cable, NEMA 4
BLL510 Display, 2 line X 16 characters, LCD, with cable, NEMA 4
BurnerLogix wiring bases
60-2810-1 Pigtail wires, 4 foot long, 4"W x 5"H
60-2812-1 Closed base with terminal block and knockouts, 4"W x 7"H
60-2814-1 Open base with terminal block. 4"W x 7"H
BurnerLogix Accessories
129-178-4 Kit, remote mounting, BurnerLogix display, 4 ft. cable, provides NEMA 4 protection
129-178-8 Kit, remote mounting, BurnerLogix display, 8 ft. cable, provides NEMA 4 protection
BLD500 Blank display module, included with YB module
IT1000 Alarm annunciation system using wireless technology
PPC6000 Parallel Positioning System
61-5745-3 Shutter drive assembly for redundant self-check scanners
SCANNER SELECTION
FIREYE P/N DESCRIPTION USE WITH CHASSIS BULLETIN
48PT2-1003
48PT2-9003
48PT2-1007
48PT2-9007
4-263-1
Infrared 1/2" straight mount 96"(2438mm) TC-ER cable
Infrared 1/2" straight mount 96" (2438mm) TC-ER cable
Infrared 1/2" straight mount 48" (1219mm) TC-ER cable
Infrared 1/2" 90° angle mount 48" (1219mm) TC-ER cable
Replacement photo detector
YB110IR
YB230IR
YB110IR2
YB230IR2
SC-103
UV1A3
UV1A6
UV8A
UV2
UV2A6
45UV3-1050
UV90-3
UV90-6
UV90-9
UV 1/2" straight 36" (915mm) TC-ER cable
UV 1/2" straight 72" (1830mm) TC-ER cable
UV 1/2" 90° head 72" (1830mm) flex conduit
UV 3/8" straight 36"(915mm) TC-ER cable
UV 3/8" straight 72" (1830mm) TC-ER cable
UV 3/4" cast aluminum housing 96" (2438mm) unshielded leads
UV 90° lateral view with 36" (915mm) flex conduit
UV 90° lateral view with 72" (1830mm) flex conduit
UV 90° lateral view with 108" (2745mm) flex conduit
YB110UV
YB230UV
SC-102
45UV5-1007
45UV5-1009
4-314-1
Self-check UV 1" BSP threads, 102-264VAC
Self-check UV 1" NPT threads, 102-264VAC
Replacement UV tube
YB110UVSC
YB230UVSC
SC-101
69ND1-1000K4
69ND1-1000K6
69ND1-1000K8
Flame rod, 12”, 1/2” mount
Flame rod, 18”, 1/2” mount
Flame rod, 24”, 1/2” mount
YB110FR
YB230FR
SC-103
BurnerLogix Programmer Modules
45UV5-1005
45UV5-1105
Self-check UV 1" NPT threads, 61-5745-3 required
Self-check UV 1" BSP threads, 61-5745-3 required
YB110UVSC
YB230UVSC
133-645
55UV5-1007
55UV5-1009
Self-check UV 1" BSP, 102-264VAC, Suitable for hazardous locations.
Self-check UV 1" NPT, 102-264VAC, Suitable for hazardous locations.
YB110UVSC
YB230UVSC
SC-106
PHOENIX
85UVF4-1QDWR
85UVF4-2QDWR
85IRF4-1QDWR
85IRF4-2QDWR
Phoenix Integrated Scanner, 4 sec FFRT – Ultra-violet with 8-pin electri-cal quick dissconnect. FM, UL_CUS approved.
Fiber optic version of standard Phoenix Integrated Scanner, 4 sec FFRT
– Ultra-violet with 8-pin electrical quick dissconnect. FM, UL_CUS approved.
Phoenix Integrated Scanner, 4 sec FFRT – Infrared with 8-pin electrical quick dissconnect.. FM, UL_CUS approved.
Fiber optic version of standard Phoenix Integrated Scanner, 4 sec FFRT
– Infrared with 8-pin electrical quick dissconnect. FM, UL_CUS approved.
YB110DC
YB230DC
CU-114
35-318-1 35-318-2
Mounting flange for Phoenix, 1“ NPT Mounting flange for Phoenix, 1“ BSP
59-546-3
59-546-6
59-546-9
59-546-12
59-546-15
59-546-30
59-546-45
59-546-60
59-546-90
8-Conductor 3-meter (9 ft. 10 in.) cable assembly with 8-pin female connector.
8-Conductor 6-meter (19 ft. 8 in.) cable assembly with 8-pin female connector.
8-Conductor 9-meter (29 ft. 3 in.) cable assembly with 8-pin female connector.
8-Conductor 12-meter (39 ft. 4 in.) cable assembly with 8-pin female connector.
8-Conductor 15-meter (49 ft. 2 in.) cable assembly with 8-pin female connector.
8-Conductor 30-meter (98 ft. 5 in.) cable assembly with 8-pin female connector.
8-Conductor 45-meter (147 ft. 7 in.) cable assembly with 8-pin female connector.
8-Conductor 60-meter (196 ft. 10 in.) cable assembly with 8-pin female connector.
8-Conductor 90-meter (295 ft. 3 in.) cable assembly with 8-pin female connector.
INSIGHT
95IRS2-1, 2
95UVS2-1, 2, 3
95DSS2-1
Enhanced Model InSight Scanner – Infrared with quick disconnect, FM, UL_CUS approved.
Enhanced Model InSight Scanner – Ultra-violet with quick disconnect, FM, UL_CUS approved.
Enhanced Model InSight Scanner – Dual detector with quick discon-nect, FM, UL_CUS approved.
YB110DC
YB230DC
CU-95
60-2692
60-2693
1” NPT mounting flange for InSight Scanner, includes heat insulator 35- 127-1.
1” BSP mounting flange for InSight Scanner, includes heat insulator 35- 127-3.
59-497-020-WR
59-497-020C-WR
59-497-020R-WR
59-497-020RC-WR
12-Conductor cable with straight connector (129-164), 20 feet(6 meter) 12-Conductor cable with straight connector (129-164C) and flex con-duit adapter, 20 feet(6 meter) 12-Conductor cable with right angle connector (129-164R), 20 feet(6 meter) 12-Conductor cable with right angle connector (129-164RC) and flex conduit adapter, 20 feet(6 meter)
POWER SUPPLIES
60-2685-2 60-2685-4
Power Supply, 24 VDC, 2.1A, 120/240 VAC, 50/60Hz Power Supply, 24 VDC, 4.2A, 120/240 VAC, 50/60Hz
CU-100
SCANNER SELECTION
FIREYE P/N DESCRIPTION USE WITH CHASSIS BULLETIN
NOTE: The Phoenix QDWR models with electrical quick-disconnect have replaced the original WR models equipped with ten feet of captive cable. The QDWR models (with 59-546-X cables) are also suitable for use in Class I Division 2 hazardous areas, thereby eliminating the need for the “EXWR” models.
BURNERLOGIX Ordering Information
WIRING BASE
60-2810-1
PRE-WIRED
4 FOOT
COLOR CODED
FRONT VIEW
(WITH OPTIONAL DISPLAY INSTALLED)
WIRING BASE
60-2814-1
OPEN BOTTOM
CABINET MOUNT
60-2812-1
CLOSED BOTTOM
CONDUIT KNOCKOUT
60-2814-1 SHOWN
SIDE VIEW
CHASSIS/AMPLIFIER
120 VAC, 50/60 Hz
YB110UV
YB110UVSC
YB110IR
YB110FR
YB110DC
230 VAC, 50/60 Hz
YB230UV
YB230 UVSC
YB230IR
PROGRAMMER MODULE
YP100
YP102
YP200
YP202
YP300
YP302
YP113
YP138
YP118
DISPLAY MODULE
BLV512 - VACUUM FLUORESCENT
BLL510 - LIQUID CRYSTAL
(WITH OPTIONAL PROGRAMMER AND DISPLAY INSTALLED)
INSTALLATION PROCEDURE
WIRING BASE
Select either the pre-wired wiring base (60-2810-1) or terminal block style (60-2812-1, 60-2814-1).
Either wiring base type can be mounted on a din rail or directly mounted to the cabinet back plate.
Refer to Figure 1 for mounting dimensions.
FIGURE 1.
The location should be free from excessive vibration and within the ambient temperature rating.
PRE-WIRED WIRING BASE, P/N 60-2810-1 (shown for 120 VAC)
Terminal No. Wire Color Type Description Rating
L1 (Hot) Black Line voltage supply 120 VAC (+10%,-15%), 50/60 Hz
L2 (Neutral) White Line voltage common
EARTH Green Ground
S1 Red/Wht Scanner Input 300 VAC, 3 mA (UV models only)
S2 Blu/Wht Scanner Input 300 VAC, 3 mA (UV models only)
A Red Output Alarm 120 VAC, 1 A pilot duty
M Brown Output Combustion Blower 120 VAC, 9.8 FLA, 58.8 LRA
3 Yellow Input Operating Control 120 VAC, 1 mA
13 Orange Input Fuel Valve End Switch, Pre-Ignition Interlock
120 VAC, 1 mA
P Gray Input Running Interlock 120 VAC, 1 mA
D Wht/Brn Input Low Fire Start Switch 120 VAC, 1 mA
8 Wht/Gry Input Open Damper Proving Switch 120 VAC, 1 mA
W Wht/Orn Output Delayed Main Valve See Load Ratings
5 LT Blue Output Ignition / Pilot Valve See Load Ratings
6 Tan Output Pilot Valve See Load Ratings
7 Violet Output Main Fuel Valve See Load Ratings
16 DK Blue Input Pilot Valve Hold 120 VAC, 1 mA
21 Pink Input Start Input 120 VAC, 1 mA
10 Wht/Red Output Modulator Common 120 VAC 75 VA
12 Wht/Yel Output Modulator Low Fire 120 VAC 75 VA
X Wht/Blue Output Modulator High Fire 120 VAC 75 VA
11 Wht/Grn Output Modulator Auto 120 VAC 75 VA
22 Wht/Vio Input Remote Reset 120 VAC, 1 mA
23 Brn/Wht Input Spare 2 120 VAC, 1 mA
HEIGHT WITH CONTROL INSTALLED IS 5.8" (147MM)
INSTALLATION PROCEDURE
WIRING BASE
Install the wiring base where the relative humidity never reaches the saturation point. The Burner-
Logix system is designed to operate in a maximum 90% relative humidity continuous, non-condens-ing environment. Do not install the BurnerLogix system where it can be subjected to vibration in excess of 0.5G continuous maximum vibration. The BurnerLogix system is not a weather tight enclosure. The standard vertical position is recommended. Allow at least one inch clearance around the control for service and installation.
1. Wiring must comply with all applicable codes, ordinances and regulations.
2. Wiring must comply with NEC Class 1 (Line Voltage) wiring.
3. Torque rating on terminal block screws is 4.4 in/lbs to 5.3 in/lbs.
4. Limits and interlocks must be rated to simultaneously carry and break current to the ignition transformer, pilot valve and main fuel valve(s).
5. Recommended wire routing of lead wires:
a. Do not run high voltage ignition transformer wires in the same conduit with any other wires.
b. Do not route flame detector lead wires in conduit with line voltage circuits. Use separate conduit where necessary.
6. Maximum wire lengths:
a. The maximum lead wire length is 200 ft. (61 meters) to terminal inputs (Operating limits, interlocks, valves, etc.).
b. Flame Detector lead wires: see section on flame scanners
c. Remote reset: The maximum length of wire is 500 feet (152 meters) to a normally open remote reset push-button, but should remain within sight and sound of the burner.
d. Modbus communications: The maximum cable length of wire is 3300 feet (1000 meters) for RS-485.
A good ground system should be provided to minimize the effects of AC quality problems. A prop-erly designed ground system meeting all the safety requirements will ensure that any AC voltage quality problems, such as spikes, surges and impulses have a low impedance path to ground. A low impedance path to ground is required to ensure that large currents involved with any surge voltages will follow the desired path in preferences to alternative paths, where extensive damage may occur to equipment.
BEFORE INSTALLING THE BURNERLOGIX CONTROL
WARNING: Controls require safety limits utilizing isolated mechanical contacts. Electronic limit switches may cause erratic operation and should be avoided.
CAUTION: Ensure that electric power is turned off. Refer to SN-100 for recommended grounding techniques.
Be aware that power to some interlocks (operating controls, air flow switches, modulating circuits, etc.) may be derived from sources other than what is controlling the BurnerLogix.
INSTALLING THE YP PROGRAMMER MODULE
The YP programmer module plugs into the side of the YB110 (YB230) chassis module and can only be installed in one direction. DO NOT ATTEMPT
TO FORCE THE YP PROGRAMMER INTO
THE CHASSIS. Referring to the illustration on the right, align the holes in the YP programmer hous-ing with the posts located within the YB chassis.
Push the YP module into the chassis until the YP module is flush with the YB housing.
If it is necessary to remove the YP programmer module from the YB chassis, 2 slots are provided on the top and bottom of the YP housing. A small screwdriver can be used to ‘pop’ the programmer from the chassis.
ELECTRICAL CHECKOUT
If either a ground or a short circuit is detected, it must be eliminated before the control is plugged into the wiring base and power turned on.
Test the electrical field wiring for short circuits and grounds. The recommended method requires the use of an ohmmeter set on its lowest resistance scale.
7. Touch the meter probes together and calibrate accurately to ensure a reliable test.
8. Disconnect the neutral wire (L2) from the control system at the power source. Clip one meter test lead to the grounded green wire or to terminal E and with the other probe touch each other terminal. At no time should the meters show continuity or read 0 ohms.
9. Reconnect the neutral wire (L2) at the power source. Remove the test probe from the grounded terminal and reconnect it to Terminal L2 in the wiring base. With the other probe, touch each other terminal. It is normal to obtain a resistance reading on the meter at some terminals during this test as there are resistive loads (coils, transformers, lamps, etc.) connected whose normal DC resistance may be less than 5 ohms. However, at no time should the test meter read zero ohms.
10. With BurnerLogix installed, measure voltage from L2 to all other terminals. Reading should be zero on all terminals except Ll.
INSTALL BURNERLOGIX INTO WIRING BASE
The BurnerLogix YB chassis/amplifier module contains 2 screws permanently retained into the top and bottom of the housing. The wiring base contains two brass inserts with recessed threads to ease the installation. Line up the printed circuit board spacer located in the YB chassis/amplifier module with the alignment tabs located in the wiring base. Firmly push the YB model into the wiring base to assure the connectors mate properly. Tighten the screws into the brass inserts until snug.
YB110
YP100
For installations requiring CE certification:
After installation, the equipment should be protected from general access by means of a cabinet which is only accessible with a key or special tool and therefore a clear responsibility who replaced the fuse. If the fuse is blown during installation or operation, the control must be sent to the manufacturer to check.
CAUTION: Restore power for the following test.
BurnerLogiX PROGRAMMER SELECTION
All programmers for the BurnerLogiX Series are designated with the prefix “YP”. The functional operation, flame failure response time, purge timings, firing rate motor circuit, trial for ignition tim-ings, recycling function and display messages are determined by the programmer.
A chart of the most common programmers is found below.
Take note of the programming sequence chart for each programming module for the proper explana-tion of prepurge timings.
*FFRT with YB110DC or YB230DC is 0.2 seconds
PTFI*MTFI TIMINGS
The BurnerLogix system provides keypad selectable timings for both PTFI and MTFI. The selec-tions offered can provide 5 or 10 second timing for terminal 5 and 6 or a shortened time for terminal
5, allowing for early spark termination. BurnerLogix also provides selectable interrupted or intermit-tent operation for terminal 6.
FIREYE
PART
NUMBER
Pre-purge Programming
(Seconds)
Proven High Fire Interlock
(M-8)
Proven Low Fire Interlock
(M-D)
Terminal 6, Interrupted or Intermittent
Early Spark Termination
PTFI
(5/6)
MTFI
(5/6)
Running Interlock
(3-P)
* Flame Fail Time (Seconds)
Firing Rate
Motor
SETTINGS SHOWN ARE FACTORY DEFAULT
YP100 30 YES YES INTRP NO 10/10 10/15 Non-recycle 4 YES
YP102 30 YES YES INTRP NO 10/10 10/15 Non-recycle 2 YES
YP138 30 YES YES INTRP NO 10/10 10/15 Non-recycle 4 YES
YP118 30 YES YES INTRP NO 10/10 10/15 Non-recycle 1 YES
YP183 30 YES YES INTRP NO 10/10 10/15 Non-recycle 4 YES
YP113 30 YES YES INTRP NO 5/5 3/5 Non-recycle 1 YES
YP115 30 YES YES INTRP NO 5/5 3/5 Non-recycle 1 YES
YP200 30 NO YES INTRP NO 10/10 10/15 Recycle 4 YES
YP202 30 NO YES INTRP NO 10/10 10/15 Recycle 2 YES
YP300 30 NO YES INTMT YES 10/10 10/
intmt
Recycle 4 NO
YP302 30 NO YES INTMT YES 10/10 10/
intmt
Recycle 2 NO
WARNING: THE INAPPROPRIATE SELECTION OR APPLICATION OF A PRO-
GRAMMER MODULE COULD RESULT IN AN UNSAFE CONDITION HAZARDOUS
TO LIFE AND PROPERTY. The various programmer modules are interchangeable because they plug into a common YB chassis. Many parameters are configurable through the keypad display. Care should be taken to insure the proper parameters are set. Refer to the appropriate programmer bulletin for appropriate settings. Selection of the programmer module and setting the various parameters for a particular application should be made by a competent professional, such as a Boiler/Burner technician licensed by a state or govern-ment agency, engineering personnel of the burner, boiler or furnace manufacturer (OEM) or in the performance of duties based on the information from the OEM.
The selections provided for PTFI*MTFI timings are:
Table 2:
LED INDICATOR LIGHTS
The BurnerLogix YB control module has seven (7) LED indicator lights to annunciate the operating status of the control, as well as provide the reason for the last lockout condition. The “Open Damper” and “Close Damper” LED's provide easy set-up of the modulating motor end switches. Each LED has a graphic symbol to describe its function (see Table 3).
SELECTION PTFI MTFI COMMENT
Term 5 Term 6 Term 5 Term 6
10/10*10/15 10 10 10 15
5/5*0/10 5 5 0 10 NO SPARK DURING MTFI
5/5*0/5 5 5 0 5 NO SPARK DURING MTFI
5/5*10/15 5 5 10 15 SHORTENED PTFI
5/5*10/10 5 5 10 10 SHORTENED PTFI
5/10*0/15 5 10 0 15 EARLY SPARK TERMINATION
5/10*0/10 5 10 0 10 EARLY SPARK TERMINATION
10/10*0/10 10 10 0 10 NO SPARK DURING MTFI
10/10*0/5 10 10 0 5 NO SPARK DURING MTFI
10/10*10/10 10 10 10 10
Table 3:
FAN
Lights when the blower motor is energized (terminal M) and flashes when the RUN/CHECK switch is in the “CHECK” position during Purge, PTFI, MTFI and AUTO.
OPEN
DAMPER
Will blink when the modulator motor is being driven to the high fire position. (circuit 10-X made). Once the high purge switch closes (M-8), this LED will light constant. This LED pro-vides the status of the high fire purge interlock circuit (M-8). This LED lights anytime the M- 8 circuit closes during Prepurge, PTFI, MTFI, Post Purge.
CLOSE
DAMPER
Will blink when the modulator motor is being driven to the low fire position (circuit 10-12 made). Once the low fire switch closes (M-D), this LED will light constant. This LED provides the status of the low fire start interlock circuit (M-D). This LED lights anytime the M-D circuit closes during Pre-purge, PTFI, MTFI, post purge.
AUTO
Will light when the control releases to automatic modulating control (circuit 10-11 made).
IGNITION
Will blink during Pilot Trial For Ignition (PTFI). Will light constant during Main Trial For Igni-tion (MTFI).
FLAME
Will light whenever flame is detected by the flame scanner.
ALARM
In the event of a lockout condition, the Alarm LED will blink, the remaining LED's will light up to indicate the lockout condition. See “Safety Lockout Codes.”
REPLACEABLE FUSE
The following applies only to the YB110 controls operating at 120 VAC, 50/60 Hz:
The chassis/amplifier modules are designed with a field replaceable fuse to protect Terminals 5, 6, 7 and W against short circuit loads or mis-wiring. In the event the fuse becomes OPEN, the display will indicate CHECK FUSE or the CLOSE DAMPER, AUTO and IGN LED’s will light. An OPEN or blown fuse is a result of an over current condition on Terminals 5, 6, 7, or W. The over current condition causing the fuse to OPEN must be resolved before another attempt to apply power.
For installations requiring CE certification:
Only Fireye or a Fireye trained technician is allowed to replace the fuse.
All other installations:
The fuse is located on the printed circuit board containing the relays. To replace the fuse, remove power from the system and remove the control from its wiring base. Using an appropriate tool, remove the defective fuse and discard. Install a Fireye replacement fuse (P/N 23-197) or equivalent
10 amp fuse (e.g. Wickman # 1937-071-K). Re-install the BurnerLogix control in accordance with the installation procedure detailed in a previous section.
The YB230 control contains a non-replaceable fuse and must be returned to the manufacturer for repair or replacement.
DESCRIPTION OF FUNCTIONS OF OPERATING CONTROLS
1. Operating Controls: Generally pressure or temperature activated, the operating control closes, causing the burner start-up sequence to begin. When the operating control opens, the burner shuts off. The operating control is connected in the L1-3 circuit on the wiring base.
2. Limit Switches: These are generally pressure, water level or temperature activated
a. Recycle — when it is desired to stop the burner when the limit switch opens and restart it when the limit switch recloses, they are connected between Terminals L1 and 3.
b. Non-Recycle —when it is necessary to stop the burner when the limit switch opens and pre-vent it from starting until both the limit switch recloses and the manual reset is activated, they are connected between terminals 3 and P.
3. Fuel Valve End Switch Interlock: This is generally an integral switch mounted on the main fuel valve and activated by the valve stem. It is connected between Terminal L1 & 13. The fuel valve end switch interlock prevents a burner start-up if the valve stem is not in the “valve closed” position. This interlock must remain closed while in STANDBY and until the start of
PTFI.
4. Purge Interlock: Generally a firing rate motor linkage position switch or a differential air-pres-sure switch, that proves a maximum purge air flow rate. It is connected between Terminals M and 8. The purge interlock proves that the air damper is fully open and purge air flow rate is at maximum during the purge.
5. Running Interlocks: These generally are air flow switches, high and low fuel pressure switches, oil temperature switches, atomizing media pressure switches, and excess smoke den-sity controls. These interlocks prove proper conditions for normal operation of the burner. They are wired in series and connected between Terminals 3 and P.
6. Low Fire Start Interlock: Generally a firing rate motor linkage position switch or a damper position switch, will prove both the linkage and dampers are in their proper positions to begin burner light off. This switch is connected between Terminals M and D.
SETTING PROGRAMMER PARAMETERS
In order to change the factory default parameters stored in the programmer module an optional key-pad/display (BLV512 or BLL510) is required. All configurable parameters are stored within the
PROGRAM SETUP sub-menu. The keypad/display module provides tactile feedback keys that are used to access the sub-menus inherent in the BurnerLogix system.
The BurnerLogix display consists of 2 lines having 16 characters per line. The default displayed item is the current operating status. This would include the current point in the burner sequence followed by the parameter pertaining to that point in the sequence, such as time or the flame signal level. The bottom line is used to display the current operating status. The BurnerLogix display also provides the historical information stored in the control’s memory such as burner hours, cycles, lockouts and sys-tem hours. The remainder of the display items are menus with sub-menus indicated by a right facing arrow. The sub-menus indicate the current value of the selected item and in some cases can be modi-fied to suit the application.
All programmed settings become permanent after 8 hours of main burner (Terminal 7) on time.
STANDBY
PROGRAM SETUP >
KEYPAD DESCRIPTION
The NEXT key is used to scroll down through the various menus and is also used to increment the value when in the modify mode. The BACK key is used to scroll up through the menus and is also used to decrement the value when in the modify mode. The MODE key is used to enter a sub-menu when the displayed item indicates a sub-menu with a right facing arrow and also to exit the sub-menu and move on to the next main menu item. The RESET/MDFY key is used to reset the BurnerLogix from a lockout condition, force a recycle of the programmer, indicate to the system the value displayed is to be modified or when done with the modification.
FIGURE 2. BURNERLOGIX MENU STRUCTURE
BNR LOCKOUTS
BNR CYCLES
START HERE
Scrolls through menu, clockwise
Keypad Legend
PROGRAM SETUP >
SYS HOURS
STANDBY
L1 - 3 OPEN
BNR HOURS
MODE STANDBY
PROGRAMMER YP100
LOCKOUT HISTORY >
MODE LO #XX PTFI
SYSTEM INFO >
MODE STANDBY
AVG. PILOT FLM. 42
NEXT
Scrolls through menu, counter-clockwise
BACK
Provides access to Sub-Menu
MODE
Provides reset of control if lockout
MODIFY
RESET
or Exits Sub-Menu
Provides recycle of control
Allows parameter to be modified/saved
FLAME FAIL
PROGRAM SET UP SUB-MENU
The sub-menu "PROGRAM SETUP" allows the user to review the various operational settings of the programmer module (e.g. programmer type, purge timing, etc.) and some instances modify the operational parameters to suit the application requirement. The MODE key is used to enter and exit the sub-menu and the NEXT and BACK keys are used to scroll through the menu as well as change the operational parameter.
P
MDFY TO CHANGE
FLM FAIL TIME 4 SEC
AMP IR
PROGRAMMER YP100
DO IR LEARN NO
LOCK SETTINGS NO
START HERE
MODE
PROVE 3-P OPEN N
MDFY TO CHANGE
COUNT METHOD DOWN
MDFY TO CHANGE
PURGE 0:30
UNIT ADDRESS 1
BAUD RATE 9600
PROVE M-D TFI NO
M-D WAIT 10m YES
POST PURGE 0:15
PROVE M-D OPEN NO
PROVE M-8 OPEN NO
TERMINAL 6 INTRP
PTFI * MTFI TIMING
FROM
MAIN
MENU LOOP
PRESS KEY FROM MAIN MENU LOOP
MODEPRESS KEY AT ANYTIME TO EXIT SUB-MENU
Note:
YB110IR only
Modifiable parameters located in PROGRAM SETUP MENU
Shaded parameters not affected by 8 hour burn-in or LOCK SETTINGS.
TO VIEW AND MODIFY A PROGRAMMABLE PARAMETER:
Use the NEXT or BACK key to scroll to PROGRAM SETUP. Press the MODE key to enter the sub-menu showing all program setup parameters. Pressing the MODE key while in the sub-menu will exit the sub-menu, and the next main menu item will be displayed. While in the sub-menu, pressing the NEXT key will scroll forward through the sub-menu. Pressing the BACK key will scroll back-ward through the sub-menu. When a modifiable parameter is displayed, the top line will indicate
MDFY TO CHANGE while the bottom line will indicate the current item and its current value.
Pressing the RESET/MDFY key will allow the displayed parameter to be modified. The item to be modified will move to the top line while its value will remain on the bottom line. At an infrequent rate, the top line will indicate MDFY TO SAVE. Use the NEXT or BACK keys to select the value to suit the application and when done, press the RESET/MDFY to save the value to memory.
Refer to SYSTEM INFO Sub Menu, page 33, for language selection.
Parameter Factory Default Range Description
Purge time 00:30s 0:30s – 60:00m, 15 second increments.
0:10s-60:00m, YP113 0:00s-60:00m, YP115 (0:00s - 60:00m in YP3XX)
Applies to open damper purge time in YP1XX and YP2XX pro-grammers and low fire start time in YP3XX programmers
Count method DOWN UP, DOWN Time counts UP to final value or DOWN to zero from starting value. This setting will apply to all timer values.
Prove 3-P open at start NO YES, NO Prevents jumped terminals. Requires the 3-P circuit to be open at the start of a cycle.
PTFI*MTFI timing 10/10*10/15
YP113 = 5/5*3/5
See chart on page 15 Applies to terminals 5 and 6 operation during PTFI and MTFI.
Terminal 6 interrupted or intermittent
INTRP INTRP, INTMT Provide interrupted or intermittent operation on terminal 6.
Prove M-8 open NO YES, NO If YES, M-8 must be open at start of open damper purge period. (YP1XX Series only).
Prove M-D open NO YES, NO If YES, M-D must be open at end of open damper purge period. Does not apply to YP3XX Series.
Post purge 0:15 0:15s - 4:00m, 5 second increments.
Selects Post Purge time
3-P Recycle YES YES, NO Applies to YP3XX series only. Allows non-recycle operation of 3-P circuit.
M-D WAIT 10m YES YES, NO Select YES for lockout on M-D open for 10 minutes. Select NO for indefinite wait for M-D to close. This wait time applies prior to pilot trial for ignition.
PROVE M-D TFI NO YES, NO Select YES to force lockout on M-D opening during PTFI and
MTFI
Baud rate 9600 4800, 9600, 19200, 38400 Sets communication baud rate
Unit address 00 00-31 Multi-drop requires unique addressing. Lowest address allowed for modbus is 01
Lock Settings NO YES, NO Parameters can be stored to memory before automatic 8 hour store.
DO IR LEARN NO YES, NO Select YES to activate IR LEARN process. See IR operation.
All programmed settings become permanent if the BurnerLogix system has been powered continuously and 8 hours of main burner (terminal 7) on time has been accumulated. If the
AC power is removed prior to accumulating 8 hours of main burner on time, the system burn-in time clock will be reset to zero. It is not necessary for the main burner on time to be continuous. The BurnerLogix accumulates burner on time in seconds. If necessary, the pro-grammed settings can be made to become permanent anytime before the required 8 hours of main burner on time through the use of the optional keypad and the LOCK SETTINGS option under the PROGRAM SETUP sub menu.
FLAME SCANNERS
INSTALLATION - UV SCANNERS
Where possible, obtain the burner manufacturer’s instructions for mounting the scanner. This infor-mation is available for most standard burners. The scanner mounting should comply with the follow-ing general instructions:
1. Position the UV1A, UV2 scanner within 30 inches of the flame to be monitored; the 45UV5 within 72 inches, closer if possible.
2. Select a scanner location that will remain within the ambient temperature limits of the UV Scan-ner. If cooling is required, use an insulating coupling (Fireye #35-69 for UV1A, UV2 Scanners, #35-127-1 for 45UV5) to reduce conducted heat.
3. The UVlA, UV2, 45UV5 Scanners are designed to seal off the sight pipe up to 1 PSI pressure.
Higher furnace pressures should be sealed off. To seal off positive furnace pressure up to 100 PSI for UV1A, UV2 Scanners, install a quartz window coupling (#60-1257) For 45UV5 Scan-ners, use #60-1100 coupling. Add cooling air to reduce the scanner sight pipe temperature.
4. Install the scanner on a standard NPT pipe (UV1A: 1/2", UV2: 3/8", 45UV5: 1") whose position is rigidly fixed. If the scanner mounting pipe sights through the refractory, do not extend it more than halfway through. Swivel flanges are available if desired (#60-302 for UV1A, UV2 Scan-ners, #60-1664-3 for 45UV5). The sight pipe must permit an unobstructed view of the pilot and/ or main flame, and both pilot and main flames must completely cover the scanner field of view
5. Smoke or unburned combustion gases absorb ultra-violet energy. On installations with negative pressure combustion chambers, a small hole drilled in the UV1A, UV2 sight pipe will assist in
CAUTION: The UV1A, UV2, UV8A, UV90 and 45UV3 flame scanners and associated amplifier module are non-self checking UV systems and should be applied only to burners that cycle often (e.g.: a minimum of once per 12 hours) in order for the safety checking cir-cuit to be exercised. If component checking is required during burner operation for con-stantly fired burners, utilize the self-checking ultra-violet flame scanners (45UV5, 55UV5) with associated amplifier modules (YB110UVSC), the infrared flame scanner (48PT2) with associated Auto Check amplifier (YB110IR), or integrated scanners (Phoenix or InSight with associated amplifier (YB110DC).
SCANNER MUST HAVE UNOBSTRUCTED
VIEW OF FLAME
NOT THIS NOT THIS BUT THIS
FLAME MUST COMPLETELY COVER
SIGHT OPENING
NOT THIS NOT THIS BUT THIS
keeping the pipe clean and free from smoke. For positive pressure furnaces, provide clean air to pressurize the sight pipe, if necessary.
6. Two UV1A or UV2 Scanners may be installed on the burner if it is necessary to view two areas to obtain reliable detection of the flame. They should be wired in parallel. Only one repetitive selfchecking 45UV5 Scanner may be installed on a burner.
7. To increase scanner sensitivity with UV1A, UV2 Scanners, a quartz lens permits location of the scanner at twice the normal distance. Use l/2" x 1 l/2" pipe nipple between UV1A Scanner and the coupling. Use 3/8" pipe nipple and a l/2" x 3/8" bushing on UV2 installations.
8. Request the assistance of any Fireye field office for recommendations of a proper scanner instal-lation on a non-standard application.
TYPICAL SCANNER INSTALLATIONS
OPERATION — 45UV5 & 55UV5 SELF-CHECKING UV SCANNER
Self-checking ultra-violet scanners should be used in applications where burner firing operation is continuous or where the burner is on for long periods of time without recycling and UV detection is the best alternative. In addition, ultra-violet self-checking systems are mandatory in some locations.
The operation of this type of system consists of maintaining the flame scanning capability at all times while also proving that the ultra-violet tube is firing properly. This is done periodically by mechanically closing off the sight of the UV tube and checking to make sure that the flame signal goes away.
A shutter assembly in the 45UV5 scanner performs this function. The diagram below explains the process further.
If the shutter assembly in the scanner fails, the tube is faulty, or there is insufficient power to the scanner, the BurnerLogix will LOCKOUT and display the following message LOCKOUT CHECK
SCANNER. The ultra-violet tube is replaceable (P/N 4-314-1).
A lockout will result if a minimum signal is detected for three consecutive shutter closed periods.
The maximum UV signal from a flame is found in the first one-third of the visible flame taken from the point where the flame begins. The scanner sight pipe should be aimed at this area.
DO NOT EXTEND
MORE THAN
HALF-WAY INTO
REFRACTORY
SCANNER
FORCED
CLEAN AIR
(FROM DISCHARGE
OF FAN)
METHODS OF COOLING SCANNER
INSULATING
TUBING
SEALING UNION
FORCED
AIR
EXTEND SIGHTING TUBE
6”(152.4) OR 8”(203.2)
DO NOT EXTEND MORE THAN
HALF-WAY INTO REFRACTORY
WIRING - UV SCANNERS
To connect the scanner to the control, the UV1A Scanner is supplied with 36" or 72" of flexible cable. The 45UV5 is supplied with four 72 lead wires. Install them in a suitable length of flexible armor cable and connect it to the control. A conduit connector is supplied with the scanner. Connect black wires (shutter) to terminals L1, L2; red wires (UV tube) to terminals S1, S2.
If it is necessary to extend the scanner wiring, the following instructions apply:
Scanner wires should be installed in a separate conduit. The wires from several scanners may be installed in a common conduit.
1. Selection of Wire
a. Wiring: For extended scanner wiring up to 500 feet, and for shorter lengths to reduce signal loss, use a shielded wire (Belden 8254-RG62 coaxial cable, or equal) for each scanner wire of
UV1A, UV2 and each red wire of the 45UV5. The ends of the shielding must be taped and not grounded.
b. Asbestos insulated wire should be avoided.
c. Multiconductor cable is not recommended without prior factory approval.
2. High voltage ignition wiring should not be installed in the same conduit with flame detector wires.
INSTALLATION—INFRARED SCANNER TYPE 48PT2
Where possible, obtain the burner manufacturer’s instructions for mounting the scanner, otherwise proceed as follows:
A single scanner is used to detect both pilot and main flames. The sight pipe on which the scanner mounts must be aimed so that the scanner sights a point at the intersection of main and pilot flames.
Proper scanner positioning must assure the following:
1. Reliable pilot flame signal.
2. Reliable main flame signal.
3. A pilot flame too short or in the wrong position to ignite the main flame reliably, must not be detected.
4. Scanner must have an unobstructed view of flame being monitored.
5. Flame being monitored must completely cover the scanner field of view.
6. To avoid nuisance shutdowns, it is important to avoid sighting hot refractory and to keep scanner temperature below 140° F (60°C).
7. When the proper position has been established, drill a hole through the furnace wall and install a 4" to 8" length of threaded l/2" black iron pipe on which to mount the 48PT2 scanner.
8. When satisfactory sighting position has been confirmed by operating tests, the sight tube should be firmly welded in place.
SHUTTER OPEN
SHUTTER CLOSED
3.7 SEC.
0.4 SEC. TIME
WIRING
Attach the cable supplied with the scanner to a junction box. Splice the cable wires to a pair of wires not smaller than #l8. Install the complete run in a separate conduit to the control. Continuous conduit bonding between scanner and the control is mandatory! Scanner may be located up to 100 feet from control. Do not pass scanner wiring through any junction box containing other wires. Do not run other wires through scanner conduit. Asbestos insulated wire should be avoided.
9. To avoid nuisance shutdowns, it is important to avoid sighting hot refractory and to keep scan-ner temperature low below 140° F (60°C).
10. When the proper position has been established, drill a hole through the furnace wall and install a 4" to 8" length of threaded l/2" black iron pipe on which to mount the 48PT2 scanner.
11. When satisfactory sighting position has been confirmed by operating tests, the sight tube should be firmly welded in place.
OPERATION - IR LEARN
The BurnerLogix IR system employs an innovative flame detection method that allows the user to adapt the operation of the amplifier to the actual burner environment and fuel type separately during pilot trial for ignition and…