36C25219B0032-005.pdf

PDF 16 MB Posted

Attached to
Oncology Renovation USP 800 556-17-014
Solicitation number
36C25219B0032
Issued by

About this file

36C25219B0032 556-17-014 Drawings Set 1.pdf

View the file

Other files

File Type Posted
36C25219C0108-000.docx DOCX document
36C25219B0032-0001000.docx DOCX document
36C25219B0032-0001005.jpg JPG image
36C25219B0032-0001009.jpg JPG image
36C25219B0032-0001006.jpg JPG image
36C25219B0032-0001003.jpg JPG image
36C25219B0032-0001004.jpg JPG image
36C25219B0032-0001002.jpg JPG image
36C25219B0032-0001008.jpg JPG image
36C25219B0032-0001001.jpg JPG image
36C25219B0032-0001007.jpg JPG image
36C25219B0032-004.pdf PDF
36C25219B0032-003.docx DOCX document
36C25219B0032-006.pdf PDF
36C25219B0032-000.docx DOCX document
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ONCOLOGY RENOVATION

FOR USP 800 REQUIREMENTS

556-17-014

NO. DESCRIPTION DATE

BLDG. 133

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

FOR BID - NOT FOR CONSTRUCTION

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0101

B

A

C

D

E

F

COVER SHEET AND DRAWING INDEX

GI001

JJPBH

556-17-014

STRUCTURAL

ABBREVIATIONS AND NOTES

S-001

RPER

ONCOLOGY RENOVATION

FOR USP 800 REQUIREMENTS

556-17-014

NO. DESCRIPTION DATE

BLDG. 133

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

FOR BID - NOT FOR CONSTRUCTION

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0101

B

A

C

D

E

F

9 10

G

9 10

F

G

ONCOLOGY RENOVATION

FOR USP 800 REQUIREMENTS

556-17-014

NO. DESCRIPTION DATE

BLDG. 133

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

FOR BID - NOT FOR CONSTRUCTION

NORTH

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0101

B

A

C

D

E

F

KEYPLAN

LEVEL 4

STRUCTURAL

PARTIAL 4TH FLOOR PLAN

SF104

RPER

G

F

G

9 1087 9 1087

9 109 10

F

G

F

G

9 1087 9 1087

F

E

F

E

ONCOLOGY RENOVATION

FOR USP 800 REQUIREMENTS

556-17-014

NO. DESCRIPTION DATE

BLDG. 133

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

FOR BID - NOT FOR CONSTRUCTION

NORTH

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0101

B

A

C

D

E

F

KEYPLAN

PENTHOUSE

STRUCTURAL

PARTIAL ROOF & PENTHOUSE PLANS

SF105

RPER

556-17-014

NO. DESCRIPTION DATE

BLDG. 133

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

FOR BID - NOT FOR CONSTRUCTION

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0101

B

A

C

D

E

F

STRUCTURAL

SECTIONS AND DETAILS

S-501

DSER

AMBULATORY HEALTHCARE

OCCUPANCY

BUILDING 133CA

BUILDING 133

BUSINESS OCCUPANCY

FIRE WALL

MGV

M G

V M

G V

M G

V

M G

V M

G V

MGV

M G

P

P

P

P

P

P

P

P

P

P P

P

P

P

P

DNDN

UPUP

AHU 6

AHU 7

AHU 9

AHU 5

1E-102

EXST.

LOBBY

C1-167

EXST. CORR.

C1-160

EXST.

ELEV.

LOBBY

C1-161

EXST.

SERVICE

LOBBY

C1-162

EXST.

CORR.

NO 1

STAIR EL-S09

ELEV.

1B-117A

EXST.

ITD

ROOM

C1-177

EXST.

WAITING

ROOM

C1-175

EXST.

CORR.

C1-176

EXST.

CORR.

C1-166

EXST.

LOBBY

ACCESS TO ITD ROOM FOR LENEL

SYSTEM CONNECTION.

AREA OF CONSTRUCTION

AREAS IN THE SCOPE OF WORK OF THIS PROJECT. THESE

AREAS INCLUDE NEW CONSTRUCTION.

AREA OF DISTURBANCE

AREAS THAT WILL BE IMPACTED BY THE BASE BID OF WORK

OF THIS PROJECT. THESE AREAS INCLUDE BUT ARE NOT

LIMITED TO AREAS THAT WILL BE SHUT DOWN, ACCESSED,

OR DISRUPTED DURING CONSTRUCTION.

ELEVATOR AND STAIR FOR CONSTRUCTION WASTE

ELEVATOR AND STAIR DESIGNATED FOR TRANSPORTATION

OF CONSTRUCTION WASTE.

CONSTRUCTION OFFICE:

AREA DESIGNATED AS THE CONSTRUCTION OFFICE.

A Serv ic e

D is ab l e d Ve t e ran Owned Sma ll Bus iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0101

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t 6 o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

FOR BID - NOT FOR CONSTRUCTION

FULLY SPRINKLERED

NORTH

ONCOLOGY RENOVATION

FOR USP 800 REQUIREMENTS

556-17-014

BLDG. 133

Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER. INFECTION CONTROL PLAN

R-1 01/18/19

JAMES A. LOVELL FEDERAL HEALTH

CENTER-NORTH CHICAGO, ILLINOIS

REF HRQ

1" = 20'-0"F1 FLOOR 1 INFECTION CONTROL PLAN

SHEET NOTES

LEGEND

1. COORDINATE INFECTION CONTROL PROCEDURES WITH THE

VA/FHCC INFECTION CONTROL MANAGER.

2. THE CONTRACTOR IS RESPONSIBLE FOR INSTALLING TEMPORARY

CONTAINMENT PARTITIONS AND TEMPORARY VENTILATION SYSTEMS

REQUIRED TO PREVENT SPREAD OF DUST FROM CONSTRUCTION

AREA TO OCCUPIED AREAS OF THE BUILDING. SEE MECHANICAL

PLANS FOR ADDITIONAL INFORMATION. OCCUPIED AREAS SHALL

REMAIN DUST FREE THROUGHOUT CONSTRUCTION.

3. THE CONTRACTOR SHALL MAINTAIN THE AFFECTED AREAS OF THIS

BUILDING (INCLUDE MATERIAL TRANSPORT ROUTES) CLEAN AND

DUST SURFACES. THE CONTRACTOR SHALL COORDINATE WITH THE

INFECTION CONTROL STAFF PRIOR TO THE START OF

CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

COMPLIANCE WITH ALL INFECTION CONTROL RECOMMENDATIONS

AND REQUIREMENTS.

4. THE FACILITY WILL REMAIN OCCUPIED THROUGHOUT THE

CONSTRUCTION PERIOD. THE CONTRACTOR SHALL TAKE EVERY

PRECAUTION TO ENSURE THE UNINTERRUPTED OPERATION OF THE

FACILITY, STAFF, PATIENTS, AND VISITORS. THE CONTRACTOR SHALL

COORDINATE ALL WORK, CONSTRUCTION, PATHWAYS, ELEVATORS

USAGE, AND UTILITY INTERRUPTION WITH FHCC/VA, PM, AND/OR

FACILITIES DIRECTOR.

5. THE CONTRACTOR SHALL MAINTAIN THE REQUIREMENTS OF A

CLASS IV SYSTEM INFECTION CONTROL SYSTEM AS DEFINED IN

SPECIFICATION SECTION 01 35 26 AND THE ICRA.

6. TEMPORARY PARTITION:

A. THE CONTRACTOR SHALL DETERMINE WHERE TEMPORARY

PARTITIONS ARE REQUIRED TO MEET CLASS IV INFECTIONS

CONTROL REQUIREMENTS, FACILITY OPERATIONS, AND

CONTRACTOR SCHEDULING.

B. CLASS IV IC REQUIRES AN ANTE ROOM.

C. PARTITIONS OUTSIDE THE CONSTRUCTION AREA SHALL BE

STARC SYSTEMS (OR EQUAL) PANEL SYSTEM WITH PRESSURE

MONITOR PORTS AND DATA RECORDING.

7. OFF HOURS ARE DEFINED AS 7:00PM-3:00 AM. MINIMIZE TIME FRAME

TO THE GREATEST EXTENTS POSSIBLE. CONTRACTOR TO

COORDINATE WITH CONSTRUCTION MANAGER PRIOR TO

COMENCEMENT OF AFTER HOURS WORK.

8. TEMPORARY PARTITIONS SHALL BE SMOKE TIGHT CONSTRUCTION

OF GYPSUM BOARD OR OTHER NON-COMBUSTIBLE OR LIMITED-

COMUBSTIBLE MATERIAL. PARTITIONS SHALL BE FULL HEIGHT,

EXTENDING THROUGH SUSPENDED CEILINGS TO THE FLOOR SLAB

OR ROOF DECK ABOVE AND SHALL BE 1-HOUR RATED, UNLESS

SPRINKLERS ARE OPERATIONAL ON BOTH SIDES OF THE

TEMPORARY PARTITION, WHEREUPON THE PARTITIONS MAY BE

PERMITTED TO TERMINATE AT THE CEILING. WHERE THE CEILING ON

ONE SIDE OF THE TEMPORARY CONSTRUCTION BARRIER HAS BEEN

REMOVED, THE TEMPORARY PARTITION MUST EXTEND TO THE DECK

ABOVE AND BE 1-HOUR RATED.

jphelan Rectangle

P

P

P

P

P

P P

P

P

P

M G

P M

G V

M G

P M

G V

MGV

MGV

MGV

MGV

M G

P

SDSD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

- MAINTAIN CLASS IV REQUIREMENTS

- INSTALLATION OF PARTITIONS/

BARRIERS TO OCCUR DURING OFF-

HOURS

- LIMIT WORK IN THIS AREA TO 7

CALENDAR DAYS MAXIMUM

- COORDINATE ALL WORK WITH COR

TEMPORARY PARTIONS SHOWN

FOR REFERENCE ONLY. COORDINATE

FINAL LOCATION AND ANY ADDITIONAL

INFECTION CONTROL REQUIREMENTS

PRIOR TO CONSTRUCTION WITH

VA CONSTRUCTION MANAGER, LIFE

SAFETY, AND INFECTION CONTROL

STAFF.

EXST.

NOURISH

2A-151B

EXST.

STORAGE

2A-151C

EXST. PACU

C2-213

EXST.

HOLD1

2A-151E

EXST.

HOLD2

2A-151F

EXST.

HOLD3

2A-151G

EXST.

HOLD4

2A-151H

EXST. NURSE

STATION

2A-151

EXST.

CORR

2A-130

EXST.

CORR

C2-209

EXST.

CORR

C2-208

EXST.

CORR

C2-209

EXST.

LOBBY

C2-207

EXST.

CHECK-IN

2A-119

EXST. NURSE

STATION

2A-150

ELEV.

LOBBY

C2-232

EXST.

CORR.

C2-231

STAIR

NO. 1

STAIR

NO.2

ELEV.

EL-S09

EXST.

CORR

C2-204

EXST. ITD

ROOM

2B-110

ACCESS TO ITD FOR CONDUIT FOR

LENEL SYSTEM WIRING TO PASS-

THROUGH.

NOTE: ALL WORK ASSOCIATED WITH THE

2ND FLOOR MUST BE COMPLETED

DURING OFF-HOURS.

AREA OF CONSTRUCTION

AREAS IN THE SCOPE OF WORK OF THIS PROJECT. THESE

AREAS INCLUDE NEW CONSTRUCTION.

AREA OF DISTURBANCE

AREAS THAT WILL BE IMPACTED BY THE BASE BID OF WORK

OF THIS PROJECT. THESE AREAS INCLUDE BUT ARE NOT

LIMITED TO AREAS THAT WILL BE SHUT DOWN, ACCESSED,

OR DISRUPTED DURING CONSTRUCTION.

ELEVATOR AND STAIR FOR CONSTRUCTION WASTE

ELEVATOR AND STAIR DESIGNATED FOR TRANSPORTATION

OF CONSTRUCTION WASTE.

CONSTRUCTION OFFICE:

AREA DESIGNATED AS THE CONSTRUCTION OFFICE.

A Serv ic e

D is ab l e d Ve t e ran Owned Sma ll Bus iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0101

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t 6 o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

FOR BID - NOT FOR CONSTRUCTION

FULLY SPRINKLERED

NORTH

ONCOLOGY RENOVATION

FOR USP 800 REQUIREMENTS

556-17-014

BLDG. 133

Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER. INFECTION CONTROL PLAN

R-2 01/18/19

JAMES A. LOVELL FEDERAL HEALTH

CENTER-NORTH CHICAGO, ILLINOIS

REF HQR

3/32" = 1'-0"F1 FLOOR 2 INFECTION CONTROL PLAN

SHEET NOTES

LEGEND

1. COORDINATE INFECTION CONTROL PROCEDURES WITH THE VA/FHCC

INFECTION CONTROL MANAGER.

2. THE CONTRACTOR IS RESPONSIBLE FOR INSTALLING TEMPORARY

CONTAINMENT PARTITIONS AND TEMPORARY VENTILATION SYSTEMS

REQUIRED TO PREVENT SPREAD OF DUST FROM CONSTRUCTION

AREA TO OCCUPIED AREAS OF THE BUILDING. SEE MECHANICAL

PLANS FOR ADDITIONAL INFORMATION. OCCUPIED AREAS SHALL

REMAIN DUST FREE THROUGHOUT CONSTRUCTION.

3. THE CONTRACTOR SHALL MAINTAIN THE AFFECTED AREAS OF THIS

BUILDING (INCLUDE MATERIAL TRANSPORT ROUTES) CLEAN AND

DUST SURFACES. THE CONTRACTOR SHALL COORDINATE WITH THE

INFECTION CONTROL STAFF PRIOR TO THE START OF

CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

COMPLIANCE WITH ALL INFECTION CONTROL RECOMMENDATIONS

AND REQUIREMENTS.

4. THE FACILITY WILL REMAIN OCCUPIED THROUGHOUT THE

CONSTRUCTION PERIOD. THE CONTRACTOR SHALL TAKE EVERY

PRECAUTION TO ENSURE THE UNINTERRUPTED OPERATION OF THE

FACILITY, STAFF, PATIENTS, AND VISITORS. THE CONTRACTOR SHALL

COORDINATE ALL WORK, CONSTRUCTION, PATHWAYS, ELEVATORS

USAGE, AND UTILITY INTERRUPTION WITH FHCC/VA, PM, AND/OR

FACILITIES DIRECTOR.

5. THE CONTRACTOR SHALL MAINTAIN THE REQUIREMENTS OF A CLASS

IV SYSTEM INFECTION CONTROL SYSTEM AS DEFINED IN

SPECIFICATION SECTION 01 35 26 AND THE ICRA.

6. TEMPORARY PARTITION:

A. THE CONTRACTOR SHALL DETERMINE WHERE TEMPORARY

PARTITIONS ARE REQUIRED TO MEET CLASS IV INFECTIONS

CONTROL REQUIREMENTS, FACILITY OPERATIONS, AND

CONTRACTOR SCHEDULING.

B. CLASS IV IC REQUIRES AN ANTE ROOM.

C. PARTITIONS OUTSIDE THE CONSTRUCTION AREA SHALL BE

STARC SYSTEMS (OR EQUAL) PANEL SYSTEM WITH PRESSURE

MONITOR PORTS AND DATA RECORDING.

7. OFF HOURS ARE DEFINED AS 7:00PM-3:00 AM. MINIMIZE TIME FRAME

TO THE GREATEST EXTENTS POSSIBLE. CONTRACTOR TO

COORDINATE WITH CONSTRUCTION MANAGER PRIOR TO

COMENCEMENT OF AFTER HOURS WORK.

8. TEMPORARY PARTITIONS SHALL BE SMOKE TIGHT CONSTRUCTION

OF GYPSUM BOARD OR OTHER NON-COMBUSTIBLE OR LIMITED-

COMUBSTIBLE MATERIAL. PARTITIONS SHALL BE FULL HEIGHT,

EXTENDING THROUGH SUSPENDED CEILINGS TO THE FLOOR SLAB

OR ROOF DECK ABOVE AND SHALL BE 1-HOUR RATED, UNLESS

SPRINKLERS ARE OPERATIONAL ON BOTH SIDES OF THE

TEMPORARY PARTITION, WHEREUPON THE PARTITIONS MAY BE

PERMITTED TO TERMINATE AT THE CEILING. WHERE THE CEILING ON

ONE SIDE OF THE TEMPORARY CONSTRUCTION BARRIER HAS BEEN

REMOVED, THE TEMPORARY PARTITION MUST EXTEND TO THE DECK

ABOVE AND BE 1-HOUR RATED.

HEALTHCARE OCCUPANCY

BUILDING 133CA

BUILDING 133

BUSINESS OCCUPANCY

M G

P M

G V

SDSD

SD

SD

SD

SD

SD

SD

SDSD

SD

SD

P

P

P

P

REMOVE WINDOW(S) FOR NEGATIVE

PRESSURE EXHAUST. TEMPORARILY

INFILL OPENING WITH PLYWOOD

AND ADAPTER FOR AIR EXHAUST.

- MAINTAIN CLASS IV REQUIREMENTS

- INSTALLATION OF PARTITIONS/

BARRIERS TO OCCUR DURING OFF-

HOURS

TEMPORARY PARTITIONS SHOWN

FOR REFERENCE ONLY. COORDINATE

FINAL LOCATION AND ANY ADDITIONAL

INFECTION CONTROL REQUIREMENTS

PRIOR TO CONSTRUCTION WITH

VA CONSTRUCTION MANAGER, LIFE SAFETY,

AND INFECTION CONTROL STAFF.

EQ

EQ

3A-159

PHARM

OFF.

3A-160

PHARM

OFF. 3A-164

EXST

RECP.

3A-165

EXST

PHARM.

3A-166

EXST

WAITING

3A-166A

EXST

RESTROOM

C3-139

EXST.

CORR.

3A-162

EXST.

WAITING.

3A-162

EXST.

WAITING.

C3-140

EXST.

CORR.

C3-137

EXST.

CORR.

C3-128

EXST.

ELEV.

LOBBY

NO. 1

STAIR

C3-130

EXST.

SERVICE

LOBBY

C3-129

EXST.

CORR.

C3-136

EXST.

CORR.

NO. 2

STAIR

EL-S09

ELEV.

TEMPORARY ZIPPERED 2' WIDE ENCLOSURE

FOR DEMOLITION AND INFILL OF DOORWAY

ONLY. MAXIMUM DURATION 7 CALENDAR DAYS

C3-153

EXST.

CORR.

3B-123

EXST. ITD

ROOM

ACCESS ITD

ROOM FOR CARD

READER.

AREA OF CONSTRUCTION

AREAS IN THE SCOPE OF WORK OF THIS PROJECT. THESE

AREAS INCLUDE NEW CONSTRUCTION.

AREA OF DISTURBANCE

AREAS THAT WILL BE IMPACTED BY THE BASE BID OF WORK

OF THIS PROJECT. THESE AREAS INCLUDE BUT ARE NOT

LIMITED TO AREAS THAT WILL BE SHUT DOWN, ACCESSED,

OR DISRUPTED DURING CONSTRUCTION.

ELEVATOR AND STAIR FOR CONSTRUCTION WASTE

ELEVATOR AND STAIR DESIGNATED FOR TRANSPORTATION

OF CONSTRUCTION WASTE.

CONSTRUCTION OFFICE:

AREA DESIGNATED AS THE CONSTRUCTION OFFICE.

A Serv ic e

D is ab l e d Ve t e ran Owned Sma ll Bus iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0101

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t 6 o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

FOR BID - NOT FOR CONSTRUCTION

FULLY SPRINKLERED

NORTH

ONCOLOGY RENOVATION

FOR USP 800 REQUIREMENTS

556-17-014

BLDG. 133

Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER. INFECTION CONTROL PLAN

R-3 01/18/19

JAMES A. LOVELL FEDERAL HEALTH

CENTER-NORTH CHICAGO, ILLINOIS

REF HQR

3/32" = 1'-0"F1 FLOOR 3 INFECTION CONTROL PLAN

SHEET NOTES

LEGEND

1. COORDINATE INFECTION CONTROL PROCEDURES WITH THE

VA/FHCC INFECTION CONTROL MANAGER.

2. THE CONTRACTOR IS RESPONSIBLE FOR INSTALLING TEMPORARY

CONTAINMENT PARTITIONS AND TEMPORARY VENTILATION SYSTEMS

REQUIRED TO PREVENT SPREAD OF DUST FROM CONSTRUCTION

AREA TO OCCUPIED AREAS OF THE BUILDING. SEE MECHANICAL

PLANS FOR ADDITIONAL INFORMATION. OCCUPIED AREAS SHALL

REMAIN DUST FREE THROUGHOUT CONSTRUCTION.

3. THE CONTRACTOR SHALL MAINTAIN THE AFFECTED AREAS OF THIS

BUILDING (INCLUDE MATERIAL TRANSPORT ROUTES) CLEAN AND

DUST SURFACES. THE CONTRACTOR SHALL COORDINATE WITH THE

INFECTION CONTROL STAFF PRIOR TO THE START OF

CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

COMPLIANCE WITH ALL INFECTION CONTROL RECOMMENDATIONS

AND REQUIREMENTS.

4. THE FACILITY WILL REMAIN OCCUPIED THROUGHOUT THE

CONSTRUCTION PERIOD. THE CONTRACTOR SHALL TAKE EVERY

PRECAUTION TO ENSURE THE UNINTERRUPTED OPERATION OF THE

FACILITY, STAFF, PATIENTS, AND VISITORS. THE CONTRACTOR SHALL

COORDINATE ALL WORK, CONSTRUCTION, PATHWAYS, ELEVATORS

USAGE, AND UTILITY INTERRUPTION WITH FHCC/VA, PM, AND/OR

FACILITIES DIRECTOR.

5. THE CONTRACTOR SHALL MAINTAIN THE REQUIREMENTS OF A

CLASS IV SYSTEM INFECTION CONTROL SYSTEM AS DEFINED IN

SPECIFICATION SECTION 01 35 26 AND THE ICRA.

6. TEMPORARY PARTITION:

A. THE CONTRACTOR SHALL DETERMINE WHERE TEMPORARY

PARTITIONS ARE REQUIRED TO MEET CLASS IV INFECTIONS

CONTROL REQUIREMENTS, FACILITY OPERATIONS, AND

CONTRACTOR SCHEDULING.

B. CLASS IV IC REQUIRES AN ANTE ROOM.

C. PARTITIONS OUTSIDE THE CONSTRUCTION AREA SHALL BE

STARC SYSTEMS (OR EQUAL) PANEL SYSTEM WITH PRESSURE

MONITOR PORTS AND DATA RECORDING.

7. OFF HOURS ARE DEFINED AS 7:00PM-3:00 AM. MINIMIZE TIME FRAME

TO THE GREATEST EXTENTS POSSIBLE. CONTRACTOR TO

COORDINATE WITH CONSTRUCTION MANAGER PRIOR TO

COMMENCEMENT OF AFTER HOURS WORK.

8. TEMPORARY PARTITIONS SHALL BE SMOKE TIGHT CONSTRUCTION

OF GYPSUM BOARD OR OTHER NON-COMBUSTIBLE OR LIMITED-

COMBUSTIBLE MATERIAL. PARTITIONS SHALL BE FULL HEIGHT,

EXTENDING THROUGH SUSPENDED CEILINGS TO THE FLOOR SLAB

OR ROOF DECK ABOVE AND SHALL BE 1-HOUR RATED, UNLESS

SPRINKLERS ARE OPERATIONAL ON BOTH SIDES OF THE

TEMPORARY PARTITION, WHEREUPON THE PARTITIONS MAY BE

PERMITTED TO TERMINATE AT THE CEILING. WHERE THE CEILING ON

ONE SIDE OF THE TEMPORARY CONSTRUCTION BARRIER HAS BEEN

REMOVED, THE TEMPORARY PARTITION MUST EXTEND TO THE DECK

ABOVE AND BE 1-HOUR RATED.

9. CONTRACTOR SHALL INSTALL (1) VA FURNISHED 'SETRA SYSTEMS

TEMPTRAK 900MHz PRESSURE DIFFERENTIAL MONTIOR, MODEL

NUMBER: SRPM0R1WBV1E' IN ACCORDANCE WITH THE

MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE VA WILL

PROVIDE PROGRAMMING TO THE TEMPTRAK SYSTEM SO THAT IT IS

OPERATIONAL BEFORE ANY NEW WORK BEGINS. PRESSURE

DIFFERENTIAL MONITOR MUST BE OPERATIONAL FOR THE

DURATION OF CONSTRUCTION. COORDINATE INSTALLATION

LOCATION AND WORK PERFORMED BY THE VA WITH THE COR IN

ADVANCE.

BUILDING 133

HEALTHCARE

OCCUPANCY

M G

P M

G V

M G

P M

G V

M G

P M

G V

P

P

P

P

P

P

- MAINTAIN CLASS IV REQUIREMENTS

- INSTALLATION OF PARTITIONS/ BARRIERS TO

OCCUR DURING OFF-HOURS

- ALL 4TH FLOOR WORK TO OCCUR DURING

ONE (21) DAY PERIOD. THIS IS TO INCLUDE

START OF INSTALLATION OF INFECTION

CONTROL BARRIERS (MEASURES), TO REVIEW,

PUNCHLIST, AND CLEANING AND APPROVAL.

- COORDINATE ALL WORK WITH COR.

EXST.

OFFICE

4A-152

EXST.

MED.

STORAGE

4A-153

EXST.

NURSE

STATION

4A-151

EXST. CORR

C4-111

STAIR

NO. 2

EXST. CORR

C4-106

ELEV.

LOBBY

C4-100

STAIR

NO. 1

ELEV.

EL-S09

EXST. CORR

C4-102 EXST.

CORR

C4-101

EXST. ADMIN

AREA

4A-123

EXST.

WAITING

4A-124EXST.

CORR

C4-110A

REMOVE WINDOW(S) FOR NEGATIVE PRESSURE

EXHAUST. TEMPORARILY INFILL OPENING WITH

PLYWOOD AND ADAPTER FOR AIR EXHAUST

AREA OF CONSTRUCTION

AREAS IN THE SCOPE OF WORK OF THIS PROJECT. THESE

AREAS INCLUDE NEW CONSTRUCTION.

AREA OF DISTURBANCE

AREAS THAT WILL BE IMPACTED BY THE BASE BID OF WORK

OF THIS PROJECT. THESE AREAS INCLUDE BUT ARE NOT

LIMITED TO AREAS THAT WILL BE SHUT DOWN, ACCESSED,

OR DISRUPTED DURING CONSTRUCTION.

ELEVATOR AND STAIR FOR CONSTRUCTION WASTE

ELEVATOR AND STAIR DESIGNATED FOR TRANSPORTATION

OF CONSTRUCTION WASTE.

CONSTRUCTION OFFICE:

AREA DESIGNATED AS THE CONSTRUCTION OFFICE.

A Serv ic e

D is ab l e d Ve t e ran Owned Sma ll Bus iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0101

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t 6 o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

FOR BID - NOT FOR CONSTRUCTION

FULLY SPRINKLERED

NORTH

ONCOLOGY RENOVATION

FOR USP 800 REQUIREMENTS

556-17-014

BLDG. 133

Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER. INFECTION CONTROL PLAN

R-4 01/18/19

JAMES A. LOVELL FEDERAL HEALTH

CENTER-NORTH CHICAGO, ILLINOIS

REF HQR

3/32" = 1'-0"F1 FLOOR 4 INFECTION CONTROL PLAN

SHEET NOTES

LEGEND

1. COORDINATE INFECTION CONTROL PROCEDURES WITH THE

VA/FHCC INFECTION CONTROL MANAGER.

2. THE CONTRACTOR IS RESPONSIBLE FOR INSTALLING TEMPORARY

CONTAINMENT PARTITIONS AND TEMPORARY VENTILATION SYSTEMS

REQUIRED TO PREVENT SPREAD OF DUST FROM CONSTRUCTION

AREA TO OCCUPIED AREAS OF THE BUILDING. SEE MECHANICAL

PLANS FOR ADDITIONAL INFORMATION. OCCUPIED AREAS SHALL

REMAIN DUST FREE THROUGHOUT CONSTRUCTION.

3. THE CONTRACTOR SHALL MAINTAIN THE AFFECTED AREAS OF THIS

BUILDING (INCLUDE MATERIAL TRANSPORT ROUTES) CLEAN AND

DUST SURFACES. THE CONTRACTOR SHALL COORDINATE WITH THE

INFECTION CONTROL STAFF PRIOR TO THE START OF

CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

COMPLIANCE WITH ALL INFECTION CONTROL RECOMMENDATIONS

AND REQUIREMENTS.

4. THE FACILITY WILL REMAIN OCCUPIED THROUGHOUT THE

CONSTRUCTION PERIOD. THE CONTRACTOR SHALL TAKE EVERY

PRECAUTION TO ENSURE THE UNINTERRUPTED OPERATION OF THE

FACILITY, STAFF, PATIENTS, AND VISITORS. THE CONTRACTOR SHALL

COORDINATE ALL WORK, CONSTRUCTION, PATHWAYS, ELEVATORS

USAGE, AND UTILITY INTERRUPTION WITH FHCC/VA, PM, AND/OR

FACILITIES DIRECTOR.

5. THE CONTRACTOR SHALL MAINTAIN THE REQUIREMENTS OF A

CLASS IV SYSTEM INFECTION CONTROL SYSTEM AS DEFINED IN

SPECIFICATION SECTION 01 35 26 AND THE ICRA.

6. TEMPORARY PARTITION:

A. THE CONTRACTOR SHALL DETERMINE WHERE TEMPORARY

PARTITIONS ARE REQUIRED TO MEET CLASS IV INFECTIONS

CONTROL REQUIREMENTS, FACILITY OPERATIONS, AND

CONTRACTOR SCHEDULING.

B. CLASS IV IC REQUIRES AN ANTE ROOM.

C. PARTITIONS OUTSIDE THE CONSTRUCTION AREA SHALL BE

STARC SYSTEMS (OR EQUAL) PANEL SYSTEM WITH PRESSURE

MONITOR PORTS AND DATA RECORDING.

7. OFF HOURS ARE DEFINED AS 7:00PM-3:00 AM. MINIMIZE TIME FRAME

TO THE GREATEST EXTENTS POSSIBLE. CONTRACTOR TO

COORDINATE WITH CONSTRUCTION MANAGER PRIOR TO

COMENCEMENT OF AFTER HOURS WORK.

8. TEMPORARY PARTITIONS SHALL BE SMOKE TIGHT CONSTRUCTION

OF GYPSUM BOARD OR OTHER NON-COMBUSTIBLE OR LIMITED-

COMUBSTIBLE MATERIAL. PARTITIONS SHALL BE FULL HEIGHT,

EXTENDING THROUGH SUSPENDED CEILINGS TO THE FLOOR SLAB

OR ROOF DECK ABOVE AND SHALL BE 1-HOUR RATED, UNLESS

SPRINKLERS ARE OPERATIONAL ON BOTH SIDES OF THE

TEMPORARY PARTITION, WHEREUPON THE PARTITIONS MAY BE

PERMITTED TO TERMINATE AT THE CEILING. WHERE THE CEILING ON

ONE SIDE OF THE TEMPORARY CONSTRUCTION BARRIER HAS BEEN

REMOVED, THE TEMPORARY PARTITION MUST EXTEND TO THE DECK

ABOVE AND BE 1-HOUR RATED.

C

B

AA

B

C

SD

SD

SD

SD

S S

S S

S S

M G

P M

G V

SD SD SD

SD

SD

SD

P

P

P

FE

C

S S

5 6 7 8 9 104321

GG

F

E

D

C

B

A

PATH "B"

PATH "A"

PATH "C"

PATH "D"

1167 SF

EXST. CORRIDOR

C3-140

90 SF

POSITIVE ANTE

ROOM

3A-165A

71 SF

POSITIVE BUFFER

ROOM

3A-165B

161 SF

NEGATIVE

BUFFER ROOM

3A-165C

53 SF

RESTROOM

3A-166

EXST

INFUSION

EXST

INFUSION

EXST

INFUSION

EXST

INFUSION

EXST

NOURISHMENT

EXST

INFUSION

EXST

INFUSION

EXST

MEDS

EXST INFUSION/

PROCEDURE

EXST

TOILET

EXST

INFUSION

EXST

ELEC.

EXST

TOILET

EXST

SPSEXST

SOILEDEXST

INTAKE

EXST

CARE

PLANNING

EXST

TOILET

EXST

TOILET

EXST

EXAM

EXST

EXAM

EXST

EXAM

EXST

EXAM

EXST MD

OFFICE

EXST

LOUNGE

EXST

OFFICE

EXST

TOILET

EXST

NURSE

OFFICE

EXST

PHARM.

OFFICE

EXST

RESIDENT

OFFICE

EXST

TOILET EXST

WAITING

EXST

CLEAN

EXST

FILING EXST

RECEPTION

EXST

OFFICE

EXST

JAN

EXST

TOILET

EXST

PATIENT

BEDRM.

EXST

NURSE

OFFICE

EXST

WAITING

99 SF

PHARMACY

RECEIVING AND

SUPPLY

3A-165

EXST

PATIENT

BEDRM

EXST

TOILET

AED

3A-1323A-133

3A-128A

3A-135

3A-134

3A-131

3A-137

3A-138

3A-139A

3A-139B

3A-139C

3A-139D3A-139E

3A-139F

3A-130

3A-141

3A-142

3A-143

3A-144

3A-145 3A-146

3A-147 3A-1483A-1493A-1503A-1513A-1523A-1533A-154

3A-155 3A-156 3A-157 3A-158 3A-159 3A-160

3A-161 3A-162 3A-162

3A-164A

3A-163

3A-156 3A-167

3A-167A

PROPOSED PHARMACY

SUITE - 470 SF

SMOKE ZONE INCREASED IN AREA

DUE TO PROPOSED PHARMACY SUITE.

ZONE AREA IS NOW 6737 SF

5 6 7 8 9 10

GG

F

E

D

C

B

A

PATH "E"

PATH "F"

PATH "G"

PATH "H"

185 SF

EXST. OFFICE

4A-152

148 SF

EXST. MEDICAL

EQUIPMENT

STORAGE

4A-153

EXST

PATIENT

RM

EXST

PATIENT

TLT

EXST

PATIENT

RM

EXST

PATIENT

RM

EXST

SOILED

EXST

CLEAN

EXST

PATIENT

RM

EXST

PATIENT

TLT

EXST

PATIENT

RM

EXST

PATIENT

RM

EXST

PATIENT

TLT

EXST

PATIENT

RM

EXST

PATIENT

TLT

EXST

PHYS.

CHART

EXST

MEDS

EXST

NOURISH

EXST

NURSE

STATION

EXST

PATIENT TLT

EXST

STAFF TLT

EXST

PATIENT

RM

EXST

PATIENT

RM

EXST

PATIENT

TLT

EXST

INFUSION

EXST

PATIENT

RM

EXST

PATIENT TLT

EXST

CLEAN

LINEN

EXST

ELEC.

EXST

ANTE RM

EXST

PATIENT

RM

EXST

PATIENT

TLT

EXST

PATIENT

RM

EXST

PATIENT

TLT

EXST

CHART RM

EXST

PATIENT

RM

EXST

PATIENT TLT

EXST

PATIENT

RM

EXST

PATIENT

RM

EXST

PATIENT TLT

EXST

PATIENT

TLT

EXST

PATIENT

RM

EXST

PATIENT

TLT

EXST

PATIENT

TLT

EXST

PATIENT TLT

EXST

PATIENT

TLT

4A-155A

4A-155B

4A-154 4A-151

4A-151A

4A-150

4A-149

4A-148A

4A-148 4A-147A4A-1474A-146

4A-146A4A-145A4A-145

4A-144 4A-144A 4A-143A 4A-143 4A-142

4A-142A 4A-141A 4A-141 4A-137 4A-139

4A-136

4A-135A

4A-135

4A-135B

4A-134

4A-134A

4A-134

4A-132

4A-132A

4A-131A

4A-131

4A-130

4A-130A

4A-127A 4A-127 4A-126A

4A-126

EXISTING SMOKE ZONE PERIMETER WALL IS AFFECTED

BY PROPOSED CONSTRUCTION AND MUST BE MAINTAINED

WITH A MINIMUM OF 1-HOUR FIRE/ SMOKE WALL

V A

PATH OF TRAVEL (FEET)

PRIVATE MODE VOICE/ALARM SYSTEM THROUGHOUT

(COORDINATE W/ ELECTRICAL)

EXIT FLOW

START OF TRAVEL

EXIT SIGN

(COORDINATE W/ ELECTRICAL)

PORTABLE FIRE EXTINGUISHER

(COORDINATE W/ FIRE MARSHAL)

SUITE SEPARATION WALL

SMOKE RESISTIVE HAZARDOUS AREA

TWO HOUR FIRE WALL CONSTRUCTION

AED AUTOMATIC ELECTRICAL DEFIBRILLATOR

ONE HOUR FIRE/ SMOKE WALL

A Serv ic e

D is ab l e d Ve t e ran Owned Sma ll Bus iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0101

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t 6 o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

FOR BID - NOT FOR CONSTRUCTION

FULLY SPRINKLERED

NORTH

ONCOLOGY RENOVATION

FOR USP 800 REQUIREMENTS

556-17-014

BLDG. 133

Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER. LIFE SAFETY SHEET

G-001 01/18/19

JAMES A. LOVELL FEDERAL HEALTH

CENTER-NORTH CHICAGO, ILLINOIS

REF HQR

LEVEL 3 LEVEL 4LEVEL 2

3/32" = 1'-0"C1 LEVEL 3 LIFE SAFETY PLAN

3/32" = 1'-0"F1 LEVEL 4 LIFE SAFETY PLAN

Path ID Common Path

Distance Allowable Common

Path Actual Travel

Distance Allowable Travel

Distance A 48' - 10" 100' - 0" 48' - 10" 200' - 0" B 44' - 5" 100' - 0" 44' - 5" 200' - 0" C 44' - 5" 100' - 0" 172' - 8" 200' - 0" D 0' - 0" 100' - 0" 137' - 10" 200' - 0" E 28' - 9" 100' - 0" 28' - 9" 200' - 0" F 27' - 6" 100' - 0" 27' - 6" 200' - 0" G 27' - 6" 100' - 0" 167' - 4" 200' - 0" H 28' - 9" 100' - 0" 116' - 1" 200' - 0"

GENERAL SHEET NOTES

LIFE SAFETY LEGEND

EXIT ACCESS TRAVEL DISTANCE

1. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE

SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL

PROVIDE A CLEAR WIDTH OF NOT LESS THAN 32 INCHES. THE

HEIGHT OF DOORS SHALL NOT BE LESS THAN 80 INCHES.

2. EGRESS DOORS SHALL BE READILY OPERABLE FROM THE EGRESS

SIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR

EFFORT. ALL EGRESS DOORS TO HAVE PANIC HARDWARE. PANIC

HARDWARE SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR

TWISTING OF THE WRIST. FORCE REQUIRED TO ACTIVATE

OPERABLE PARTS SHALL BE 5 POUNDS.

3. THE MEANS OF EGRESS, AND EXIT DISCHARGE, SHALL BE

ILLUMINATED AT ANY TIME THE BUILDING IS OCCUPIED WITH A LIGHT

INTENSITY OF NOT LESS THAN 1 FOOT-CANDLE AT THE WALKING

SURFACE LEVEL.

4. THE EGRESS PATH SHALL REMAIN FREE AND CLEAR OF ALL

OBSTRUCTIONS AT ALL TIMES. NO STORAGE IS PERMITTED IN ANY

EGRESS PATHS.

5. ALL NEW PROPOSED FIRE EXTINGUISHER LOCATIONS ARE

DETERMINED BY IFC TABLE 906.3(1), NFPA 10, AND/OR BY THE

DIRECTION OF THE LOCAL AUTHORITY.

6. THE INFORMATION CONTAINED IN THESE LIFE SAFETY PLANS

(SHEET) ARE IN REFERENCE TO THE PROJECT SCOPE OF WORK

(PROJECT LIMIT LINE) CONTAINED IN THE ARCHITECTURAL PLANS

(ONLY). A COMPLETE LIFE SAFETY REVIEW OF THE FACILITY WAS

NOT COMPLETED AS PART OF THIS SCOPE OF WORK. AREAS

OUTSIDE OF THE SCOPE OF WORK (PROJECT LIMIT LINE) OF THESE

DOCUMENTS WERE PROVIDED BY FHCC FOR REFERENCE BY THE

DESIGN TEAM AND ARE ASSUMED TO BE ACCURATE AND COMPLETE

FOR USE IN THESE CONSTRICTION DOCUMENTS. COORDINATE WITH

FHCC FOR ANY ADDITIONAL LIFE SAFETY INFORMATION OUTSIDE OF

THIS SCOPE OF WORK.

PROJECT SUMMARY:

THIS PROJECT CONSISTS OF AN ONCOLOGY RENOVATION OF THE THIRD AND FOURTH FLOORS, BUILDING 133. WITH WORK TO SUPPORT THE RENOVATION ON THE SECOND FLOOR, MECHANICAL PENTHOUSE, AND ROOF. THIS PROJECT IS TO INCORPORATE INTERIOR FINISHES AND COLORS, SIGNAGE AND WAYFINDING AND NEW MEDICAL EQUIPMENT SELECTION WITH ENGINEER. THE PROPOSED PHARMACY IS CONSIDERED A NON-INPATIENT SUITE. THE

CONSTRUCTION SCOPE SHALL INCLUDE COMPLIANCE WITH THE SUITE REQUIREMENTS BELOW.

APPLICABLE CODES

INTERNATIIONAL BUILDING CODE (IBC)(ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS)

NFPA 101 LIFE SAFETY CODE 2018 EDITION

VA FIRE PROTECTION DESIGN GUIDE 7TH EDITION

NFPA NATIONAL FIRE CODE (EXCEPTION OF NFPA 5000 AND NFPA 900)

USP 797

USP 800

VA SEISMIC DESIGN REQUIREMENTS, H-18-8

NATIONAL ELECTRICAL CODE (NEC)

INTERNATIONAL PLUMBING CODE (IPC)

ENERGY POLICY ACT OF 2005 (EPACT)

FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU) EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY, AND TRANSPORTATION MANAGEMENT

THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGN

VENTILATION FOR ACCEPTABE INDOOR AIR QUALITY - ASHRAE STANDARD 62.1 -2004

SAFETY STANDARD FOR REFRIGERATION SYSTEMS - ASHRAE STANDARD 15-2007

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)

GENERAL SUITE REQUIREMENTS

• SUITES MUST BE SEPARATED FROM THE REST OF THE BUILDING AND OTHER SUITES BY WALLS AND DOORS BUILT TO AT LEAST THE

SAME REQUIREMENTS AS THE CORRIDOR (CHAPTER 18 - 19.2.5.7.1.2)

• INTERVENING ROOMS MUST NOT BE HAZARDOUS AREAS (CHAPTER 18 - 19.2.5.7.1.3A)

• HAZARDOUS ROOMS MUST BE ENCLOSE PER 19.3.2.1 (CHAPTER 18 - 19.2.5.7.1.3B)

• MULTIPLE CONTIGUOUS HAZARDOUS SPACES WITHIN A SUITE DO NOT NEED TO BE INDIVIDUALLY ENCLOSED WITHIN RATED WALLS, PROVIDED THE SUITE IS PRIMARILY A HAZARDOUS AREA AND THE PERIMETER OF THE SUITE IS CONSTRUCTED PER 19.3.2.1

(CHAPTER18 - 19.2.5.7.1.3C)

• EXISTING STERILE STORAGE AREAS, WITH ONLY A SINGLE DAY SUPPLY, WITHIN A SPRINKLED OPERATING ROOM SUITE DO NOT NEED

TO BE ENCLOSED AS A HAZARDOUS SPACE (CHAPTER 18 - 19.2.5.7.1.3D

• SUBDIVISION WALLS WITHIN A SUITE MUST BE MADE WITHIN NONCOMBUSTIBLE OR LIMITED COMBUSTIBLE MATERIALS OR WITH FIRE- RETARDANT WOOD THAT IS ENCAPSULATED BEHIND DRYWALL OR PLASTER (CHAPTER 18 - 19.2.5.7.1.4)

• THERE ARE NO SPECIFIC MINIMUM SUITE AISLE/ HALL/ PASSAGE WIDTH AND CORRIDOR WIDTHS O NOT APPLY (7.3.4.1.2)

• PER NFPA 101, THE PHARMACY COMPOUNDING AREA CAN BE CLASSIFIED AS A SUITE FOR PURPOSED OF EGRESS AND LIFE SAFETY

REQUIREMENTS. SUITES ARE COVERED IN CHAPTERS 18.2.5.7 AND 19.2.5.7.

TRAVEL DISTANCE AND COMMON PATH OF TRAVEL (CHAPTER 19):

HEALTH CARE (EXISTING): MAX TRAVEL DISTANCE MAX COMMON PATH OF TRAVEL

SPRINKLED = 200' - 0" SPRINKLED = NR

UNSPRINKLED = 150' - 0" UNSPRINKLED = NR

BUSINESS (CHAPTER 38): MAX TRAVEL DISTANCE MAX COMMON PATH OF TRAVEL

SPRINKLED = 300' - 0" SPRINKLED = 100' - 0"

UNSPRINKLED = 200' - 0" UNSPRINKLED = 75' - 0"

*NON-(IN) PATIENT SUITES MUST FOLLOW COMMON PATH OF TRAVEL EGRESS LIMIT OF THE PRIMARY USE AND OCCUPANCY OF THE SPACE

(CHAPTER 18 - 19.2.5.7.4)(PHARMACY = BUSINESS)

*PASSAGES/ HALLS IN A SUITE SHALL NOT BE LESS THAN 36", NO DOOR LATCHING REQUIREMENTS, NO DOOR SWING REQUIREMENTS AND

NO DOOR CLOSING REQUIREMENTS (7.3.4.1)

CORRIDOR WALL/ DOOR REQUIREMENTS (18.2.5.7.1.2):

• SUITES SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING AND FROM OTHER SUITES, BY WALLS AND DOORS MEETING

CORRIDOR WALL/ DOOR REQUIREMENTS.

INTERIOR WALLS (18.2.5.7.1.2):

• NONCOMBUSTIBLE PARTITIONS (4.6.13)

• LIMITED-COMBUSTIBLE PARTITIONS (4.6.14)

1. PARTITIONS CONSTRUCTED WITH FIRE-RETARDANT, TREATED WOOD ENCLOSED WITH NONCOMBUSTIBLE OR LIMITED-

COMBUSTIBLE MATERIALS

2. SUCH PARTITIONS SHALL NOT BE REQUIRED TO BE FIRE RATED

EXIT ACCESS:

• CORRIDOR EXIT ACCESS - MINIMUM OF (1) (18/19.2.5.6.1)

• CORRIDOR EXIT ACCESS - MINIMUM OF (2) IF GREATER THAN 2,500SF. SECOND CAN BE TO CORRIDOR, STAIR, EXTERIOR OR SUITE

(18/19.2.5.5.2)

• THE EGRESS EXCEPTION FOR SUITES IS IN NFPA 101 - 18/19.2.5.6.4

HAZARDOUS CLASSIFICATION

SUITES CONTAINING HAZARDOUS SPACES (18.2.5.7.1.3):

• INTERVENING ROOMS SHALL NOT BE HAZARDOUS AREAS AS DEFINED BY (18.3.2)

• HAZARDOUS AREAS WITHIN A SUITE SHALL BE SEPARATED FROM THE REMAINDER OF THE SUITE IN ACCORDANCE WITH 18.3.2.1, UNLESS OTHERWISE PROVIDED IN 18.2.5.7.1.3C

• HAZARDOUS AREAS WITHIN A SUITE SHALL NOT BE REQUIRED TO BE SEPARATED FROM THE REMAINDER OF THE SUITE IF:

1. SUITE IS PRIMARILY A HAZARDOUS AREA

2. SUITE HAS APPROVED AUTOMATIC SMOKE DETECTION

3. SUITE IS ENCLOSED AS A HAZARDOUS AREA

*THE CLASSIFICATION OF "HAZARDOUS" IN THE NFPA 101 DIFFERS FROM USP 800. ROOMS LABELED "HAZARDOUS" IN THE CONSTRUCTION DOCUMENTS REFER TO USP 800 REQUIREMENTS. "HAZARDOUS" REGARDING USP 800 RELATES TO THE TYPE OF DRUGS COMPOUNDED IN

THE PHARMACY AND NOT THE COMBUSTIBILITY OF THE MATERIALS IN THE PHARMACY.

GENERAL SHEET NOTES

NR

NR

NR

NR

NR

NR

NR

NR

NR

NR

NR

NR

NR

NR

NR

NR

F+G E+H

B+C A+D

EXISTING CONSTRUCTION TO BE

DEMOLISHED

EXISTING CONSTRUCTION TO

REMAIN

EXISTING DOOR TO REMAIN

EXISTING DOOR TO BE REMOVED

(DEMO)

1. ALL SHADED AREAS INDICATE "NO WORK" OR "NOT IN CONTRACT"

UNLESS OTHERWISE NOTED ON PLAN.

2. REFER TO MEP SHEETS FOR ADDITIONAL DEMOLITION SCOPE AND

REQUIREMENTS.

3. THE DEMOLITION PLANS ARE DERIVED FROM EXISTING BUILDING

PLANS AND ARE INTENDED TO REASONABLY REPRESENT EXISTING

AND CURRENT CONDITIONS. ALL DIMENSIONS AND INFORMATION IN

THESE DRAWINGS ARE BASED, IN PART, ON THAT FACT. ACTUAL

CONDITIONS MAY VARY FROM THAT SHOWN. NOTIFY THE ARCHITECT

IMMEDIATELY FOR REVIEW SHOULD ANY DISCREPANCIES WHICH

SIGNIFICANTLY AFFECT THE DEMOLITION OR NEW CONSTRUCTION

WORK OCCUR.

4. CONTRACTOR TO VERIFY EXISTING CONDITIONS IN THE FIELD.

5. REMOVE ALL WALL MOUNTED ACCESSORIES AND WIRE MOLD

COMPLETE. SALVAGE ACCESSORIES FOR POSSIBLE REUSE.

6. ALL PARTITIONS INDICATED FOR REMOVAL SHALL BE REMOVED TO

THE UNDERSIDE OF STRUCTURE ABOVE, UNLESS NOTED

OTHERWISE.

7. ALL FOURTH FLOOR WORK (ALL TRADES) TO OCCUR DURING ONE

MAXIMUM 21 CALENDAR DARY PERIOD. COORDINATE WORK WITH

COR. SEE R SHEETS FOR ADDITIONAL INFORMATION

8. TEMPORARY PARTITIONS SHALL BE SMOKE TIGHT CONSTRUCTION

OF GYPSUM BOARD OR OTHER NON-COMBUSTIBLE OR LIMITED-

COMUBSTIBLE MATERIAL. PARTITIONS SHALL BE FULL HEIGHT,

EXTENDING THROUGH SUSPENDED CEILINGS TO THE FLOOR SLAB

OR ROOF DECK ABOVE AND SHALL BE 1-HOUR RATED, UNLESS

SPRINKLERS ARE OPERATIONAL ON BOTH SIDES OF THE

TEMPORARY PARTITION, WHEREUPON THE PARTITIONS MAY BE

PERMITTED TO TERMINATE AT THE CEILING. WHERE THE CEILING ON

ONE SIDE OF THE TEMPORARY CONSTRUCTION BARRIER HAS BEEN

REMOVED, THE TEMPORARY PARTITION MUST EXTEND TO THE DECK

ABOVE AND BE 1-HOUR RATED.

8 9 10

G

F

E

PROJECT LIMIT LINE

X-VCT X-VCT

1 1

12 12

4" 3' - 4"

1' - 10 3/4" 3' - 4"

190 SF

EXST. PATIENT

BEDROOM

3A-167

56 SF

EXST. RESTROOM

3A-167A

195 SF

EXST. RECEPTION

3A-164

EXST. CORRIDOR

3C-139

EXISTING PATIENT

ROOM

EXISTING COMPOUNDING

ROOM

3 3 18

3A-165 3A-166 (EXST.)

EXST.

RESTROOM

3A-166A (EXST.)

8 9 10

G

F

E

X-ACT

8' - 7"A.F.F.

X-ACT

9' - 0"A.F.F.

PROJECT LIMIT LINE

CLG-1

9' - 0"A.F.F.

13 13 13

EXIST. RECEPTION

EXISTING PATIENT ROOM

EXISTING COMPOUNDING

ROOM

EXIST.

RESTROOM

EXIST. CORR.

EXIST. RESTROOM

EXIST. PATIENT BEDROOM

9 10

G

F

E

X-GYP-EXIST

9' - 0"A.F.F.

CLG-1

9' - 0"A.F.F.

COORD. WITH STRUCTURAL

1' - 0" +/-

6"

PROJECT LIMIT LINE

EXIST. CORR.

185 SF

EXST. OFFICE

4A-152

148 SF

EXST. MEDICAL

EQUIPMENT

STORAGE

4A-153

52 SF

EXST. PATIENT

TOILET

4A-155B

51 SF

EXST. STAFF

TOILET

4A-154

EXIST. HAC

4A-155A

9 10

G

F F

E

PROJECT LIMIT LINE

EXIST. CORR.

185 SF

EXST. OFFICE

4A-152

148 SF

EXST. MEDICAL

EQUIPMENT

STORAGE

4A-153

52 SF

EXST. PATIENT

TOILET

4A-155B

51 SF

EXST. STAFF

TOILET

4A-154

EXIST. HAC

4A-155A

SHEET NOTES

LEGEND

# NOTE

1 REMOVE EXISTING FLOORING AND WALL BASE IN ITS ENTIRETY. PREP SUBFLOOR TO RECEIVE

NEW FLOOR FINISH. LEVEL FLOOR AS REQUIRED.

3 MAINTAIN FIRE/SMOKE RATING OF EXISTING WALLS THROUGHOUT CONSTRUCTION.

4 REMOVE CEILING TILE, CEILING GRID, SUSPENSION SYSTEM, AND CEILING COMPONENTS IN ITS

ENTIRETY. REFER TO MEPFP DRAWINGS FOR ADDITIONAL INFORMATION.

6 REMOVE EXISTING DOOR AND FRAME IN ITS ENTIRETY. IN FILL OPENING WITH CONSTRUCTION

TO MATCH THE EXISTING WALL CONSTRUCTION. PREP WALLS TO RECIEVE NEW FINISH.

7 REMOVE EXISTING WALL IN ITS ENTIRETY. PATCH AND REPAIR SURFACES TO MATCH ADJACENT

FINISHES.

8 RELOCATE EXISTING EYE WASH STATION. REFER TO MEP DRAWINGS FOR ADDITIONAL

INFORMATION.

9 REMOVE EXISTING HEADWALL IN ITS ENTIRETY. REFER TO MEP DRAWINGS FOR ADDITIONAL

INFORMATION, INCLUDING BUT NOT LIMITED TO MEDICAL GAS REMOVAL

11 REMOVE EXISTING WALL COVERING. PATCH AND PREP WALLS TO RECEIVE NEW FINISHES.

12 WARDROBE CABINET TO BE REMOVED IN ITS ENTIRETY.

13 EXISTING CEILING LED LIGHT FIXTURES TO BE REMOVED AND TURNED OVER TO FHCC.

14 REMOVE EXISTING SINK IN ITS ENTIRETY. REFER TO MEP DRAWINGS FOR ADDITIONAL

INFORMATION.

15 REMOVE EXISTING BEDRAIL IN ITS ENTIRETY.

16 REMOVE EXISTING WALL FINISH IN ITS ENTIRETY. PATCH AND PREP WALLS FOR NEW FINISHES.

17 REMOVE EXISTING WALL IN ITS ENTIRETY. REMOVE OR RELOCATE ANY EXISTING UTILITIES

INCLUDING BUT NOT LIMITED TO ELECTRICAL CONDUITS AND PLUMBING PIPING IN THE WALLS

REQUIRED. REFER TO MEPFP DRAWINGS FOR ADDITIONAL INFORMATION. PATCH AND REPAIR

ADJACENT SURFACES AS REQUIRED. COORDINATE AND MINIMIZE ANY OUTAGE WITH COR.

18 REMOVE PORTION OF EXISTING WALL TO ACCOMODATE NEW DOOR AND FRAME. PATCH AND

REPAIR WALL AS REQUIRED. PREP WALLS TO RECEIVE NEW WALL FINISH.

19 PATCH AND PREP WALLS AS REQUIRED TO RECEIVE NEW FINISHES.

20 REMOVE PORTION OF EXISTING FLOOR SLAB TO ACCOMODATE NEW DUCTWORK. REFER TO MEP

AND STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION.

21 EXISTING CEILING FINISH TO REMAIN.

22 REMOVE PORTION OF EXISTING GYP. CEILING TO ACCOMODATE NEW DUCTWORK. REFER TO

MEP AND STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION.

23 REMOVE EXISITNG EXHAUST DUCT AND CHASE. COORDINATE WITH MECHANICAL AND

STRUCTURAL DRAWINGS FOR ADDITIONAL REMOVAL AND INFILL INFORMATION. PATCH AND

REPAIR AFFECTED FINISHES TO MATCH EXISTING ADJACENT SURFACES.

KEYNOTES

A Serv ic e

D is ab l e d Ve t e ran Owned Sma ll Bus iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0101

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t 6 o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

FOR BID - NOT FOR CONSTRUCTION

FULLY SPRINKLERED

NORTH

ONCOLOGY RENOVATION

FOR USP 800 REQUIREMENTS

556-17-014

BLDG. 133

Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER. DEMOLITION PLANS

AD-100

01/18/19

JAMES A. LOVELL FEDERAL HEALTH

CENTER-NORTH CHICAGO, ILLINOIS

REF HQR

1/4" = 1'-0"C1 FLOOR 3 DEMOLITION FLOOR PLAN

1/4" = 1'-0"F1 FLOOR 3 DEMOLITION RCP

1/4" = 1'-0"E6 FLOOR 4 DEMOLITION RCP LEVEL 3 LEVEL 4LEVEL 2

1/4" = 1'-0"C6 FLOOR 4 DEMOLITION FLOOR PLAN

SS

S S

S S

S S

S S

S S

S S

S S

S S

S S

PARTIAL HT PARTITION - SEE

ELEVATION FOR HEIGHT

NEW PARTITION

EXISTING CONSTRUCTION TO REMAIN

RATED PARTITION

EXISTING DOOR

NEW CONSTRUCTION DOOR

SUITE PERIMETER PARTITION

8 9 10

G

F

E

5-

A

165A-A

5C

-A

165B-A

A-200

B2

A-200

B3

A-200B5

A 1 a

A 1 a

A 1 a

A 1 a

D 4 aD 4 a

E 4 e

99 SF

PHARMACY

RECEIVING AND

SUPPLY

3A-165

90 SF

POSITIVE ANTE

ROOM

3A-165A 71 SF

POSITIVE BUFFER

ROOM

3A-165B

161 SF

NEGATIVE

BUFFER ROOM

3A-165C

EPY-1

EPY-1

EPY-1

EPY-1

PROJECT LIMIT LINE

53 SF

RESTROOM

3A-166

B1 131131

EXIST

6-

A

LINE INDICATES

LOCATION OF PROPOSED

PHARMACY SUITE

A-500 E9

195 SF

EXST. RECEPTION

3A-164

190 SF

EXST. PATIENT

BEDROOM

3A-167

56 SF

EXST. RESTROOM

3A-167A

E 4 e 118 118E 4 e

E9

A-500

A-500 E9

A-500 E9

SIGN 99.1 & 99.a

SIGN 69.1

SIGN

69.1

SIGN

69.1

SIGN 99.6

8 9 10

G

F

E

99 SF

PHARMACY

RECEIVING AND

SUPPLY

3A-165

90 SF

POSITIVE ANTE

ROOM

3A-165A

71 SF

POSITIVE BUFFER

ROOM

3A-165B

161 SF

NEGATIVE

BUFFER ROOM

3A-165C

6' - 7 1/4" 4' - 6" 18' - 4 3/4"

1' - 10 3/4" 3' - 4" R.O. 1' - 4 1/2"

7'

- 9

4"

3'

- 4

R.

O.

4'

- 0 1/

2"

6' - 11 1/2" 12' - 10" 9' - 8 1/2"

6' - 0 1/2" 3' - 4" R.O. 3' - 1 1/4" 5" 9' - 7 3/4"

5" 3'

- 4

R.

O.

3'

- 9

6' - 3 3/4" +/-

4' - 1" 5' - 11 3/4"

3'

- 4

1'

- 5

PROJECT LIMIT LINE

53 SF

RESTROOM

3A-166

4" 3' - 4" R.O.

EJ 56 SF

EXST. RESTROOM

3A-167A

190 SF

EXST. PATIENT

BEDROOM

3A-167

195 SF

EXST. RECEPTION

3A-164

C L

1'

- 7

CL

4' - 6" CL

EJ

1'

- 6

1. ALL SHADED AREAS INDICATE "NO WORK" OR "NOT IN CONTRACT" UNLESS

OTHERWISE NOTED ON PLAN.

2. ALL DIMENSIONS ARE TO FACE OF STUD OR BLOCK FACE.

3. PATCH AND REPAIR REMAINING SURFACES AS NEEDED DUE TO THE

DEMOLITION OR THE REMOVAL OF CONSTRUCTION. PARTITIONS AND

CONSTRUCTION THAT IS TO REMAIN AND IS ADJACENT TO CONSTRUCTION OR

EQUIPMENT TO BE DEMOLISHED SHALL BE REPAIRED TO BE LIKE NEW

APPEARANCE. FINISH SURFACES ARE TO BE SMOOTH AND FLUSH WITH

ADJACENT SURFACES AND PREPPED FOR NEW FINISH.

4. VERIFY THAT ALL BUILDING CORE PARTITIONS AND COLUMNS SHOWN AS

EXISTING CONSTRUCTION ARE READY TO RECEIVE NEW FINISHES AS

SPECIFIED. IF NOT, PROVIDE DRYWALL FINISH AS REQUIRED. DRYWALL

THICKNESS TO MATCH BUILDING STANDARD NOTED ON PARTITION TYPES. AT

ALL EXISTING GYPSUM BOARD CORNERS, VERIFY THAT ALL CORNER BEADS ARE

STRAIGHT, UNBROKEN AND NOT DAMAGED. PROVIDE NEW CORNER BEADS AS

REQUIRED.

5. ALL ANGLES SHALL BE 90 DEGREES UNLESS OTHERWISE NOTED ON PLAN.

6. ALL OPENINGS TO BE 3'-0" WIDE CLEAR UNLESS OTHERWISE DIMENSIONED ON

PLAN. BULKHEAD TO ALIGN

7. PROVIDE [3/8" (IF INTERIOR) / 1/2” (IF EXTERIOR)] CLEAR TEMPERED GLASS,

TYPICAL UNLESS OTHERWISE NOTED. SEE PLAN OR ELEVATIONS FOR SPECIFIC

GLASS DIMENSIONS. ANY JOINTS IN GLASS TO BE POLISHED EDGE, BUTT

GLAZED, NO SEALANT. 1/16" MAXIMUM HORIZONTAL DIMENSION BETWEEN

ADJACENT PANELS, TYPICAL.

8. GENERAL CONTRACTOR TO COORDINATE FIRE EXTINGUISHER LOCATIONS

WITH CONSTRUCTION MANAGER PRIOR TO CONSTRUCTION. FIRE

EXTINGUISHERS ARE TO BE MOUNTED TO MEET ADA STANDARDS.

9. GENERAL CONTRACTOR TO COORDINATE ALL HORN STROBE AND/OR FIRE

ALARM PULL STATION LOCATIONS WITH CONSTRUCTION MANAGER PRIOR TO

CONSTRUCTION.

10. PIPES AND COLUMN FURRING SHALL BE HELD AS CLOSE TO THE PIPING AND/OR

COLUMNS AS POSSIBLE (U.N.O.)

11. OPENINGS THROUGH EXISTING FLOOR SLABS SHALL BE SAW CUT OR CORE

DRILLED. SUCH OPENINGS WILL BE LOCATED TO MINIMIZE THE SIZE

REQUIREMENTS FOR THE FURRED CHASES. THE CONTRACTOR WILL LOCATE

ALL FLOOR OPENINGS IN THE FIELD AND REVIEW PROPOSED LOCATIONS WITH

THE OWNER AND ARCHITECT PRIOR TO BEGINNING WORK.

12. PROVIDE NEW FINISHES AS REQUIRED WHERE DEMOLITION/NEW

CONSTRUCTION IS TAKING PLACE AT BUILDING CORRIDOR TO MATCH EXISTING

CORRIDOR FINISHES.

13. CONTRACTOR TO COORDINATE AND INSTALL FIRE RETARDANT WOOD

BLOCKING AT ALL BUT NOT LIMITED TO THE FOLLOWING LOCATIONS - ALL

FIXTURES, EQUIPMENT, SIGNAGE, MILLWORK.

14. IF ANY FIRE RATED PARTITION FALLS DIRECTLY BENEATH AND PARALLEL TO A

FLOOR JOIST OR BEAM, NOTIFY THE ARCHITECT PRIOR TO FRAMING THE

PARTITION.

15. ALL SWITCHES TO BE MOUNTED NO HIGHER THAN 48" A.F.F. TO MEET ADA

STANDARDS.

16. MOUNT THERMOSTATS 48" A.F.F. MAXIMUM TO MEET ADA STANDARDS.

17. PROVIDE 3" TALL HELVETICA LETTERS STENCILED AT ALL RATED WALLS,

STENCILING TO READ AS FOLLOWS "FIRE AND SMOKE BARRIER-PROTECT ALL

OPENINGS". INCLUDE UL NUMBERS TYPICAL OF ALL RATED WALLS.

18. A.T.P. INDICATES ADA TRAP PROTECTION, PROVIDE ON ALL EXPOSED

SINK/LAVATORY TRAPS.

19. PROVIDE AND INSTALL ALL STIFFENERS, BRACING, BACK-UP PLATES AND

SUPPORTING BRACKETS REQUIRED FOR THE INSTALLATION OF ALL CASEWORK,

TOILET ACCESSORIES AND OF ALL FLOOR-MOUNTED OR SUSPENDED

MECHANICAL AND ELECTRICAL EQUIPMENT.

20. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR EXAMINING AND

CONFIRMING ALL SUBSTRATE CONDITIONS WHERE NEW MATERIALS ARE

APPLIED. SUBSTRATE SHALL BE SMOOTH, FREE OF DEFECTS AND SHALL

CONFORM TO THE REQUIREMENTS OF THE FINISHED MATERIAL

MANUFACTURERS’ RECOMMENDATIONS.

21. WHERE ADJOINING ROOMS HAVE DIFFERENT TYPES OF FLOORING OR SIMILAR

FLOORING OF DIFFERENT COLORS, MAKE TRANSITION UNDER CENTER LINE OF

DOOR.

22. WHERE INDICATED TO MATCH EXISTING FINISH, NEW FINISH TO MATCH IN

MANUFACTURER, PRODUCT, COLOR, STYLE, SIZE AND ALL OTHER ATTRIBUTES.

23. ALL CAULK AT CASEWORK AND COUNTER TOPS TO BE CLEAR. PROVIDE

CAULKING AT ALL FIXTURES.

24. TEMPORARY PARTITIONS SHALL BE SMOKE TIGHT CONSTRUCTION

OF GYPSUM BOARD OR OTHER NON-COMBUSTIBLE OR LIMITED-

COMUBSTIBLE MATERIAL. PARTITIONS SHALL BE FULL HEIGHT,

EXTENDING THROUGH SUSPENDED CEILINGS TO THE FLOOR SLAB

OR ROOF DECK ABOVE AND SHALL BE 1-HOUR RATED, UNLESS

SPRINKLERS ARE OPERATIONAL ON BOTH SIDES OF THE

TEMPORARY PARTITION, WHEREUPON THE PARTITIONS MAY BE

PERMITTED TO TERMINATE AT THE CEILING. WHERE THE CEILING ON

ONE SIDE OF THE TEMPORARY CONSTRUCTION BARRIER HAS BEEN

REMOVED, THE TEMPORARY PARTITION MUST EXTEND TO THE DECK

ABOVE AND BE 1-HOUR RATED.

25. ALL FOURTH FLOOR WORK, ALL TRADES, TO OCCUR DURING ONE MAXIMUM 21

DAY CALENDAR DAY PERIOD COORDINATION WITH COR.

9 10

G

F

148 SF

EXST. MEDICAL

EQUIPMENT

STORAGE

4A-153

6"

PROJECT LIMIT LINE

SE

E

ST

RU

CT

UR

AL

185 SF

EXST. OFFICE

4A-152

B 4 a

C 1 a 51 SF

EXST. STAFF

TOILET

4A-154

52 SF

EXST. PATIENT

TOILET

4A-155B

SEE STRUCTURAL DRAWINGS

3'

- 9

1/ 4"

- 9 1/2" VIF

SEE STRUCTURAL

B 4 a

D 1 a

8 9 10

G

F

E

PRNT

PPE2

PPE2

HOOD

(1)

99 SF

PHARMACY

RECEIVING AND

SUPPLY

3A-165

90 SF

POSITIVE ANTE

ROOM

3A-165A 71 SF

POSITIVE BUFFER

ROOM

3A-165B

161 SF

NEGATIVE

BUFFER ROOM

3A-165C

PH COMP

REF1

SD

TD

PROJECT LIMIT LINE

CH1

SH1 SH1

SH2

SH2

SH2

PPE TRPPE

CH1 CH1

TR

CH1

TR

53 SF

RESTROOM

3A-166

133 PT

190 SF

EXST. PATIENT

BEDROOM

3A-167

56 SF

EXST. RESTROOM

3A-167A

195 SF

EXST. RECEPTION

3A-164

EXT

REF1

HOOD (3)

HOOD

(2)

1167 SF

EXST. CORRIDOR

C3-140

58 SF

EXST. TOILET

3A-157

155 SF

EXST. NURSE

OFFICE

3A-158

118 SF

PHARMACY

OFFICE

3A-159

104 SF

PHARMACY

OFFICE

3A-160 507 SF

EXST. WAITING

3A-162

25 SF

EXST. STAFF

TOILET

3A-161

128 SF

EXST. EXAM

3A-150

124 SF

EXST. EXAM

3A-151

145 SF

EXST. EXAM

3A-152

134134

PR

OJ

EC

T

LIM

IT

LI

NE

SHEET NOTES

LEGEND

KEYNOTES

# NOTE

116 EXISTING WALL TO BE THE NEW SMOKE AREA BARRIER WALL. EXISTING METAL STUD FRAMING AND GYP. FINISHES EXTEND TO THE DECK. MUD AND TAPE ALL UNTAPED GYP. BD. JOINTS. SEAL

ALL UNSEALED PENETRATIONS AND JOINTS WITH FIRE CAULK AS REQUIRED.

117 RELOCATED GUARDIAN GBF1735DP EYEWASH CABINET. INSTALL PER MANUFACTURERS

SPECIFICATIONS REFER TO PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.

118 BLACK-OUT PANELS MECHANICALLY FASTENED TO EXISTING WINDOW FRAME BEHIND NEW

GYP.FURRING. PANELS TO BE PAINTED 1/2" MIN. FINISH GRADE PLYWOOD. PAINT EXTERIOR

FACE OF PLYWOOD BLACK.

122 EXTEND GYP BOARD FINISH BELOW WINDOW SILL TO EXTERIOR WALL.

123 SHAFT OPENING FOR NEW DUCT WORK. COORDINATE SHAFT OPENING AND LOCATION WITH

STRUCTURAL DRAWINGS. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.

124 WALL MOUNTED FIRE EXTINGUISHER. COORDINATE FINAL LOCATION WITH CONSTRUCTION

MANAGER IN FIELD.

125 PACS ACCESS CONTROL. FACILITY STANDARD - LENEL ONGUARD SYSTEM. REX REQUEST TO

EXIT. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION

126 15" X 17" STAINLESS STEEL SCRUB SINK WITH FOOT CONTROLS. SEE PLUMBING DRAWINGS FOR

ADDITIONAL INFORMATION.

127 PROVIDED 24"x24" RATED ACCESS DOOR(S) IN SHAFT WALL AS REQUIRED TO ACCESS DAMPERS

IN THE DUCTWORK. COORDINATE FINAL LOCATION(S) AND SILL HEIGHT WITH MECHANICAL AND

STRUCTURAL DRAWINGS.

131 WALL PROTECTION WP-1. REFER TO ELEVATIONS.

132 WALL INFILL TO MATCH EXISTING CONSTRUCTION.

133 AIRLOCK PASS THROUGH.

134 NEW WALL MOUNTED MONITOR AND BRACKET.

136 ROOM SIGNAGE. REFER TO SPECIFICATIONS FOR ADDITONAL INFORMATION.

137 LOCATION OF FIRE RATED ENCLOSURE. SEAL ALL PENETRATIONS PER SPECIFICATIONS. GC TO

COORDINATE LOCATION OF ENCLOSURE WITH EXISTING PNEUMATIC TUBE (OUTSIDE

ENCLOUSRE) AND DUCT WORK (OUTSIDE ENCLOSURE). RATED WALLS AND ENCLOSURE IS NOT

TO INTERFERE WITH EXISTING RADIANT HEAT PANEL. REFER TO MEPFP DRAWINGS FOR

ADDITIONAL INFORMATION.

138 REPAIR FINISHES AS NEEDED AT REMOVED DUCT CHASE LOCATION

A Serv ic e

D is ab l e d Ve t e ran Owned Sma ll Bus iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0101

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t 6 o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

FOR BID - NOT FOR CONSTRUCTION

FULLY SPRINKLERED

NORTH

ONCOLOGY RENOVATION

FOR USP 800 REQUIREMENTS

556-17-014

BLDG.

This is the start of the file's text. The full file is on GovTribe.