Gen Model No. and Specs Updated.xlsx

XLSX spreadsheet 3 MB Posted

Attached to
J030--Generator Testing and Maintenance - Battle Creek, MI
Solicitation number
36C25026Q0551
Issued by

About this file

This file is a generator and automatic transfer switch (ATS) inventory spreadsheet for the Department of Veterans Affairs facility in Battle Creek, Michigan. The facility operates 20 generators ranging from 8 kW to 750 kW in capacity, with models from manufacturers including Onsite Energy, Kohler, Caterpillar, Cummins, and John Deere. Generator specifications include voltage configurations (primarily 120/208V and 277/480V), amperage ratings, dates of birth ranging from 1966 to 2021, serial numbers, and engine specifications. Stack gas temperatures are recorded for each unit, ranging from 797°F to 1,157°F. The facility also maintains 43 ATS units distributed across multiple buildings, with amp ratings between 150 and 1,600 amps and primarily 120/208V configurations, along with some 277/480V units.

The spreadsheet documents comprehensive equipment details for maintenance and testing purposes, including transfer times to normal power ranging from 2 seconds to 15 minutes and cooldown times from 0 to 11 minutes. ATS manufacturers include Zenith, ASCO, Emerson, Kohler, Cummins, Russelectric, ONAN, and Cutler-Hammer, with asset tracking numbers and equipment room locations. This inventory data supports the Battle Creek Generator Testing and Maintenance contract opportunity (Solicitation 36C25026Q0551) administered by the VA Veterans Health Administration, Veterans Integrated Service Network 10, and provides baseline equipment information necessary for developing testing and maintenance service requirements.

View the file

Other files

File Type Posted
36C25026Q0551 0002.docx DOCX document
36C25026Q0551 0001.docx DOCX document
BCVA.StationMap.0624.pdf PDF
Station Map.pdf PDF
36C25026Q0551_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

#Bldg/Rm #Serves BldgEE #Asset #Size - kWAmpsVoltageD.O.B.Model No.MFRSerial #Generator Mfg.Engine Mfg.Engine Serial #Engine Model #Gas Temp (Stack)
11352/1571398768715527502604120/2085/1/15750PXC6DT2Onsite Energy3704-13-5-3-0314MTUMTU1,076 F
21593/141398798580404001388120/2085/1/15DS00400DSPAH1574Onsite Energy3704 13-2-1-0214MTUMTU892 F
31694/7/121398788446316002083120/2085/1/15DS00600DSPAH1484Onsite Energy3704 13-4-2-0214MTUMTU797 F
413551398778312957502604120/2085/1/15750PXC6DT2Onsite Energy3714-13-5-1-0314MTUMTU1,076 F
3018/9/13249345024934505001735120/2085/6/21500REOZJKohler33GKGMHN0003KohlerJohn Deer6135HFG75975F
7Outside 22221322388604295001736120/2081/23/13C15DITACaterpiller447-1212CatCatFT01066951 F
8Outside 2525/2412720984325250173120/20810/14/1050PJC6DT3Onsite320162-1-1-0410John DeerMTU4024HF2851,029 F
9171308717843190275954120/2087/10/66AC Generator Set # NT-855-GS6CumminsGenerator Set # L880186977CumminsCumminsID # 275NT6?31032B975 F
10170391398838370096002083120/2085/1/15DS00600DSPAH1484Onsite Energy3704-13-4-1-0214MTUMTU797 F
11161821398818565595001736120/2085/1/15DS00500DSPAH1484Onsite Energy370413-5-3-0314MTUMTU862 F
1216583/841398828612607502604120/2085/1/15750PXC6DT2Onsite Energy3704-13-5-2-0314MTUMTU1,076 F
13136, Rm 133136139880844110300451277/4805/1/15DS00300DSPAH1574Onsite Energy370413-1-1-0214MTUMTU824 F
14Outside 15715714338385889925086812/20810/1/16250REOZJEKohler250REOZJEKohler1157 F
15300,Rm A121300 NG133497828745500751277/48011/15/13TSB-2ST-2100-150OnsiteMX162357-0611John DeerKohler862 F
16300,outside300 CHP16618821661882250375277/4801/1/16250REOZJEKohlerGM66808-KPKohlerJohn Deer6090HF4841,157 F
17Portable 200KWMobil127177846520229344277/48010/28/10200REOZTKohler10006024John DeerKohler
18Portable 500KWMobil1271768312714581527120/20810/28/10500REOZTKohler10008471VolvoKohler
19Portable 55KWMobil188258418825845543120/20812/4/1855REOZT4-CP1Kohler33HFGMFN0002KohlerKohlerKDI 3404 TCR824 F
201631 W MichTRP House133191836420833120/24012/3/14GRD/GEN-NO T/SW8381425
21560 NE CapitalTRP House13319287197983312/24012/3/14GRD/GEN-NO T/SW8381426

Nameplate Pics

Generator Nameplates
Bldg 8, 9 & 13
Bldg. 22
Bldg. 25
Bldg. 30
Bldg. 157
Portable 150 Whisperwatt

ATS & MTS

#Bldg #IDServingLocationAsset #AmpsVoltsMakeModel/Cat #Serial #Part NO.DateTransfer Time to NormalCool Down Time for Gen
12ATS #1B2Rm 004 (137)26796681600120/208ZenithDWG NO. IR-0093ZTS-160E-4AAELLPTU-6A-VA7-802min7min
22ATS #2B2 SWBD-B2ACourtyard near 0F030267966960012/208ASCO?????????????5min5min
33ATS #1B3Rm 1112679670400120/208Emerson7000 Series996383-001 WEJ07ATBB30400C5XC5min5min
44ATS #1P-1Basement2679671400120/208KohlerK13575K-168341-0400 02AS 08CS 14C7min0
54ATS #2P-2Basement2679672400120/208KohlerKCS-DCTA-0400SSGM32FX725min5min
65ATS #1B5 MDP-1Rm 00426796781600120/208CumminsCTCU1600C 1081GH8902630307 Min5min
75ATS #2B5 MDP-2Rm 00426796791600120/208ASCOG07ATSA31600C5XC160412812334215 Min5min
87ATS #1CRRm 006E2679680400120/208RusselectricRMTCostomer # N-TS-899DWG NO. R-1A-1203-110/695min5min
97ATS #2LSRm 006E2679681400120/208RusselectricRMTCostomer # N-TS-899DWG NO. R-1A-1202-110/695min0
108ATSB8RM SP0012679682400120/208ZenithZTSH406C-424130412min10min
119ATSB9Basement2679673400120/208ZenithZTSH40EC-424130915min7min
1212ATSB12Basement2679674400120/208KohlerK13574K-168341-0400 02AS 08CS 1409min0
1313ATSB13Rm 019E26796751200120/208ASCOH03ATSA31200CGXC1772001 RE101909011min11min
1414ATS-AA, EquipmentRm 008E2679676400120/208ASCO862064-2940840049XC2min6min
1514ATS-BB, Life SafetyRm 008E2679677400120/208ASCO862065940326049XC2sec7min
1614ATS-CC, CriticalRm 008E2679683200120/208ASCO??2064-1940340049XC2sec7min
1722ATSB22Rm 137E26796841000120/208ASCO
Hoskins, Dean M: ATS has a 2 second delay when transfering to normal power, from generator power.963584908582 REH7ADTSB31000C5XC10min6min
1825ATSB25Rm 101E2679685400120/208ASCO915641622803 REE00300030400C1XC9min5min
1927MTSB27/28Exterior West400120/208MidwestGS3404B01ULMTSMTS
2030ATS #1#1Rm 100H2679686600120/208ASCO917332C94036004915min5min
2130ATS #2#2Rm 100F2679687260120/208ONANOTCU 260CA93049710610min4min
2239ATS #1LSRm BC302680306225120/208ASCO959532895238 WEJ07ATBB30230C5XC5min5min
2339ATS #2CRRm BC302680307400120/208ASCO959534895240 WEJ07ATBB30400C5XC5min5min
2439ATS #3EQRm BC302680308800120/208ASCO959538895241 WEH07ATBB30800C5XC5min5min
2539ATS #4ChillerRm BC302680309400120/208ASCO959534895239 WEJ07ATB30400C5XC5min5min
2639ATS #5LP-ARm 013E2680310600120/208ASCO940360049XC8620661sec9min
2739ATS #6LP-BRm 013E2680311400120/208ASCOB940340049S 89087-21sec6min
2882ATS #1LS82Rm 016E2680312150120/208ONANOTBCA150-4U/3101EL850790729(Inside) P/N 306-243910min5min
2982MTS #2CriticalRm 016E225120/208ONANOTBCA150-4U/3101EL850790728(Inside) P/N 306-243910min5min
3082ATS #3EE 82Rm 016E2680313400120/208ASCO993858996383-002 WEJ07ATBB240400C5XC7min4min
3182ATS #4PDRm Sub-Base2680730450277/480ASCO311123996384 WEJ07ATBB30600N5XC5min5min
3282ATS #5LP-LRm 016E2680731400120/208CumminsOTECC-1532118K15M89648099-24337/215min5min
3383ATS #1LSATSOARm 014E2680733600120/208KohlerKBS-DCVA-0600BSGM32BPC29/145min5min
3483ATS #2SBATSOARm 014E26807341200120/208KohlerKBS-DCVA-100SSGM32BPC49/145min5min
3583ATS #3SBATSOBRm 014E26807351000120/208KohlerKBS-DCVA-1200SSGM32BPC39/145min5min
3683ATS #4EQRm 014E2680736300120/208KohlerKCS-FCTA-0800SSGM32BPC55min5min
3784MTS #1MCC84Rm 08E400
Department of Veterans Affairs: 800 amp rated120/208Cutler-Hammer30-11324-15MTSMTS
38136ATS #1B136Rm 117E2680738600277/480ASCO837672515274* WEJ07ATBB30600N5XC5min5min
39157ATS #1157Rm 100C937494800120/208ASCO10175801362618 WEH07ATBB300800C5XC7min5min
40157ATS #2157Rm 100C936662800120/208ASCO11301101362619 WEH07ATBB30800C5XC10min10min
41300 BoilerATS #1300Rm A1212680739260277/480ASCO915188668215 WEJ07ATSB30260N5XC5min5min
42300 BoilerATS #2300Rm A1212680740600277/480ASCO915187668214 WEH07ATBB308000N5XC2min5min
43300CHPATS-#3300RmB1032680741600277/480KohlerKBS-DMVA-00BSGM32888411/1310min5min