This is an amendment to a previous combined solicitation for engineering services related to a reverse osmosis water system at the VA Medical Center in Chillicothe, Ohio. The solicitation (36C25026Q1034) is issued by the Department of Veterans Affairs Network Contracting Office in Cleveland, with a response deadline of September 22, 2026, at 3:00 PM Eastern Time. The contracting officer is Christopher A. Callihan (christopher.callihan@va.gov, 216-707-7736). The work involves modifications to an existing water distribution loop system with mixed materials (CPVC and polypropylene) spanning approximately 240 linear feet in sizes of 1" and 1.5" piping.

The amendment clarifies the scope of work through a questions-and-answers format addressing contractor inquiries. Key clarifications include: 0.2-micron filter cartridges are for bacterial removal from water and must be compatible with housing provided under CLIN 0003; the return loop is constrained via a 3 GPM flow control device with pressure-sensing variable flow rate pumps (neither of which are within scope); existing pumps and equipment are being retained by the facility; and tank vent cartridges are excluded from the scope. The solicitation uses NAICS code 221310 (water supply and irrigation systems) and product service code 4610. No set-aside is indicated, and no Recovery Act funds are involved. The place of performance is the Chillicothe VAMC located at 17273 State Route 104, Chillicothe, Ohio 45601.

View the file

Other files

File Type Posted
36C25026Q1034.docx DOCX document
OPPORTUNITIES-DESCRIPTION 02.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment to a Previous Combined Solicitation

Amendment to a Previous Combined Solicitation

SUBJECT*
Engineering Request - SPS REVERSE OSMOSIS | 538-26-3-6064-0049 (VA-26-00079545) - VAMC Chillicothe

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
44131-6969
SOLICITATION NUMBER*
36C25026Q1034
RESPONSE DATE/TIME/ZONE
09-22-2026 15:00 EASTERN TIME, NEW YORK, USA
ARCHIVE
30 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N
SET-ASIDE
SBA
PRODUCT SERVICE CODE*
4610
NAICS CODE*
221310
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Network Contracting Office 10 6100 Oak Tree Boulevard Suite 490 Cleveland OH 44131-6969

POINT OF CONTACT*

Contracting Officer Christopher A. Callihan christopher.callihan@va.gov 216-707-7736 N/A N/A

PLACE OF PERFORMANCE

ADDRESS
Department of Veterans Affairs

Chillicothe VAMC

17273 State Route 104

Chillicothe OH

POSTAL CODE
45601
COUNTRY
USA

ADDITIONAL INFORMATION

AGENCY’S URL
https://www.va.gov/contact-us/
URL DESCRIPTION
Department of Veterans Affair
AGENCY CONTACT’S EMAIL ADDRESS
christopher.callihan@va.gov
EMAIL DESCRIPTION
Contracting Officer

DESCRIPTION

The purpose of this amendment is to post questions received and provide the facilities responses. The response date and time remain unchanged.

1. Are the 0.2 Micron Filter Cartridges the ones that are for the tank vent filter we would be providing? Or is this for an existing endotoxin filter housing the facility has?

0. 0.2 Micron Filter Cartridges are for bacterial removal from water and to be compatible with housing provided under CLIN 0003. Tank vent cartridges are maintained separately and not within scope.

1. What flow rates do the 60-gallon and 160-gallon storage tank loop return need to handle? Specifically, when sizing the loop return flow meter we need to ensure it can handle the pump demand. I would assume 20 GPM and 40 GPM based on the UV assembly?

1. Return is being constrained via 3gpm flow control device. Pumps are pressure sensing variable flow rate. Both flow control and pumps are not within scope of the solicitation. UV sized for peak demand.

1. Are there existing pumps within the facility that they are keeping? I do not see a distribution pump mentioned in this bid.

2. Pumps are not within scope.

1. Do you have a list of existing equipment that is being kept for both systems?

3. No

1. What are the distribution loop sizes, loop material and loop length – are they existing or is this a new loop?

4. Modifying existing loop. Mixed materials, CPVC and Polypropylene. Loop is approximately 240 LF with mixed sizes of 1” and 1-1/2”