J061--Maintenance Services for Emergency Generators Aleda E. Lutz VA Medical Center
Solicitation number
36C25025Q0188
Issued by

About this file

This is a Sources Sought notice from the Department of Veterans Affairs seeking capability statements from contractors able to provide maintenance services for emergency generators at the Aleda E. Lutz VA Medical Center in Saginaw, MI. The period of performance is April 5, 2025 - April 4, 2026.

The scope includes maintenance services for five emergency generators (two Cummins/Onan and three MTU Onsite Energy units), requiring manufacturer-certified technicians to perform 46 specific maintenance checks, operational checks, and maintenance services including fluid analysis, filter changes, and used oil recycling in compliance with Michigan state regulations. Contractors must submit fluid analysis reports within 7-10 days of maintenance completion and perform all services within 60 days of award. Responses are due by January 3, 2025, at 3:00 PM ET and must include business information, SAM UEI, NAICS code 811310, business size status, and socioeconomic status. The contract specialist is Ariel Bautista-Lagares, and this market research may be used to determine potential set-asides.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SUBJECT*

Maintenance Services for Emergency Generators Aleda E. Lutz VA Medical Center

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
46240
SOLICITATION NUMBER*
36C25025Q0188
RESPONSE DATE/TIME/ZONE
01-03-2025 15:00 EASTERN TIME, NEW YORK, USA
ARCHIVE
60 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N

SET-ASIDE

PRODUCT SERVICE CODE*
J061
NAICS CODE*
811310
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Network Contracting Office 10 8888 Keystone Crossing Suite 325 Indianapolis IN 46240

POINT OF CONTACT*

Contract Specialist Ariel Bautista-Lagares Ariel.Bautista-Lagares@va.gov 734.222.7169

PLACE OF PERFORMANCE

ADDRESS
Aleda E. Lutz VA Medical Center

1500 Weiss Street

Saginaw MI

POSTAL CODE
48602
COUNTRY
USA

ADDITIONAL INFORMATION

AGENCY’S URL
https://www.va.gov/saginaw-health-care/locations/aleda-e-lut
URL DESCRIPTION
Aleda E. Lutz VA Medical Center
AGENCY CONTACT’S EMAIL ADDRESS
Ariel.Bautista-Lagares@va.gov
EMAIL DESCRIPTION
Ariel Bautista-Lagares

Sources Sought Notice Sources Sought Notice

DESCRIPTION

*= Required Field
Sources Sought Notice

Sources Sought Notice

This Sources Sought/Market Survey Notice is being conducted by Aleda E. Lutz VA Medical Center, 1500 Weiss Street, Saginaw MI, 48602 to identify all sources that are capable of providing Maintenance Service for Emergency Generator for the period of April 5, 2025 – April 4, 2026 at the discretion of the Government in strict accordance with all schedules, specifications, terms, conditions and provisions of this contract.

General Information VISIT #1 Furnish all tools, labor, materials, parts, and laboratory services to perform the following specified maintenance on the five generators listed at the end of this document:

All maintenance, service, operational checks, and parts shall be performed and supplied per the manufacturer’s recommendations by manufacturer certified technicians.

Contractor shall provide all fluid analysis reports and within 7 – 10 days after completion of maintenance.

Contractor performance shall be monitored through service reports that shall be submitted after each repair has been conducted. Field service reports must be submitted within 7-10 days and will be reviewed for accuracy and timely submission.

Contractor shall perform services within 60 days of award.

Maintenance Checks:

1.

Page 1 of

2. Radiator core for air flow

3. Antifreeze protection

4. Coolant level

5. Coolant inhibitor strength (add conditioner if required to update strength)

6. Radiator cap and seal

7. Coolant leaks

8. Lube oil level

9. Fan belt tension

10. Condition of all hoses

11. Hose clamps

12. Condition of flex fuel lines

13. Day tank float controls, solenoid, and main fuel pump operation

14. Fuel system for leaks

15. Cranking voltage drop

16. Battery electrolyte level

17. Battery voltage

18. Battery charger rate

19. Battery cables and connections

20. Flex exhaust couplings rain flashing

21. Turbo wheel for bearing wear

22. Terminal strip connections

23. Loose relays in control panel

24. Jacket water heater operation

25. Governor oil level

26. Governor linkage

27. Remote governor control operation

28. Air gap on generator

29. Collector rings and brushes

30. Oil and dirt buildup in generator

31. System for loose bolts, etc.

32. Crank termination time

33. Engine instruments

34. Abnormal noise or vibration

35. Exhaust characteristics

36. Louver operation

37. Crankcase blow by

38. Voltage and frequency

39. All switches in correct position

40. Drain water and sediment from day tank

41. Lubricate generator bearing

42. Clean engine crankcase breather

43. Lubricate fan pulley

44. Clean primary filter

45. Drain exhaust moisture traps

46. Inspect the turbocharger for end play and leaks

Page 1 of Page 1 of

Maintenance Services:

Note: All filters shall be OEM

1. Change air cleaner elements, check seals, air cleaner indicators and air induction system

2. Take oil sample and perform infrared analysis (performed by a Fluid Analysis Lab)

3. Take fuel and coolant samples and perform analysis (performed by a Fluid Analysis Lab)

4. Change lube oil and filters, lube oil is to be replaced with fully-synthetic oil in accordance with manufacturers recommendations

5. Change fuel filters

6. Oil, fuel, and coolant samples taken will be delivered to the testing laboratory in a reasonable time as to not compromise the samples. Care will be taken as to storing the samples as recommended by the testing laboratory until they are delivered.

Operational Checks:

1. Recheck oil level while running

2. Recheck all fluid systems for leaks Used Oil Transportation and Recycling:

Transportation and recycling of used oil shall be performed in accordance with Federal, state and local regulations including:

· Michigan Natural Resources and Environmental Protection Act 451, of 1994 as amended, Part 121 Liquid Industrial By-Product.

· Prior to transporting used oil from the property, the transporter must provide a shipping document describing the materials in accordance with above regulation for certification by the Detroit VAMC GEMS Program Manager or designee. The contractor shall arrange for the designated recycling facility to notify the COR, in writing, that the shipment(s) arrived at its destination within 7 days of the date the shipment left the facility.

· Michigan Hazardous Material Transportation Act 138.

· Prior to transporting used oil from the property, the contractor shall provide a copy of the Act 138 transporter’s permit and registration to the COR for the approval of the GEMS Program Manager. During transport, the transporter must also be able to produce a copy of the Act 138 permit and registration, either via electronic record or hard copy, to DEQ staff or a peace officer when requested.

Generator #1 Cummins/Onan Model: DFEB-4955010 Sn: B010204440 KW: 400 PF: .8 Volt: 120/208 Amp: 1387 Generator #2 MTU Onsite Energy Model: 400PXC6DT3 Sn: 331914-1-1-0411 KW: 400 PF: .8 Volt: 120/208 Amp: 1387 Generator #3 Cummins/Onan Model: 350 DFCC Sn: G920477586 KW: 350 PF: .8 Volt: 277/480 Amp: 526 Generator #6 MTU Onsite Energy Mod: 750RXC6DT2(G05) Sn: WA-572596-0410 KW: 750 PF: .8 Volt: 277/480 Amp: 1127 Generator #7 MTU Onsite Energy Mod: DS00500D6SRAH1583 Sn: 331787-1-1-0411 KW: 500 PF: .8 Volt: 277/480 Amp: 751 If this is a service your business can provide, respond to this Sources Sought by Friday, January 3, 2025; 3:00 P.M. Eastern time. Responses should include: (1) Business Name and Address (2) Point of Contact Name, Phone Number, and E-mail Address (3) SAM UEI and NAICS code (4) Business Size SMALL or LARGE (5) Type of Business SERVICE DISABLED VETERAN OWNED, VETERAN OWNED, 8A, HUBZone, WOMEN-OWNED etc. (6) Applicable GSA/FSS Contract Number (if applies). All businesses eligible to provide this service are encouraged to reply as this information may be used to determine potential set-asides for the above noted service. E-mail responses to: Ariel Bautista-Lagares, at Ariel.Bautista-Lagares@va.gov (Note: This is NOT A REQUEST FOR QUOTE or an announcement of a solicitation.)