36C25219B0058-004.pdf
PDF 5 MB Posted
- Attached to
- Replace B58-4 FCUs/Hot/Chilled Piping 550-18-102
- Solicitation number
- 36C25219B0058
About this file
36C25219B0058 550-18-102 Drawings - 9july2019.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25219C0224-000.docx | DOCX document | |
| 36C25219B0058-0002003.pdf | ||
| 36C25219B0058-0002000.docx | DOCX document | |
| 36C25219B0058-0002002.pdf | ||
| 36C25219B0058-0002001.pdf | ||
| 36C25219B0058-0001000.docx | DOCX document | |
| 36C25219B0058-003.pdf | ||
| 36C25219B0058-002.pdf | ||
| 36C25219B0058-001.docx | DOCX document | |
| 36C25219B0058-000.docx | DOCX document | |
| 36C25219B0058-000.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING 58
E. MAIN STREET
Palm er D r.
B lue S tar H w y
Danville National Cemetery
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
FULLY SPRINKLERED
PROJECT SITE MAPPROJECT LOCATION MAP
C:\Users\esanborn\Documents\Revit\A_BUILDING 58 - REPLACE FCU - 18-152_esanborn.rvt
6/12/2019 11:04:09 AM
58-G-001
COVER SHEET
1900 E Main St, Danville, IL 61832
DGC, ES
LW
JUNE 11, 2019
REPLACE F58-4 FCUS AND
HOT/CHILLED WATER PIPING
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
REPLACE F58-4 FCUS AND HOT/CHILLED
WATER PIPING
1900 E Main St, Danville, IL 61832
VA PROJECT #: 550-18-102
NORTH
TRUE
NORTH
TRUE
SHEET LIST
SHEET
NUMBER SHEET NAME DWG OF DWG
GENERAL
58-G-001 COVER SHEET 1 3
58-G-002 GENERAL SYMBOLS, ABBREVIATIONS AND NOTES 2 3
58-G-003 TYPICAL ICRA DETAILS AND NOTES 3 3
ARCHITECTURAL
58-A-001 THIRD FLOOR PLAN (REFERENCE ONLY) 1 8
58-A-002 THIRD FLOOR PLAN (REFERENCE ONLY) 2 8
58-AD111 THIRD FLOOR REFLECTED CEILING DEMOLITON PLAN 3 8
58-AD112 THIRD FLOOR REFLECTED CEILING DEMOLITION PLAN 4 8
58-A-101 FOURTH FLOOR PLAN 5 8
58-A-102 FOURTH FLOOR PLAN 6 8
58-A-111 THIRD FLOOR REFLECTED CEILING PLAN 7 8
58-A-112 THIRD FLOOR REFLECTED CEILING PLAN 8 8
MECHANICAL
58-M-001 MECHANICAL GENERAL INFORMATION 1 7
58-MD101 THIRD FLOOR MECHANICAL DEMOLITION PLAN 2 7
58-MD102 FOURTH FLOOR MECHANICAL DEMOLITION PLAN 3 7
58-M-101 THIRD FLOOR MECHANICAL PIPING PLAN 4 7
58-M-102 FOURTH FLOOR HVAC PLAN 5 7
58-M-501 MECHANICAL DETAILS 6 7
58-M-601 MECHANICAL SCHEDULES 7 7
ELECTRICAL
58-E-001 ELECTRICAL GENERAL NOTES, LEGENDS, AND ABBREVIATIONS 1 6
58-ED101 THIRD FLOOR LIGHTING DEMOLITION PLAN 2 6
58-ED102 FOURTH FLOOR ELECTRICAL DEMOLITION PLAN 3 6
58-EL101 THIRD FLOOR LIGHTING PLAN 4 6
58-EP101 FOURTH FLOOR POWER PLAN 5 6
58-E-601 ELECTRICAL SCHEDULES AND LIGHTING DETAILS 6 6
DocuSign Envelope ID: 94BD6672-7352-4EAD-AA87-0512B57C546C
6/12/2019
AFF ABOVE FINISHED FLOOR
ACP/APC ACOUSTIC CEILING PANEL/
ACOUSTIC PANEL CEILING
ACT ACOUSTIC(AL) TILE
ADJ ADJUSTABLE
ADT'L ADDITIONAL
AGG AGGREGATE
ALT ALTERNATE
AL ALUMINUM
APPROX APPROXIMATE(LY)
ASPH ASPHALT
AUTO AUTOMATIC
B/O BOTTOM OF
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BRG BEARING
CENTERLINE
C/C CENTER TO CENTER
CJ CONTROL JOINT
CLL CONTRACT LIMIT LINE
CEM CEMENT(ITIOUS)
CMU CONCRETE MASONRY UNIT
CLG CEILING
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CTR CENTER(ED)
DF DRINKING FOUNTAIN
DS DOWNSPOUT
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DET/DTL DETAIL
DIA DIAMETER
DIM DIMENSION
DN DOWN
DWG(S) DRAWING(S)
E EAST
EC ELECTRICAL CONTRACTOR
EHO ELECTRICAL HOLD OPEN
EJ EXPANSION JOINT
EW EACH WAY
EA EACH
EIFS EXTERIOR INSULATION
FINISH SYSTEM
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXT EXTERIOR
EWC ELECTRIC WATER COOLER
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FFE FINISH FLOOR ELEVATION
FV FIELD VERIFY
FEC FIRE EXTINGUISHER CABINET
FDN FOUNDATION
FIN FINISH
FLSHG FLASHING
FLR FLOOR
FRMG FRAMING
FT FOOT/FEET
FTG FOOTING
GC GENERAL CONTRACTOR
GA GAUGE
GALV GALVANIZED
GEN GENERAL
GYP GYPSUM
HM HOLLOW METAL
HDWR HARDWARE
HOL HOLLOW
HOR HORIZONTAL
HT HEIGHT
HVAC HEATING/VENTILATION/AIR
CONDITIONING
IDPH ILLINOIS DEPARTMENT OF
PUBLIC HEALTH
ID INSIDE DIAMETER
IN INCH
INCL INCLUDING
INSUL INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
LAV LAVATORY
LB(S) POUND(S)
L/S LANDSCAPE
LT LIGHT
MO MASONRY OPENING
MAS MASONRY
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTL METAL
N NORTH
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NOM NOMINAL
OC ON CENTER
OD OUTSIDE DIAMETER
O TO O OUT TO OUT
OPNG OPENING
OPP OPPOSITE
OVHD OVERHEAD
PEB PRE-ENGINEERED BUILDING
PJF PREFORMED JOINT FILLER
PT PRESSURE TREATED
PERIM PERIMETER
PL PLATE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLYWD PLYWOOD
PNT PAINT
PR PAIR
PTD PAINTED
PWR POWER
RB RUBBER BASE
RD ROOF DRAIN
RO ROUGH OPENING
RAD RADIUS
REC RECESSED
REINF REINFORCED
REQ'D REQUIRED
REV REVISED (REVISION)
RM ROOM
S SOUTH
SB SPLASH BLOCK
SF SQUARE FEET
SS STAINLESS STEEL
SIM SIMILAR
SPEC SPECIFICATIONS
SQ SQUARE
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
T&G TONGUE AND GROOVE
T/O TOP OF
TELE TELEPHONE
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VERT VERTICAL
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WWF WELDED WIRE FABRIC
WD WOOD
WH WATER HEATER
WT WEIGHT
CL
GENERAL NOTES
1. REFER TO PLUMBING, ELECTRICAL, AND MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.
2. PROVIDE BLOCKING AT PARTITIONS AS REQUIRED FOR MOUNTING OF WALL-MOUNTED ITEMS: PROVIDE SUPPLEMENTAL FRAMING AT WALL OPENINGS INCLUDING KING STUDS, JACK STUDS, AND CRIPPLE STUDS, AS
REQUIRED FOR COMPLETION OF THE WORK.
3. COORDINATE THE WORK OF TRADES PRIOR TO THE START OF CONSTRUCTION.
4. FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE START OF WORK FOR EACH PHASE.
5. NOTIFY THE COR OF DISCREPANCIES IN THE DRAWINGS AND SPECS PRIOR TO THE START OF WORK.
6. DIMENSIONS SHOWN ARE TO FACE OF STUD FRAMING, FACE OF CONCRETE/MASONRY WALLS, OR FINISHED
FACE OF EXISTING WALL SURFACE.
7. ALL WOOD IN CONTACT WITH CONCRETE SHALL BE PRESSURE TREATED.
8. INSTALL ALL WORK IN ACCORDANCE WITH CURRENT APPLICABLE CODES AND PUBLISHED STANDARDS.
9. INDICATIONS OF PROJECT LIMITS OR LINES OF DEMARCATION ARE SHOWN FOR GENERAL SCOPE DEFINITION AND REFLECT THE UNDERSTANDING OF THE DESIGNER AS TO THE LIMITATIONS OF THE WORK AREA IN AN OCCUPIED AREA. ACTUAL CONTRACT LIMITS ARE TO BE DETERMINED BY AGREEMENT BETWEEN THE COR AND
CONTRACTOR BEFORE THE START OF THE WORK.
10. THE DRAWINGS AND SPECIFICATIONS ARE SEPARATED INTO DISCIPLINES FOR CONVENIENCE. THE SEPARATIONS USED ARE USED ONLY FOR THE PURPOSES OF CONVENIENCE AND REFERENCE AND IN NO WAY DO THEY DEFINE OR LIMIT THE SCOPE OR INTENT OF ANY PART OF THE DRAWINGS, OR OF THE DRAWINGS AND SPECIFICATIONS AS A WHOLE. THE FACT THAT THE DRAWINGS ARE SEPARATED IN NO WAY SUGGESTS THAT THE WORK IS NOT TO BE CONSTRUCTED AS A COMPLETE, INTEGRATED AND UNIFIED WHOLE.
11. THE DRAWINGS AND SPECIFICATIONS, INCLUDING DRAWINGS PREPARED BY SPECIFIC ENGINEERING DISCIPLINES ARE COMPLEMENTARY; ITEMS SHOWN IN ANY ONE LOCATION IN THE DRAWINGS SHALL BE
CONSIDERED TO BE REQUIREMENTS OF THE CONTRACT FOR CONSTRUCTION.
12. DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR REFERENCE ONLY AND ARE NOT INTENDED TO ACCURATELY DEPICT ACTUAL OR DESIGNATED CONDITIONS. WRITTEN DIMENSIONS SHALL
GOVERN.
13. AT AREAS INDICATED TO BE PATCHED AND REPAIRED, THE CONSTRUCTION AND ASSEMBLY OF THE PATCH OR REPAIR SHALL MATCH THE ASSEMBLY AND INTEGRITY OF THE ADJACENT EXISTING CONSTRUCTION, FOR FIRE
RATING, MATERIALS, FINISH, THICKNESS, AND QUALITY.
DEMOLITION NOTES
1. KEY NOTES AND DRAWINGS ARE INTENDED TO GRAPHICALLY REPRESENT
GENERAL WORK AND DO NOT PORTRAY FULL SCOPE OF THE PROJECT. SEE
SPECIFICATIONS FOR DETAILED REQUIREMENTS.
2. REMOVE EXISTING CONSTRUCTION AS INDICATED AND CLEAR AREA OF DEBRIS
PRIOR TO PROCEEDING WITH NEW CONSTRUCTION.
3. EQUIPMENT REMOVED SHALL BE LEGALLY DISPOSED OFF MEDICAL CENTER
GROUNDS.
4. COORDINATE WITH VA COR FOR DEMOLITION SCHEDULE AND SCHEDULE OF
WASTE REMOVAL.
5. NOTIFY COR OF DEMOLITION REQUIRED AND NOT INDICATED FOR
INSTALLATION OF ELECTRICAL OR DATA ITEMS. AFTER SUCH DEMOLITION AND
INSTALLATION, PATCH OR REPLACE MATERIALS AND FINISHES TO MATCH
EXISTING.
6. THE INFORMATION CONTAINED IN THESE DEMOLITION DOCUMENTS DEFINES
GENERAL SCOPE ONLY AND DOES NOT RELIEVE THE CONTRACTOR OF THE
RESPONSIBILITY OF PROVIDING ALL DEMOLITION REQUIRED FOR THE
COMPLETION OF THE PROJECT.
7. REFER TO THE ELECTRICAL DRAWINGS FOR FURTHER INFORMATION
REGARDING DEMOLITION OF ELECTRICAL SYSTEMS.
8. BEFORE THE START OF WORK, IDENTIFY ANY REQUIRED DEMOLITION BEYOND
THE IDENTIFIED PROJECT SCOPE WHETHER ABOVE, BELOW OR OUTSIDE
PROJECT AREA. NOTIFY AND COORDINATE WITH THE COR, PROVIDE
DEMOLITION OF THESE AREAS AND PATCH THE SAME AS A PART OF THE
SCOPE OF THE PROJECT.
9. ALL DEMOLITION WORK SHALL BE PERFORMED WITH DUE CARE AND
DILIGENCE IN ORDER TO PREVENT ARBITRARY DAMAGE OR INTERRUPTION OF
SERVICE OR CONCEALED UTILITIES INTENDED TO REMAIN IN SERVICE.
DISCOVERY OF UTILITIES OR CONDITIONS LOCATED DIFFERENTLY FROM THAT
INDICATED OR THAT ARE NOT IDENTIFIED. SHALL BE REPORTED TO THE
CONTRACTING OFFICER (COR).
10. COORDINATE WITH VA COR FOR CONSTRUCTION ACCESS ROUTE AND
LOCATIONS OF DUMPSTER AREA. COORDINATE WITH COR FOR SCHEDULE OF
USE OF ACCESS ROUTE FOR WASTE REMOVAL AND CONTRACTOR USE OF
FREIGHT ELEVATOR.
WALL SECTION
SYMBOL
INTERIOR ELEVATION
SYMBOL
COLUMN GRID
ELEVATION SYMBOL
REVISION NOTE
ENLARGED DETAIL CALLOUT
ROOM DESIGNATION
SYMBOL
BREAK LINE
ROOF SLOPE
DIRECTION SYMBOL
TYPICAL GRAPHIC SCALE
DETAIL #
PAGE #
DETAIL #
PAGE #
TRUE NORTH ARROW
PROJECT NORTH ARROW
A8.1
EXTERIOR ELEVATION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
A8.1
BUILDING SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
DETAIL SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
WALL GRID
(REPRESENTS
FACE OF EXISTING
WALL)
XX.X
XX.X
ELEVATION
0'-0"
ROOM
NAME
101A
NORTH
PLAN
NORTH
TRUE
0 4 8 16
DEMOLITION KEYNOTE WINDOW TYPE
WALL TYPE
ROOF PITCH SYMBOL
DOOR NUMBER
TYPICAL KEYNOTE CEILING/ SOFFIT
HEIGHT
MATL
1'-0"
W1
P
-1
SITE NOTES
1. WORKING SPACE AND SPACE AVAILABLE FOR STORING MATERIALS SHALL
BE AS DETERMINED BY THE COR
2. KEEP ROADS CLEAR OF CONSTRUCTION MATERIAL, DEBRIS, STANDING
CONSTRUCTION EQUIPMENT AND VEHICLES AT ALL TIMES. DO NOT STORE
MATERIALS AND EQUIPMENT IN OTHER THAN ASSIGNED AREAS.
3. SCHEDULE DELIVERY OF MATERIALS AND EQUIPMENT TO IMMEDIATE
CONSTRUCTION WORKING AREAS IN QUANTITIES SUFFICIENT FOR NOT
MORE THAN TWO WORK DAYS. PROVIDE UNOBSTRUCTED ACCESS TO
MEDICAL CENTER AREAS REQUIRED TO REMAIN IN OPERATION.
4. COORDINATE WITH COR FOR REMOVAL OF EXISTING FURNISHINGS AND
EQUIPMENT TO PERMIT WORK TO PROCEED.
5. COORDINATE THE WORK FOR THIS CONTRACT WITH OTHER
CONSTRUCTION OPERATIONS AS DIRECTED BY COR. THIS INCLUDES THE
SCHEDULING OF TRAFFIC AND THE USE OF ROADWAYS.
6. UTILITIES SERVICES: MAINTAIN EXISTING UTILITY SERVICES FOR MEDICAL
CENTER AT ALL TIMES. PROVIDE TEMPORARY FACILITIES, LABOR,
MATERIALS, EQUIPMENT, CONNECTIONS, AND UTILITIES TO ASSURE
UNINTERRUPTED SERVICES AS REQUIRED BY THE DRAWINGS AND
SPECIFICATIONS. WHERE NECESSARY TO CUT EXISTING WATER, STEAM,
GASES, SEWER OR AIR PIPES, OR CONDUITS, WIRES, CABLES, ETC. OF
UTILITY SERVICES OR OF FIRE PROTECTION SYSTEMS AND
COMMUNICATIONS SYSTEMS (INCLUDING TELEPHONE), THEY SHALL BE
CUT AND CAPPED AT SUITABLE PLACES WHERE SHOWN; OR, IN ABSENCE
OF SUCH INDICATION, WHERE DIRECTED BY COR.
7. OBTAIN ASBESTOS ABATEMENT PLANS FROM VA COR PRIOR TO START OF
WORK. COMPLETE WORK FOR ASBESTOS ABATEMENT PRIOR TO THE
START OF CONSTRUCTION OR DEMOLITION. REFER TO SPECIFICATIONS
FOR REQUIREMENTS FOR ASBESTOS ABATEMENT.
8. COORDINATE PROJECT PHASING WITH COR.
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
FULLY SPRINKLERED
C:\Users\esanborn\Documents\Revit\A_BUILDING 58 - REPLACE FCU - 18-152_esanborn.rvt
6/12/2019 11:04:09 AM
58-G-002
GENERAL SYMBOLS,
ABBREVIATIONS AND NOTES
1900 E Main St, Danville, IL 61832
DGC, ES
LW
JUNE 11, 2019
REPLACE F58-4 FCUS AND
HOT/CHILLED WATER PIPING
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
ABBREVIATIONS
GENERAL SYMBOL LEGEND
SURGERY
ROOM
SURGERY
ROOM
OFFICE
PCC
EXAM
CORR.
C3-11
TLT.
346A
TLT.
347A
3 5/8" INSULATED WALL WITH
16 GAUGE METAL STUDS @
16" O.C. WALL TO EXTEND TO
UNDERSIDE OF DECK
5/8" FIRE RESISTANT GYPSUM
BOARD - BOTH SIDES
EXISTING CEILING SYSTEM
BASE - TO MATCH
EXISTING AREA
EXISTING FLOOR
UNDERSIDE OF EXISTING
DECK
C E
IL
IN
G H
E
IG
H T
V A
R
IE
S F
IE
L D
V E
R
IF
Y
W A
L L
H E
IG
H
T V
A R
IE
S
F
IE
L D
V E
R
IF
Y
5"
5/8" FIRE RESISTANT GYPSUM
BOARD - BOTH SIDES
EXISTING CEILING SYSTEM
BASE - TO MATCH
EXISTING AREA
EXISTING FLOOR
UNDERSIDE OF EXISTING
DECK
C E
IL
IN
G H
E
IG
H T
V A
R
IE
S F
IE
L D
V E
R
IF
Y
W A
L L
H E
IG
H
T V
A R
IE
S
F
IE
L D
V E
R
IF
Y
5"
3 5/8" 16 GAUGE METAL
STUDS @ 16" O.C. WALL TO
EXTEND TO UNDERSIDE OF
DECK
A B
ILSM SIGNAGE
INTERIM LIFE SAFETY MEASURES IN EFFECT FOR THE
REPLACE F58-4 FCUS AND HOT/CHILLED WATER PIPING
• THIS EXIT IS CLOSED AND LEADS TO A
CONSTRUCTION AREA
• PLEASE USE ALTERNATE EXITS AS MARKED
PLASTIC WINDOW
SWIVEL CASTERS
WITH TWO
LOCKING BRAKES
MOBILE CART
A D
J U
S T
A B
L E
H
E
IG
H T
HEPA NEGATIVE AIR UNIT
EXISTING WALL
EXISITNG CEILING
FLEX DUCT
A. TAPE ALL SERVICES TO PROTECT AGAINST
CONTAMINATION.
B. THE CONTRACTOR SHALL NOT HAUL DEBRIS
THROUGH PATIENT-CARE AREAS WITHOUT
PRIOR APPROVAL OF THE COR AND THE
MEDICAL CENTER.
C. USING A HEPA VACUUM, CLEAN INSIDE THE
BARRIER AND VACUUM CEILING TILE PRIOR TO
REPLACEMENT. ANY CEILING ACCESS PANELS
OPENED FOR INVESTIGATION BEYOND
SEALED AREAS SHALL BE SEALED
IMMEDIATELY WHEN UNATTENDED.
D. AT COMPLETION, REMOVE CONSTRUCTION
BARRIERS AND CEILING PROTECTION
CAREFULLY, OUTSIDE OF NORMAL WORK
HOURS. VACUUM AND CLEAN ALL SURFACES
FREE OF DUST AFTER THE REMOVAL.
E. ASBESTOS ABATEMENT WILL BE REQUIRED
AS PART OF THIS PROJECT. REFER TO
EXISTING ACM SURVEY BY VA FOR EXTENTS
AND SCOPE OF ASBESTOS REMOVAL.
58-G-003
A .F
.F
ISLM TEMPORARY BARRIER TAG
PROJECT:
PRIME CONTRACTOR:
SUB CONTRACTOR:
EMERGENCY CONTACT NO.:
BARRIER INSTALLATION DATE:
BARRIER EXPIRATION DATE:
# SHEET KEY NOTES:
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
SHEET NOTES:
FULLY SPRINKLERED
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
C:\Users\esanborn\Documents\Revit\A_BUILDING 58 - REPLACE FCU - 18-152_esanborn.rvt
6/12/2019 11:04:10 AM
58-G-003
TYPICAL ICRA DETAILS AND NOTES
1900 E Main St, Danville, IL 61832
DGC, ES
LW
JUNE 11, 2019
REPLACE F58-4 FCUS AND
HOT/CHILLED WATER PIPING
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
Scale: 3/4" = 1'-0"
ICRA WALL TYPES
Scale: No Scale
ILSM SIGNAGE
Scale: No Scale
MOBILE CONTAINMENT CART
01 PROVIDE A MINIUM 6'-0" X 4'-0" WALK OFF
MATT INSIDE OF THE WORK AREA. CHANGE
WHEN NECESSARY TO MAINTAIN
CLEANLINESS.
02 PROVIDE STICKY MATS, CHANGED AT END
OF SHIFT OR MORE IN NECESSARY TO
MAINTAIN CLEANLINESS.
03 POST I.C.R.A. I.L.S.M. FIRE INSPECTION TAGS
VISIBLE TO THE PUBLIC. REFER TO SHEET
G-003 DETAIL 3 FOR DETAILS.
04 CONSTRUCTION SIGN: INFORMATION
DESIGNATING THE SPECIFIC DEPARTMENT
OF VETERNS AFFAIRS PROJECT UNDER
CONSTRUCTION AS WELL AS THE NAE OF
THE GENERAL CONTRACTOR AND OTHER
PROJECT SPECIFIC CONSULTANTS. REFER
TO SHEET G-003 DETAIL 5 FOR MORE
INFORMATION.
05 SUSPENDED PLASTIC ZIPPER WALL CURTAIN
BARRIER.
06 FIRE EXTINGUISHER ON PORTABLE FLOOR
BRACKET.
07 HEPA FILTRATION IS REQUIRED WHERE THE
EXHAUST DUST MAY RE-ENTER THE
BREATHING ZONE. CONTRACTOR SHALL
VERIFY THAT CONSTRUCTION EXHAUST TO
EXTERIOR IS NOT REINTRODUCED TO THE
MEDICAL CENTER THROUGH INTAKE VENTS,
OR BUILDING OPENINGS.
Scale: 1/8" = 1'-0"
TYPICAL CONSTRUCTION LAYOUT
Scale: 1/4" = 1'-0"
TYPICAL INTERIOR
ELEVATION
Scale: No Scale
ISLM TEMPORARY BARRIER TAG
FHC
E P
UCR
1 / 2
9.1 10 11.1 11.9 13 13.8 14.9 16.1 17.2 18.1 19 20 21 22
G
H
G.7
J
K
L
M
N
10.8 12.2
10.7 12.3 20.7
M.8
14.2 15.6 16.6 17.814 15 16 17 18
TLT
337A
EXAM
RM
MED
OFFICE
COMM.
CHUTE
CORR.
C3-2
PHYS.
OFFICE
LINEN
RM
SOCIAL
WORKERS
OFFICE
CHIEF
PULM.
MITS &
RTS
CORR.
C3-1
CORR.
C3-3
SOIL
HOLD
PUBLIC
TLT
STAFF
TLT
333D
CORR.
C3-4
PHYS.
OFFICE
333C
STAFF
LOUNGE
333B
WARD
CLERK
333A
TLT
332A
PATIENT
RM
TLT
331A
CARDIO
EXAM
RM
WAITING/KITCHENETTE
TLT
330B
EXAM
RM
330C
WORK
AREA
330A
EXAM
RM
330D
SUPERV.
OFFICE
EQUIP.
STORAGE
SUPERV.
OFFICE
330F
E.C.
CORR.
C3-5
CARDIO
NP
OFFICE
EXAM
RM
330E
WAIT/
COMFORT
PULM.
RECPT.
PFT
CORR.
C3-8
CPAP
BC/EEG
PANTRY
P.L.
STORAGE
321A
OFFICE
MED.
GAS
STORAGE
PAT'NT
TLT
EXAM
CORR.
C3-6
OFFICE
OFFICE
RESIDENT
WORK
RESIDENT
WORK
CORR.
C3-7
EXAM
EXAM
EXAM
STAIR #1
STAIR #2
EQUIP
ALCOVE
A -0
A -0
A -0
A -0
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
FULLY SPRINKLERED
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
C:\Users\esanborn\Documents\Revit\A_BUILDING 58 - REPLACE FCU - 18-152_esanborn.rvt
6/12/2019 11:04:03 AM
58-A-001
THIRD FLOOR PLAN (REFERENCE
ONLY)
1900 E Main St, Danville, IL 61832
DGC, EGS
LW
JUNE 11, 2019
REPLACE F58-4 FCUS AND
HOT/CHILLED WATER PIPING
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
0 4 8 16
NORTH
PLAN
Scale: 1/8" = 1'-0"
THIRD FLOOR PLAN (REFERENCE ONLY)
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
FF 2 3 4 4.8 5.8 6.9 8.1 9.1
H
G.7
J
K
L
M
N
2.3
5 6 7 8
5.1 6.4 7.4
8.8
M.8
A -0
A -0
A -0
A -0
LPN
OFFICE
ORTHO
RM
ANTE
351A ORTHO
TELEH.
RM
WORK
TLT
352A
TLT
350A
TLT
349A
CORR.
C3-12
STOR.
CORR.
C3-10
SURG.
TELEH.
RM
CORR.
C3-11
OFFICE
PCC
EXAM
SURGERY
RM
SURGERY
RM
TLT
346A
TLT
347A
EXAM
RM
TLT
344A
TLT
343A
WAITING
RM
E.C.
CORR.
C3-9
EXAM
RM
E.C.
EXAM
RM
NOURISH.
OFFICE
TLT
341A
EXAM
RM
NURSE
STATION
EXAM
RM
TLT
339A
TLT
337A
JAN. CL.
EXAM
RM
CORR.
C3-9
MED
OFFICE
58-G-003
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
FULLY SPRINKLERED
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
C:\Users\esanborn\Documents\Revit\A_BUILDING 58 - REPLACE FCU - 18-152_esanborn.rvt
6/12/2019 11:04:03 AM
58-A-002
THIRD FLOOR PLAN (REFERENCE
ONLY)
1900 E Main St, Danville, IL 61832
DGC
LW
JUNE 11, 2019
REPLACE F58-4 FCUS AND
HOT/CHILLED WATER PIPING
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
0 4 8 16
NORTH
PLAN
Scale: 1/8" = 1'-0"
THIRD FLOOR PLAN (REFERENCE ONLY)
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
E P
STAIR #1
STAIR #2
10 11.1
11.9 13 13.8 14.9 16.1 17.2 18.1 19 20 21 22
G
H
G.7
J
K
L
M
N
10.8 12.2
10.7 12.3 20.7
M.8
14.2 15.6 16.6 17.814 15 16 17 18
COMM.
CHUTE
CORR.
C3-2
PHYS.
OFFICE
LINEN
RM
SOCIAL
WORKERS
OFFICE
CHIEF
PULM.
MITS &
RTS
CORR.
C3-1
CORR.
C3-3
SOIL
HOLD
PUBLIC
TLT
STAFF
TLT
333D
CORR.
C3-4
PHYS.
OFFICE
333C
STAFF
LOUNGE
333B
WARD
CLERK
333A TLT
332A
PATIENT
RM
TLT
331A
CARDIO
EXAM
RM
WAITING/KITCHENETTE
TLT
330B
EXAM
RM
330C
WORK
AREA
330A
EXAM
RM
330D
SUPERV.
OFFICE
EQUIP.
STORAGE
SUPERV.
OFFICE
330F
E.C.
CORR.
C3-5
CARDIO
NP
OFFICE
EXAM
RM
330E
WAIT/
COMFORT
PULM.
RECPT.
PFT
CORR.
C3-8
CPAP
BC/EEG
PANTRY
P.L.
STORAGE
321A
OFFICE
MED.
GAS
STORAGE
PAT'NT
TLT
EXAM
CORR.
C3-6
OFFICE
OFFICE
RESIDENT
WORK
RESIDENT
WORK
CORR.
C3-7
EXAM
EXAM
EXAM
04 04
8' - 6"
GWB
7' - 11"
ACT
8' - 0"
ACT
9' - 6"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 5"
GYP
7' - 11"
ACT
7' - 11"
ACT
7' - 1"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 1"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 1"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
8' - 5"
ACT
7' - 11"
ACT
7' - 11"
ACT
8' - 5"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
8' - 3"
ACT
7' - 11"
ACT
9' - 0"
ACT
8' - 11"
ACT
8' - 11"
ACT 8' - 6"
ACT
7' - 1"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
9' - 0"
ACT
8' - 0"
ACT
9' - 6"
ACT
9' - 6"
ACT
9' - 5"
ACT
9' - 5"
ACT
9' - 6"
ACT
9' - 6"
ACT
9' - 6"
ACT
9' - 8"
ACT
9' - 7"
ACT
9' - 7"
ACT
9' - 7"
ACT
9' - 6"
ACT
7' - 11"
ACT
7' - 11"
ACT
7' - 11"
ACT
8' - 6"
GWB
7' - 11"
ACT
SD
REMOVE AND REPLACE
PORTION OF ACOUSTIC CEILING
AS REQUIRED TO FACILITATE
MECHANICAL WORK ABOVE
CEILING.
TEMPORARY SUPPORT CEILING
MOUTNED DEVICES UNTIL
CEILING IS RE-INSTALLED.
REMOVE EXISTING GYPSUM
BOARD CEILING AND SUPPORT
FRAMING. REMOVE EXISTING
CEILING MOUNTED DEVICES.
PROVIDE NEW SUSPENDED
ACOUSTICAL CEILING.
- SEE MECHANCIAL AND
ELECTRICAL DRAWINGS FOR
NEW CEILING MOUNTED
DEVICES.
03 EXISTING PATIENT LIFT AND SUPPORT
FRAMING TO REMAIN.
04 REMOVE EXISTING SUSPENDED
ACOUSTIC CEILING WINDOW POCKET.
CONSTRUCT NEW WINDOW POCKET.
- SEE DETAIL 2/A-112
EXISTING WINDOW POCKET TO REMAIN.
CONSTRUCT NEW BULKHEAD. REFINISH
WINDOW POCKET.
- SEE DETAIL 2/A-112, SIM
# SHEET KEY NOTES:
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
FULLY SPRINKLERED
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
C:\Users\esanborn\Documents\Revit\A_BUILDING 58 - REPLACE FCU - 18-152_esanborn.rvt
6/12/2019 11:04:08 AM
58-AD111
THIRD FLOOR REFLECTED CEILING
DEMOLITON PLAN
1900 E Main St, Danville, IL 61832
DGC
LW
JUNE 11, 2019
REPLACE F58-4 FCUS AND
HOT/CHILLED WATER PIPING
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
Scale: 1/8" = 1'-0"
THIRD FLOOR REFLECTED CEILING DEMOLITION PLAN 0 4 8 16
NORTH
PLAN
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
STAIR #1
STAIR #3
FF 2 3 4 4.8 5.8 6.9 8.1 9.1
H
G.7
J
K
L
M
N
2.3
5 6 7 8 95.1 6.4 7.4 8.8
M.8
LPN
OFFICE
ORTHO
RM
ANTE
351A
ORTHO
TELEH.
RM
WORK
TLT
352A
TLT
350A
TLT
349A
CORR.
C3-12
STOR.
CORR.
C3-10
SURG.
TELEH.
RM
CORR.
C3-11OFFICE
PCC
EXAM
SURGERY
RM
SURGERY
RM
TLT
346A
TLT
347A
EXAM
RM
TLT
344A
TLT
343A
WAITING
RM
E.C.
CORR.
C3-9
EXAM
RM
E.C.
EXAM
RM
NOURISH.
OFFICE
TLT
341A
EXAM
RM
NURSE
STATION
EXAM
RM
TLT
339A
TLT
337A
JAN. CL.
EXAM
RM
CORR.
C3-9
MED
OFFICE
A D
A -1
A D
A -1
05 05
REMOVE AND REPLACE
PORTION OF ACOUSTIC CEILING
AS REQUIRED TO FACILITATE
MECHANICAL WORK ABOVE
CEILING.
TEMPORARY SUPPORT CEILING
MOUTNED DEVICES UNTIL
CEILING IS RE-INSTALLED.
REMOVE EXISTING GYPSUM
BOARD CEILING AND SUPPORT
FRAMING. REMOVE EXISTING
CEILING MOUNTED DEVICES.
PROVIDE NEW SUSPENDED
ACOUSTICAL CEILING.
- SEE MECHANCIAL AND
ELECTRICAL DRAWINGS FOR
NEW CEILING MOUNTED
DEVICES.
03 EXISTING PATIENT LIFT AND SUPPORT
FRAMING TO REMAIN.
04 REMOVE EXISTING SUSPENDED
ACOUSTIC CEILING WINDOW POCKET.
CONSTRUCT NEW WINDOW POCKET.
- SEE DETAIL 2/A-112
EXISTING WINDOW POCKET TO REMAIN.
CONSTRUCT NEW BULKHEAD. REFINISH
WINDOW POCKET.
- SEE DETAIL 2/A-112, SIM
# SHEET KEY NOTES:
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
FULLY SPRINKLERED
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
C:\Users\esanborn\Documents\Revit\A_BUILDING 58 - REPLACE FCU - 18-152_esanborn.rvt
6/12/2019 11:04:08 AM
58-AD112
THIRD FLOOR REFLECTED CEILING
DEMOLITION PLAN
1900 E Main St, Danville, IL 61832
DGC
LW
JUNE 11, 2019
REPLACE F58-4 FCUS AND
HOT/CHILLED WATER PIPING
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
0 4 8 16
NORTH
PLAN
Scale: 1/8" = 1'-0"
THIRD FLOOR REFLECTED CEILING DEMOLITION PLAN
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
10 11.1 11.9 13 13.8 14.9 16.1 17.2 18.1 19 20 21 22
G
H
G.7
J
K
L
M
N
10.8 12.2
1210.7 12.3
20.7
M.8
14.2 15.6 16.6 17.814 15 16 17 18
3 BED
CORR.
C4-1
STAIR #1
TIP
CHUTE
CORR.
C4-2
OPTHALMOLOGY
EXAM
OPTHALMOLOGY
TESTING
RM
PT.
WAITING
TLT
437A
3 BED
TREATMENT
RM
OFFICE
CA1
TLT
406A
X-RAY
STORAGE
SOILED
UTILITY
ENDO
HOLDING
ENDOSCOPY
(TB)
EQUIP.
433A
STRG
OFFICE
LOUNGE
ENDOSCOPY
EQUIP.
432A
STORAGE
432B
E.C.
TLT
STAIR #2
NURSE
STATION
RESTROOM
CLEAN
UTIL
TLT
428A
MED. RM
430A
NURSE
SUPERVISOR
430B
OFFICE
PHYSICIAN
EXAM
EXAM
CORR.
C4-3
CORR.
C4-4 EXAM
WAITING
RM
PHYSICIANS
OFFICE
CYSTO
CLINIC
NURSE
423P.A.
(MOLLY)
CORR.
C4-5RESTROOM
STRG
NURSING
MOTHERS
RESTROOM
STRG
A -0
A -0
A -0
A -0
REMOVE EXISTING FCU AND REPLACE
WITH NEW UNIT. PATCH AND REPAIR
FLOOR AND WALL FINISHES.
REMOVE EXISTING RADIATOR. PATCH
AND REPAIR FLOOR AND WALL
FINISHES.
- SEE DETAIL 2/A-102 FOR DETAIL OF
NEW LOUVER.
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
SHEET NOTES:
FULLY SPRINKLERED
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
C:\Users\esanborn\Documents\Revit\A_BUILDING 58 - REPLACE FCU - 18-152_esanborn.rvt
6/12/2019 11:04:04 AM
58-A-101
FOURTH FLOOR PLAN
1900 E Main St, Danville, IL 61832
DGC, ES
LW
JUNE 11, 2019
REPLACE F58-4 FCUS AND
HOT/CHILLED WATER PIPING
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
Scale: 1/8" = 1'-0"
FOURTH FLOOR PLAN
LEGEND
0 4 8 16
NORTH
PLAN
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A. ROOMS 404, 417 AND 419 WHERE
EXISTING FAN COIL UNITS WERE
REMOVED, A NEW UNIT IS NOT NEEDED
AND, WALL AND FLOOR PATCHING IS
REQUIRED.
FF 2 3 4 4.8 5.8 6.9 8.1 9.1
H
G.7
J
K
L
M
N
2.3 5 6 7 8 95.1 6.4 7.4 8.8
M.8
O.D.
SLEEPING
RM
2 BED
OFFICE
CORR.
C4-7
MED.
SUPPLY
STOR.
HSK
MED.
SUPPLY
STOR.
3 BED
4 BED
3 BED
OFFICE
TLT
447A
CLEAN
UTIL.
TLT
STORAGE
444A
RESTROOM
CORR.
C4-6
457A
E.C.
MED. RM
442B
NURSES
STATION
SHOWER
TREATMENT
RM
3 BED
2 BED
3 BED
SOILED
UTILITY
LINEN
RM
462 464
A -0
A -0
A -0
A -0
REMOVE EXISTING FCU AND REPLACE
WITH NEW UNIT. PATCH AND REPAIR
FLOOR AND WALL FINISHES.
REMOVE EXISTING RADIATOR. PATCH
AND REPAIR FLOOR AND WALL
FINISHES.
- SEE DETAIL 2/A-102 FOR DETAIL OF
NEW LOUVER.
SILICONE SEALANT AT
PERIMETER OF COVER
PLATE (CONT.)
STAINLESS STEEL MASONRY
FASTENERS AT EACH COVER
OF PLATE - MIN. 1" EMBED.
NEW ALUMINUM LOUVER - SEE
MECHANICAL DRAWINGS
LOUVER TO BE PREFINISHED W/
KYNAR COATING. COLOR TO
MATCH EXISTING LOUVERS.
EXISTING BRICK VENEER
TO REMAIN
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
FULLY SPRINKLERED
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
C:\Users\esanborn\Documents\Revit\A_BUILDING 58 - REPLACE FCU - 18-152_esanborn.rvt
6/12/2019 11:04:05 AM
58-A-102
FOURTH FLOOR PLAN
1900 E Main St, Danville, IL 61832
DGC
LW
JUNE 11, 2019
REPLACE F58-4 FCUS AND
HOT/CHILLED WATER PIPING
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
0 4 8 16
NORTH
PLAN
Scale: 1/8" = 1'-0"
FOURTH FLOOR PLAN
LEGEND
Scale: 3" = 1'-0"
DETAIL AT EXTERIOR LOUVER
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
E P
339A
STAIR #1
STAIR #2
E
E E E
E E E E E E
E
E
E
E
E
EEE
E
E
E
E
E
E
E E
E
REFLECTED CEILING PLAN
LEGEND
DENOTES GWB
SOFFIT/CEILING
CEILING HEIGHT
DESIGNATION
(WHEN HEIGHT
VARIES FROM
TYPICAL)
WIRELESS
COMMUNICATION
EQ. A EQ. A
E Q
B
E Q
B
EXIT SIGN (SHADED
AREA INDICATES
DIRECTION OF
EGRESS)
MECHANICAL SUPPLY
MECHANICAL RETURN
DOWN LIGHT
FIXTURE
1' - 0"
MATL
OUTLET
FIRE ALARM
STROBE
FAA
FIRE ALARM
ENUNCIATOR
F
FIRE ALARM PULL
STATION
FIRE ALARM
STROBE LIGHT
SD
H
HEAT DETECTOR
SMOKE DETECTOR
FIRE ALARM / HORN /
STROBE LIGHT -
CEILING MOUNTED
SPRINKLER HEAD
2'x4' LAY-IN
FIXTURE
EXHAUST GRILL
PATIENT LIFT
SUPPORT LEGS
WHERE OCCURS
ACCESS DOOR
CURTAIN TRACK
NEW PORTION OF ACOUSTIC
CEILING AS REQUIRED TO
FACILITATE MECHANICAL WORK
ABOVE CEILING.
TEMPORARY SUPPORT CEILING
MOUNTED DEVICES UNTIL
CEILING IS RE-INSTALLED.
02 EXISTING PATIENT LIFT AND SUPPORT
FRAMING.
03 NEW WINDOW POCKET
- SEE DETAIL 2/A-112.
9.1 10 11.1 11.9 13 13.8 14.9 16.1 17.2 18.1 19 20 21 22
G
H
G.7
J
K
L
M
N
9 11
10.8 12.2
10.7 12.3 20.7
M.8
14.2 15.6 16.6 17.814 15 16 17 18
A -1
A -1
A -1
A -1
TLT
337A
JAN. CL.
EXAM
RM
CORR.
C3-9
MED
OFFICE
COMM.
CHUTE
CORR.
C3-2
PHYS.
OFFICE
LINEN
RM
SOCIAL
WORKERS
OFFICE
CORR.
C3-1
CORR.
C3-3
SOIL
HOLD
PUBLIC
TLT
STAFF
TLT
333D
CORR.
C3-4
PHYS.
OFFICE
333C
STAFF
LOUNGE
333B
WARD
CLERK
333A
TLT
332A
PATIENT
RM
TLT
331A
CARDIO
EXAM
RM
WAITING/KITCHENETTE
TLT
330B
EXAM
RM
330C
WORK
AREA
330A
EXAM
RM
330D
SUPERV.
OFFICE
EQUIP.
STORAGE
SUPERV.
OFFICE
330F
E.C.
CORR.
C3-5
CARDIO
NP
OFFICE
EXAM
RM
330E
WAIT/
COMFORT
PULM.
RECPT.
PFT
CORR.
C3-8
CPAP
BC/EEG
PANTRY
P.L.
STORAGE
321A
OFFICE
MED.
GAS
STORAGE
PAT'NT
TLT
EXAM
CORR.
C3-6
OFFICE
OFFICE
RESIDENT
WORK
RESIDENT
WORK
CORR.
C3-7
EXAM
EXAM
EXAM
JAN. CL.
CORR.
C3-9
03 03
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
FULLY SPRINKLERED
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
C:\Users\esanborn\Documents\Revit\A_BUILDING 58 - REPLACE FCU - 18-152_esanborn.rvt
6/12/2019 11:04:06 AM
58-A-111
THIRD FLOOR REFLECTED CEILING
PLAN
1900 E Main St, Danville, IL 61832
DGC, EGS
LW
JUNE 11, 2019
REPLACE F58-4 FCUS AND
HOT/CHILLED WATER PIPING
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
0 4 8 16
NORTH
PLAN
KEYNOTES
Scale: 1/8" = 1'-0"
THIRD FLOOR REFLECTED CEILING PLAN
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
MED.
OfficeSTAIR #3
Exam
ROOM
E
E
E
E
E
E
E
E E
E E E E E
EE
E
EXISTING
EXTERIOR WALL
TO REMAIN
3 5/8" METAL STUDS
ATTACHED TO EXISTING
STRUCTURE
5/8" GYPSUM
WALL BOARD
SEE REFLECTED
CEILING PLAN
CORNER BEAD
FV
1'-6"
REFLECTED CEILING PLAN
LEGEND
DENOTES GWB
SOFFIT/CEILING
CEILING HEIGHT
DESIGNATION
(WHEN HEIGHT
VARIES FROM
TYPICAL)
WIRELESS
COMMUNICATION
EQ. A EQ. A
E Q
B
E Q
B
EXIT SIGN (SHADED
AREA INDICATES
DIRECTION OF
EGRESS)
MECHANICAL SUPPLY
MECHANICAL RETURN
DOWN LIGHT
FIXTURE
1' - 0"
MATL
OUTLET
FIRE ALARM
STROBE
FAA
FIRE ALARM
ENUNCIATOR
F
FIRE ALARM PULL
STATION
FIRE ALARM
STROBE LIGHT
SD
H
HEAT DETECTOR
SMOKE DETECTOR
FIRE ALARM / HORN /
STROBE LIGHT -
CEILING MOUNTED
SPRINKLER HEAD
2'x4' LAY-IN
FIXTURE
EXHAUST GRILL
PATIENT LIFT
SUPPORT LEGS
WHERE OCCURS
ACCESS DOOR
CURTAIN TRACK
NEW PORTION OF ACOUSTIC
CEILING AS REQUIRED TO
FACILITATE MECHANICAL WORK
ABOVE CEILING.
TEMPORARY SUPPORT CEILING
MOUNTED DEVICES UNTIL
CEILING IS RE-INSTALLED.
02 EXISTING PATIENT LIFT AND SUPPORT
FRAMING.
03 NEW WINDOW POCKET
- SEE DETAIL 2/A-112.
FF 2 3 4 4.8 5.8 6.9 8.1 9.1
H
G.7
J
K
L
M
N
2.3
5 6 7 8 95.1 6.4 7.4 8.8
M.8
A -1
A -1
A -1
A -1
TLT
337A
JAN. CL.
CORR.
C3-9
LPN
OFFICE
ORTHO
RM
ANTE
351A
ORTHO
TELEH.
RM
WORK
TLT
352A
TLT
350A
TLT
349A
CORR.
C3-12
STOR.
CORR.
C3-10
SURG.
TELEH.
RM
CORR.
C3-11
OFFICE
PCC
EXAM
SURGERY
RM
SURGERY
ROOM
347 TLT
346A
TLT
347A
EXAM
RM
TLT
344A
TLT
343A
WAITING
RM
E.C.
CORR.
C3-9
EXAM
RM
E.C.
EXAM
RM
NOURISH.
OFFICE
TLT
341A
EXAM
RM
NURSE
STATION
EXAM
RM
TLT
339A
JAN. CL.
CORR.
C3-9
1 1 1
01 01
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
FULLY SPRINKLERED
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
C:\Users\esanborn\Documents\Revit\A_BUILDING 58 - REPLACE FCU - 18-152_esanborn.rvt
6/12/2019 11:04:07 AM
58-A-112
THIRD FLOOR REFLECTED CEILING
PLAN
1900 E Main St, Danville, IL 61832
DGC
LW
JUNE 11, 2019
REPLACE F58-4 FCUS AND
HOT/CHILLED WATER PIPING
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
0 4 8 16
NORTH
PLAN
Scale: 1 1/2" = 1'-0"
TYPICAL POCKET WINDOW DETAIL
KEYNOTES
Scale: 1/8" = 1'-0"
THIRD FLOOR REFLECTED CEILING PLAN
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
ACCU AIR-COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERGE
ARI AIR CONDITIONING AND REFRIGERATION
INSTITUTE
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
BDR BASE BOARD RADIATOR
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BIW BACKWARD INCLINED WHEEL (FAN)
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CO CLEAN OUT
COP COEFFICIENT OF PERFORMANCE
CU CONDENSING UNIT
CW COLD WATER (POTABLE)
D CONDENSATE DRAIN
dB DECIBELS Db DRY-BULB TEMPERATURE
DEG DEGREE
DIA DIAMETER
DP DEW POINT TEMPERATURE
DN DOWN
EA EXHASUT AIR
EAT ENTERING AIR TEMPERATURE
ECC ENGINEERING CONTROL CENTER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
F FARENHEIT
FCU FAN COIL UNIT
FM FLOW METER
FPM FEET PER MINUTE
FT FEET
FT-LB FOOT-POUND
GA GAUGE
GAL GALLONS
GPM GALLONS PER MINUTE
H HUMIDIFER
HAC HOUSEKEEPING AID CLOSET
HC HEATING COIL
HD HEAD
HHW HEATING HOT WATER
HWC HEATING HOT WATER COIL
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
HP HORSEPOWER
HSTAT HUMIDISTAT
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
Hz HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
ID INSIDE DIAMETER
INWG INCHES WAATER GAUGE
IN-LB INCH-POUND
kW KILOWATT kWh KILOWATT HOUR
LAT LEAVING AIR TEMPERATURE
LH LATENT HEAT
LWT LEAVING WATER TEMPERATURE
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAX MAXIMUM
MBH 1000 BTUH
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MTD MEAN TEMPERATURE DIFFERENCE
NA NOT APPLICABLE
NC NOISE CRITERIA
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NTS NOT TO SCALE
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
P PUMP
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PF PRE-FILTER
PG PRESSURE GAGE
PHC PREHEAT COIL
PHCP PREHEAT COIL PUMP
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH –
ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
RA RETURN AIR
RAT RETURN AIR TEMPERATURE
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
SA SUPPLY AIR
SAT SUPPLY AIR TEMPERATURE
SEN SENSIBLE HEAT
SF SUPPLY FAN
SI SQUARE INCHES
SP STATIC PRESSURE
SQ FT SQUARE FOOT (FEET)
TD TEMPERATURE DIFFERENCE
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
UV UNIT VENTILATOR
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED
BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
W WATTS
Wb WET-BULB (TEMPERATURE)
MECHANICAL ABBREVIATIONS
1. WORK SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND APPLICABLE VA STANDARDS.
2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.
3. OBTAIN AND PAY FOR PERMITS, FEES, AND INSPECTIONS REQUIRED FOR THIS WORK.
4. PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE GRADE FOR THE PURPOSES INTENDED.
5. WHERE POSSIBLE, PROVIDE STANDARD PRODUCTS OF THE VARIOUS MANUFACTURERS EXCEPT WHERE SPECIAL CONSTRUCTION OR PERFORMANCE FEATURES ARE
REQUIRED.
6. EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS SHALL BE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY AND CAPACITY TO THAT EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.
7. PROVIDE MECHANICAL EQUIPMENT THAT IS LISTED AND LABELED BY UNDERWRITERS LABORATORIES (U.L.).
8. INSTALL EQUIPMENT AS INDICATED, ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR EQUIPMENT MAINTENANCE, REPAIRS, AND REPLACEMENT.
9. INSTALL EQUIPMENT WITH PROPER CLEARANCES FOR REQUIRED PIPING AND ELECTRICAL SERVICES AND CONNECTIONS. INSTALL EQUIPMENT WITH REQUIRED ACCESS AND CLEARANCES IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS AND APPLICABLE CODES AND STANDARDS.
10. COORDINATE LOCATION, INSTALLATION, AND ROUTING OF DUCTWORK, PIPING, AND EQUIPMENT WITH WORK OF ALL OTHER TRADES.
11. PROVIDE SUPPORT FOR MECHANICAL EQUIPMENT. COORDINATE SUPPORT LOCATIONS WITH ALL CONTRACTORS PRIOR TO INSTALLATION.
12. PROVIDE POWER CONNECTIONS TO EQUIPMENT PROVIDED UNDER THIS CONTRACT AS WORK OF DIVISION 26.
13. PROVIDE CONTROL WIRING FOR MECHANICAL EQUIPMENT AS WORK OF DIVISION 23.
14. DUCTWORK AND PIPING LAYOUTS AND LOCATIONS ARE SCHEMATIC. DO NOT SCALE THESE DRAWINGS. COORDINATE AND DETERMINE EXACT ROUTING OF DUCTWORK AND
PIPING IN THE FIELD.
15. FIELD VERIFY DIMENSIONS BY ACTUAL MEASUREMENT AND OBSERVATION BEFORE ORDERING OR FABRICATING DUCTWORK, PIPING OR EQUIPMENT.
16. NOTIFY COR REGARDING DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND EXISTING CONDITIONS OR DIMENSIONS BEFORE PERFORMING WORK. FAILURE TO VERIFY AND REPORT SHALL CONSTITUTE CONTRACTOR'S ACCEPTANCE OF EXISTING CONDITIONS AS FIT FOR THE PROPER EXECUTION OF THE WORK.
17. SEE ARCHITECTURAL DRAWINGS FOR FINAL LOCATION OF CEILING INSTALLED EQUIPMENT.
18. INSTALL DUCTWORK AND PIPING AS HIGH AS POSSIBLE AND AS CLOSE AS POSSIBLE TO BUILDING WALLS, CEILING AND FLOOR AND ROOF STRUCTURE. PROVIDE OFFSETS, FITTINGS, AND DIMENSIONAL TRANSITIONS NOT SHOWN BUT REQUIRED TO MAINTAIN MINIMUM CLEAR SPACE TO BUILDING SURFACES AT NO ADDITIONAL COST.
19. PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH MECHANICAL WORK OF THIS CONTRACT, UNLESS NOTED OTHERWISE.
20. SUBMIT BOUND SET OF OPERATING AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT AT COMPLETION OF PROJECT.
21. INSTALL ESCUTCHEONS IN ALL PLACES WHERE PIPING PENETRATES A WALL IN AN EXPOSED LOCATION.
22. MAKE A COMPLETE REVIEW OF DRAWINGS, INCLUDING SCHEDULES AND DETAILS, PRIOR TO BEGINNING MECHANICAL SYSTEM INSTALLATION. RESOLVE CONFLICTS WITH
COR.
23. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING SYSTEMS.
24. INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND SERVICE AREAS AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS
ARE NOT ACCEPTABLE UNLESS SPECIFICALLY INDICATED OTHERWISE.
25. INSTALL PIPING FREE OF SAGS AND BENDS.
26. INSTALL PIPING TO ALLOW APPLICATION OF INSULATION.
27. PIPING SHALL NOT BE ROUTED OVER TELECOM OR ELECTRICAL CLOSETS/ROOMS.
28. PREPARE DRAWINGS SHOWING MECHANICAL SYSTEMS AND EQUIPMENT FOR COORDINATION WITH WORK OF OTHER DIVISIONS AND WORK BY THE GOVERNMENT.
A. INCLUDE PLAN VIEWS, SECTIONS, AND ELEVATIONS, AS REQUIRED, TO FULLY COORDINATE ALL NEW WORK WITH ITSELF AND EXISTING CONDITIONS.
B. DRAWINGS SHALL SHOW, BUT NOT BE LIMITED TO, ALL DUCTWORK, AIR DISTRIBUTION, MECHANICAL EQUIPMENT, MECHANICAL PIPING, FIRE PROTECTION PIPING, PLUMBING PIPING, CABLE TRAYS, LIGHTING FIXTURES, CEILING GRID AND HEIGHT, BEAMS AND JOISTS (WITH ELEVATIONS MARKED), ELECTRICAL CONDUIT LARGER THAN 2 INCHES IN DIAMETER AND OTHER CEILING MOUNT DEVICES OR EQUIPMENT THAT PROTRUDE INTO THE CEILING CAVITY.
C. IF THERE ARE OUTSTANDING ISSUES THAT CANNOT BE RESOLVED, CONSULT WITH COR FOR GUIDANCE AND MAKE CORRECTIONS IN ACCORDANCE WITH DIRECTIONS
GIVEN.
D. DO NOT BEGIN FABRICATION OR PLACE EQUIPMENT ORDERS UNTIL COORDINATION DRAWINGS HAVE BEEN APPROVED.
29. INSTALLATION COMMENCED PRIOR TO COORDINATION DRAWING APPROVAL IS TAKEN AT THE CONTRACTORS OWN RISK. MODIFY, MOVE OR RECONFIGURE WORK LACKING
COORDINATION AT NO ADDITIONAL COST
MECHANICAL GENERAL NOTES
YR YEAR
T
CO2 CARBON DIOXIDE
THERMOSTAT
SUPPLY DIFFUSER
RETURN DIFFUSER/GRILLE
EXHAUST GRILLE
ROUND FLEX DUCT
EG-88 2000 DIFFUSER TAG | DIFFUSER CFM
LINEAR SLOT DIFFUSER
BALANCING DAMPER
(RECTANGULAR)
BALANCING DAMPER
(ROUND)
FIRE DAMPER
SMOKE DAMPER
D
R INCLINED RISE, IN
DIRECTION OF AIRFLOW
INCLINED DROP, IN DIRECTION
OF AIRFLOW
CONNECT NEW DUCT
TO EXISTING
LIMIT OF DEMOLITION
VANED ELBOW (PROVIDE ALL
SQUARE OR RECTANGULAR
ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
STANDARD RADIUS ELBOW
(LONG RADIUS)
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
DUCT TRANSITION
SIDE MOUNTED GRILLE
SUPPLY
RETURN45°
45°
DN
DN
UP
UP
DNUP
STANDARD BRANCH SUPPLY OR
RETURN, NO SPLITTER (45° TAP)
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
RETURN DUCT (UP & DOWN)
MECHANICAL LEGEND
LPS
LPR
CHS
CHR
LOW PRESSURE STEAM PIPING
(15 PSI AND BELOW)
LOW PRESSURE STEAM
CONDENSATE RETURN
CHILLED WATER SUPPLY PIPING
CHILLED WATER RETURN PIPING
PIPE UP
PIPE DOWN
BOTTOM CONNECTION
TOP CONNECTION
CAPPED OUTLET
GLOBE VALVE
GATE VALVE
BALL VALVE
STEAM SAFETY VALVE
PRESSURE REGULATING VALVE
WYE STRAINER VALVE
BALANCING VALVE
MOTORIZED CONTROL VALVE
STEAM TRAP
D CONDENSATE DRAIN LINE
HWS
HWR
HEATING HOT WATER SUPPLY
PIPING
CONNECT TO EXISTING PIPE
LIMITS OF DEMOLITION
INLINE CENTRIFUGAL PUMP
TANGENTIAL AIR SEPARATOR
EXPANSION TANK
WALL-MOUNTED INDOOR
SPLIT-SYSTEM
SPLIT-SYSTEM CONDENSING UNIT
UTILITY SET EXHAUST FAN
STEAM PRESSURE
REDUCING STATION
DRAIN VALVE
TEST PLUG
SUPPLY
TERMINAL UNIT SUPPLY
DUCT BRANCH (CONICAL
TAP)
TERMINAL UNIT
CHECK VALVE
HEATING HOT WATER RETURN
PIPING
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
FULLY SPRINKLERED
C:\Users\jterpsta\Documents\M_BUILDING 58 - REPLACE FCU - 18-152_jterpstra.rvt
6/27/2019 2:39:47 PM
58-M-001
MECHANICAL GENERAL
INFORMATION
1900 E Main St, Danville, IL 61832
JT
RCM
JUNE 11, 2019
Replace B58-4 FCUS & Hot/Chilled Water Piping
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
DocuSign Envelope ID: 4CA5BF0B-E86B-4A6C-9D1E-6C734CCECDAD
6/28/2019
CARDIO
ORTHO
ROOM
SOIL
HOLD
SURGERY
ROOM
ORTHO TELEH.
ROOM
SURG. TELEH.
ROOM
SURGERY
ROOM
EXAM
ROOM
TLT
349A
TLT
350A
OFFICE
PCC
TLT
352A
TLT
344A
TLT
337A
TLT
341A
TLT
343A
TLT
339A
TLT
332A
STAFF
TLT
333D
PAT'NT
TLT
WAITING
ROOM
EXAM
ROOM
LPN
OFFICE
CPAP
RESIDENT
WORK
OFFICE
EXAM
OFFICE
OFFICE
EXAM
PANTRY
ANTE
351A
EXAM
WORK
CORR.
C3-12
CORR.
C3-11
STOR.
TLT.
346A
TLT.
347A
NOURSH.
Office
357CLEAN
SUPPLY/UTIL.
EXAM
ROOM
SOCIAL WORKERS
OFFICE
MED.
OFFICE
PHYS.
OFFICE
CHIEF
PULM., MITs &RTs
E.C.
E.C.
EXAM
ROOM
PHYS.
OFFICE
333C
JAN. CL.
WARD
CLERK
333A
EQUIP.
STOR.
STAFF
LOUNGE
333B
WAITING/
KITCHENETTE
E.C.
NP OFFICE
CORR.
C3-9
CORR.
C3-7
CORR.
C3-8
CORR.
C3-5
CORR.
C3-1
SUPERV.
OFFICE
MECH. RM
TLT.
330B
WAIT/
COMFORT
PULM.
RECPT.
MED GAS
STOR.
EXAM
BC/EEG
Office
STAIR #1
PFT
CHART
EQUIP
ALCOVE CHART IP
HOLDPUBLIC
TLT
CORR.
C3-2
TLT
331A
COMM.
CHUTE
STAIR #2STAIR #3
CORR.
C3-10
CORR.
C3-3
P.L.
STOR.
321A
CORR.
C3-6
EQUIP
ALCOVE
NURSE
STATION
LINEN
ROOM
EXAM
ROOM
2-PATIENT
ROOM
CARDIO EXAM
ROOM
RESIDENT
WORK
WORK
AREA
330A
EXAM
Room 330C
EXAM
ROOM
330D
EXAM
ROOM
330E
STORAGE
ROOM
330F
CORR.
C3-4
FHC
FHC
E P
FHC
UCR
1 / 2
3RD FLOOR CONTINUED
1"
D
5" D
D
3/4" D3/4" D3/4" D
D
3/4" D
3/4" D
5" CHR
2" D2" D2" D2" D
1" D
2" D 2" D2" D
D
1"
D
D
D
D
C H R
222120.7201918.117.216.114.913.81312.312.211.911.110.810.7109.18.16.95.84.8432.32FF
F
G
H
G.7
J
K
L
M
M.8
N
17.8
16.6
15.6
14.2
8.8
7.4
6.4
5.1
01 01 01 01
03 03
03 03
03 03
030303030303
030303
0303030303030303
# SHEET KEY NOTES:
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
SHEET NOTES:
FULLY SPRINKLERED
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
C:\Users\jterpsta\Documents\M_BUILDING 58 - REPLACE FCU - 18-152_jterpstra.rvt
6/27/2019 2:40:08 PM
58-MD101
THIRD FLOOR MECHANICAL
DEMOLITION PLAN
1900 E Main St, Danville, IL 61832
JT
RCM
JUNE 11, 2019
Replace B58-4 FCUS & Hot/Chilled Water Piping
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
0 84 16
NORTH
TRUE
01 REMOVE SUPPLY, RETURN AND DRAIN
PIPING AND ASSOCIATED HANGERS AND
SUPPORTS SERVING FAN COIL UNITS ON
FOURTH FLOOR ABOVE.
02 EXISTING SUPPLY AND RETURN RISER TO
REMAIN.
03 REMOVE SUPPLY, RETURN, AND DRAIN
PIPING UP TO CONNECTION AT FAN COIL
UNIT ON FLOOR ABOVE.
04 EXISTING 4" SUPPLY COPPER PIPING TO
REMAIN.
05 REMOVE EXISTING DIFFUSER IN CEILING
AND RETAIN FOR INSTALLATION IN NEW
CEILING GRID. SEE 58-M-101.
06 REMOVE STEAM AND CONDENSATE PIPING
UP TO RADIATOR AND CAP AT MAINS.
Scale: 3/32" = 1'-0"
THIRD FLOOR HVAC DEMOLITION PLAN
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
PHYSICIAN EXAM
EXAM
BATHROOM
STORAGE
C4-4
EXAM
WAITING ROOM
PHYSICIAN'S
CYSTO CLINIC
P.A. (MOLLY)
C4-5
BATHROOM
STORAGE
NURSING MOTHERS
CLEAN UTIL.
RESTROOM
428A
MED. ROOM
430A
NURSE
430B
NURSE'S STATION
STAIR 2
RESTROOM
E.C.
EQUIPMENT
432A
STORAGE
432B
RSTRM
LOUNGE
SUPERVISOR
OFFICE
SOILED
X-RAY
408RESTROOM
406A
TREATMENT
ENDOSCOPY (TB)
ENDOSCOPY
OFFICE
OFFICE
STORAGE UTILITY
EQUIPMENT
433A
3 BED
436437438
RESTROOM
437A
3 BED
STAIR 1
TIP
CHUTE
OPTHALMOLOGY EXAM
C4-1
2 BED
3 BED
NURSE'S
MED. ROOM
442B
E.C.
STORAGE
444A
RESTROOM
C4-6
RESTROOM
SHOWER
458 TREATMENT ROOM
SOILED
LINEN
STATION
UTILITY
ROOM
STAIR 3
CLEAN UTIL.
RESTROOM
447A
3 BED
4 BED
3 BED
OFFICE
2 BED
HSK.
C4-7
STRG
O.D. SLEEPING
OFFICE
OPTHALMOLOGY
TESTING ROOM
CA1
PT. WAITING
NURSE
ENDO
ROOM
ROOM
HOLDING
OFFICE
MED.
SUPPLY
STORG.
MED
SUPPLY
STORG.
C4-3
C4-2
457A T
222120191310432FF
H
J
K
L
M
N
1817161514
98765
01 01
01 02
01 0101 01 01 01 01 01
01 01 01
01 01 01 01 01 01 01
010101
030301 03
03030303
3/4" D
3/4" CHS
3/4" CHR
# SHEET KEY NOTES:
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
SHEET NOTES:
FULLY SPRINKLERED
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
C:\Users\jterpsta\Documents\M_BUILDING 58 - REPLACE FCU - 18-152_jterpstra.rvt
6/27/2019 2:40:09 PM
58-MD102
FOURTH FLOOR MECHANICAL
DEMOLITION PLAN
1900 E Main St, Danville, IL 61832
JT
RCM
JUNE 11, 2019
Replace B58-4 FCUS & Hot/Chilled Water Piping
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
0 84 16
NORTH
TRUE
Scale: 3/32" = 1'-0"
FOURTH FLOOR HVAC DEMOLITION PLAN
01 REMOVE FAN COIL UNIT CONTROLS,
SUPPLY, RETURN, AND DRAIN PIPING DOWN
THROUGH FLOOR. REMOVE MATERIAL
BLOCKING EXISTING WALL LOUVER AND
MAKE READY FOR INSTALLATION OF NEW
UNIT AT THIS LOCATION.
02 EXISTING TO REMAIN.
03 EXISTING RADIATOR AND ALL ASSOCIATED
CONTROLS AND PIPING DOWN THROUGH
FLOOR TO REMAIN.
04 REMOVE FAN COIL UNIT ABOVE CEILING,
INCLUDING ASSOCIATED DUCT, PIPING,
GRILLES, AND CONTROLS. REMOVE
SUPPLY, RETURN, AND DRAIN PIPING BACK
TO MAIN AND CAP
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
CARDIO
ORTHO
ROOM
SOIL
HOLD
SURGERY
ROOM
ORTHO TELEH.
ROOM
SURG. TELEH.
ROOM
SURGERY
ROOM
EXAM
ROOM
TLT
349A
TLT
350A
OFFICE
PCC
TLT
352A
TLT
344A
TLT
337A
TLT
341A
TLT
343A
TLT
339A
TLT
332A
STAFF
TLT
333D
PAT'NT
TLT
WAITING
ROOM
EXAM
ROOM
LPN
OFFICE
CPAP
RESIDENT
WORK
OFFICE
EXAM
OFFICE
OFFICE
EXAM
PANTRY
ANTE
351A
EXAM
WORK
CORR.
C3-12
CORR.
C3-11
STOR.
TLT.
346A
TLT.
347A
NOURSH.
Office
357CLEAN
SUPPLY/UTIL.
EXAM
ROOM
SOCIAL WORKERS
OFFICE
MED.
OFFICE
PHYS.
OFFICE
CHIEF
PULM., MITs &RTs
E.C.
E.C.
EXAM
ROOM
PHYS.
OFFICE
333C
JAN. CL.
WARD
CLERK
333A
EQUIP.
STOR.
STAFF
LOUNGE
333B
WAITING/
KITCHENETTE
E.C.
NP OFFICE
CORR.
C3-9
CORR.
C3-7
CORR.
C3-8
CORR.
C3-5
CORR.
C3-1
SUPERV.
OFFICE
MECH. RM
TLT.
330B
WAIT/
COMFORT
PULM.
RECPT.
MED GAS
STOR.
EXAM
BC/EEG
Office
STAIR #1
PFT
CHART
EQUIP
ALCOVE CHART IP
HOLDPUBLIC
TLT
CORR.
C3-2
TLT
331A
COMM.
CHUTE
STAIR #2STAIR #3
CORR.
C3-10
CORR.
C3-3
P.L.
STOR.
321A
CORR.
C3-6
EQUIP
ALCOVE
NURSE
STATION
LINEN
ROOM
EXAM
ROOM
2-PATIENT
ROOM
CARDIO EXAM
ROOM
RESIDENT
WORK
WORK
AREA
330A
EXAM
Room 330C
EXAM
ROOM
330D
EXAM
ROOM
330E
STORAGE
ROOM
330F
CORR.
C3-4
FHC
FHC
E P
FHC
UCR
1 / 2
3RD FLOOR CONTINUED
1 1/2" CHS
222120191310432FF
F
G
H
G.7
J
K
L
M
N
1817161514
98765
CO
0.60° 0 .6
.6
0.60°
010101
01 01 01 01 01 01 01 01 01 01
01 01 01 01 01 01 01
1 1/2" D
1 1/2" D
3/4" D
2 1/2" CHR
1 1/2" CHS
1 1/2" CHS
2 1/2" CHR
3" CHR
3/4" CHS
3/4" CHR
3/4" D
4" CHR
1" CHS
4" CHR
C H
R
/4
D
1" CHS
3/4" CHR
3" CHS
3/4" D 2" CHR
3" CHS
2 1/2" CHR
1" D
2 1/2" CHR
2" CHS
1 1/2" CHR
3" CHS
3" CHS
2" CHR
3/4" CHS
3/4" CHR
1 1/2" CHR
1 1/2" CHS
3/4" CHR
3/4" CHS
3/4" D 3/4" D
3/4" D
3/4" D
2 1/2" CHR
1 1/2" CHS
1" D
3" CHR
1 1/2" CHS
3/4" D
3" CHR
1 1/2" CHS
3/4" D
3" CHR
1 1/2" CHS
3" CHR
1 1/2" CHS1 1/2" CHS
1" D
1" CHS
4" CHR
3/4" D
1" CHS
1" D
4" CHS
1" CHR
1" D
4" CHS
1" CHR
1" D
4" CHS
1 1/2" CHR
1 1/2" D
4" CHS
1 1/2" CHR
1 1/2" D
4" CHS
1 1/2" CHR
1 1/2" D
1 1/2" CHR
3/4" D
3" CHS
2" CHR
2" CHR
3" CHS
3/4" D
3" CHS
2" CHR
1" D
2" CHR
2 1/2" CHS 2 1/2" CHR
2 1/2" CHS 2 1/2" CHS
2 1/2" CHR
2 1/2" CHR
2" CHS
2 1/2" CHR
2" CHS
2 1/2" CHR
2" CHS
2 1/2" CHR
2" CHS
2 1/2" CHR
2" CHS
2 1/2" CHR
2" CHS
2 1/2" CHR
2" CHS
3" CHS
2" CHR
1" D
2" CHR
3" CHS
CO
1" D 1" D
2 1/2" CHS
2 1/2" CHR
3/4" D 2 1/2" CHR
2" CHS
1 1/2" D
2" CHS
2 1/2" CHR
1" D
1" D
2 1/2" CHR
2" CHS
3/4" D
2 1/2" CHR
2" CHS
2" CHS
1 1/2" CHS
2 1/2" CHR
3/4" D
1" D
CO
3" CHS
1" D
1" D
1" D 1" D
1" D
3/4" D
1 1/2" D
1" D
1" D
1 1/2" D
3" CHR
03 03
3/4" D
CO
# SHEET KEY NOTES:
DWG OF
DRAWN BY:
CHECKED BY:
ISSUE DATE:
DATE
File Path:
Plot Date:
REV # REVISION DESCRIPTION
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Suite 120 Cary, NC 27511 www.acg-pa.com
919-858-7420
VA PROJECT NO.
© COPYRIGHT Apogee Consulting Group, P.A.
DRAWING NO.:
CONSULTANTS: Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ACG Project NO.:
LOCATION:
PROJECT TITLE:
APPROVED:
DRAWING TITLE: BUILDING NO.
SHEET NOTES:
FULLY SPRINKLERED
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
C:\Users\jterpsta\Documents\M_BUILDING 58 - REPLACE FCU - 18-152_jterpstra.rvt
6/27/2019 2:39:56 PM
58-M-101
THIRD FLOOR MECHANICAL PIPING
PLAN
1900 E Main St, Danville, IL 61832
JT
RCM
JUNE 11, 2019
Replace B58-4 FCUS & Hot/Chilled Water Piping
550-18-102
18-152
FINAL CONSTRUCTION DOCUMENTS
Scale: 3/32" = 1'-0"
THIRD FLOOR MECHANICAL PIPING PLAN 0 84 16
NORTH
TRUE
01 3/4" SUPPLY, 3/4" RETURN, AND 3/4" DRAIN UP
THROUGH EXISTING OPENINGS AND
CONNECT TO UNIT ABOVE. COORDINATE
HAND OF NEW UNIT WITH EXISTING PIPING
LOCATION.
02 EXISTING SUPPLY AND RETURN WATER
RISERS TO REMAIN.
03 VALVE AND CAP 3/4" SUPPLY, 3/4" RETURN,
AND CAP 3/4" DRAIN FOR FUTURE
CONNECTION.
04 INSULATED DRAIN PIPING DOWN ALONG
WALL AND TERMINATE ABOVE MOP BASIN.
PROVIDE WHITE PVC COVER OVER PIPE
INSULATION WHERE EXPOSED IN ROOM 338.
05 3/4" INSULATED DRAIN ABOVE CEILING
THROUGH WALL INTO…