36C25021B0072 - Amd 3.pdf
PDF 4 MB Posted
- Solicitation number
- 36C25021B0072
About this file
This solicitation seeks renovation services for sleep labs and home oxygen areas at the Louis Stokes Cleveland VA Medical Center in Cleveland, Ohio. The project will provide additional sleep labs and renovate adjacent space to reconfigure and consolidate the sleep and home oxygen programs. The solicitation is set aside for service-disabled veteran-owned small businesses. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 is the contracting agency. The solicitation number is 36C25021B0072 and responses are due based on the amended deadline in the solicitation.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE 7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO. 1. CONTRACT ID CODE
FACILITY CODE CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30 PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243
(Type or print) (Type or print)
(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code)
(If other than Item 6)
(Specify type of modification and authority)
(such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
1 17
08-29-2022
541-21-104
36C250
Department of Veterans Affairs Network Contracting Office (NCO) 10 VA Healthcare System 2780 Airport Dr, Suite 340 Columbus OH 43219
36C250
Department of Veterans Affairs Network Contracting Office (NCO) 10 VA Healthcare System 2780 Airport Dr, Suite 340 Columbus OH 43219
To all Offerors/Bidders 36C25021B0072
08-01-2022 X
X X
X 01
The purpose of this solicitation amendment is to notify all potential bidders that the pre-award RFI (requests for information) & their responses are attached to this amendment & can be found in this amendment's continuation pages.
Documents supporting the RFI answers can also be located in this amendment's continuation pages.
All other terms & conditions remain unchanged & in full effect.
Brian S. Kish Contracting Officer
CONTINUATION PAGE
Please see the next page.
CONTINUATION PAGES
RENOVATE SLEEP & HOME OXYGEN AREAS FOR THE LOUIS STOKES VETERANS
AFFAIRS MEDICAL CENTER (VAMC)—CLEVELAND, OH
PROJECT NUMBER: 541-21-104
QUESTIONS AND RESPONSES TO INVITATION FOR BID (IFB) NUMBER
36C25021B0072
IFB AMENDMENT NUMBER 0003
1. QUESTION – Ref spec 02 82 13.13, PART 2.3- Is the general contractor or the VA responsible to pay for services of the VPIH? With the services of the CPIH being a requirement paid for by the abatement contractor the VPIH is typically hired and paid for by the VA or the general contractor. Will clarification be provided?
Response: Per spec 02 82 13.13, PART 2.3, A, 2 the Contractor is responsible for hiring the VPIH/ CIH.
2. QUESTION – Could more detail be provided for the Sleep Lab Cameras & Duress Buttons be provided?
Response: Please see attached documents 22-0826 Sleep and Home Oxygen Areas – ADDENDUM 02 Letter, and 22-8026 Sleep and Home Oxygen Areas - Addendum 02 Drawings.
3. QUESTION – Cameras: We see the use of discontinued Axis PTZ cameras in the Sleep Labs we can use the replacement model camera for new installations on the project, but the Hospital Viewing/Control software and hardware are not detailed or available for inspection during the Pre-Bid walk through today. How do the Hospital staff control the cameras? How is the video is stored? How is playback of Live & Recorded video is achieved?
Response: Please see attached documents 22-0826 Sleep and Home Oxygen Areas –
4. QUESTION - Panic/Duress Buttons: We see the use of STI wall mounted panic/duress buttons being used in the Sleep Labs, the question is are these currently and in the future monitored by the VA Police Dept.? If the duress buttons are monitored differentially can you please detail the hardware involved?
Response: Please see attached documents 22-0826 Sleep and Home Oxygen Areas –
5. QUESTION – The QS-1, Synthetic Quartz Arlington Q1005 has been discontinued as of 4/22/2020. How would you like me to proceed?
Response: Please see the attached documents: 22-0822 Sleep and Home Oxygen Areas – ADDENDUM 01 Letter and 22-8022 Sleep and Home Oxygen Areas – Addendum 01 drawings.
6. QUESTION – As discussed at today’s site visit – we are requesting the RFI due date to be extended to allow RFIs to be submitted following the site visit. Please advise.
Response: The RFI due date was extended to 08-24-2022
7. QUESTION – The cut-off date for RFI’s is 08/19/2022 at 3:00 pm. With the site visit 08/19/22 it does not give us and subs time to review and ask questions. Can it be extended two weeks?
Response: Please see the answer to question 6.
8. QUESTION - My name is Zach Brzezinski and I am with Concierge Business Solutions. We have been working on a bid proposal for the project mentioned above, and am hoping that you could either post or send me the site visit sign-in sheet. Being based out of Georgia, it would be greatly helpful for finding subcontractors to get in contact with. Thank you for your time.
Response: Thank you for your interest. The site visit sign in sheet was posted.
400 Western Reserve Building Fax 216.687.1558 1468 West 9th Street Cleveland, Ohio 44113 Phone 216.687.1555
Addendum #1
ISSUE DATE: 8.22.2022
PROJECT: Renovate Sleep and Home Oxygen Areas Proj. #541-21-104 Louis Stokes VA Medical Center Cleveland, Ohio
The following August 22, 2022 Addendum #1 is being made to supplement the original Bid Issue Submission specifications and drawings prepared by Kaczmar architects incorporated dated
05.20.2022 for the above referenced Project. The intent of the issuance of Addendum #1 is to more clearly identify, amend, clarify and/or provide prospective bidders additional information relative to the work prior to the bid due date. The sections and/or paragraphs listed below supersede the original publication and any previously issued addenda in their entirety.
Architectural
1. Sheet AS-702 – Finish Schedule
a. Synthetic Quartz QS-1 has been changed to Wilsonart Haldi Q40320.
If you require any further information or have any questions, please feel free to contact our office.
Cordially, KACZMAR ARCHITECTS INCORPORATED
Richard L. Yanusaitis, RA cc: Project Team Attachments: Addendum #1 Letter 22-0822 Renovate Sleep and Home Oxygen Areas – Addendum 1 Drawings
File: K:\VA CLEVELAND\SLEEP & HOME OXYGEN RENOVATION\PLOT\22-0825 ADDENDUM 01\22-0822 ADDENDUM 1 - ARCH Letter.docx
1. ALL FINISH MATERIALS SHALL BE INSTALLED PER MANUFACTURER'S DIRECTIONS.
2. SUBMIT ALL SAMPLES FOR ARCHITECT'S APPROVAL. REFER TO MATERIAL SPECIFICATIONS FOR
REQUIREMENTS.
3. REFER TO FINISH SCHEDULE FOR ALL ABBREVIATIONS AND MATERIAL SPECS. REFER TO FINISH PLAN FOR
ADDITIONAL MATERIAL/COLOR LOCATIONS.
4. ANY SPECIFIC BRAND NAMES LISTED, OR ITEMS NOTED AS "BASIS OF DESIGN," ARE INTENDED TO INDICATE THE QUANTITY, STYLE, AND/OR GENERAL APPEARANCE FOR A SPECIFIC PRODUCT, AND ARE NOT INTENDED TO INDICATE SOLE SOURCING OF THAT PRODUCT. CONTRACTOR MAY USE PRODUCTS FROM OTHER MANUFACTURERS THAT ARE EQUIVALENT IN STYLE, QUALITY, AND APPEARANCE TO THOSE LISTED.
SUBSTITUTIONS MUST BE SUBMITTED TO VA INTERIOR DESIGNER AND ARCHITECT OF RECORD FOR
APPROVAL PRIOR TO ORDERING SUCH MATERIALS.
5. CONTRACTOR RESPONSIBLE FOR APPROPRIATE TRANSITION STRIPS AT CENTERLINE OF DOOR THRESHOLD
OR AS DELINEATED ON FINISH PLAN WHEREVER THERE IS A CHANGE IN FLOOR MATERIAL.
6. REFER TO REFLECTED CEILING PLAN FOR ADDITIONAL CEILING INFORMATION.
7. ALL OUTSIDE CORNERS OF QUARTZ OR SOLID SURFACE COUNTERTOPS SHALL RECEIVE 3/4" RADIUS.
8. CONTRACTOR TO PROVIDE SOLID FIRE RETARDANT TREATED WOOD BLOCKING IN STUD SPACE AND
PROVIDE ANCHORS THROUGH GYPSUM WALLBOARD AND WOOD BLOCKING. PLASTIC HANGERS AND
INSERTS TO BE AVOIDED.
9. ALL MILLWORK TO BE CONSTRUCTED OF 3/4" PLASTIC LAMINATE MATERIAL AS INDICATED IN SECTIONS, UNLESS NOTED OTHERWISE.
10. FASTENERS FOR KNEE BRACE SUPPORTS ARE TO BE FINISHED CHROME HEADED SCREWS.
11. DRAWER CONSTRUCTION, MATERIALS, AND JOINERY IS TO BE PREMIUM GRADE PER AWI STANDARDS.
12. ALL SURFACES, INCLUDING THOSE CONCEALED AFTER INSTALLATION, ARE TO BE FINISHED PER
SPECIFICATION. MIN. BACKER BK-20.
13. ALL CABINETS WITH DOORS SHALL RECEIVE CYLINDER LOCKS AT EACH DOOR LEAF. COORD. REQUIRED
KEYING W/VA.
14. EXPOSED WALL CLEATS ARE TO BE PAINTED FINISH. AT WORK SURFACES PROVIDE BEVELED CUT AND
HOLD BACK MIN. 4" FROM LEADING EDGE OF WORK SURFACE.
15. 1" OVERHANG TYPICAL @ COUNTERTOPS WITH BASE CABINETS BELOW UNLESS NOTED OTHERWISE.
16. SCRIBES AT CABINET BODY ARE TO BE FLUSH WITH BODY. SCRIBES/FILLERS AT DOORS AND DRAWER
FRONTS ARE TO BE FLUSH WITH DOOR OR DRAWER FRONTS.
17. DRAWERS ARE TO BE FULL-DEPTH OF COUNTER U.N.O.
18. ALL CABINET INTERIORS ARE TO BE PER SPECIFICATIONS. HPDL GP-28 (VERTICAL GRADE LAMINATE).
19. ALL COUNTERTOPS SHALL BE INSTALLED UPON MIN. 3/4" PLYWOOD SUBSTRATE.
20. REFER TO SPECIFICATIONS FOR HARDWARE GUIDELINES AND STANDARDS.
21. CONTRACTOR TO COORDINATE POWER/CABLE OUTLET LOCATIONS WITH VA-PROVIDED TV'S IN FIELD WHERE
APPLICABLE, TYP.
22. GROMMET LOCATIONS SHALL BE PROVIDED/DRILLED BY GC IN FIELD, AND FINAL LOCATIONS SHALL BE COORDINATED WITH VA. CONTRACTOR SHALL FIGURE MIN. (2) GROMMETS PER INDIVIDUAL COUNTERTOP, AND (3) SHALL BE FIGURED WHERE (3) CHAIRS ARE SHOWN IN PLAN.
23. FINISHED END PANELS SHALL BE PROVIDED AT ALL EXPOSED ENDS OF CABINETRY AND SOFFITS ABOVE.
24. FINISHED FILLER STRIPS SHALL BE PROVIDED AT ALL CABINETRY AS REQUIRED BASED ON FIELD
DIMENSIONS.
25. FLOORING MATERIALS THAT ARE TO BE PLACED ON EXISTING FLOOR SLABS SHALL HAVE THE FLOOR SLAB ADEQUATELY PREPPED PER FOR THE FLOORING MATERIAL REQUIREMENTS. ALL FINISH MATERIALS SHALL
BE INSTALLED PER MANUFACTURER'S DIRECTIONS.
FINISH & CASEWORK NOTES:
PAINT NOTES:
1. STANDARD WALL FINISH SHALL BE SATIN OR EGGSHEL SHEEN.
2. ALL METAL TRIM ITEMS TO BE PAINTED (E.G. DOOR FRAMES, LOUVERS, ETC.) SHALL RECEIVE SEMI-GLOSS
SHEEN AND SHALL MATCH THE COLOR OF THE WALL IN WHICH THEY ARE INSTALLED.
3. CEILING SHALL RECEIVE FLAT PAINT FINISH. SEE FINISH SCHEDULE.
FLOORING/BASE NOTES:
1. EXISTING VINYL FLOORING IN MAIN CORRIDORS IS 5 MM THICK, EQUAL TO NEW FLOORING IN PROJECT AREAS. CONTRACTOR SHALL ENSURE THAT SEAM @ DOOR THRESHOLDS IS FULLY WELDED AND FLUSH
BETWEEN NEW AND EXISTING SPACES. NO TRANSITION STRIPS SHALL BE REQUIRED.
2. ORIENTATION OF LONG DIRECTION OF LVT TILE INDICATED BY SYMBOL:
3. BASE MATERIAL SHALL BE PROVIDED BELOW ALL CABINET UNIT HEATERS @ EXTERIOR WALLS/WINDOWS
4. ALL TILE FLOOR IN BATHROOMS SHALL BE SLOPED TO DRAIN. HIGH POINT CREATED AT BATHROOM ENTRY DOOR SHALL TRANSITION CLEANLY INTO ADJACENT BEDROOM WITH A TRANSITION STRIP @ DOOR THRESHOLD AND/OR EXTENSION OF FLOOR LEVELING COMPOUND IN BEDROOM. COORDINATE FINAL
REQUIREMENT IN FIELD. REFER TO SPEC SECTION 09 30 13 FOR SLOPING REQUIREMENTS
1"
HR-1 & CR-1WALL PANELING
CORNER GUARD
WALL PANELING
WALL PANELING SHALL
RUN BEHIND ALL
CORNER GUARDS
WALL TILE, SEE INT.
ELEVATIONS
EXTEND WATERPROOF
BARRIER (HEAVY DASHED
LINE) TO CEILING
SCHLUTER (OR EQUAL) COVE
MOULDING - SB-1
FLOOR TILE
MOLD/MILDEW
RESISTANT GYP. BD.
WATERPROOF BARRIER TO
BE PROVIDED BELOW TILE IN
ENTIRETY OF BATHROOM
FLOOR
FLOOR DRAIN, SEE PLAN.
ENSURE ALL DRAINS ARE NOT
CORED THROUGH EXISTING
CONCRETE BEAMS. ALL TILE IN
ROOM SHALL BE SLOPED TO
DRAIN LOCATION
SLOPE
SEE DRAIN DETAIL ON
P-601. CLAMP
WATERPROOFING
MEMBRANE INSIDE OF
DRAIN BODY
NOTE: HIGH POINT CREATED AT
BATHROOM ENTRY DOOR SHALL
TRANSITION CLEANLY INTO
ADJACENT BEDROOM WITH A
TRANSITION STRIP @ DOOR
THRESHOLD AND/OR EXTENSION OF
FLOOR LEVELING COMPOUND IN
BEDROOM. COORDINATE FINAL
REQUIREMENT IN FIELD.
CRASH RAIL - CR-1.
PROVIDE IN-WALL
BLOCKING AS
REQ'D. FOR
ANCHORAGE, TYP.
HAND RAIL - HR-1
(HR-2 MAY OCCUR).
PROVIDE IN-WALL
BLOCKING AS
REQ'D. FOR
ANCHORAGE, TYP.
V
IF
V
IF
VERIFY MOUNTING
HEIGHTS IN FIELD -
ALIGN W/EXISTING
RAILS
BASE MAT'L
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
ATE
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
MECHANICAL/TECH. ENGINEERING:
HEAPY
THE HANNA BUILDING
1422 EUCLID AVE. STE. 1162
CLEVELAND, OH 44115
P. 216.862.5846
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
ELECTRICAL ENGINEERING:
FFE, INC.
110 BOGGS LN, SUITE 170
SPRINGDALE, OH 45246
P. 513.522.0956
HAZ. MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOC., INC.
30628 DETROIT RD. #258
WESTLAKE, OH 44145
P. 216.781.0060
STRUCTURAL ENGINEERING:
THORSON BAKER & ASSOC.
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
BID ISSUE SUBMISSION
k a c z s v r\ a c ti v e \V
A C
L E
V E
L A
N D
\S L
E E
P
H O
M E
O X
Y G
E N
R E
N O
V A
T
IO
N \R
E V
IT
\V
A M
P
S le e p
L a b
H o m e O x y g e n
R
.r v t
/2
/2
:5
:5
P
M
AS-702
FINISH SCHEDULE RENOVATE SLEEP AND HOME
OXYGEN AREAS
10701 EAST BLVD. CLEVELAND, OHIO
541-21-104
5.20.22 CJK DAK
3" = 1'-0"
TYP. HANDRAIL @ DOOR FRAME
3" = 1'-0"
TYP. WALL PANEL/CORNER GUARD
6" = 1'-0"
TYP. BATHROOM COVE
BASE/WATERPROOFING DETAIL
1 1/2" = 1'-0"
TYPICAL HAND/CRASH RAIL
Revisions: Date:
SCHEMATIC DESIGN 9.2.20
DESIGN DEVELOPMENT 11.13.20
65% CDs SUBMISSION 3.26.21
100% CDs SUBMISSION 5.5.21
FINAL CDs SUBMISSION 5.28.21
BID ISSUE SUBMISSION 5.20.2022
ADDENDUM 01 08.22.2022
Rich Line
Rich Line
400 Western Reserve Building Fax 216.687.1558 1468 West 9th Street Cleveland, Ohio 44113 Phone 216.687.1555
Addendum #2
ISSUE DATE: 8.26.2022
PROJECT: Renovate Sleep and Home Oxygen Areas Proj. #541-21-104 Louis Stokes VA Medical Center Cleveland, Ohio
The following August 26, 2022 Addendum #2 is being made to supplement the original Bid Issue Submission specifications and drawings prepared by Kaczmar architects incorporated dated
05.20.2022 for the above referenced Project. The intent of the issuance of Addendum #2 is to more clearly identify, amend, clarify and/or provide prospective bidders additional information relative to the work prior to the bid due date. The sections and/or paragraphs listed below supersede the original publication and any previously issued addenda in their entirety.
This Addendum 02 is being issued to respond to several questions asked after the pre-bid walk-through.
Question 1:
Could more detail be provided for the Sleep Lab Cameras and Duress Buttons provided?
Response 1:
Yes. See responses below and attached product data.
Question 2:
Cameras: We see the use of discontinued Axis PTZ cameras in the Sleep Labs we can use the replacement model camera for new installations on the project, but the Hospital Viewing/Control software and hardware are not detailed or available for inspection during the Pre-Bid walk through today. How do the Hospital staff control the cameras? How is the video is stored? How is playback of Live & Recorded video is achieved?
Response 2:
The cameras in each of the Sleep Labs that connect to the adjacent Control Room, those cameras will be furnished and installed by the VA, and the conduit and backbox will be furnished and installed by the Electrical Subcontractor. The hospital software and hardware will be by the VA.
Question 3:
Panic/Duress Buttons: We see the use of STI wall mounted panic/duress buttons being used in the Sleep Labs, the question is are these currently and, in the future, monitored by the VA Police Dept.? If the duress buttons are monitored differentially, can you please detail the hardware involved?
Response 3:
All panic/duress buttons are tied into the Lenel Security System and monitored by VA Police.
The following types of panic duress buttons are based on the locations.
a. Under-counter / desk: Potter, HUB-T. See attached product data.
b. Wall-mounted: STI (Safety Technology International). See attached product data.
Page - 2 – VA Renovate Sleep and Home Oxygen Areas - Addendum #2 – 08.26.2022
Revised Drawings:
Technology
1. Sheet T-001 – Legend, Notes, and Index of Drawings
a. Symbol for Sleep Lab Camera has been revised to “SC”.
b. “SC” note states “Sleep Lab closed system camera. Provide Rough-in and Cabling.
Coordinate with Owner for exact location and cable routing requirements.
2. Sheet T-102 – Partial Second Floor Technology Plan
a. Sleep Lab Camera symbols have been revised to “SC”, and are indicated in the four
(4) Sleep Lab Rooms (Rooms 2B131, 2B132, 2B134, & 2B135-2).
b. Wall-mounted Panic Duress Buttons are indicated in the four (4) Sleep Lab Rooms.
See attached product data for under-counter / desk, & wall-mounted buttons. Exact model number of Panic Duress Button is to be verified with the VA.
If you require any further information or have any questions, please feel free to contact our office.
Cordially, KACZMAR ARCHITECTS INCORPORATED
Richard L. Yanusaitis, RA, LEED AP BD+C, CDT cc: Project Team Attachments: Addendum #2 Letter 22-0822 Renovate Sleep and Home Oxygen Areas – Addendum 1 Drawings Undercounter/desk panic duress button Wall-mounted panic duress button
File: K:\VA CLEVELAND\SLEEP & HOME OXYGEN RENOVATION\PLOT\22-0826 ADDENDUM 02\22-0826 Sleep and Home Oxygen Areas - ADDENDUM 02 Letter.docx
MKT #8900085 - REV L
8/02
PRINTED IN USA PAGE 1 OF 2
HUB-T
HOLD-UP BUTTON
UL & CUL Listed Dimensions: 2 1/16"W x 3 7/16"L x 1 1/4"H 52,4 cm W x 87,3 cm L x 2,7 cm H Weight: 2.4 oz.
68,0 g.
Switch Rating: 3 Amps at 28V DC/AC .05 Amp at 125V DC Resistive Enclosure: ABS Plastic Temperature Range: 32°F to 140°F (85% maximum humidity) Environmental Limitations: Not recommended for outdoor use or use in coolers or freezers.
Stock No. 2020132
The HUB-T Series Hold-Up Buttons provide two sets of momentary or latching DPDT contacts for actuating surveillance cameras or other security applications, in addition to the hold-up signal. The two sets of contacts may be used independently of each other, or they may be wired in series with a jumper wire for additional protection against false alarms. See illustration on page 2.
Installation Install in accordance with UL 681. Devices should be installed so they cannot be observed by the public and so they can be operated inconspicuously. At least one shall be installed in each vault open during business hours. In banks they shall also be installed in offi ces commanding a view of the public space.
BREAK OUT FOR SURFACE
MOUNT WIRING ADD JUMPER WIRE
WIRE EXIT
AREA
WIRE EXIT
AREA
BREAK OUT FOR
SURFACE MOUNT WIRING
DWG# 996-1
HUB-T (Shown without cover)
Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com
LATCHING CAP LATCHING RAMP
DWG# 996-6
Converting The HUB-T To Optional Latching Operation Remove the installed button caps and discard. Replace with alternate latching caps (supplied). Align the cap such that the latching mechanism is directly over the latching ramp in the base.
See illustration at right.
HUB-T (Shown with cover) To unlatch the HUB-T, insert the reset key, provided with the HUB-T, between the switch cap and the base. The unit unlatches when the cap is released.
Rich Text Box under-counter / desk
Normally Open Hold-up Circuit With EOL Supervision Normally Closed Hold-up Circuit With EOL Supervision
Electrical interlock requires both buttons to be activated simultaneously before alarm will occur. Any single button will activate camera.
Note: Jumpers required
PRINTED IN USA
HUB-T
HOLD-UP BUTTON
MKT #8900085 - REV L
8/02
TO CAMERA
TRIGGER
DWG# 997-1 TO HOLD-UP ZONE
BREAK OUT FOR SURFACE
MOUNT WIRING
WIRE EXIT
AREA
TO CAMERA
TRIGGER
TO HOLD-UP ZONE
HUB-T (Shown without cover)
Stopper® Stations
MODEL NUMBER: SS2432EM-EN
Build these North American style, ADA Compliant, multipurpose push button switches to your specifications. Unique, patented design helps dramatically stop accidental activation.
Available in six colors, several button activation choices, with or without a protective cover and in any language to accommodate most applications. Part numbers may vary when ordering between the US and UK offices.
Below represents US part numbers.
Contact sales by email or phone.
sales@sti-usa.com 248-673-9898 mailto:sales@sti-usa.com?subject=SS part number confirmation mailto:sales@sti-emea.com?subject=SS part number confirmation Rich Text Box Model number to be verified with VA
BUTTONS AND SWITCHES
For more information, call 248-673-9898 or visit www.sti-usa.com
STI STOPPER®
STATION SERIES
ADA
Compliant
ADA
Compliant
See Inside For Details
PRODUCT OVERVIEW
These ADA Compliant, multipurpose push button switches cover a wide range of applications both indoors and outdoors. They’re called Stopper Stations. They incorporate a unique, patented design that helps dramatically to stop accidental activation. A number of standard models are available or we can create custom units to meet your needs exactly. You have your choice of any of six universal shell colors, several button styles, standard or custom wording and language.
HOW THEY WORK
Because of their superior, patented design combined with quality construction throughout, you can expect outstanding performance for years to come. In fact, many STI customers are surprised to find that all this quality is available at no increase in price.
Plus, customers appreciate the option to protect the switches with STI protective covers that carry a three year guarantee against breakage in normal use, one year on electro mechanical and electronic components. For indoor applications, you can order your Stopper Station with a pre-alarm cover to help stop malicious and accidental activation.
General Information
· Multipurpose push button switches cover a wide range of applications both indoors and outdoors.
· Three year guarantee against breakage of polycarbonate in normal use (one year on electro mechanical and electronic components).
Design
· Unique, curved design helps protect against accidental activation.
Construction
· Station housing molded of tough polycarbonate.
· UL Listed to U.S. and Canadian safety standards.
· Momentary models used with LT-
1UL Latching Timer Module are Listed for access control.
· Stainless steel backplate.
· Push buttons are ADA Compliant
(excludes “3” key switch button).
Installation
· 5VA flammability rating on backplate and spacer.
· Typical working properties of polycarbonate are -40° to 250°F (-40° to 121°C).
Options
· Your choice of colors — red, green, yellow, white, blue or orange.
· Standard or custom text or hi-res logo.
· Custom text in any language.
· Protect with STI indoor/outdoor protective covers.
KEY FEATURES
For more information, call 248-673-9898 or visit www.sti-usa.com.
STI Stopper® Station Series Dimensions and Technical Information
UNIQUE BUTTON FEATURES
Models SS2xy0, SS2xy1, SS2xy3, SS2xy4
• Interchangeable or replaceable N.O. or N.C., SPST gold-plated contact blocks rated for 6 amps @ 600 VAC or 1 amp @ 250 VDC.
• Standard switch includes one N.O. and one N.C. contact. Holds up to three individual isolated contacts.
• SS2xy0 and SS2xy1 rated for 6000 operations.
• SS2xy4 rated for 100,000 operations.
Note: some standard single gang boxes need additional depth. To add 5/8” depth, order KIT-102722-color (B=blue, G=green, R=red, Y=yellow, W=white, E=orange).
Models SS2xy2, SS2xy5, SS2xy9
• Two (2) Form “C” contacts, DPDT, rated 10 amps @ 125/250 VAC, 1/2 HP, 6 amps @ 30 VDC.
• 12-24VAC/VDC LED (LED red, green, and white).*
• Over 100,000 operations.
Model SS2xy6
• Two (2) Form “C” contacts, DPDT, rated 10 amps @ 125/250 VAC, 1/2 HP, 6 amps @ 30 VDC.
• 12-24VAC/VDC LED.*
• 100,000 operations.
Model SS2xy7
• Two (2) Form “C” contacts, DPDT, rated 10 amps @ 125/250 VAC, 1/2 HP, 6 amps @ 30 VDC.
• Operating range -31°F to 150°F (-35°C to 66°C).
• 12-24VAC/VDC LED.*
• Weather resistant, suitable for indoor or outdoor use without a cover.
• 100,000 operations.
Model SS2xy8
• Switch rating 10 amps @ 240 VAC resistive and has a timer range:
2 - 60 seconds (± 15%).
• Indoor use only. Not recommended for outdoor/water applications, temperature range of button 15° to 120°F (-9° to +49°C).
• Timer life of over 1,000,000 operations.
• Pneumatic adjustable timer opens or closes a circuit and has a timed delay before reset. No electricity to operate.
• Ideal for security applications.
• 1 Form Z, 1 N.O. and 1 N.C. contact.
* Power supply not included
EXISTING STANDARD
SINGLE GANG BOX
STI RECOMMENDS THE
USE OF THIS SPACER
FOR SWITCH CLEARANCE
ON STANDARD SINGLE
GANG BOXES.
SEE NOTE.
.69 in.
(17mm)
BACKPLATE ASSEMBLY
NOTE: TO PROVIDE ADEQUATE CLEARANCE FOR INSTALLATION,
ONE OF THE FOLLOWING IS RECOMMENDED: SUB-102722 SPACER,
OR RACO #660 W/1/2" K.O. AND RACO #653 EXTENSION RING.
ALSO RACO #696 MASONRY BOX.
PRODUCT DIMENSIONS
3.25 in.
(82mm)
4.87 in.
(124mm)
1.62 in.
(41mm) 2.25 in.
(57mm)
SWITCH/BUTTON ACTIVATION TYPE
REFER TO CHART ON PAGE 3
SWITCH ASSEMBLY
SEE VIEW BELOW
N.O.
N.C.
COM
LAMP
SWITCH ASSEMBLY-SEE BELOW
N.O./N.C.
TERMINAL BLOCKS.
(1 OF EACH PROVIDED)
UP TO 3 TERMINALS MAY
BE USED FOR EACH STATION
SWITCH INSTALLATION
SWITCH REMOVAL
ILLUMINATED BUTTON
MOMENTARY MUSHROOM
PUSH TO ACTIVATE
AND TURN TO RESET
PUSH TO ACTIVATE
AND KEY TO RE SET
KEY TO ACTIVATE
5VA FLAMMABILITY RATING
ON BACKPLATE AND SPACER
19030 KEY ONLY
SPACER
SUB-102722
NOTE: TO PROVIDE ADEQUATE CLEARANCE FOR INSTALLATION,
MAY REQUIRE: SUB-102722 SPACER, OR RACO #660
W/1/2" K.O. AND RACO #653 EXTENSION RING.
ALSO RACO #696 MASONRY BOX.
PRODUCT DIMENSIONS
3.25 in.
(82mm)
4.87 in.
(124mm)
1.62 in.
(41mm) 2.25 in.
(57mm)
SUB-102722-COLOR
STI RECOMMENDS THE USE OF THIS SPACER
FOR SWITCH CLEARANCE ON
STANDARD SINGLE GANG BOXES
FOR THE #0, #1, #3 AND #4 BUTTON AND
ADDS 5/8” TO DEPTH OF EXISTING
STANDARD SINGLE GANG BOX
.69 in.
(17mm)
BACKPLATE ASSEMBLY
5VA FLAMMABILITY RATING
ON BACKPLATE AND SPACER
EXISTING STANDARD
SINGLE GANG BOX
#8
PUSH-TO-ACTIVATE
AND KEY-TO-RESET
19030 KEY ONLY
#0
PNEUMATIC ADJUSTABLE
TIMER BUTTON
KEY-TO-ACTIVATE#3
PUSH-TO-ACTIVATE AND TURN-TO-RESET#1
MOMENTARY MUSHROOM#4
KEY-TO-RESET
MOMENTARY
TURN-TO-RESET BUTTON #9
#2 #5
EXISTING STANDARD
SINGLE GANGBOX
HOUSING INDEXING SLOTS
BACKPLATE ASSEMBLY
(SEE REVERSE SIDE)
102722 SPACER RED, GREEN,
YELLOW, WHITE AND BLUE.
STI RECOMMENDS THE USE OF THIS
SPACER FOR SWITCH CLEARANCE
ON STANDARD SINGLE GANG BOXES.
ASSIGNED A 5VA FLAMMABILITY RATING.
SEE NOTE IN PRODUCT DIMENSION VIEW.
10274 OCTAGON SHELL
RED, GREEN, YELLOW, WHITE AND BLUE
10105 MOMENTARY BUTTON (#4)* KEYS
(2) PROVIDED
10271 STATION HOUSING
RED, GREEN, YELLOW,
WHITE AND BLUE
10100 PUSH/TURN
RESET BUTTON (#1)
10104 KEY BUTTON (#3)
KEY REQUIRED TO ACTIVATE - IN
ACTIVATE MODE KEY CAN BE REMOVED
#8-32 x 3/8 in.
(1) PROVIDED
KIT-H19030 KEYS
(2) PROVIDED
10102 KEY RESET SWITCH
OCTAGON KEY RESET BUTTON (#0)
RED, GREEN, YELLOW, WHITE
AND BLUE
02050
TO PROVIDE ADEQUATE
CLEARANCE FOR INSTALLATION
STI RECOMMENDS THE USE OF
PART #102722 SPACER
OR RACO #660 WITH 1/2 in. K.O.
AND RACO #653 EXTENSION RING,
ALSO RACO #696 MASONRY BOX.
3.25 in.(82mm)
4.87 in.(124mm)
1.62 in.
(41mm)
NC
NO
2.25 in.
(57mm)
TO PROVIDE ADEQUATE
CLEARANCE FOR
INSTALLATION STI
RECOMMENDS THE USE OF
PART #102722 SPACER OR RACO #660 WITH 1/2 in. K.O.
AND RACO #653 EXTENSION RING, ALSO RACO #696 MASONRY BOX.
3.25 in.
(82mm)
4.87 in.
(124mm)
1.62 in.
(41mm)
2.25 in.
(57mm)
STRIP 1/4 in. OF WIRE INSULATION
INSERT IN TERMINAL (AS SHOWN) THEN
USING A PHILLIPS SCREWDRIVER TURN
CLOCKWISE UNTIL TIGHT.
SEPARATION OF TERMINAL ASSEMBLY.
FROM BUTTON ASSEMBLY IS AS FOLLOWS:
GRASP TERMINAL HOUSING AND USING THUMB
APPLY PRESSURE DOWNWARD, REMOVE TERMINAL.
REMOVAL OF TERMINAL BLOCK
FROM TERMINAL HOUSING: INSERT
SMALL SCREWDRIVER (AS SHOWN)
AND PRY UPWARD, REMOVE TERMINAL.
TERMINAL BLOCK
RELEASE LEVER
MUST FACE UPWARD
AS SHOWN FOR SWITCH
TO FUNCTION CORRECTLY.
ELECTRICAL TERMINAL BLOCK
UP TO 3 TERMINALS MAY BE USED
INSERT NOTCH, AS SHOWN
THEN ROTATE UPWARD
TERMINAL BLOCK 10196 NO (1) PROVIDED
10198 NC (1) PROVIDED
SEE VIEW IN DIRECTION OF ARROW
FOR CONTACT INDENTIFIER LOCATIONS
UP TO (3) TERMINALS MAY BE USED FOR EACH
STATION ASSEMBLY.
OUTGOING
INCOMING
SCREWS #6-32 x 1
OUTLET BOX (2) PROVIDED.
SCREWS #6-32 x 1.50 WHEN
USING 102722 SPACER
(SEE REVERS SIDE).
#10-32 x 3/8 in. GROUND SCREW
(1) PROVIDED
BUTTON LOCK NUT
10272 BACKPLATE
GREEN, YELLOW, WHITE AND BLUE
PUSH
A
MESSAGE
HERE
MESSAGE
HERE
MESSAGE
HERE
C O
M N
O N
C
LOW PROFILE
CONTACT SWITCH
PNEUMATIC
ADJUSTABLE
TIMER BUTTON
5/8” SPACER
KIT-102722-B (BLUE)
KIT-102722-G (GREEN)
KIT-102722-R (RED)
KIT-102722-W (WHITE)
KIT-102722-Y (YELLOW)
KIT-102722-E (ORANGE)
KIT-71100A-COLOR BACK BOX
NOT FOR USE WITH SWITCH
CONFIGURATION #0
1.58 in.
(40mm)
0.625 in.
(16mm)
CONTACT SWITCH
SS2xy8
(PNEUMATIC
ADJUSTABLE TIMER)
SS2xy2 (KEY-TO-RESET) SS2xy5 (MOMENTARY) SS2xy9 (TURN-TO-RESET)
KIT-H18061 KEYS ONLY (2)
SS2xy3 (KEY-TO-ACTIVATE)
KIT-H18062 KEYS ONLY (2)
SS2xy1 (TURN-TO-RESET) SS2xy4 (MOMENTARY MUSHROOM)
SS2xy0 (KEY-TO-RESET)
REQUIRES 2.25” MOUNTING DEPTH
INTERNAL DEPTH
1.45 in. (37mm) x = COLOR y = COVER
KIT-H19030 KEYS ONLY (2)
SS2xy6 (ILLUMINATED) SS2xy7
(WEATHER RESISTANT
ILLUMINATED)
MULTICOLOR ILLUMINATION BAR
ILLUMINATED BUTTON
(ONE COLOR)
CONTACT SWITCH
PUSH
PUSH
PUSH
PUSH
EXISTING STANDARD GANG BOX
NOTE: USE SPACER SUB-102722
WITH #0, #1, #3, #4 AND
#7 BUTTON TYPE
.69 in.
(17mm)
BACKPLATE ASSEMBLY
SWITCH/BUTTON ACTIVATION TYPE
REFER TO CHART ON PAGE 4
5VA FLAMMABILITY RATING
ON BACKPLATE AND SPACER
SPACER
SUB-102722
#8
PUSH-TO-ACTIVATE
KEY-TO-RESET
19030 KEY ONLY
#0
ILLUMINATED
WEATHER RESISTANT
#7
PNEUMATIC
ADJUSTABLE
TIMER BUTTON
KEY-TO-ACTIVATE#3
PUSH-TO-ACTIVATE
TURN-TO-RESET
#1
MOMENTARY MUSHROOM#4
KEY-TO-RESET
MOMENTARY
TURN-TO-RESET BUTTON #9
#2 #5
MESSAGE
HERE
EXISTING STANDARD GANG BOX
NOTE: USE SPACER SUB-102722
WITH #0, #1, #3, #4 AND
#7 BUTTON TYPE
.69 in.
(17mm)
BACKPLATE ASSEMBLY
5VA FLAMMABILITY RATING
ON BACKPLATE AND SPACER
SPACER
SUB-102722
PUSH-TO-ACTIVATE
KEY-TO-RESET
19030 KEY ONLY#0
PUSH-TO-ACTIVATE
TURN-TO-RESET
#1
MOMENTARY MUSHROOM#4
KEY-TO-ACTIVATE#3
#8 PNEUMATIC
ADJUSTABLE
TIMER BUTTON
KEY-TO-RESET
MOMENTARY
TURN-TO-RESET BUTTON #9
#2 #5
MESSAGE
HERE
PUSH
ILLUMINATED
WEATHER RESISTANT
#7
For more information, call 248-673-9898 or visit www.sti-usa.com.
STI Stopper® Station Series Dimensions and Technical Information
Stopper® Station Shield (Cover 2, A)
This inexpensive and highly durable cover, with or without alarm, was invented to mount directly onto the Stopper Station series of buttons with two tabs that snap into the Stopper Station shell. It takes hard knocks in stride while protecting the button against vandalism, damage and accidental activation. Ideal for use when space is limited.
No labeling can be placed on the Stopper Station shield.
Universal Stopper® (Covers 3, 4, 7, 8)
This indoor/outdoor cover helps stop false fire alarms and can protect Stopper Stations against damage as well as malicious or accidental activation. It consists of a clear polycarbonate shield that fits easily over any STI Stopper Station model. When it is lifted to gain access to the Stopper Station, the optional piercing 105 dB warning horn sounds. Legitimate activation is not affected. The protective cover options include: dome or low profile, with or without horn, flush mount, surface mount.
Additional labeling may be placed on the Universal
Note:
Stopper Station #7 button is UL/cUL Listed for outdoor use without a cover. All others are approved for outdoor use with an outdoor rated protective cover. Excludes pneumatic button.
APPROVALS & WARRANTY
TESTING
It has been tested and approved or listed by:
WARRANTY
Three year guarantee against breakage of polycarbonate in normal use (one year on electro mechanical and electronic components).
Accessories LT-1UL UL Latching/Timer Module KIT-71100A-* Back box for 2, 5, 6, 7, 8 and 9 switch KIT-71101A-* Back box & Spacer Kit for 1, 3 or 4 switch KIT-E10196 N.O. contact for 0, 1, 3 or 4 switch KIT-M10197H Replacement contact holder for 0, 1, 3 & 4 switch KIT-E10198 N.C. contact for 0, 1, 3 or 4 switch KIT-102720-* Stackable 10mm Spacer, European and US Mounting KIT-102722-* Plastic Spacer - adds 5/8” depth KIT-H19030 Two Extra Keys for 0 switch KIT-H18061 Two Extra Keys for 2 switch KIT-H18062 Two Extra Keys for 3 switch KIT-E10197H Pack of two contact switch holders, one N.O. and one
N.C. for 0, 1, 3 or 4 switch
* R=red, B=blue, G=green, Y=yellow, W=white, E=orange
3.18 (81mm)
1.62 (41mm)
3.25 (82mm)
4.8
(1 mm
PNEUMATIC OPERATED TIMER, OPENS
OR CLOSES CIRCUIT AFTER TIME DELAY.
NO ELECTRICITY TO OPERATE
10 AMP, FOR C CONTACTS
IDEAL FOR SECURITY APPLICATIONS
CORROSION RESISTANT BODY
ADJSTABLE TIME RANGE
PRODUCT DIMENSIONS
CAN BE INSTALLED ON ANY
EXISTING SINGLE GANG BOX
FAST
SLOW
TIME RANGE ADJUSTMENT SCREW
TURN COUNTER CLOCKWISE TO
INCREASE TIMER SPEED.
ADJUSTMENT RANGE - 2 TO 60 SECONDS
FACTORY SETTING - 25 TO 45 SECONDS
SWITCH DATA
RESOLUTION: 2 TO 60 SECONDS
ACCURACY: 10% REPEAT ACCURACY
POWER: NONE TO OPERATE, SWITCHES
UP TO 10 AMPS @ 240 VOLTS
RESET: AT CYCLE END
LIFE CYCLES: 1,000,000
NC
NO
PNEUMATIC TIMER
SWITCH ASSEMBLY
FAST
SLOW
NC
NO
PNEUMATIC TIMER
SWITCH ASSEMBLY
BACKPLATE WITH MOLDED-IN
STAINLESS STEEL INSERT
SWITCH HOUSING MOLDED OF
POLYCARBONATE. CHOOSE RED,
GREEN, YELLOW, WHITE OR BLUE.
ALLEN HEAD
LOCKING SCREW
AND WRENCH
ALSO CAN BE INSTALLED ON ANY
EXISTING SINGLE GANG BOX
BUTTON AND SWITCH ASSEMBLY
19015 WRENCH
(1) PROVIDED
FIGURE C
SURFACE BOX
INSTALLATION
19011 SCREW ALLEN HEAD
#8-32 x 3/8 (1) PROVIDED
10271 SWITCH HOUSING
RED, GREEN, YELLOW,
WHITE AND BLUE
1.62 in.
(41mm)3.25 in. (82mm)
4.8 7 i n.
(1 mm
PRODUCT DIMENSIONS
1.58 in.
(40mm)
1.375 in.
(35mm)
1.62 in.
(41mm)
3.25 in.(82mm)
4.87 in.
(124mm)
PRODUCT DIMENSIONS
1.56 in.
(40mm)
"A"
TO PROVIDE ADEQUATE CLEARANCE FOR CONTACTS,
(#0, #1, #3, #4) INSTALLATION
1.62 in.
(41mm)
3.25 in.(82mm)
4.87 in.
(124mm)
1.58 in.
(40mm)
"A"
GROUND SCREW
BUTTON AND SWITCH ASSEMBLY
SCREW #6-32 x 1 in.
(2) PROVIDED
SCREW #6 x 1-1/4 in.
(4) PROVIDED
KIT-71100A-COLOR SURFACE BOX
ANCHOR
(4) PROVIDED
DRILL (4) 3/16 in.
DIA HOLES
J
J
J
J
H SWITCH BACKPLATE
MOUNTING HOLES
BOX MUST BE INSTALLED WITH
ARROWS POINTING UPWARD
THESE HOLES MUST BE
DRILLED OUT USING A
5/32 in. DRILL BIT
H
DRILL POINT LOCATIONS PROVIDED
TOP AND BOTTOM FOR 1/2 in.
CONDUIT FITTINGS.
DRILL AS NEEDED
DRILL POINT LOCATIONS PROVIDED
TOP AND BOTTOM FOR 1/2 in.
CONDUIT FITTINGS.
DRILL AS NEEDED
KIT-71100A BOX (SURFACE MOUNT)
RED, GREEN, YELLOW, WHITE AND BLUE
19039 SCREW #6 x 1-1/4 in.
(4) PROVIDED
PNEUMATIC TIMER MODEL
WITH PROVIDED
SURFACE BACKBOX
19060 SCREW #6-32 x 1 in.
(2) PROVIDED
BUTTON AND SWITCH ASSEMBLY
19021 GROUND SCREW
19018 ANCHOR
(4) PROVIDED
THIS VIEW FOR PAGE 6
DRILL (4)
3/16 DIA. HOLES
DRILL POINT LOCATIONS PROVIDED
TOP AND BOTTOM FOR 1/2 in.
CONDUIT FITTINGS.
DRILL AS NEEDED
KIT-71100A BOX (SURFACE MOUNT)
RED, GREEN, YELLOW, WHITE AND BLUE
SCREW #6 x 1-1/4 in.
(4) PROVIDED
PNEUMATIC TIMER MODEL
WITH PROVIDED
SURFACE BACKBOX
SCREW #6-32 x 1 in.
(2) PROVIDED
BUTTON AND SWITCH ASSEMBLY
GROUND SCREW
ANCHOR
(4) PROVIDED
THIS VIEW FOR PAGE 6
DRILL (4)
3/16 DIA. HOLESBACKPLATE WITH MOLDED-IN
STAINLESS STEEL INSERT
SWITCH HOUSING MOLDED
OF POLYCARBONATE. CHOOSE
RED, GREEN, YELLOW,
WHITE OR BLUE.
ALLEN HEAD
LOCKING SCREW
AND WRENCH
DRILL POINT LOCATIONS PROVIDED
TOP AND BOTTOM FOR 1/2 in.
CONDUIT FITTINGS.
DRILL AS NEEDED
KIT-71100A BOX (SURFACE MOUNT)
RED, GREEN, YELLOW, WHITE AND BLUE
19039 SCREW #6 x 1-1/4 in.
(4) PROVIDED
PNEUMATIC TIMER MODEL
WITH PROVIDED
SURFACE BACKBOX
19060 SCREW #6-32 x 1 in.
(2) PROVIDED
19021
GROUND SCREW
19018 ANCHOR
(4) PROVIDED
DRILL (4)
3/16 DIA. HOLES
.728 in.
(18.49mm)
2.4 in.
(60.96mm)
3.218 in.
(81.74mm)
4.132 in.
(104.95mm)
4.83 in.
(122.68mm)
1.578 in.
(40.08mm)
Covers to protect your STI Stopper Station from damage or weather and to help stop malicious or accidental activation.
“A” - Contact Depth SS2xy0* 2.16” SS2xy1 2.04” SS2xy2 1.00” SS2xy3* 2.13” SS2xy4 2.04” SS2xy5 1.00” SS2xy6 .875” SS2xy7 .875” SS2xy8 1.4” SS2xy9 1.00”
* If extra depth needed in electrical box order KIT-102722-color.
· UL/cUL File No. S7255
· Complies with UL 2017. UL Listed for indoor and outdoor use
(“8” button indoor only, temperature range 15° to 120°F). When mounting outdoor, must use an STI weather cover.
· UL/cUL Type NM suitable for indoor or outdoor use without a cover (#7 button only)
· UL 294 (models used with LT-1UL)
· CSA C22.2 No. 205
· ADA Compliant (excludes “3” button)
05/22
2306 Airport Road Waterford, Michigan
48327, USA
Tel: 248-673-9898 Fax: 248-673-1246 Toll-free: 800-888-4784 info@sti-usa.com www.sti-usa.com
Unit 49G Pipers Road Park Farm Industrial Estate Redditch, Worcestershire B98 OHU England
Tel: 44 (0) 1527 520 999 Fax: 44 (0) 1527 501 999 Free: 0800 085 1678 (UK) www.sti-europe.com
2306 Airport Road info@sti-usa.com Waterford, MI www.sti-usa.com 48327, USA Tel:248-673-9898
Taylor House info@sti-emea.com 34 Sherwood Rd., Bromsgrove, www.sti-emea.com Worcs., B60 3DR, England Tel: +44 (0) 1527 520 999
Unit 7A Lockheed Avenue Airport Business Park Waterford X91 HWF2 Ireland
Printed in U.S.A., © 1987-2020 Safety Technology International, Inc. Subject to change without notice.
2017_12
SS2COLOR
0. Red
1. Green
2. Yellow
3. White
4. Blue
5. Orange
SWITCH CONFIGURATION
2. Key-to-Reset (Illuminated Bar)
5. Momentary (Illuminated Bar)
9. Turn-to-Reset (Illuminated Bar)
8. Pneumatic (Illuminated Bar)**
6. Momentary (Illuminated)
7. Weather Resistant Momentary (Illuminated)
0. Key-to-Reset* ***
1. Turn-to-Reset ***
3. Key-to-Activate ***
4. Momentary ***
TEXT
AB = ABORT
EM = EMERGENCY
EX = EMERGENCY EXIT
PO = EMERGENCY POWER OFF *
ES = EMERGENCY STOP
EV = EVACUATION
XT = EXIT
PS = FUEL PUMP SHUT DOWN *
HV = HVAC SHUT‐DOWN
LD = LOCKDOWN
PX = PUSH TO EXIT
NT = No Text ZA = Custom Text
* Not available with pneumatic #8 button
LANGUAGE
EN = English ES = Spanish FR = French ZL = Other Language
COVER
Flush
3. Universal Stopper, label shell*
4. Universal Stopper, horn* Surface
7. Universal Stopper, label shell*
8. Universal Stopper, horn* Flush or Surface
2. Shield A. Shield with sound
0. No Cover *Orange coming soon
*Not available in orange ** Switch 8 not recommended for outdoor/water applications, temperature range 15°F to 120°F.
*** Switch 0, 1, 3, 4 may require spacer SUB-102722 (color) to accommodate depth or a deep single-gang box.
STI Stopper® Station Series Dimensions and Technical Information
CUSTOMIZE YOUR TEXT - text option ZA White text on blue, red and green; black text on yellow, white and orange.
CUSTOM TEXT FOR TOP OF SHELL: 2 LINES, 20 CHARACTERS EACH (INCLUDES SPACES)
CUSTOM TEXT FOR BOTTOM OF SHELL: 1 LINE, 20 CHARACTERS (INCLUDES SPACES)
CUSTOM TEXT COVER 3, 4, 7, 8: 2 LINES, 40 CHARACTERS EACH (INCLUDES SPACES)
ST1
ST2
SB
C1
C2
T2
B
T2
DETAIL: B = DETAIL DESIGNATION
T2 = SHEET WHERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
T2 = SHEET WHERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
CONDUIT RUN IN WALL OR ABOVE CEILING PER DIV 26.
CONDUIT RUN IN SLAB OR UNDERGROUND PER DIV 26.
CABLE MANAGEMENT SYSTEM PATHWAY PER DIV 27 / DIV 28.
LADDER TRAY PER DIV 26, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
CM
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SWITCH
BLDG - BUILDING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTWN - BETWEEN
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - CIRCUIT
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CORR - CORRIDOR
CTR - CENTER
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DIV - DIVISION
DN - DOWN
DWG - DRAWING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EX - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
GC - GENERAL CONTRACTOR
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT
FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC (DIVISION 23)
HP - HORSE POWER OR HIGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
IN - INCHES
KEC - KITCHEN EQUIPMENT
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
PC - PLUMBING (DIVISION 22)
PLBG - PLUMBING
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH-IN
S - SURFACE MOUNTED
SC - SECURITY (DIVISION 28)
SCH - SCHEDULE
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TC - TECHNOLOGY (DIVISION 27)
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W/ - WITH
W/O - WITHOUT
WP - WEATHERPROOF
ZVC - ZONE VALVE CABINET
A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.
B. SITE VISIT(S) SHALL BE AS OUTLINED IN PROJECT SPECIFICATIONS.
C. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO
ARCHITECTURAL DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
D. THE CONTRACTOR SHALL REFER TO ALL SPECIFICATION SECTIONS AND THE
DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND
SATISFACTORY ARRANGEMENT FOR THEIR WORK. THE VARIOUS DRAWINGS
COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT
ALL TIMES. THE CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS
OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAWINGS
ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST
BE FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF DISCREPANCIES OCCUR,
CONTACT THE COR THROUGH THE CONTRACTING OFFICER FOR CLARIFICATION
BEFORE PROCEEDING.
E. ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND (FOR
ALL OTHERS) TO MAINTAIN OPERATION OF THE EXISTING FACILITY.
F. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL CURRENT
OVERNING CODES AND STANDARDS.
G. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON AVAILABLE DRAWING
INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN PLACE. THE
CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD
VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY
DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE
CONTACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL
BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN WRITING
FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.
H. REFER TO ARCHITECTURAL FIRE-RATED PARTITION PLAN(S) FOR LOCATIONS AND
FIRE-RATING OF NEW AND EXISTING WALL ASSEMBLIES. ALL PENETRATIONS
THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROJECTED AND/OR FIRE-STOPPED
AS REQUIRED TO MAINTAIN FIRE-RATINGS INDICATED. COORDINATE WITH ALL
TRADES TO ENSURE FIRE-RATED PENETRATION REQUIREMENTS AND DETAILS
ARE MET.
I. ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT AND OTHER SIMILAR PENETRATIONS
OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION, PENETRATIONS
THROUGH 0-HOUR RATED WALLS AND FLOORS SHALL BE FIRESTOPPED TO RETARD
PASSAGE OF FIRE AND SMOKE.
J. ALL CONDUITS IN FINISHED ROOMS AND CORRIDORS SHALL BE CONCEALED IN A
WALL OR ABOVE CEILING.
K. ACCESS PANELS IN NON ACCESSIBLE CEILINGS SHALL BE PROVIDED FOR ALL
ELECTRICAL ITEMS REQUIRING ACCESS.
L. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF
LIGHTS, SPEAKERS, NURSE CALL DEVICES, ETC.
M. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN
THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER THIS WORK TO MATCH
EXISTING.
N. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT DESIRED
BY THE VA SHALL BE REMOVED FROM THE PREMISES AND DISPOSED OF PROPERLY
BY THE CONTRACTOR.
O. THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL
OFFSET WHICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE WORK IN
ADVANCE WITH ALL OTHER TRADES AND REPORT IMMEDIATELY AND DIFFICULTIES
WHICH CAN BE ANTICIPATED.
P. ALL ABANDONED EXTRANEOUS CONDUITS, WIRING, DEVICES, ETC. SHALL BE REMOVED.
Q. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION CONCERNING
MECHANICAL EQUIPMENT THAT REQUIRES ELECTRICAL CONNECTIONS.
GENERAL NOTES
SECURITY SYMBOLS
CC
1 CCTV SYSTEM CEILING MOUNTED CAMERA. REFER TO CAMERA SCHEDULE FOR MOUNTING HEIGHT AND CAMERA
SPECIFICATIONS. SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE.
IM DESK MOUNTED INTERCOM MASTER STATION.
CE PROVIDE INTERFACE FROM CARD ACCESS SYSTEM INTO ELEVATOR CONTROLLER INCLUDING ALL NECESSARY
HARDWARE, PROGRAMMING AND CABLING AS COORDINATED WITH ELEVATOR CONTRACTOR.
MD CEILING MOUNTED MOTION DETECTOR.
PB DESK MOUNTED PUSH BUTTON FOR LOCAL ELECTRONIC DOOR RELEASE.
JS CCTV SYSTEM REMOTE JOYSTICK/CONTROLLER AND KEYPAD OPERATOR'S STATION.
GLASS BREAK.GB
X
PP DESK MOUNTED PANIC/DURESS BUTTON.
SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS
CC
CCTV SYSTEM WALL MOUNTED CAMERA (REFER TO CAMERA SCHEDULE FOR MOUNTING HEIGHT AND CAMERA SPECIFICATIONS). SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE. 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE
ACCESSIBLE CEILING PER DIV 26. CAMERA AND CABLING PER DIV 28.
PS
LOCAL LOW VOLTAGE POWER SUPPLY FOR EXTERIOR CAMERA. SUBSCRIPT "X" INDICATES ASSOCIATED CAMERA. 120V POWER INTO LOCAL JUNCTION BOX ABOVE CEILING AND CONNECTION TO POWER SUPPLY PER DIV 26. POWER SUPPLY
MOUNTED ABOVE CEILING AND LOW VOLTAGE WIRING TO LOCAL CAMERA PER DIV 28.
IC
WALL MOUNTED INTERCOM DOOR STATION (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO
ABOVE ACCESSIBLE CEILING PER DIV 26. INTERCOM AND CABLING PER DIV 28.
DM
DOOR POSITION SWITCH WITH WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. PROVIDE ONE CONTACT FOR EACH LEAF IN MULTI-DOOR
OPENINGS. REFER TO SECURITY ROUGH-IN DETAILS.
EL
ELECTRONIC DOOR LOCK AND INSTALLATION BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY
ROUGH-IN DETAILS.
EM
ELECTRONIC MAG LOCK AND INSTALLATION BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY ROUGH-IN
DETAILS.
ES
ELECTRONIC STRIKE AND INSTALLATION BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY ROUGH-IN
DETAILS.
LB
RX
REQUEST TO EXIT SWITCH IN DOOR HARDWARE BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY
ROUGH-IN DETAILS.
HD
HANDICAP DOOR OPERATOR MOTOR ASSEMBLY BY OTHERS. 120V POWER CONNECTION AND CONDUIT FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. LOW VOLTAGE WIRING AND INTERFACE WITH SMS AND DOOR ACTUATOR BUTTONS PER DIV 28. REFER TO SECURITY ROUGH-IN DETAILS.
HA
WALL/PEDESTAL MOUNT HANDICAP DOOR ACTUATOR BUTTON, FURNISHED BY OTHERS. BOX AS REQUIRED BY SYSTEM MANUFACTURER WITH INSTALLATION AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. ALL LOW VOLTAGE WIRING AND INTERFACE WITH SMS AND DOOR MOTOR PER DIV 28. REFER TO SECURITY
ROUGH-IN DETAILS.
HO
FA
WALL/FLOOR MOUNTED ELECTROMAGNETIC DOOR HOLD OPEN WITH POWER SUPPLY INSTALLED BY OTHERS. 120V POWER AND CONNECTION, BOX AS REQUIRED BY MANUFACTURER AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. LOW VOLTAGE WIRING FROM POWER SUPPLY TO HOLD OPEN AND INTERFACE WITH SMS PER DIV 28. SUBSCRIPT "FA" INDICATES DEVICES POWERED FROM FIRE ALARM SYSTEM AND INTERFACE FROM SMS TO FIRE ALARM SYSTEM REQUIRED FOR DOOR RELEASE PER DIV 28. REFER TO SECURITY ROUGH-IN DETAILS.
CR
WALL MOUNTED PROXIMITY CARD READER (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY ROUGH-IN DETAILS. CARD
READER IS ROUGH-IN ONLY.
CR EL
ELEVATOR CAB MOUNTED CARD READER. READER TO BE INSTALLED IN ELEVATOR CAB AS COORDINATED WITH ELEVATOR CONTRACTOR. WIRING FROM CAB THRU TRAVELING CABLE TO ELEVATOR CONTROLLER IN ELEVATOR MACHINE ROOM AND INTERFACE WITH ELEVATOR CONTROLLER AND SMS PER DIV 28, COORDINATE WITH ELEVATOR
CONTRACTOR. REFER TO SECURITY ROUGH-IN DETAILS.
KC
WALL MOUNTED COMBINATION KEYPAD/CARDREADER (46" MH UNLESS NOTED OTHERWISE). 2-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. DEVICE AND CABLING PER DIV 28.
K WALL…