Addendum 1.pdf
PDF 14 MB Posted
- Attached to
- Z2DA--Project No. 539-CSI-207 - Prepare Site for MRI. Federal contract opportunity
- Solicitation number
- 36C25024B0100
About this file
This document is Addendum 1 related to Solicitation Number 36C25024B0100, a federal contract opportunity titled "Z2DA--Project No. 539-CSI-207 - Prepare Site for MRI" posted by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.
The addendum provides clarification and additional information for the solicitation. It includes updated specifications for the project, revised pricing templates, and answers to questions submitted by interested parties. The key details are: the project involves preparing the site for installation of an MRI machine, the solicitation has a response deadline of June 15, 2024, and the anticipated award date is August 1, 2024. The contract will be awarded as a firm-fixed price contract. The solicitation is set aside for service-disabled veteran-owned small businesses. No information is provided about any incumbent contractors.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25024B0100 0005.docx | DOCX document | |
| 36C25024B0100 0004.docx | DOCX document | |
| 36C25024B0100 0003.docx | DOCX document | |
| 36C25024B0100 0002.docx | DOCX document | |
| 36C25024B0100 0001.docx | DOCX document | |
| Attachment III - Drawings.pdf | ||
| Attachment II - Specs.pdf | ||
| Attachment I - DBA WD.pdf | ||
| 36C25024B0100_1.docx | DOCX document | |
| Attachment V- RFI Form.pdf | ||
| Attachment IV - EMR Form.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MRI Site Prep
Cincinnati VAMC – Project #539-CSI-207
Addendum No. 1
524 Fernwood Drive, Altamonte Springs, Florida 32701 | rdcjpa.com | 800.362.1523
August 5, 2024
Addendum No. 1
MRI Site Prep
Cincinnati VAMC – Proj. #539-CSI-207
3200 Vine Street
Cincinnati, OH 45220
This Addendum supplements and amends the original Drawings and Specifications for the above referenced project. This Addendum shall be forwarded to all Prime Bidders and all appropriate building code authorities. This Addendum shall be taken into account in the preparation of bids and shall become a part of the Contract Documents.
Receipt of this Addendum must be acknowledged on the Bid Form.
This addendum consists of the following items:
General
1. Pre-Solicitation Site Visit – Sign-In List
2. Responses to “Requests For Information” (RFI’s).
Specifications
3. Section 013526 SAFETY REQUIREMENTS – Section Reissued. Revisions include the following:
a. Section adopts latest VA template language updates.
b. Paragraph 1.17, E – Temporary Construction Partitions:
i. Language included noting modular wall systems as an acceptable alternative.
c. ICRA & PCRA Forms included.
d. Paragraph 1.17, E – Temporary Construction Partitions:
i. Language included noting modular wall systems as an acceptable alternative.
Drawings
4. Sheet A101 – New Work Plan – 2nd Floor: – Sheet Reissued. Revisions include:
a. Added location & configuration of temporary construction partition & door.
b. General Note D: Revised maximum time limit of chiller change-over to 5 days.
5. Sheet A102 – Partial 3rd Floor Plan – Step #2r: – Sheet Reissued. Revisions include:
a. Revised configuration and orientation of new roof curbs for new chiller.
b. General Note D: Revised maximum time limit of chiller change-over to 5 days
6. Sheet M101 - Partial Second Floor Plan – Removals and New Work: – Sheet Reissued.
Revisions include:
a. Extended chiller replacement time to 5 days per General Note A.
b. Added components required per plan note 4.
7. Sheet E100 – Electrical Partial Floor Plans: – Sheet Reissued. Revisions include:
a. New location for disconnect switch.
End of Addendum No. 1
Ques�ons & Answers
1. Can the CQ Manager be the superintendent?
Response: YES.
2. Needs verified: Siemens cut sheets, O & M, and install instruc!ons are needed.
Response: No cut sheets provided since no addi�onal/replacement equipment being provided for GC use.
3. Needs verified: What gets replaced in the controls room needs verified. What I supplied/provided by Siemens vs. contractor’s responsibility.
Response: No Contractor work required in Control Room.
4. Needs verified: Is there space in the control room for new connec!ons.
Response: No new Contractor connec�ons are required in Control Room.
5. Needs verified: With a 48-hour window of needing the old unit down and the new unit opera!onal no connec!ons can be made prior. How is a pressure test to be performed in the component room before MRI is set into place. Only pressure test able to be perform is at the !e in point of the exis!ng unit to loca!on of new unit.
Response: 48 hour limit no longer applies. Maximum �me chiller offline = 5 days (pending helium level.). Siemens to verify and increase helium quan�ty as required prior to or during work. Sample �meline for similar project as follows.
6. Needs verified: Are tools and material able to be store inside of room leading to the roof access door.
Response: No.
7. Needs verified: Will ICRA precau!ons outlined in solicita!on documents be grandfathered in.
Response: No. Revised Div. 1 Safety Specs + ICRA Forms reissued under Addendum #1.
8. Can the submi5al data and Install manual be provided for the HASKRIS chiller and equipment?
Response: HASKRIS cut sheets & installa�on manual provided under Addendum #1.
9. Can a detail be provided for the Hook up of the HASKRIS equipment?
Response: HASKRIS piping diagram along with Mechanical drawing revisions provided under
Addendum #1.
10. There is not a controls spec provided. Can one be issued?
Response: Approved Controls Shop Drawing submi9al for system in which the chiller is to be integrated provided under Addendum #1.
PART NUMBER
CUSTOMER/PROJECT
FG23216 REV
OPC24-7G2C24-FMR-EKQ-12-M518
BK26 OCTOBER 2020
25 FEBRUARY 2022 BK
25 FEBRUARY 2022 KK
SIEMENS HEALTHCARE
A
SHEET 1 OF 5
NOT TO SCALE
APPROVED
UPDATED
CREATED
DESCRIPTION
CONFIDENTIAL
NOT TO SCALE
APPROVED
UPDATED
CREATED
DESCRIPTION
CONFIDENTIAL
For use with Siemens MAGNETOM MRI models Aera XJ Lumina Spectra Aera XQ Prisma Symphony Altea Prisma Fit Trio a TIM Avanto Skyra Verio Avanto Fit Skyra Fit Vida XQ Espree Sola XJ Free Max Sola XQ
Technical Details
- Cooling Capacity: 214,965 BTU/hr 63 kW
- Refrigerant: R407C
- Supply Temperature: +43°F to +59°F +6°C to +15°C
- Temperature Stability: ±0.9°F ±0.5°C
- Pumping Capacity: 32 GPM 120 LPM
- Coolant: Clean, potable distilled water
Mixture with pure, lab-grade glycol
- Reservoir Volume: 25 gallons 95 liters
- Connection Size: 1-½” NPT
- Electrical: 460V-3Ø-60Hz
- Voltage Tolerance: ±10%
- Full Load Amps: 48.3 A
- Min. Circuit Ampacity: 53.0 A
- Max. Overcurrent Protection: 70 A
- Short Circuit Current Rating: 5 kA
- Shipping Weight: 2,070 lbs 939 kg
- Operational Weight: 1,860 lbs 844 kg
- Dimensions (WxDxH): 76.5" x 41.8" x 73.9" 194cm x 106cm x 188cm
Ambient Air Conditions
- Temperature Range: -40°F to +122°F -40°C to +50°C
- Air Discharge: Vertical
- Condensers treated for compatibility with coastal installations
Certifications
- cETLus label per UL and CSA specifications
- Special seismic certification per OSHPD specifications
- Seismic SDS level 1: IP=1.5; SDS=2.00g for z/h=1 & SDS=2.50g for z/h=0
Enhanced Chiller Features
- Remote monitoring via cellular internet connection for real time diagnostics
- Additional sensors for comprehensive visibility of unit operation
- Remote control panel with cable
- E-coated condensers for corrosion resistance for coastal installation
- Primary-standby redundant pumps with automatic switchover
- Internal wye-strainer on return line
- Louvered hail guard panels to protect condensers
HASKRIS MODEL OPC24 CUT SHEET FOR SIEMENS
PART NUMBER FG23282 REV
OPC24-7G2C24-FMR-EKQ-12-M505
A
DESCRIPTION
dfisher Text Box
RFI #8
PART NUMBER FG23216 REV A
Clearance Maintain an unobstructed space for free air discharge above unit
CUSTOMER/PROJECT
OPC24-7G2C24-FMR-EKQ-12-M518
BK26 OCTOBER 2020
25 FEBRUARY 2022 BK
25 FEBRUARY 2022 KK
SIEMENS HEALTHCARE
SHEET 2 OF 5
NOT TO SCALE
APPROVED
UPDATED
CREATED
DESCRIPTION
CONFIDENTIAL
NOT TO SCALE
APPROVED
UPDATED
CREATED
DESCRIPTION
CONFIDENTIAL
Mounting Holes for
OSHPD Sites Quantity=8
Bottom View
Mounting Holes for non-OSHPD Sites Quantity=12
Top View
PART NUMBER FG23282 REV A
OPC24-7G2C24-FMR-EKQ-12-M505
DESCRIPTION
Consult Haskris if clearances will be smaller than these recommendations. Haskris will evaluate individual site conditions as needed to ensure proper operation.
CUSTOMER/PROJECT
OPC24-7G2C24-FMR-EKQ-12-M518
BK26 OCTOBER 2020
25 FEBRUARY 2022 BK
25 FEBRUARY 2022 KK
SIEMENS HEALTHCARE
SHEET 3 OF 5
NOT TO SCALE
APPROVED
UPDATED
CREATED
DESCRIPTION
CONFIDENTIAL
NOT TO SCALE
APPROVED
UPDATED
CREATED
DESCRIPTION
CONFIDENTIAL
Center of Gravity
X
Y
X
Z
PART NUMBER FG23282 REV A
OPC24-7G2C24-FMR-EKQ-12-M505
DESCRIPTION
BACK
Louvered panels covering condensers
CUSTOMER/PROJECT
OPC24-7G2C24-FMR-EKQ-12-M518
BK26 OCTOBER 2020
25 FEBRUARY 2022 BK
25 FEBRUARY 2022 KK
SIEMENS HEALTHCARE
SHEET 4 OF 5
NOT TO SCALE
APPROVED
UPDATED
CREATED
DESCRIPTION
CONFIDENTIAL
NOT TO SCALE
APPROVED
UPDATED
CREATED
DESCRIPTION
CONFIDENTIAL
Transportation
PART NUMBER FG23282 REV A
OPC24-7G2C24-FMR-EKQ-12-M505
Packaged unit as shippedOther included parts
Remote control panel and cable
PN FG23216 includes 150 ft of cable
PN FG23282 includes >150 ft per site requirements dimensions in mm
CUSTOMER/PROJECT
OPC24-7G2C24-FMR-EKQ-12-M518
BK26 OCTOBER 2020
25 FEBRUARY 2022 BK
25 FEBRUARY 2022 KK
SIEMENS HEALTHCARE
SHEET 5 OF 5
NOT TO SCALE
APPROVED
UPDATED
CREATED
DESCRIPTION
CONFIDENTIAL
NOT TO SCALE
APPROVED
UPDATED
CREATED
DESCRIPTION
CONFIDENTIAL
PART NUMBER FG23216 REV A
OPC24-7G2C24-FMR-EKQ-12-M505
PART NUMBER FG23282 REV A
Page 1 of 19 Effective Date: 16 April 2022 Revision: 11
Step 1: Foundation, Vibration Isolation, Elevation, Clearances, Transportation
Foundation
• The OPC unit must be installed on a level concrete foundation, level roof curb, or level perimeter beam system.
• Comply with local codes for proper anchoring and vibration isolation.
• Use of a level roof curb or perimeter beam system requires the specifying engineer to identify all necessary materials of construction, thickness, and additional bracing or supports.
• See the diagrams below for mounting hole locations.
• Point load at each mounting location is 200 lbs or less.
OPC24 Mounting Hole Locations for Non-OSHPD Sites dfisher
Page 2 of 19 Effective Date: 16 April 2022 Revision: 11
OPC24 Mounting Hole Locations for OSHPD Sites
• Seismic SDS level 1: IP=1.5; SDS=2.00g for z/h=1 & SDS=2.50g for z/h=0
Page 3 of 19 Effective Date: 16 April 2022 Revision: 11
OPC36 Mounting Hole Locations for Non-OSHPD Sites
Page 4 of 19 Effective Date: 16 April 2022 Revision: 11
OPC36 Mounting Hole Locations for OSHPD Sites
• Seismic SDS level 1: IP=1.5; SDS=2.00g for z/h=1 & SDS=2.50g for z/h=0
Page 5 of 19 Effective Date: 16 April 2022 Revision: 11
Vibration Isolation
• The chiller does not require vibration isolation on the mounting for the chiller to operate normally.
• The motors in the chiller are hard mounted to the metal structure of the chiller. They are not internally isolated.
• It is common for the chiller to be hard mounted directly to a pad on grade, roof curb, or perimeter beam system.
• If vibration transmission to the building structure is a concern, an engineer should provide a detailed specification for vibration damping.
• There are two common approaches o Rubber or synthetic pads between the chiller and the mounting o Spring vibration isolators. These cannot be installed directly between the chiller and the mounting. The chiller must be mounted on a perimeter beam. The spring vibration isolators can be installed between the beam and the mounting.
• If OSHPD compliance is required and isolators are used, the spring isolators must comply with Haskris OSHPD
OSP-0673 file.
Elevation
• If the chiller is located at a higher elevation than the MRI, the maximum recommended height difference is
100 ft (30.5 m).
o The maximum height difference is based on several factors including the maximum inlet water pressure for the MRI, normal water pump discharge pressure, and pressure losses in the piping to the MRI.
o Consult Haskris (847-956-6420) if the height difference needs to be more than 100 ft (30.5 m).
• If the chiller is located at a lower elevation than the MRI, the maximum recommended height difference is
100 ft (30.5 m).
o It is best if the height difference can be less than 32 ft (9.8 m).
o Consult Haskris (847-956-6420) if there are questions.
Page 6 of 19 Effective Date: 16 April 2022 Revision: 11
Clearances
• See the diagrams below showing recommended clearances.
• Air flow is horizontal into the unit and vertical out of the unit.
• Maintain an unobstructed space for free air discharge above the OPC unit.
• Consult Haskris (847-956-6420) if clearances will be smaller than these recommendations. Haskris will evaluate individual site conditions as needed to ensure proper operation.
• Avoid areas where a heat source will discharge heat towards the OPC unit.
o Examples: condenser vents, heating exhaust, etc.
• Avoid areas where debris may accumulate on the condenser.
Page 7 of 19 Effective Date: 16 April 2022 Revision: 11
OPC24 Clearance Recommendations
Page 8 of 19 Effective Date: 16 April 2022 Revision: 11
OPC36 Clearance Recommendations
Transportation
• Transport the OPC unit using the fork pockets or rigging lift points. Ensure forks are past the chiller center post.
• If rigging the unit, lift only from the points shown below. Proper rigging technique (including spreader bars) is critical to avoid damaging the unit.
• Do not remove any panels from the unit during the rigging process.
• See below for rigging and lift points and center of mass.
Weights OPC24 OPC36
Unit with packaging 2,070 lbs 939 kg 3,060 lbs 1,388 kg
Empty without packaging 1,630 lbs 739 kg 2,420 lbs 1,098 kg
Full installed with fluid 1,860 lbs 844 kg 2,650 lbs 1,202 kg
Page 9 of 19 Effective Date: 16 April 2022 Revision: 11
OPC24 Rigging Example
Page 10 of 19 Effective Date: 16 April 2022 Revision: 11
OPC36 Rigging Example
Page 11 of 19 Effective Date: 16 April 2022 Revision: 11
OPC24 and OPC36 Lift Points
Page 12 of 19 Effective Date: 16 April 2022 Revision: 11
Step 2: Line Sizing, Piping Details
Line Sizing
• Haskris is available to review pipe runs, pressure drop, etc and make recommendations for individual sites.
Call 847-956-6420.
• If the total straight pipe length is less than 450 ft (137.2 m) use 1-1/2” nominal pipe size.
• If the total straight pipe length is less than 1,800 ft (548.6 m) use 2” nominal pipe size.
• If the total straight pipe length is greater than 1,800 ft (548.6 m) consult Haskris for assistance.
Piping Details
• Comply with local codes for proper piping.
• Use type L copper piping and non-ferrous materials.
• Insulate piping to minimize condensation.
• Terminate the beginning and ends of hard runs with vibration isolators.
• Ensure piping is clean and free of flux at solder joints.
• Install manual ball valves at high points in the system for purging air while filling the lines. If automatic purge valves are used, isolation ball valves should be installed before the purge valves. Purge valves must be closed during normal operation.
• Install drain valves at the base of every rise for emptying the lines.
• Install a heat trace on piping exposed to temperatures below +20°F (-6.7°C). Cover heat trace with closed cell UV resistant insulation. Power the heat trace from a dedicated disconnect.
• Label supply and return lines over insulation with arrows indicating flow directions.
• Install isolation ball valves on inlet and outlet connections at the Siemens separator.
• Install isolation ball valves on the supply and return connections at the chiller.
• Install flush ports with isolation valves after the supply and return ball valves.
• Sleeve and insulate pipe penetrations through all roof and/or walls.
• Install a loop of reinforced opaque hose between supply and return connections in equipment room for flushing.
• After the lines are flushed, connect the lines in the equipment room to the Siemens separator.
Page 13 of 19 Effective Date: 16 April 2022 Revision: 11
Connection Locations
Piping Drawing dfisher
RFI #9
Page 14 of 19 Effective Date: 16 April 2022 Revision: 11
Step 3: Electrical Details, Remote Control Panel
Electrical Details
• Comply with local codes for proper electrical.
• Contact a licensed electrician to perform the electrical installation.
• The electrician should verify that the wiring is adequate in the installation area.
OPC24 OPC36
Electrical 460V-3Ø-60Hz 460V-3Ø-60Hz
Voltage Tolerance ±10% ±10%
Full Load Amps 48.3 A 72.5 A
Minimum Circuit Ampacity 53.0 A 77.2 A
Maximum Overcurrent Protection 70 A 95 A
Short Circuit Current Rating 5 kA 5 kA
• Use a dedicated service disconnect and time delay fusing.
• Do not mount or support any electrical service disconnect directly to the chiller.
• Use flexible conduit from service panel disconnect through pilot hole to main electrical panel. Do not use rigid conduit at chiller.
• Connect incoming electrical to the distribution block in the main electrical box.
Electrical Box Location, OPC24 Shown Distribution Block exterior panel installed exterior panel removed
Page 15 of 19 Effective Date: 16 April 2022 Revision: 11
• Units include a phase monitor. Refer to the fault indicators provided on the phase monitor and contact a licensed electrician to correct any faults.
• Electrical power must be applied to the unit at least 12 hours in advance of start-up. This energizes the crankcase heater and drives out any accumulated liquid refrigerant in the compressor.
Remote Control Panel
• A remote control panel is provided with the Haskris OPC unit.
• Mount the remote control panel on a wall indoors. See the templates on the next page.
• Standard units include a 150 ft cable to connect this remote control panel with the Haskris OPC unit. The cable is inside the unit. Use the plug provided on the cable to connect the remote control panel to the OPC unit.
• Optionally, some units may include a longer cable. The cable is inside the unit. The remote control panel is mounted on an electrical box that should be mounted on the wall. Connect the three wires on the cable to
#2 (GND), #3 (TX -), and #4 (RX +) inside the box. Connect the box to 115V electrical from a wall outlet.
Page 16 of 19 Effective Date: 16 April 2022 Revision: 11
Distance Between Chiller & Panel
Remote Control Panel Template for Mounting
≤ 150 ft
≤ 46 m
≤ 500 ft
≤ 152 m
* This is an optional feature at additional cost
Type I
Type
II
Page 17 of 19 Effective Date: 16 April 2022 Revision: 11
Step 4: Piping Flush and Purge
Piping Flush
An external water source is required to flush the piping.
1. Close supply and return ball valves.
2. Remove caps from flush ports and connect external water hose to each flush port.
3. Flush piping with external water until water runs clear.
4. Close return side flush valve and apply 100 psi gas for 30 minutes to check for leaks.
5. Repair any leaks and perform flush again.
Piping Purge
1. After a successful leak check, open all drains including those installed on piping rise.
2. Use compressed air or nitrogen to eliminate water from lines.
3. Close all drains and purge isolation valves.
Page 18 of 19 Effective Date: 16 April 2022 Revision: 11
Step 5: Preparing Glycol Mixture, Filling
Prepare Glycol Mixture
• Use potable distilled water.
• Use pure, lab-grade glycol. Haskris strongly recommends propylene glycol. Ethylene glycol is acceptable but not recommended because it is toxic.
• Use refractometer to verify glycol mix percentage (35-40%).
• Provide an extra supply of glycol mixture to replenish the reservoir during the start-up.
Fill the Reservoir
1. Close supply and return ball valves.
2. Remove the cap from the top of the reservoir.
3. Fill the reservoir with glycol mixture.
4. Replace cap after filling.
Fill the Piping
1. Verify supply and return ball valves are closed.
2. Remove cap from supply flush port and connect fill hose. Connect the other end of the hose to external fill pump.
3. Remove cap from return flush port and connect hose. Place the other end of hose in a large bucket. This will act as a vent when filling piping with glycol mix.
4. Open the return side flush valve and energize external fill pump to fill piping with glycol mix.
5. Stop filling piping when glycol solution begins to drain from return flush port.
6. Close both supply and return flush valves, deenergize external fill pump, and replace caps.
7. Open both supply and return ball valves.
Page 19 of 19 Effective Date: 16 April 2022 Revision: 11
Step 6: Final Checks
Phase Monitor
• If the voltage and phase from the service disconnect is correct, the phase monitor should have a solid green LED.
• If the phase monitor has a solid or flashing red LED, contact a licensed electrician to correct the fault.
Controller Faults
• Press the button on the controller.
• The screen should say NO ALARMS.
• If any faults are described, consult Haskris (847-956-6420) to resolve these.
Page 1 of 19 Effective Date: 14 October 2021 Revision: 03
MODEL OPC24 & OPC36
FOR SIEMENS
dfisher
Page 2 of 19 Effective Date: 14 October 2021 Revision: 03
Table of Contents
I. Startup
Phase Monitor
ON/OFF Switch
Pump Priming
Pump Supply Pressure
II. Controller Display
Main Display
Status Modes
Adjusting Set Value (sv)
Units of Measure
Faults
Access Service Menu
Logout of Service Menu
Capabilities in the Service Menu
Force A Specific Pump to Run or Adjust Pump Cycle Schedule
Observe Detailed Refrigeration Data or Force A Specific Circuit to Run
III. Chiller Features
Cellular Communication and Remote Monitoring
Separate Independent Refrigeration Circuits
Redundant Primary/Standby Pumps
Additional Sensors
Remote Control Panel
E-coated Condensers for Corrosion Resistance
Louvered Hail Guard Panels
Energy Saving eco Mode
IV. Maintenance
Frequency
Glycol Mixture
Wye Strainer
Condenser Coils
Electrical Inspection
Page 3 of 19 Effective Date: 14 October 2021 Revision: 03
I. Startup
Phase Monitor
Purpose: The chiller has a phase monitor to check incoming electrical power.
Operation: The phase monitor is factory adjusted by Haskris according to the proper electrical settings for the chiller. Do not adjust the knobs on the phase monitor without discussion and approval from Haskris.
The phase monitor will show a solid green LED if the voltage and phase from the service disconnect is correct (Figure 1). If the phase monitor has a solid or flashing red LED, contact a licensed electrician to correct the fault (Figure 2).
• Reversal is caused by the 3 lines being in an improper sequence. To correct a reversal, switch any 2 of the 3 line connections. Make this switch at the disconnect, not in the chiller.
• Loss/unbalance is caused by a percentage difference in voltage between the 3 lines relative to each other.
• Undervoltage is caused by a percentage difference in voltage between the 3 lines compared to the line-line voltage knob setting.
• Overvoltage is caused by the voltage between the 3 lines being >10% over the line-line voltage knob setting.
Figure 1: Phase monitor
Figure 2: Phase fault LED status patterns
Page 4 of 19 Effective Date: 14 October 2021 Revision: 03
ON/OFF Switch
Location: The chiller has a rotary ON/OFF switch located on the outside of the low voltage box with the main controller (Figure 3).
Operation: Rotate the switch to make the chiller run when in the ON position (horizontal) or stop when in the OFF position (vertical). If a fault occurs, turning the switch to OFF and then back ON will reset the fault.
Figure 3: ON/OFF switch, vertical position
Page 5 of 19 Effective Date: 14 October 2021 Revision: 03
Pump Priming
Purpose: All fluid is removed from the pump head prior to shipment from Haskris. When starting the pump, it needs to be filled with fluid. This process is called priming the pump.
When the tank is full, the pump suction line is “flooded”. In some cases, this flooded suction will automatically prime the pump. When the chiller is turned ON, the pump will run. If the controller display shows the pump generating pressure, then the pump is primed.
If the controller display shows a low pressure <10 psi, then the pump did not automatically prime.
Follow the procedure below.
1. Identify the priming plug on the face of the pump head (Figure 4)
2. Use a 10mm hex or Allen wrench to loosen the priming plug slightly. The plug should remain threaded into the port, but air and liquid should be able to escape.
3. Allow air and a small amount of fluid to escape
4. Tighten the priming plug
Figure 4: Pump priming plug circled
Page 6 of 19 Effective Date: 14 October 2021 Revision: 03
Pump Supply Pressure
Purpose: The chiller uses a centrifugal pump. For the pump to run properly it needs some restriction in the piping system to push against the pump and generate pressure. If this does not happen the chiller may stop and give a fault. To correct this, follow the procedure below.
1. Identify the ball valve inside the chiller on the return line. The handle of the ball valve has been removed and it may be wrapped in insulation (Figure 5 and 6).
2. Start by closing this valve approximately halfway so it is at a 45° angle
3. Cycle the ON/OFF switch on the chiller
4. Observe the pump supply pressure on the controller display
5. If the pump pressure is <50 psi, close the ball valve further. The target pump supply pressure is 55-65 psi.
6. Continue cycling the ON/OFF switch and adjusting the valve until you achieve this target
Figure 5: Internal return line ball valve circled Figure 6: Internal return line ball valve circled
Page 7 of 19 Effective Date: 14 October 2021 Revision: 03
II. Controller Display
Main Display
Status Indicates the state of the chiller
Supply Set Value The desired temperature for the water/glycol mixture
Present Value - Supply/Return Measured supply and return temperatures
Pressure - Supply/Return Measured supply and return pressures
Ambient Air Temperature Measured value of the air temperature around the chiller
Status Modes
• Startup – This appears while the chiller is initially working to control temperature. This mode appears any time the system is deenergized or turned off with the ON/OFF switch.
• ON – This is the normal running status for the chiller once the sv is achieved.
• ON eco – The chiller is running in a reduced power consumption mode.
• OFF – This appears when the chiller is off due to the ON/OFF switch.
• OFF by Alarm – This appears when a fault has occurred.
• OFF by Keypad – This appears when the chiller has been turned OFF using a virtual switch in the controller
Status
Supply Set Value
Units of Measure
Pressure – Supply Pressure – Return Present Value – Supply
Present Value – Return Ambient Air Temperature
Figure 7: Main display
Page 8 of 19 Effective Date: 14 October 2021 Revision: 03
Adjusting Set Value (sv)
Notes: Set Value is the only adjustable value on this screen (Figure 7). Haskris limits the range to
9.0°C-11.1°C (48.2°F-52°F). To change the setting, follow the procedure below.
1. To change the value, press the button to move the blinking cursor to the value
2. Press the or buttons to adjust the value
3. Press the button to move the blinking cursor to the top left corner
Units of Measure
Purpose: Several combinations of units of measure are available depending on what is most useful.
The following units of measure are available:
• CAN (°C, psi, GPM)
• UK (°C, bar, IGM)
• USA (°F, psi, GPM)
• SI (°C, bar, LPM)
To change the units of measure, follow procedure below.
1. Begin on the main display
2. Press the button on the controller
3. Press the or buttons to highlight Settings
4. Press the button to go into that menu section
5. Press the or buttons until you see Unit of Measure Zone
Figure 8: Units of measure screen
6. Press the button to move the blinking cursor around the screen
7. Press the or buttons to select different units of measure
8. Press the button several times to return to the main display
Page 9 of 19 Effective Date: 14 October 2021 Revision: 03
Faults
Identify if there is a fault: The button will flash red when there is a fault.
Display faults and details: Press the button to see fault descriptions.
Description: Provides information about the specific fault.
Multiple faults: If only 1 fault is active, you will see 01 of 01. If multiple faults occur before the faults have been cleared, you will see ## of ## in the top right hand corner. At the bottom you will see a time and date stamp HH:MM DD/MM/YY
Fault reset: Press the button until you go past the last active fault, you will see this screen which explains how to reset faults (Figure 12).
# of simultaneous faults
Time and date stamp
Description
Figure 9: Example fault screen
Figure 10: Fault reset screen
Page 10 of 19 Effective Date: 14 October 2021 Revision: 03
Fault history: When the screen says NO ALARMS, there are no faults currently. Press the button to see the fault history if needed (Figure 13).
Start and Stop: In the bottom right hand corner, certain faults will display “Start” or “Stop”. Start indicates when the fault occurred. Stop indicates when the fault was cleared.
Common Faults
Wording Notes
Incoming electrical power error
Check the phase monitor in the high voltage electrical box, see the
LED status light and error codes
Liquid level in tank is low, refill fluid
This is a warning, add fluid so the level is at the fill line marked on the tank
Low liquid level in the tank This fault will stop the chiller because there is insufficient liquid in the tank
Fluid pump pressure below alarm setpoint
Check the supply line ball valve, adjust so that there is sufficient restriction in the piping for the pump to run
Fluid pump pressure above alarm setpoint
Check all valves in the piping system, look for a valve that is fully closed, make sure that there is an open path for fluid flow
High fluid return pressure Check the internal wye strainer on the return of the chiller, clean the strainer screen
Refrigerant pressure high Check the condenser for debris or blockage that could reduce air flow
Refrigerant pressure low Contact Haskris for diagnostics and troubleshooting
Log #, higher number is more recent
Description
Time and date stamp
Figure 11: Example fault history screen
Page 11 of 19 Effective Date: 14 October 2021 Revision: 03
Access Service Menu
Purpose: A separate Service menu is locked behind a password. This gives access to hidden displays and some override controls. Entering the password enables advanced options to interact with the chiller. To access the Service menu, follow the procedure below.
Password: 6420
3. Press the or buttons to highlight Service. Press the button 2 times.
4. Press the or buttons to change 1 digit at a time
5. Press the button to move the blinking cursor
6. Press the button to enter the password
7. You will see the Service menu
Figure 12: Service menu
8. Press the button several times to return to the main display
Logout of Service Menu
Notes: When you have completed using the advanced capabilities of the Service menu it is important to logout.
3. Press the or buttons to highlight Service. Press the button.
4. Press the or buttons to highlight Logout. Press the button 2 times.
Page 12 of 19 Effective Date: 14 October 2021 Revision: 03
Capabilities in the Service Menu
Purpose: There are additional main displays that give the following abilities:
• Observe and force a specific pump to run
• Observe detailed refrigeration data
• Override refrigeration circuits ON or OFF
Force A Specific Pump to Run or Adjust Pump Cycle Schedule
Purpose: The chiller has primary-standby redundant pumps. This screen allows you to adjust the normal cycle schedule or force a specific pump to run.
Operation: When “cycle” is highlighted (per Figure 15), the 2 pumps will switch back and forth after a fixed period of time. This will evenly distribute run time between the pumps. To adjust the pump cycle schedule, follow the procedure below.
1. Access the Service menu
2. Press the button until you see the main display
3. Press the or buttons until you see Primary/Standby Pumps
4. Press the button to move the blinking cursor to the numbers next to Freq.
5. Press the or buttons to change 1 digit at a time
6. Press the button to move the blinking cursor
7. Changing the number changes how long a pump will run before switching to the other pump
How many times the pumps have cycled back and forth Figure 13: Primary/standby pump screen
How long a pump will run before switching to the other pump
Page 13 of 19 Effective Date: 14 October 2021 Revision: 03
When either “pump #1” or “pump #2” is highlighted, that pump only is forced to run and automatic pump cycling is disabled. To force a specific pump to run, follow the procedure below.
1. Access the Service menu
2. Press the button until you see the main display
3. Press the or buttons until you see Primary/Standby Pumps
4. Press the button to move the blinking cursor to the vertical double dash
5. Press the or buttons to choose pump #1 or pump #2
Cycle mode enabled
200 hrs between cycles
Cycle mode disabled
Pump #1 forced to run
6. Press the button to return the blinking cursor to the top left corner
7. When you want to stop forcing a specific pump to run, highlight cycle
8. Logout of the Service menu when finished
Page 14 of 19 Effective Date: 14 October 2021 Revision: 03
Observe Detailed Refrigeration Data or Force A Specific Circuit to Run
Purpose: The chiller has sensors to monitor the following refrigeration conditions for each refrigeration circuit using the screen below (Figure 16).
CondP Refrigerant pressure in the condenser
SubCool Refrigerant subcooling
SuctP Refrigerant pressure in the evaporator
SuperH Refrigerant Superheat
DscgT Refrigerant compressor discharge temperature
HotGas The % which the hot gas bypass valve is open
FanSpd The % to which the EC fans are at their max speed
Circuit 2 – Conditions
Status Present Value – Supply
Circuit 1 – Conditions
Override Lock
Indicates compressor running
Figure 14: Detailed refrigeration screen
Page 15 of 19 Effective Date: 14 October 2021 Revision: 03
Operation: It may be necessary for preventative maintenance or service to force a specific refrigeration circuit ON or OFF. Follow the procedure below.
1. Access the Service menu
2. Press the button until you see the main display
3. Press the button to move the blinking cursor to the symbol of the circuit you want to override
4. Press the button to unlock this symbol, it should look like this
5. Press the button so the blinking cursor is on the ON/OFF status of that circuit
6. Press the or buttons to force that circuit to be ON or OFF
Both Overrides Locked Circuit 1 Override Unlocked
Override ON
7. To stop the override, press the button to move the blinking cursor to the symbol
8. Press the button to lock this symbol, it should look like this
8. Logout of the Service menu when finished
Page 16 of 19 Effective Date: 14 October 2021 Revision: 03
III. Chiller Features
Cellular Communication and Remote Monitoring
Purpose: The chiller uses a cellular connection to allow Haskris to remotely view the controller for diagnostics and addressing issues in the field. Haskris can receive alerts if there are faults.
Method: The chiller has a cellular modem and uses 2 antennas to communicate with the cell towers.
Separate Independent Refrigeration Circuits
Purpose: The chiller has identical, parallel refrigeration circuits to enhance uptime.
Notes: If one of the refrigeration circuits has a fault, the other(s) can continue running. All circuits have adequate capacity to keep the magnet cold on their own, so the magnet can continue to have proper cooling while service or repairs are being performed.
Redundant Primary/Standby Pumps
Purpose: The chiller has 2 identical pumps for a fully redundant pumping system to enhance uptime.
Operation: During normal operation, the pumps switch back and forth on a schedule to distribute run time. In case of a failure with the primary pump, the standby pump will take over and circulate the water/glycol for the MRI. Both pumps have suction isolation valves for easier replacement which minimizes downtime.
Additional Sensors
Purpose: The chiller has additional pressure and temperature sensors that are used for improved real-time diagnostics.
Page 17 of 19 Effective Date: 14 October 2021 Revision: 03
Remote Control Panel
Purpose: The chiller includes a remote control panel which can be installed indoors in the MRI equipment room. This provides a convenient way to interact with the chiller indoors.
Operation: This is a direct mirror of the controller in the outdoor chiller. Any changes done on the remote control panel are immediately reflected on the chiller. For example, if someone changes the set point on the remote control panel, the chiller will reflect this change.
See the Installation Instructions for details on mounting and wiring.
E-coated Condensers for Corrosion Resistance
Purpose: The condensers that are installed on this chiller have an e-coating. This coating protects the condenser from corrosion. This is particularly important in coastal areas with salty ocean air.
Louvered Hail Guard Panels
Purpose: The chiller includes panels to protect the condensers from hail damage. The panels have louvers to allow airflow while blocking hail.
Page 18 of 19 Effective Date: 14 October 2021 Revision: 03
Energy Saving eco Mode
Purpose: When the chiller is under a reduced load, the chiller will use fewer refrigeration circuits to provide cooling to reduce power consumption.
Operation: When the chiller is in eco mode, the status on the display will say “ON eco” (Figure 17).
The controller initiates eco mode based on the operation of the hot gas bypass valves and the refrigerant head pressure.
IV. Maintenance
Frequency
Notes: Approximately every 6 months the chiller should be inspected, and preventative maintenance should be performed. Use the Haskris provided Preventative Maintenance checklist.
Glycol Mixture
Purpose: The unit is designed to circulate a mixture of potable distilled water and pure glycol. This glycol is intended to help resist freezing water.
Notes: The full level in the tank is marked on the side of the tank. If the level falls, replenish the tank as needed until the tank remains full. Use a refractomester to verify glycol mix percentage (35-40%).
If the glycol mix is visibly dirty or contaminated flush the glycol from the whole system and refill with a fresh glycol mix.
Figure 15: Eco mode active
Page 19 of 19 Effective Date: 14 October 2021 Revision: 03
Wye Strainer
Purpose: A wye strainer is installed inside the chiller on the return line to catch particles in the fluid
(Figure 16).
Operation: If the return pressure is above 15 psi, clean the wye strainer. The chiller will give a fault if the return pressure is too high, but the chiller will stay running.
Condenser Coils
Notes: Dust and debris may collect on the condenser during normal operation. Accumulated debris restricts air flow and reduces heat transfer which affects chiller performance. Use a brush to loosen compacted debris and use a vacuum to collect the debris.
Electrical Inspection
Notes: Use a multimeter to check electrical values. Take measurements at contactors or terminal blocks. Compare values to the chiller or component name plate. Units include a phase monitor. Refer to the fault indicators provided on the phase monitor and contact a licensed electrician to correct any faults.
Figure 16: Wye strainer
Dayton Office
1400 W. Dorothy Lane
Dayton, OH 45409
P: 937-224-0861
F: 937-224-5777
Columbus Office
1800 Watermark Dr. Ste. 410
Columbus, OH 43215
P: 614-457-2696
F: 614-457-4021
Lawrenceburg Office
PO Box 3637
121 S. Tanners Creek Dr.
Lawrenceburg, IN 47025-5001
P: 812-537-0331
Indianapolis Office
3850 Priority Way South, Ste. 204
Indianapolis, IN 46240
P: 317-571-8795
F: 317-641-1705
HT013_23 09 23-1R1 1/30/2015 8:38:00 AM
SHOP DRAWING REVIEW
Project No. 2013-04023
January 30, 2015
Department of Veterans Affairs Medical Center
3200 Vine Street
Cincinnati, Ohio 45220
Attn: Kevin Henderson
Project: CVAMC Replace Induction Units
#539-15-201
Discipline: HVAC
Item
No.
Copies
A/E File No.
Manufacturer Description Disposition
A E 23 09 23-1R1 Siemens DDC
X
Reviewed
Approved as Submitted
Approved as Noted
Rejected-Resubmit
B
Approved as Submitted
C
D
E
F
G
H
Item Remarks:
Distribution and No. of Copies:
1 File Copy 2013-04023
By: Don Van Winkle
Dayton Office dfisher
RFI #10
23 09 23-1R1 DDC_AN 1/30/2015 8:42:00 AM Page 1
MEMORANDUM NO. 1
The Following Recommendations are Based Upon a Check of This Submission Against Contract
Requirements.
APPROVAL IS RECOMMENDED AS TO GENERAL ARRANGEMENT SUBJECT TO COMPLIANCE
WITH CIRCLED A/E COMMENTS AND/OR CORRECTIONS ON THE ATTACHED MATERIAL.
ALSO RECOMMENDED: CREDIT PROPOSAL
AT NO ADDITIONAL COST
MINOR MODIFICATION
A/E ASSUMES NO RESPONSIBILITIES FOR CHECKING SCHEDULES, QUANTITIES, LAYOUT
DRAWINGS, LAYOUT ILLUSTRATIONS OR DIMENSIONS.
CHECKED January 30, 20 15 BY Don Van Winkle Date
PROJECT NO. VA # 539-15-201, Heapy # 2013-04023 A/E FILE NO. 23 09 23-1R1 DDC Heapy Engineering- Dayton Office A/E
1 – Manufacturer shall verify that valve actuators can fit inside fan coil endpockets and steam convector cabinets, and that they are suitable to operate in the ambient conditions below the heating element in a steam convector cabinet, prior to ordering.
STATION & LOCATION
HEAPY ENGINEERING
PROJ. No. CONTR No. ________________________________
FOR RECORD ONLY
SUPERSEDES A/E FILE No. ______________________
SUPERSEDED BY A/E FILE No. ______________________
NOT CHECKED
(See Section "S" OF Specifications)
A/E COMMENTS AND / OR CORRECTIONS ARE
CIRCLED THUS
BY __________________ DATE _______________
A/E FILE No. __________________ DATE _______________
VA ACTION
APPROVED
OTHER
REJECTED/RESUBMIT
BY __________________ DATE _______________
COTR
CVAMC REPLACE INDUCTION UNITS
539-15-201
23 09 23-1R1 01-27-2015
23 09 23-1
1/30/2015
A/E REVIEWER
N/A
DON VAN WINKLE
Transmittal
TO: VAMC Cincinnati
Department Of Veterans Affairs Date: 1/27/14
3200 Vine Street Job Name: VAMC Induction Unit Project
Cincinnati, Ohio 45220 Location: Cincinnati Ohio
Customer PO#: VA250-14-C-0111
Attn: Kevin Henderson Contract #: 14.445
We are sending you herewith the following drawings, documents or instructions for:
For Submittal Destroy Previous Prints As Requested
Preliminary Final Distribution Record and File
Reference
Approval - We have detailed these units based on our interpretation of the contract drawings & specifications
Please have your detailing department look carefully at the attached submittals. We cannot be held responsible for any cost or lead time changes incurred for modifications once the equipment has been released for fabrication.
Return 1 Approved Copies
Fabrication Held for Approval & Written Release
Equipment is being fabricated and any changes may create a delay in shipment and a possible increase in price.
SUBMITTAL OF THESE DRAWINGS DOES NOT CONSTITUTE OFFICIAL ACCEPTANCE OF THIS ORDER
Item Description / Comments Document # / Ref Rev # of Sets
1 Control System Re-Submittals ASA-1 1 1
Comments:
Kevin, Please see the attached revised Submittals for Approval. Please forward through to the Engineer
CC to: # of Copies TRANSMITTED BY:
Ed Braemer
Sr. Controls Manager
ASA Controls, Inc. VA Hospital - Cincinnati Job #14175 January 26, 2015
RE-SUBMITTAL
CLARIFICATIONS
14175CLA2
1. Engineer’s Note #1
a. Network Controllers NC-1 and NC-2 will communicate to existing front-end via
BACnet. Front-end graphics to be generated by Johnson Controls.
2. Engineer’s Note #2
a. “Modified Equal Percentage” is a combination Linear/Equal Flow Percentage characteristic offering typical linear flow characteristic at low end of valve position with typical equal percentage flow characteristic at higher end of the valve position;
providing a more linear heat transfer from the valve/coil combination over the entire valve range. Refer to “Flow Characteristic” chart that follows.
3. Engineer’s Note #3
a. Valves to be bronze body.
4. Steam convector details on drawing M502 indicate a 5 PSIG steam supply to convectors;
specification 230923, item 2.14.E.6.b states modulating steam control valve pressure drop to be 80% of inlet gauge pressure for steam pressure up to 15 PSIG (4 PSIG pressure drop with 5 PSIG inlet pressure), convector schedule on drawing M601 and convector submittal indicates convectors sized based on an inlet steam pressure of 5 PSIG.
a. Submitted steam control valve based on a maximum 1 PSIG steam pressure drop to provide a 4 PSIG steam inlet pressure at the convector under full load.
5. 2-Pipe fan coil unit control detail on M601 shows cooling coil valve being Normally Open and steam convector heating coil valve being Normally Closed.
a. Submitted control valve actuators are Fail-in-Place. Fail-in-Place actuators are preferable in this application since neither the fan coil unit nor the convector are ducted to outside air. Having the valves remain in current state when there is a power outage is preferable to forcing valves open or closed when power is turned off.
Sequence of Operation Vetreran’s Affairs Hospital ASA Controls, Inc. December 15, 2014
Dwg. 14175 / 1A Revised:
jaw:14175S01
ROOM HEATING, COOLING AND VENTILATION:
1. Room heating and cooling are provided by a cooling-only fan coil unit and a steam convector. Constant ventilation is provided by a fixed supply air diffuser served by a Constant Air Volume (CAV) Box.
2. One Direct Digital Controller (DDC) operates the cooling-only fan coil unit and the steam convector to provide heating and cooling to the space.
3. Heating and cooling equipment operated in an Occupied or Unoccupied mode of operation as determined by the existing Energy Management
System.
4. Occupied Time Period:
a.) Fan coil unit supply fan started and runs continuously.
b.) Fan coil controller operates unit’s cooling coil control valve to provide cooling to space if space temperature goes above controller’s Occupied Cooling Setpoint (73°F, adj). Steam convector valve remains closed.
c.) Fan coil controller operates steam convector valve to provide heating to space if space temperature goes below controller’s
Occupied Heating Setpoint (71°F, adj). Fan coil cooling coil control valve remains closed.
5. Unoccupied Time Period:
a.) Fan coil unit supply fan remains off unless space temperature goes above controller’s Unoccupied Cooling setpoint (78°F, adj) or falls below controller’s Unoccupied Heating setpoint (60°F, adj).
b.) Controller starts fan coil unit’s supply fan, and operates unit’s cooling coil control valve to provide cooling to space, if space temperature goes above controller’s Unoccupied Cooling
Setpoint. Steam convector valve remains closed.
c.) Controller operates steam convector valve to provide heating to space if space temperature goes below controller’s Unoccupied
Heating Setpoint. Fan coil unit’s supply fan remains off and cooling coil control valve remains closed.
6. Fan Coil Unit Supply Fan/Cooling Coil Valve Interlock:
a.) Fan coil unit cooling coil control valve is driven closed whenever unit’s supply fan is commanded off.
ROOM HEATING, COOLING AND VENTILATION (cont’d):
7. Outside Air Disabling of Steam Convector Valve:
a.) Steam convector control valve is driven closed, and remains closed, if outside air temperature is above 55°F (adj.).
ROOM COOLING AND VENTILATION:
1. Room cooling is provided by a cooling-only fan coil unit. Constant ventilation is provided by a fixed supply air diffuser served by a Constant
Air Volume (CAV) Box.
a.) Note that there is no direct heating source for these rooms.
2. A Direct Digital Controller (DDC) operates the cooling-only fan coil unit to provide cooling to the space.
3. Cooling equipment operated in an Occupied or Unoccupied mode of operation as determined by the existing Energy Management System.
4. Occupied Time Period:
a.) Fan coil unit supply fan started and runs continuously.
b.) Fan coil controller operates unit’s cooling coil control valve to provide cooling to space if space temperature goes above controller’s Occupied Cooling Setpoint (73°F, adj).
5. Unoccupied Time Period:
a.) Fan coil unit supply fan remains off unless space temperature goes above controller’s Unoccupied Cool ing setpoint (78°F, adj).
b.) Controller starts fan coil unit’s supply fan, and operates unit’s cooling coil control valve to provide cooling to space, if space temperature goes above controller’s Unoccupied Cooling
Setpoint.
6. Fan Coil Unit Supply Fan/Cooling Coil Valve Interlock:
a.) Fan coil unit cooling coil control valve is driven closed whenever unit’s supply fan is commanded off.
HEATING/COOLING
SETPOINTS:
1. Occupied Heating/Cooling Setpoints.
a.) Occupied Heating/Cooling setpoints are determined based on a heating/cooling offset applied to a Nominal Space Temperature setpoint.
Dwg. 14175 / 1A Revised:
jaw:14175S01
HEATING/COOLING SETPOINTS (cont’d):
b.) Default “Nominal Space Temperature” setpoint is 72°F (adj.) and default heating/cooling offset is +/-1°F. This results in a nominal
Occupied Heating setpoint of 71°F and a nominal Occupied
Cooling setpoint of 73°F.
LOCAL OCCUPANT SPACE TEMPERATURE SETPOINT ADJUSTMENTS
1. Setpoint knob permits occupant to locally adjust DDC system Nominal
Space Temperature setpoint command +/- 2°F.
a.) This allows occupant to adjust Nominal Space Temperature setpoint between 70°F and 74°F based on default Nominal
Space Temperature setpoint of 72°F.
b.) This provides for an overall Occupied Heating setpoint range of 69°F to 73°F, and an overall Occupied Cooling setpoint range of 71°F to 75°F.
LOCAL OCCUPANT UNOCCUPIED OVERRIDE
1. Unoccupied override button on space temperature sensor allows occupant to index controller to Occupied for a fixed time period of one hour.
ASA Controls, Inc. Veteran’s Affairs Hospital Job #14175 4th & 9th Floor Units
December 15, 2014 Revised:
Bill of Material, Room HVAC Drawings 14175 / 1A Page 1 of 1
DEVICE TAG QTY PART # MANUFACTURER DESCRIPTION
FIELD DEVICES
DDC-FC 42 550-433 Siemens BACnet Fan Coil Controller R-X 42 PAM-1 Kele & Associates Remote Interface Relay TCV-CC 42 -------- Siemens Refer to Valve Schedule TCV-CONV 41 --------- Siemens Refer to Valve Schedule TT-RM 40 QAA2330.FWNN Siemens Room Sensor, 10K Type 2, Thermistor with Setpoint
Adjustment and Unoccupied Override TT-DA 42 KTM24-SC Kele & Associates Single-Point Temp Sensor, 10K Type 2 Thermistor, 8”
Length jaw:14175BOM01
Dwg. 14175 / 2A Revised:
jaw:14175S02
OUTSIDE AIR VENTILATION BOXES:
1. Air handling unit provides conditioned outside air to Constant Air Volume
(CAV) Boxes. CAV’s then provide conditioned outside air to rooms via fixed supply air diffusers.
2. CAV boxes are operated in an Occupied or Unoccupied mode of operation as determined by the existing Energy Management System.
3. Occupied Time Period:
a.) CAV box Direct Digital Controller (DDC) provides constant air flow to supply diffusers.
4. Unoccupied Time Period:
a.) CAV box Direct Digital Controller (DDC) drives box damper closed.
ASA Controls, Inc. Veteran’s Affairs Hospital Job #14175 4th & 9th Floor Units
December 15, 2014 Revised:
Bill of Material, Outside Air Ventilation Boxes Drawings 14175 / 2A Page 1 of 1
DEVICE TAG QTY PART # MANUFACTURER DESCRIPTION
FIELD DEVICES
DDC-CAV 3 550-430 Siemens BACNet VAV Controller with Integral Actuator jaw:14175BOM02
Integrating BUILDING AUTOMATION, ENERGY, and SECURITY to the enterprise.
CONTROL SYSTEM
OVERVIEW
JWahlbrink 11/23/11 13:51:18: CONTROL SYSTEM
OVERVIEW
Today’s facilities are equipped with a wide range of computerized systems to control HVAC, energy management, lighting, and security.
Integration and interoperability between all of these systems are critical to improving operations, lowering costs, and achieving the security and comfort demanded in today’s dynamic business environments.
The challenge is to get these diverse systems that communicate using many different protocols to connect and converse with each other – and with the enterprise – so you can derive actionable intelligence from the information they contain.
The answer is Vykon®.
Integrating building
Vykon is a complete management and control suite that…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .