2022-05-20 Renovate Sleep and Home Oxygen Areas FINAL BID ISSUE-DRAWINGS.pdf

PDF 25 MB Posted

Attached to
Z2DA--Z2DA - Renovate Sleep and Home Oxygen Areas - Project # 541-21-104 Louis Stokes Cleveland VAMC - Cleveland, OH SDVOSB Set-Aside
Solicitation number
36C25021B0072
Issued by

About this file

This federal contract opportunity solicits bids to renovate sleep and home oxygen areas at the Louis Stokes Cleveland VA Medical Center in Cleveland, Ohio. The project includes providing additional sleep labs on the second floor and reconfiguring adjacent space to consolidate the Sleep and Home Oxygen programs. The solicitation is identified as number 36C25021B0072 and is a SDVOSB set-aside issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10. Bids are due in response to the solicitation to provide renovations that will expand and improve facilities for sleep labs and home oxygen programs at the Cleveland VA medical center.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: NICK CARROZZA

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

E T

G

DE

I

RET

S

HCRA

I

KACZMAR

STANLEY

NO. 4988

T

E R

S

AT

E

I

T C

J.

O

O

FO

H

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

MECHANICAL/TECH. ENGINEERING:

HEAPY

THE HANNA BUILDING

1422 EUCLID AVE. STE. 1162

CLEVELAND, OH 44115

P. 216.862.5846

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

ELECTRICAL ENGINEERING:

FFE, INC.

110 BOGGS LN, SUITE 170

SPRINGDALE, OH 45246

P. 513.522.0956

HAZ. MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOC., INC.

30628 DETROIT RD. #258

WESTLAKE, OH 44145

P. 216.781.0060

STRUCTURAL ENGINEERING:

THORSON BAKER & ASSOC.

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

BID ISSUE SUBMISSION

C U s e rs \d a v e \D o c u m e n ts \V

A M

P

S le e p

L a b H o m e O x y g e n

R d a k a p la n .r v t

/2

/2

:0

:2

A

M

GI-1

TITLE SHEET & DRAWING INDEX RENOVATE SLEEP AND HOME

OXYGEN AREAS

10701 EAST BLVD. CLEVELAND, OHIO

541-21-104

5.20.22 CJK DAK

DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER - WADE PARK

RENOVATE SLEEP AND HOME OXYGEN AREAS

10701 EAST BLVD. CLEVELAND, OH 44106

PROJECT NO. 541-21-104

Cleveland Veterans Affairs Medical Center

SECOND FLOOR

NORT

H

CODE INFORMATION:

I. PROJECT LOCATION: CLEVELAND VETERANS AFFAIRS MEDICAL CENTER

10701 EAST BLVD.

CLEVELAND, OHIO

II. DESCRIPTION & USER GROUP CLASSIFICATION OF BUILDING

A. NATURE OF PROJECT: INTERIOR RENOVATIONS OF EXISTING 2ND FLOOR PULMONARY DEPT.

AREAS - SLEEP LAB, HOME OXYGEN, PULMONARY FUNCTION TESTING

B. DESIGN CODES: 2018 NFPA LIFE SAFETY CODE 101, IBC 2018

C. USE GROUP: I-2 HEALTH CARE - NO CHANGE PROPOSED

D. CONSTRUCTION TYPE: TYPE I-332, IB - NON-COMBUSTIBLE, PROTECTED

FIRE RATED CONSTRUCTION (LSC A.8.2.1.1)

EXTERIOR BEARING WALLS 3 HRS

INTERIOR BEARING WALLS 3 HRS

STRUCTURAL COLUMNS 3 HRS (SUPPORTING > 1 FLOOR)

2 HRS (SUPPORTING 1 FLOOR ONLY)

2 HRS (SUPPORTING ROOF ONLY)

BEAMS, GIRDERS, TRUSSES 3 HRS (SUPPORTING > 1 FLOOR, COLS., OR BEARING WALLS)

FLOOR-CEILING ASSEMBLIES 2 HRS

ROOF-CEILING ASSEMBLIES 1-1/2 HRS

INTERIOR NON-BEARING WALLS 0 HRS

EXTERIOR NON-BEARING WALLS 0 HRS

WALL ASSEMBLIES

EXIT ACCESS CORRIDOR WALLS 0 HR SMOKE PARTITIONS

E. PROJECT AREA: 5,468 SF

F. PROJECT AREA OCCUPANT LOAD: 55

G. FIRE PROTECTION: EXISTING BUILDING FULLY SPRINKLED. MODIFICATIONS AS REQUIRED PER

NEW IMPROVEMENTS PROPOSED

DRAWING INDEX:

BID ISSUE SUBMISSION

5.20.22

GI-1 TITLE SHEET & DRAWING INDEX

ARCHITECTURAL

LS-2.1 SECOND FLOOR LIFE SAFETY PLAN - PHASE I

LS-2.2 SECOND FLOOR LIFE SAFETY PLAN - PHASE II

AS-X-2.0 SECOND FLOOR - EXISTING CONDITIONS PLAN

AS-XC-2.0 SECOND FLOOR - EXISTING REFLECTED CEILING PLAN

AS-D-2.1 SECOND FLOOR DEMOLITION PLAN - PHASE I & PHASE II WEST

AS-D-2.2 SECOND FLOOR DEMOLITION PLAN - PHASE II EAST

AS-DC-2.1 SECOND FLOOR CEILING DEMOLITION PLAN - PHASE I & PHASE II WEST

AS-DC-2.2 SECOND FLOOR CEILING DEMOLITION PLAN - PHASE II EAST

AS-2.0 SECOND FLOOR MASTER IMPROVEMENT PLAN - PHASES I & II

AS-2.1 SECOND FLOOR IMPROVEMENT PLAN - PHASE I & PHASE II WEST

AS-2.2 SECOND FLOOR IMPROVEMENT PLAN - PHASE II EAST

AS-C-2.1 SECOND FLOOR REFLECTED CEILING PLAN - PHASE I & PHASE II WEST

AS-C-2.2 SECOND FLOOR REFLECTED CEILING PLAN - PHASE II EAST

AS-200 ENLARGED FLOOR PLANS & INTERIOR ELEVATIONS

AS-201 INTERIOR ELEVATIONS

AS-202 INTERIOR ELEVATIONS, MILLWORK SECTIONS, & DETAILS

AS-203 MILLWORK SECTIONS & DETAILS

AS-500 DOOR SCHEDULE, DETAILS, AND PARTIAL ROOF PLAN

AS-600 WALL TYPES AND DETAILS

AS-700 PHASE I & PHASE II WEST - FINISH PLANS

AS-701 PHASE II EAST - FINISH PLAN

AS-702 FINISH SCHEDULE

PHASING DURATION:

THE SCOPE OF WORK DESCRIBED IN THIS DRAWING PACKAGE REPRESENTS A MULTI-PHASED

PROJECT THAT MUST BE UNDERTAKEN SIMULTANEOUSLY WITH THE FULL OCCUPANCY AND

FUNCTION OF THE EXISTING HOSPITAL. THE PROPOSING PHASING DURATION PLAN IS AS FOLLOWS:

PRE-CONSTRUCTION: 60 DAYS

PHASE I: 20 DAYS

VA ACTIVATION: 30 DAYS

PHASE II: 270 DAYS

TOTAL TIMEFRAME: 380 DAYS

THE TIMEFRAMES IDENTIFIED ABOVE ARE IN REFERENCE TO NORMAL CONSTRUCTION ACTIVITIES AND, UNLESS APPROVED BY VA COR, SHALL NOT APPLY TO WORK INCLUDING BUT NOT LIMITED

TO:

-UTILITY SHUTDOWNS

-EXISTING MEP SYSTEM SHUTDOWNS

-WORK IN PUBLIC CORRIDORS

-CUTTING OF FLOOR OPENINGS

-WORK OUTSIDE OF TEMPORARY CONSTRUCTION PARTITIONED AREAS, INCLUDING

ACCESS OF CEILING PLENUM SPACES IN FLOORS ABOVE OR BELOW CONSTRUCTION

AREAS (1ST FLOOR CEILING/MEP WORK)

WORK IDENTIFIED ABOVE SHALL OCCUR EITHER IN THE EVENING SHIFT, OR IF REQUIRED BY THE

VA, ON WEEKENDS. ALL CONSTRUCTION ACTIVITIES AND SCHEDULES MUST BE REVIEWED AND

APPROVED BY COR. REFER TO SPEC DIVISION 01 FOR GENERAL PROJECT REQUIREMENTS

SCOPE OF WORK

AREAS IN GRAY

MECHANICAL

M-001 MECHANICAL LEGEND, NOTES, & INDEX OF DRAWINGS

MD-102 HVAC SECOND FLOOR - DEMOLITION - DUCTWORK & PIPING

MH-102 HVAC SECOND FLOOR - NEW WORK - DUCTWORK

MH-104 HVAC FOURTH FLOOR & SEVENTH FLOOR - DUCTWORK

MP-102 HVAC SECOND FLOOR - NEW WORK - PIPING

M-501 DETAILS

M-502 DETAILS

M-601 SCHEDULES

M-901 CONTROLS

PLUMBING

P-001 ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS

PD-101.2 PARTIAL 1ST FLOOR - DEMOLITION - PHASE II

PD-102.2 PARTIAL 2ND FLOOR - DEMOLITION - PHASE II

PL-101.1 PARTIAL 1ST FLOOR - DRAINAGE - PHASE I

PL-101.2 PARTIAL 1ST FLOOR - DRAINAGE - PHASE II

PL-102.1 PARTIAL 2ND FLOOR - DRAINAGE - PHASE I

PL-102.2 PARTIAL 2ND FLOOR - DRAINAGE - PHASE II

PP-102.1 PARTIAL 2ND FLOOR - DISTRIBUTION - PHASE I

PP-102.2 PARTIAL 2ND FLOOR - DISTRIBUTION - PHASE II

P-601 SCHEDULES AND DIAGRAMS

ELECTRICAL

E-001 LEGEND AND ABBREVIATIONS

ED-102 ELECTRICAL DEMOLITION PLAN -

PHASES I & II

EL-102.2 ELECTRICAL LIGHTING PLAN - PHASE II

EP-102.2 ELECTRICAL POWER & FIRE ALARM PLAN -

PHASE 2

EP-107 ROOF PLAN - ELECTRICAL

E-501 ELECTRICAL DETAILS

E-601 PANEL SCHEDULES

TECHNOLOGY

T-001 LEGEND, NOTES, & INDEX OF DRAWINGS

TD-102 PARTIAL SECOND FLOOR TECHNOLOGY

DEMOLITION PLAN

T-102 PARTIAL SECOND FLOOR TECHNOLOGY

PLAN

T-500 DETAILS

T-501 DETAILS

FIRE PROTECTION

FS-102 PARTIAL SECOND FLOOR - FIRE SUPPRESSION

HAZARDOUS MATERIALS ABATEMENT

HA-001 STANDARD ASBESTOS ABATEMENT DETAILS

HA-102 PARTIAL SECOND FLOOR ASBESTOS ABATEMENT PLAN - PHASE II

Revisions: Date:

SCHEMATIC DESIGN 9.2.20

DESIGN DEVELOPMENT 11.13.20

65% CDs SUBMISSION 3.26.21

100% CDs SUBMISSION 5.5.21

FINAL CDs SUBMISSION 5.28.21

BID ISSUE SUBMISSION 5.20.2022

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

LIFE SAFETY LEGEND:

TEMPORARY ZIP WALL PROTECTION TO BE PROVIDED AROUND CONSTRUCTION AREA PER VA

SAFETY STANDARDS. INSTALLATION OF ZIP WALL MAY NEED TO OCCUR AFTER RELOCATION OF

CASEWORK/FURNITURE. CONTRACTOR TO COORDINATE SEQUENCING OF INSTALL WITH COR

EXISTING/NEW 2 HOUR RATED FIRE BARRIER

EXISTING/NEW 1 HOUR RATED FIRE BARRIER

EXISTING/NEW 1 HOUR RATED SMOKE BARRIER

EXISTING/NEW O HOUR RATED SMOKE PARTITION

E EXIT

FE

FIRE EXTINGUISHER

EXIT SIGN LOCATION

LIFE SAFETY GENERAL NOTES:

1. SEE COVER SHEET FOR APPLICABLE CODE INFORMATION. PROJECT AREA IS CLASSIFIED AS A

RECONSTRUCTION IN COMPLIANCE WITH "NEW HEALTH CARE OCCUPANCY" PER NFPA 101 2018.

2. PROJECT SCOPE LINE IS INDICATED FOR GENERAL INTENT ONLY. CONTRACTOR WILL COMPLETE ALL WORK REGARDLESS IF IT IS LOCATED OUTSIDE OF PROJECT SCOPE AREA AS INDICATED ON ANY DRAWINGS

3. CONTRACTOR TO COVER OR ALTER EXIT SIGNS, OR TEMPORARILY RELOCATE EXISTING EXIT SIGNS WHICH, DUE TO CONSTRUCTION, TEMPORARILY DO NOT DEPICT EXIT PATHS AND/OR ARE IN THE WAY OF TEMPORARY CONSTRUCTION BARRIERS (TYP. OF ALL EXIT SIGNS IN OR BEYOND PROJECT AREA)

4. TRAVEL DISTANCES OVER 200' WILL REQUIRE INTERIM LIFE SAFETY MEASURES. COORDINATE WITH VA.

5. EXISTING FLOOR SLABS ARE 2 HR RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, CONTRACTOR SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE COMPROMISED, AND SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD.

CONTRACTOR SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS.

FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, CONTRACTOR

SHALL PATCH CONC. SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING

6. PROVIDE FIRESTOPPING AT ALL PENETRATIONS THROUGH NEW AND EXISTING FIRE/SMOKE RATED BARRIER WALLS AND FLOOR SLABS TO COMPLY WITH THE REQUIRED BARRIER RATINGS. PROVIDE

FIRESTOPPING AROUND TEN (10) PENETRATIONS LESS THAN 6 SQUARE INCHES AND FOUR (4)

PENETRATIONS BETWEEN 16 AND 36 SQUARE INCHES TO COMPLY WITH REQUIRED RATING NOT

ASSOCIATED WITH NEW WORK. LARGER OPENINGS SHALL BE BROUGHT TO THE ATTENTION OF THE COR.

CONTRACTOR SHALL SUBMIT UL LISTED METHODS FOR PATCHING ALL FIRE BARRIERS THAT MEET THE MINIMUM FIRE RATING REQUIREMENTS OF THE PENETRATING BARRIER AND ARE IN COMPLIANCE WITH THE

OPENING SIZE AS DICTATED BY THE ASSEMBLY.

7. TEMPORARY FIRE ALARMS IN CONSTRUCTION AREAS: CONTRACTOR SHALL PROVIDE TEMPORARY FIRE ALARMS IN ALL CONSTRUCTION AREAS THROUGHOUT THE CONSTRUCTION DURATION UNTIL SUCH TIME THAT NEW FIRE ALARM SYSTEM DEVICES ARE INSTALLED, TESTED, AND IN FULL OPERATION. HEAT DETECTION DEVICES SHALL BE UTILIZED AND SHALL BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM AND COORDINATED THROUGH THE VA ELECTRICAL SHOP. CONTRACTOR SHALL COORDINATE WITH VA SAFETY DEPARTMENT FOR ALL TEMPORARY FIRE ALARM INSTALLATIONS TO ENSURE COMPLIANCE WITH SAFETY STANDARDS. TEMPORARY FIRE ALARM DEVICES SHALL BE PROGRAMMED INTO THE SYSTEM BY CERTIFIED NOTIFIER VENDOR. ANY OLD FA DEVICES THAT ARE REMOVED SHALL BE DEPROGRAMED OUT BY THE SAME CERTIFIED VENDOR. ALL COSTS ASSOCIATED WITH THE PROGRAMMING/DE-PROGRAMMING OF THE TEMPORARY FIRE ALARM SYSTEM SHALL BE INCLUDED IN THE CONTRACTOR'S SCOPE/BID.

HAZARDOUS ROOM

EXISTING/NEW 2 HOUR RATED SMOKE BARRIER

FIRE-RATED PLASTIC SHEETING/METAL STUD WALL TEMPORARY PARTITION WALL W/3'-0" X 7'-0"

SCWD DOOR FOR CONTRACTOR ACCESS ONLY. WALL AND DOOR TO BE REMOVED UPON

COMPLETION OF WORK U.N.O. PATCH/REPAIR EXISTING CONDITIONS AS REQUIRED UPON

REMOVAL OF ALL TEMPORARY CONSTRUCTION. REFER TO "TEMPORARY CONSTRUCTION BARRIER"

TYPICAL PARTITION DETAIL ON SHEET AS-600. SCHEDULE NOTE: CONSTRUCTION OF TEMPORARY

BARRIERS SHALL BE PERFORMED AFTER NORMAL BUSINESS HOURS UNLESS OTHERWISE

APPROVED BY THE COR.

SEPARATE ALL OCCUPIED AREAS OF THE RENOVATION AREA BY TEMPORARY SMOKE-TIGHT

CONSTRUCTION PARTITIONS BUILT TO THE DECK ABOVE, AND FOR AREAS WITHOUT ACTIVE

SPRINKLER PROTECTION ON BOTH SIDES, THE PARTITION SHALL BE ONE-HOUR FIRE RATED.

PROJECT SCOPE BOUNDARY

SOLID WHITE AREA INDICATES

CONSTRUCTION AREA WITHIN SCOPE

OF WORK

GRAY HATCHED AREA INDICATES AREA

OUTSIDE OF SCOPE OF WORK

SUITE AREA DESIGNATION

INFECTION CONTROL CLASS & SAFETY MEASURES:

THE WORK IDENTIFIED IN THIS PROJECT IS ASSIGNED A CLASS III INFECTION CONTROL CLASS AND SHALL APPLY TO THIS PROJECT THROUGHOUT THE ENTIRETY OF CONSTRUCTION. ALL CONTRACTORS AND CONSTRUCTION WORKERS ARE REQUIRED TO VACUUM THEIR CLOTHING FULLY IN THE TEMPORARY CONSTRUCTION ANTEROOMS IDENTIFIED ON THE DRAWINGS PRIOR TO ENTERING OCCUPIED PORTIONS OF THE

BUILDING.

REFER TO LIFE SAFETY AND DEMOLITION PLANS FOR SCOPE OF TEMPORARY CONSTRUCTION BARRIERS REQUIRED FOR THE PROJECT. REFER TO AND FOLLOW ALL PROTOCOL IDENTIFIED IN "SAFETY REQUIREMENTS"

01 35 26 THROUGHOUT THE ENTIRETY OF THE PROJECT.

SPECIAL NOTE:

* NOTE 1 - CONTRACTOR SHALL BE AWARE THAT NEGATIVE PRESSURIZATION MUST BE MAINTAINED IN ALL CONSTRUCTION AREAS THROUGHOUT CONSTRUCTION. THIS AREA OF THE SECOND FLOOR HAS BEEN HISTORICALLY DIFFICULT TO MAINTAIN NEGATIVE PRESSURE WITHOUT ADDITIONAL MEASURES DUE TO THE

FOLLOWING ISSUES:

1) EXHAUST FROM THE ADJACENT MAIN ATRIUM PULLS AIR DOWN THE CORRIDOR

2) THE LOCATION OF THE PROJECT IS AT THE END OF THE RUN FOR THE AIR HANDLER SERVING THE AREA

CONTRACTOR SHALL INCLUDE IN BID TEMPORARY REMOVAL OF WINDOWS IN A MINIMUM OF THREE (3) LOCATIONS AS NOTED, AND PROVDING INFILL PANELS/HEPA EXHAUST FANS IN OPENINGS TO ACHIEVE PRESSURIZATION. ANTEROOM SHALL ALSO BE CONSTRUCTED AS DEPICTED. GC SHALL RE-INSTALL AND RECAULK WINDOWS AT PROJECT COMPLETION, PATCH/REPAIR ALL SURROUNDING CONDITIONS AS REQUIRED TO RESTORE TO ORIGINAL CONDITIONS. GC MAY SELECT DIFFERENT WINDOW LOCATIONS IF DESIRED, OBTAIN

APPROVAL FROM VA PRIOR TO PROCEEDING

F E

FE

F E

E

E

E

E

PHASE I SCOPE OF WORK

BOUNDARY

FE

E.

FE

F

OFFICE

2C137

UPS

ROOM

2C135

Comm.

2B149

Hemodialysis Storage

2B150

Elect.

2B148

Equip.

Closet 2C144A

E.P. Lab 2C144

Storage 2C143

Lockers 2C142

Toilet 2C141

Corridor 2C140

Control 2C145A

Control 2C145B

Scrub 2C145

Office 2C146

Intervention 2C148

Cath. Lab 2C147

Equip.

Closet 2C147A

Soiled Utility 2C149

Clean Utility 2C150

Staff Work 2C151

Endo.

Computers

2C171

Endo. Conf.

2C170

EMS Clos.

2C154

Corridor 2C157

Holding 2C153

Viewing/Fellows 2C155

Exam Room 2C424

Exam Room 2C425

Holding 2C423

G.I. Office 2C438

Storage 2C437

ICU

Cleveland

Clinic Resident

2C439

Sec'y Reception

2C422

G.U.

Urology Clinic 2C420

Stair #6 2C121

Cardiothoracic 2C440

F.A.C.

2C421

Office 2C415

Office 2C414

Office 2C413

Electrical Room 2C411

Corridor 2C400A

Fan Room 2C129

Reception Alcove 2C133

Control 2C133A

Elevator Lobby 2C400B

Endo/Cath Waiting 2C133B

TELECOMM

2C134

CORRIDOR

2C100C

OPEN

OFFICE

AREA

2C136

Sub-Sterile 2C235

Procedure 2C233

Stair #9 2C202

OXYGEN

STORAGE

(CLEAN)

2B121A

HOME

OXYGEN

CLINIC

2B119

CLEAN

UTILITY

2B120

OFFICE/CONSULT

2B122

OFFICE/CONSULT

2B123

OFFICE/CONSULT

2B124

ELECT.

ROOM

2B125

ELEC.

ROOM

2B126

RECEPTION/WAITING

2B141

PFT LAB

2B142

TOILET

2B143

PFT LAB

2B144

PFT LAB

(CPET)

2B145

Administration Center 2B336

Passage 2B330

Meds 2B339 Cubicle 6

2B336A

Cubicle 7 2B336B

Clean Utility 2B338

Soiled 2B337

Seclusion 2 2B333B

Seclusion 3 2B333C

Seclusion 4 2B333D

Seclusion 5 2B333E

Linen 2B338A

Chute 2B335

Seclusion 1 2B333A

Water Processing/ Equip. Rm

2B332A

Toilet 2B334

Water Processing/ Equipment

Room 2B332

Waiting 2B310

PD Training Room 2B321

Office 2B322

IT Closet 2B322A

Corridor 2B320Supply

Room 2B234

Closet 2B324A

Break Room 2B323

Office Space 2B325

Office 2B325A

Office 2B325B

Office 2B325C

Office 2B325D

Office 2B325E

Office 2B325F

Office 2B325G

Office 2B325HToilet

2B325J

Stair #11 2B146

Endoscopy Procedure

Procedure Room

Sub-Sterile 2052A

Scrub 2C172

Medication

Male Lockers

Female Lockers

Toilet 2064A

Toilet 2065A

Workroom/ Inst Clean

Electrical Closet 2C156

Corridor

Corridor 2C100A

Corridor 2C100B

CORRIDOR

2B134

SLEEP

LAB

2B133

TOILET/SHOWER

2B133A

OFFICE

2B132

OFFICE

2B131

OFFICE

2B130

SLEEP

LAB

2B135

TOILET/SHOWER

2B135A

OFFICE

2B136

SLEEP

LAB DAY

TESTING

2B137

Stair #8 2B138

OFFICE

2B139

PCAS/CHECK-IN

2B140

OFFICE

2B127

FELLOWS

OFFICE

2B128

OFFICE

2B129

Corridor 2B147

CORRIDOR

2B100B

CORRIDOR

2B100A

HAC

2C224

CLOSET

2B126A

Stair #5 2C127

Service Elevator Lobby 2C400C

EMS

2C416

Office 2C417

EMS

2C100

Elect.

2C140A

Chute 2C134A

CONTROL

STATION

2B134A

ALCOVE

2B143A

Elect.

2B146A

Corridor 2B480A

Penthouse 2B480

HOME

O2/CPAP

2B121E

HOME

O2/CPAP

2B121C

HOME

OXYGEN -

ENTRY

2B121

Clean Linen 2B412

Procedure 2B413

Exam 8 2B414

Exam 7 2B415

Staff Lounge

2B411

Exam 4 2B420

Exam 3 2B421

Corridor 2B410

Corridor 2B418

Corridor 2B419

Exam 6 2B416

Exam 5 2B417

Exam 2 2B423

Exam 1 2B422

ASMT.

2B432

Office 2B431

Nurse Intake 2B433

Storage 2B435

Corridor 2B430

Waiting 2B434

Recpt.

2B462

Pharmacy Buffer Room 2B461A

Pharmacy Anteroom

2B461 Staff Toilet

2B460

Patient Toilet 2B438

EMS

2B436

Family/ Consult

2B437

Patient Toilet 2B439

Private Infusion 1

2B440

Private Infusion 2

2B453

2B146B

Mech 2C412

OFFICE

2C138

OFFICE

2C139

Nurse Mgr.

2D262

Work

2D260F

Control

2D261

Corridor

2D260J

Holding

Corridor

2500B

Stretcher Storage

Anesthesia

Corridor

2500H

OR-7

General

2504 OR-6

General

Electric

EMS

Anesthesia Storage

EMS

2508A

Control

Sub Sterile

Corridor

2500A

Corridor

2500C

Corridor

2500J Corridor

2C280

Storage

JC

2B201

Rehab Office

2B203

Psychology Office

2B204

Psychology Office

2B206

Psychology Office

2B207

Psychology Office

2B209

Surgical Lounge

2B211

Corridor

2B200C

HOME

O2/CPAP

2B121D

MINOR IMPROVEMENTS IN EXISTING

HOME O2 DEPARTMENT. EXISTING

OFFICES ARE OCCUPIED MON. - FRI. UNTIL

5:30 PM DAILY. CONTRACTOR SHALL

PROVIDE TEMP. PROTECTION OF EX.

FURNITURE/ITEMS WITHIN EACH SPACE

AS REQ'D. ICRA MEASURES SHALL BE

FULLY IN PLACE DURING DOORWAY

DEMOLITION

EGRESS PATHS THROUGH ALL EXISTING

CORRIDORS SHALL AND WILL NOT BE IMPEDED AS

A RESULT OF PHASE I CONSTRUCTION IN ANY WAY

CONSTRUCTION

AREA

PACU

CUBICLE 1

2C237A

PACU

CUBICLE 2

2C237B

PACU

CUBICLE 3

2C237C

PACU

CUBICLE 4

2C237D

PACU

CUBICLE 6

2C237F

PACU

CUBICLE 5

2C237E

PACU/EMS

2C234

PACU

PASSAGE

2C323A

PACU

ADMIN.

CENTER

2C323

PACU

MEDS.

2C324

PACU

NOUR.

2C325

PACU

CUBICLE 7

2C326A

PACU

CUBICLE 8

2C326B

PACU

CUBICLE 9

2C326C

PACU

CUBICLE

2C326D

PACU

CUBICLE

2C326E

PACU

TOILET

2C322

PACU

CLEAN

2C330A

PACU

STORAGE

2C328

PACU

CUBICLE

2C326H

PACU

CUBICLE

2C326G

PACU

CUBICLE

2C326F

PACU

SOILED

UTILITY

2C321

ELEC.

2C327

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: NICK CARROZZA

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

E T

G

DE

I

RET

S

HCRA

I

KACZMAR

STANLEY

NO. 4988

T

E R

S

AT

E

I

T C

J.

O

O

FO

H

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

MECHANICAL/TECH. ENGINEERING:

HEAPY

THE HANNA BUILDING

1422 EUCLID AVE. STE. 1162

CLEVELAND, OH 44115

P. 216.862.5846

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

ELECTRICAL ENGINEERING:

FFE, INC.

110 BOGGS LN, SUITE 170

SPRINGDALE, OH 45246

P. 513.522.0956

HAZ. MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOC., INC.

30628 DETROIT RD. #258

WESTLAKE, OH 44145

P. 216.781.0060

STRUCTURAL ENGINEERING:

THORSON BAKER & ASSOC.

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

BID ISSUE SUBMISSION

C U s e rs \d a v e \D o c u m e n ts \V

A M

P

S le e p

L a b H o m e O x y g e n

R d a k a p la n .r v t

/2

/2

:5

:5

A

M

LS-2.1

SECOND FLOOR LIFE SAFETY PLAN - PHASE I RENOVATE SLEEP AND HOME

OXYGEN AREAS

10701 EAST BLVD. CLEVELAND, OHIO

541-21-104

5.20.22 CJK DAK

SCALE: 3/32" = 1'-0"

SECOND FLOOR LIFE SAFETY PLAN - PHASE I

NORTH

Revisions: Date:

SCHEMATIC DESIGN 9.2.20

DESIGN DEVELOPMENT 11.13.20

65% CDs SUBMISSION 3.26.21

100% CDs SUBMISSION 5.5.21

UP

UP

UP

UP

UP

UP

UP

UP

UP

LIFE SAFETY LEGEND:

TEMPORARY ZIP WALL PROTECTION TO BE PROVIDED AROUND CONSTRUCTION AREA PER VA

SAFETY STANDARDS. INSTALLATION OF ZIP WALL MAY NEED TO OCCUR AFTER RELOCATION OF

CASEWORK/FURNITURE. CONTRACTOR TO COORDINATE SEQUENCING OF INSTALL WITH COR

EXISTING/NEW 2 HOUR RATED FIRE BARRIER

EXISTING/NEW 1 HOUR RATED FIRE BARRIER

EXISTING/NEW 1 HOUR RATED SMOKE BARRIER

EXISTING/NEW O HOUR RATED SMOKE PARTITION

E EXIT

FE

FIRE EXTINGUISHER

EXIT SIGN LOCATION

LIFE SAFETY GENERAL NOTES:

1. SEE COVER SHEET FOR APPLICABLE CODE INFORMATION. PROJECT AREA IS CLASSIFIED AS A

RECONSTRUCTION IN COMPLIANCE WITH "NEW HEALTH CARE OCCUPANCY" PER NFPA 101 2018.

2. PROJECT SCOPE LINE IS INDICATED FOR GENERAL INTENT ONLY. CONTRACTOR WILL COMPLETE ALL WORK REGARDLESS IF IT IS LOCATED OUTSIDE OF PROJECT SCOPE AREA AS INDICATED ON ANY DRAWINGS

3. CONTRACTOR TO COVER OR ALTER EXIT SIGNS, OR TEMPORARILY RELOCATE EXISTING EXIT SIGNS WHICH, DUE TO CONSTRUCTION, TEMPORARILY DO NOT DEPICT EXIT PATHS AND/OR ARE IN THE WAY OF TEMPORARY CONSTRUCTION BARRIERS (TYP. OF ALL EXIT SIGNS IN OR BEYOND PROJECT AREA)

4. TRAVEL DISTANCES OVER 200' WILL REQUIRE INTERIM LIFE SAFETY MEASURES. COORDINATE WITH VA.

5. EXISTING FLOOR SLABS ARE 2 HR RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, CONTRACTOR SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE COMPROMISED, AND SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD.

CONTRACTOR SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS.

FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, CONTRACTOR

SHALL PATCH CONC. SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING

6. PROVIDE FIRESTOPPING AT ALL PENETRATIONS THROUGH NEW AND EXISTING FIRE/SMOKE RATED BARRIER WALLS AND FLOOR SLABS TO COMPLY WITH THE REQUIRED BARRIER RATINGS. PROVIDE

FIRESTOPPING AROUND TEN (10) PENETRATIONS LESS THAN 6 SQUARE INCHES AND FOUR (4)

PENETRATIONS BETWEEN 16 AND 36 SQUARE INCHES TO COMPLY WITH REQUIRED RATING NOT

ASSOCIATED WITH NEW WORK. LARGER OPENINGS SHALL BE BROUGHT TO THE ATTENTION OF THE COR.

CONTRACTOR SHALL SUBMIT UL LISTED METHODS FOR PATCHING ALL FIRE BARRIERS THAT MEET THE MINIMUM FIRE RATING REQUIREMENTS OF THE PENETRATING BARRIER AND ARE IN COMPLIANCE WITH THE

OPENING SIZE AS DICTATED BY THE ASSEMBLY.

7. TEMPORARY FIRE ALARMS IN CONSTRUCTION AREAS: CONTRACTOR SHALL PROVIDE TEMPORARY FIRE ALARMS IN ALL CONSTRUCTION AREAS THROUGHOUT THE CONSTRUCTION DURATION UNTIL SUCH TIME THAT NEW FIRE ALARM SYSTEM DEVICES ARE INSTALLED, TESTED, AND IN FULL OPERATION. HEAT DETECTION DEVICES SHALL BE UTILIZED AND SHALL BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM AND COORDINATED THROUGH THE VA ELECTRICAL SHOP. CONTRACTOR SHALL COORDINATE WITH VA SAFETY DEPARTMENT FOR ALL TEMPORARY FIRE ALARM INSTALLATIONS TO ENSURE COMPLIANCE WITH SAFETY STANDARDS. TEMPORARY FIRE ALARM DEVICES SHALL BE PROGRAMMED INTO THE SYSTEM BY CERTIFIED NOTIFIER VENDOR. ANY OLD FA DEVICES THAT ARE REMOVED SHALL BE DEPROGRAMED OUT BY THE SAME CERTIFIED VENDOR. ALL COSTS ASSOCIATED WITH THE PROGRAMMING/DE-PROGRAMMING OF THE TEMPORARY FIRE ALARM SYSTEM SHALL BE INCLUDED IN THE CONTRACTOR'S SCOPE/BID.

HAZARDOUS ROOM

EXISTING/NEW 2 HOUR RATED SMOKE BARRIER

FIRE-RATED PLASTIC SHEETING/METAL STUD WALL TEMPORARY PARTITION WALL W/3'-0" X 7'-0"

SCWD DOOR FOR CONTRACTOR ACCESS ONLY. WALL AND DOOR TO BE REMOVED UPON

COMPLETION OF WORK U.N.O. PATCH/REPAIR EXISTING CONDITIONS AS REQUIRED UPON

REMOVAL OF ALL TEMPORARY CONSTRUCTION. REFER TO "TEMPORARY CONSTRUCTION BARRIER"

TYPICAL PARTITION DETAIL ON SHEET AS-600. SCHEDULE NOTE: CONSTRUCTION OF TEMPORARY

BARRIERS SHALL BE PERFORMED AFTER NORMAL BUSINESS HOURS UNLESS OTHERWISE

APPROVED BY THE COR.

SEPARATE ALL OCCUPIED AREAS OF THE RENOVATION AREA BY TEMPORARY SMOKE-TIGHT

CONSTRUCTION PARTITIONS BUILT TO THE DECK ABOVE, AND FOR AREAS WITHOUT ACTIVE

SPRINKLER PROTECTION ON BOTH SIDES, THE PARTITION SHALL BE ONE-HOUR FIRE RATED.

PROJECT SCOPE BOUNDARY

SOLID WHITE AREA INDICATES

CONSTRUCTION AREA WITHIN SCOPE

OF WORK

GRAY HATCHED AREA INDICATES AREA

OUTSIDE OF SCOPE OF WORK

SUITE AREA DESIGNATION

INFECTION CONTROL CLASS & SAFETY MEASURES:

THE WORK IDENTIFIED IN THIS PROJECT IS ASSIGNED A CLASS III INFECTION CONTROL CLASS AND SHALL APPLY TO THIS PROJECT THROUGHOUT THE ENTIRETY OF CONSTRUCTION. ALL CONTRACTORS AND CONSTRUCTION WORKERS ARE REQUIRED TO VACUUM THEIR CLOTHING FULLY IN THE TEMPORARY CONSTRUCTION ANTEROOMS IDENTIFIED ON THE DRAWINGS PRIOR TO ENTERING OCCUPIED PORTIONS OF THE

BUILDING.

REFER TO LIFE SAFETY AND DEMOLITION PLANS FOR SCOPE OF TEMPORARY CONSTRUCTION BARRIERS REQUIRED FOR THE PROJECT. REFER TO AND FOLLOW ALL PROTOCOL IDENTIFIED IN "SAFETY REQUIREMENTS"

01 35 26 THROUGHOUT THE ENTIRETY OF THE PROJECT.

SPECIAL NOTE:

* NOTE 1 - CONTRACTOR SHALL BE AWARE THAT NEGATIVE PRESSURIZATION MUST BE MAINTAINED IN ALL CONSTRUCTION AREAS THROUGHOUT CONSTRUCTION. THIS AREA OF THE SECOND FLOOR HAS BEEN HISTORICALLY DIFFICULT TO MAINTAIN NEGATIVE PRESSURE WITHOUT ADDITIONAL MEASURES DUE TO THE

FOLLOWING ISSUES:

1) EXHAUST FROM THE ADJACENT MAIN ATRIUM PULLS AIR DOWN THE CORRIDOR

2) THE LOCATION OF THE PROJECT IS AT THE END OF THE RUN FOR THE AIR HANDLER SERVING THE AREA

CONTRACTOR SHALL INCLUDE IN BID TEMPORARY REMOVAL OF WINDOWS IN A MINIMUM OF THREE (3) LOCATIONS AS NOTED, AND PROVDING INFILL PANELS/HEPA EXHAUST FANS IN OPENINGS TO ACHIEVE PRESSURIZATION. ANTEROOM SHALL ALSO BE CONSTRUCTED AS DEPICTED. GC SHALL RE-INSTALL AND RECAULK WINDOWS AT PROJECT COMPLETION, PATCH/REPAIR ALL SURROUNDING CONDITIONS AS REQUIRED TO RESTORE TO ORIGINAL CONDITIONS. GC MAY SELECT DIFFERENT WINDOW LOCATIONS IF DESIRED, OBTAIN

APPROVAL FROM VA PRIOR TO PROCEEDING

Toilet 2064A

Workroom/ Inst Clean

Corridor

Corridor 2C100B

Exam Room 2C424

Sec'y Reception

2C422

Stair #6 2C121

F.A.C.

2C421

Office 2C415

Office 2C414

Office 2C413

Electrical Room 2C411

Fan Room 2C129

Procedure Room

Sub-Sterile 2052A

Scrub 2C172

Medication

Male Lockers

Female Lockers

Toilet 2065A

Electrical Closet 2C156

Corridor 2C100A

Stair #5 2C127

Mech 2C412

TELECOM

2C134

UPS

ROOM

2C135

ELECTRICAL

2B125

ELECT./

OIT

2B126

CLOSET

2B126A

SLEEP

MDs

OFFICE

2B128

SLEEP

NPs

OFFICE

2B129

SLEEP

LAB DAY

STUDY

2B130

SLEEP

LAB

2B131

STAIR #8

2S10

BC353

SLEEP MD

CHIEF

OFFICE

2B138

PFT LAB

2B143

PFT LAB

2B144

EXISTING

PFT LAB

CPET

2B145

WAITING

2B140

Comm.

2B149

Hemodialysis Storage

2B150

Elect.

2B148

Equip.

Closet 2C144A

E.P. Lab 2C144

Storage 2C143

Lockers 2C142

Toilet 2C141

Corridor 2C140

Control 2C145A

Control 2C145B

Scrub 2C145

Office 2C146

Intervention 2C148

Cath. Lab 2C147

Equip.

Closet 2C147A

Soiled Utility 2C149

Clean Utility 2C150

Staff Work 2C151

Endo.

Computers

2C171

Endo. Conf.

2C170

EMS Clos.

2C154

Corridor 2C157

Holding 2C153

Viewing/Fellows 2C155

Exam Room 2C425

Holding 2C423

Passage 2C400D

G.I. Office 2C438

Storage 2C437

ICU

Cleveland

Clinic Resident

2C439

G.U.

Urology Clinic 2C420

Cardiothoracic 2C440

Corridor 2C400A

Reception Alcove 2C133

Control 2C133A

Elevator Lobby 2C400B

Endo/Cath Waiting 2C133B

CORRIDOR

2C100C

PACU

ADMIN.

CENTER

2C323

PASSAGE

2C323A

PACU

TOILET

2C322

PACU

STORAGE

2C328

PACU

SOILED

UTILITY

2C321

Oxygen Storage 2B121A

PACU

MEDS.

2C324

PACU

NOUR.

2C325

Lead Therapist

2B119 Clean Utility

2B120

Administration Center 2B336

Passage 2B330

Meds 2B339 Cubicle 6

2B336A

Cubicle 7 2B336B

Clean Utility 2B338

Soiled 2B337

Seclusion 2 2B333B

Seclusion 3 2B333C

Seclusion 4 2B333D

Seclusion 5 2B333E

Linen 2B338A

Chute 2B335

Seclusion 1 2B333A

Water Processing/ Equip. Rm

2B332A

Toilet 2B334

Water Processing/ Equipment

Room 2B332

Waiting 2B310

PD Training Room 2B321

Office 2B322

IT Closet 2B322A

Corridor 2B320Supply

Room 2B234

Closet 2B324A

Break Room 2B323

Stair #11 2B146

Corridor 2B147

CORRIDOR

2B100B

CORRIDOR

2B100A

Service Elevator Lobby 2C400C

EMS

2C416

Office 2C417

EMS

2C100

Elect.

2C140A

Chute 2C134A

Elect.

2B146A

Corridor 2B480A

Clean Linen 2B412

Procedure 2B413

Exam 8 2B414

Exam 7 2B415

Staff Lounge

2B411

Exam 4 2B420

Exam 3 2B421

Corridor 2B410

Corridor 2B418

Corridor 2B419

Exam 6 2B416

Exam 5 2B417

Exam 2 2B423

Exam 1 2B422

ASMT.

2B432

Office 2B431

Nurse Intake 2B433

Storage 2B435

Corridor 2B430

Waiting 2B434

Recpt.

2B462

Pharmacy Buffer Room 2B461A

Pharmacy Anteroom

2B461 Staff Toilet

2B460

Patient Toilet 2B438

EMS

2B436

Family/ Consult

2B437

Patient Toilet 2B439

Private Infusion 1

2B440

Private Infusion 2

2B453

2B146B

F E

FE

F E

E

E

E

E

PHASE II SCOPE OF WORK BOUNDARY

P H

A S

E

II

S C

O P

E O

F W

O R

K B

O U

N D

A R

Y

P H

A S

E I

I S C

O P

E O

F W

O R

K B

O U

N D

A R

Y

PHASE II SCOPE OF WORK BOUNDARY

SOILED

HOLDING

2B127

MD

OFFICE

2B128A

56'-5" COMMON

PATH OF TRAVEL

OPEN

OFFICE

AREA

2C136

PULM. MD

ATTENDING

OFFICE

2C137

CLEAN O2

STORAGE

2C138

PULM.

ADMIN./CHIEF

OFFICE

2C139

HOME O2

CLINIC

2B123

PULM. NPs

OFFICE

2B124

HOME

O2/CPAP

2B121C

HOME

O2/CPAP

2B121D

HOME

O2/CPAP

2B121E

HOME

OXYGEN

ENTRY

2B121

PAT.

TOILET

2B142

PULM.

FELLOWS

OFFICE

2B141

PCAS/CHECK-IN

2B139

MD

OFFICE

2B137

PAT.

TOILET

2B135A

SLEEP

LAB

2B135

SLEEP

LAB

2B134

PAT.

TOILET

2B134A

CONTROL

STATIONS

2B133

CORRIDOR

2B136

PAT.

TOILET

2B131A

PAT.

TOILET

2B132A

FE

E.

FE

F

PACU

CLEAN

2C330AELEC.

2C327

Stair #9 2C202

PACU EMS

2C234

HAC

2C224

SPACES CLASSIFIED AS "WAITING AND

SIMILAR AREAS" - OPEN TO CORRIDOR.

SHALL BE PROTECTED BY AN AUTOMATIC

FIRE AND SMOKE DETECTION SYSTEM

ALIGN

M

IN

6'-0" CLEAR MINIMUM IN

CORRIDOR MUST BE

MAINTAINED AT ALL TIMES

VIF

GC SHALL LOCATE EAST TEMP. WALL IN

FIELD TO ENSURE THAT EX. DOUBLE

EGRESS DOORS (ON HOLD-OPENS) CAN

FULLY OPEN AS SHOWN

GC ACCESS

DOOR

GC ACCESS

DOOR M

IN

6'-0" CLEAR MINIMUM IN

CORRIDOR MUST BE

MAINTAINED AT ALL TIMES

NOTE: ACCESS FROM STAIR

INTO PROJECT SITE TO BE

CONTROLLED BY THE VA

DASHED LINES INDICATE EXISTING

EGRESS PATHS WHICH SHALL BE

MAINTAINED THROUGHOUT

CONSTRUCTION, TYP.

CARE PROVIDER'S

STATION - PERMITTED TO

BE OPEN TO CORRIDOR

CONSTRUCTION AREACONSTRUCTION AREA

CONSTRUCTION AREA

SPECIAL PHASING NOTE: DOOR REMOVAL AND WALL

DEMOLITION ALONG THIS PORTION OF CORRIDOR WALL SHALL

BE DEFERRED TOWARDS THE END OF PHASE 2 AT A TIME

WHEN THE TEMPORARY CONSTRUCTION PARTITION LOCATED

TO THE WEST CAN BE TAKEN DOWN (SINK REMOVAL CAN BE

DONE PRIOR). THE INTENT IS TO PERMIT SAFE USAGE OF THE

EXISTING DOUBLE EGRESS AND SAFE PASSAGE OF

STRETCHERS, BOTH OF WHICH WOULD BE AFFECTED BY THE

PRESENCE OF TWO (2) CONSTRUCTION PARTITIONS. UPON

REMOVAL OF WEST CONST. PARTITION, GC SHALL SET UP A

NEW PARTITION AROUND THESE DOORS/CORRIDOR WALLS

FOR DEMOLITION & IMPROVEMENTS. MAINTAIN 6'-0" CLEAR IN

CORRIDOR. ALL OTHER ICRA MEASURES SHALL BE ADHERED

TO (BLOCKING OF DIFFUSERS, SMOKE DETECTORS, ETC.)

A N

T E

R O

O M

GC SHALL PERMIT VA

ACCESS INTO ELEC. RM.

DURING CONSTRUCTION

NOTE 1

NOTE 1

NOTE 1

GC ACCESS

DOOR

PACU

CUBICLE 1

2C237A

PACU

CUBICLE 2

2C237B

PACU

CUBICLE 3

2C237C

PACU

CUBICLE 4

2C237D PACU

CUBICLE 6

2C237F

PACU

CUBICLE 5

2C237E

PACU

CUBICLE

2C326E

PACU

CUBICLE

2C326D

PACU

CUBICLE 9

2C326C

PACU

CUBICLE 8

2C326B

PACU

CUBICLE 7

2C326A

PACU

CUBICLE

2C326F

PACU

CUBICLE

2C326G

PACU

CUBICLE

2C326H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: NICK CARROZZA

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

E T

G

DE

I

RET

S

HCRA

I

KACZMAR

STANLEY

NO. 4988

T

E R

S

AT

E

I

T C

J.

O

O

FO

H

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

MECHANICAL/TECH. ENGINEERING:

HEAPY

THE HANNA BUILDING

1422 EUCLID AVE. STE. 1162

CLEVELAND, OH 44115

P. 216.862.5846

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

ELECTRICAL ENGINEERING:

FFE, INC.

110 BOGGS LN, SUITE 170

SPRINGDALE, OH 45246

P. 513.522.0956

HAZ. MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOC., INC.

30628 DETROIT RD. #258

WESTLAKE, OH 44145

P. 216.781.0060

STRUCTURAL ENGINEERING:

THORSON BAKER & ASSOC.

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

BID ISSUE SUBMISSION

C U s e rs \d a v e \D o c u m e n ts \V

A M

P

S le e p

L a b H o m e O x y g e n

R d a k a p la n .r v t

/2

/2

:5

:0

A

M

LS-2.2

SECOND FLOOR LIFE SAFETY PLAN - PHASE II RENOVATE SLEEP AND HOME

OXYGEN AREAS

10701 EAST BLVD. CLEVELAND, OHIO

541-21-104

5.20.22 CJK DAK

SCALE: 3/32" = 1'-0"

SECOND FLOOR LIFE SAFETY PLAN - PHASE II

NORTH

Revisions: Date:

SCHEMATIC DESIGN 9.2.20

DESIGN DEVELOPMENT 11.13.20

65% CDs SUBMISSION 3.26.21

100% CDs SUBMISSION 5.5.21

24 25 26 27 29 30 33 34 35

E

G1

H

J

K

L1

L2

N

P

Q

R

T

V

F

D

C1

G

L3

S

U

23d 24b 25a 26a 28a 30a 38

M

OFFICE

2C137

UPS

ROOM

2C135

Equip.

Closet 2C144A

E.P. Lab 2C144

Storage 2C143

Lockers 2C142

Toilet 2C141

Corridor 2C140

Control 2C145A

Control 2C145B

Scrub 2C145

Office 2C146

Intervention 2C148

Cath. Lab 2C147

Equip.

Closet 2C147A

Soiled Utility 2C149

Clean Utility 2C150

G.I. Office 2C438

ICU

Cleveland

Clinic Resident

2C439

Cardiothoracic 2C440

TELECOMM

2C134

CORRIDOR

2C100C

OPEN

OFFICE

AREA

2C136

PACU

CUBICLE 4

2C237D

PACU

CUBICLE 6

2C237F

PACU

CUBICLE 7

2C326A

PACU

CUBICLE 8

2C326B

PACU

CUBICLE 9

2C326C

PACU

CUBICLE

2C326D

PACU

ADMIN.

CENTER

2C323

PACU

PASSAGE

2C323A

PACU

TOILET

2C322

PACU

CUBICLE

2C326E

PACU

STORAGE

2C328

PACU

CUBICLE

2C326F

PACU

CUBICLE

2C326G

PACU

CUBICLE

2C326H

PACU

SOILED

UTILITY

2C321

OXYGEN

STORAGE

(CLEAN)

2B121A

PACU

MEDS

2C324

PACU

NOUR.

2C325

HOME

OXYGEN

CLINIC

2B119

CLEAN

UTILITY

2B120

OFFICE/CONSULT

2B122

OFFICE/CONSULT

2B123

OFFICE/CONSULT

2B124

ELECT.

ROOM

2B125

ELEC.

ROOM

2B126

RECEPTION/WAITING

2B141

PFT LAB

2B142

TOILET

2B143

PFT LAB

2B144

PFT LAB

(CPET)

2B145

Administration Center 2B336

Passage 2B330

Meds 2B339 Cubicle 6

2B336A

Cubicle 7 2B336B

Clean Utility 2B338

Soiled 2B337

Seclusion 2 2B333B

Seclusion 3 2B333C

Seclusion 4 2B333D

Seclusion 5 2B333E

Linen 2B338A

Chute 2B335

Seclusion 1 2B333A

Water Processing/ Equip. Rm

2B332A

Toilet 2B334

Water Processing/ Equipment

Room 2B332

Closet 2B324A

Stair #11 2B146

CORRIDOR

2B134

SLEEP

LAB

2B133

TOILET/SHOWER

2B133A

OFFICE

2B132

OFFICE

2B131

OFFICE

2B130

SLEEP

LAB

2B135

TOILET/SHOWER

2B135A

OFFICE

2B136

SLEEP

LAB DAY

TESTING

2B137

Stair #8 2B138

OFFICE

2B139

PCAS/CHECK-IN

2B140

OFFICE

2B127

FELLOWS

OFFICE

2B128

OFFICE

2B129

CORRIDOR

2B100B

CORRIDOR

2B100A

CLOSET

2B126A

EMS

2C416

Office 2C417

Elect.

2C140A

Chute 2C134A

CONTROL

STATION

2B134A

ALCOVE

2B143A

Corridor 2B480A

Penthouse 2B480

HOME

OXYGEN

OFFICE

2B121E

HOME

OXYGEN -

EXAM

2B121C

HOME

OXYGEN -

ENTRY

2B121

Staff Lounge

2B411

Exam 3 2B421

Corridor 2B419

Exam 1 2B422

Nurse Intake 2B433

Storage 2B435

Family/ Consult

2B437

OFFICE

2C138

OFFICE

2C139

Elevator Lobby 2C400B

HOME

OXYGEN

OFFICE

2B121D

PHASE II SCOPE OF WORK BOUNDARY

P H

A S

E I

I S C

O P

E O

F W

O R

K B

O U

N D

A R

Y

P H

A S

E I

I S C

O P

E O

F W

O R

K B

O U

N D

A R

Y

EXISTING ROOF

AREA

EXISTING ROOF

AREA

EXISTING ROOF

AREA

EXISTING ROOF

AREA

EXISTING ROOF

AREA

PHASE II SCOPE OF WORK BOUNDARY

EXISTING

ROOF

AREA

PHASE I SCOPE OF WORK BOUNDARY

ELEC.

2C327

PACU

CUBICLE 3

2C237C

PACU

CUBICLE 2

2C237B

PACU

CUBICLE 5

2C237E

PACU

CUBICLE 1

2C237A

PACU EMS

2C234

HAC

2C224

PACU

CLEAN

2C330A

STAIR #9

2C202

HOME

OXYGEN

DEPT.

2" BUILDING

EXPANSION JT.

GENERAL NOTES:

CONSIDER ALL AREAS OWNER-OCCUPIED UNLESS NOTED OTHERWISE.

ALL WALLS ARE DRAWN AND DIMENSIONED TO A 5" NOMINAL WIDTH TYPICAL UNLESS OTHERWISE NOTED.

ALL DIMENSIONS ARE CLEAR DIMENSIONS FROM FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.

CONTRACTOR (I.E. FIRE PROTECTION, HVAC, FIRE ALARM, ELECTRICAL, ETC.) TO INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE

CODES.

PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING CONDITIONS.

WHERE NEW UTILITIES ARE TO BE INSTALLED IN EXISTING PARTITIONS, CONTRACTOR SHALL REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME AND PATCH AND REPAIR WITH NEW TO

MATCH EXISTING CONDITIONS UPON COMPLETION OF UTILITY INSTALLATION.

ALL DAMAGE TO EXISTING AREAS OCCURING AS A RESULT OF CONSTRUCTION SHALL BE REPAIRED AS REQUIRED BY THE CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL, CEILING, AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL BE REPLACED BY THE

CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.

ALL NEW PENETRATIONS IN FIRE-RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF ASSEMBLY AS

REQUIRED.

NEW AND EXISTING FURNITURE SHOWN FOR REFERENCE ONLY. THE OWNER SHALL REMOVE, PRIOR TO CONSTRUCTION, ALL ITEMS THAT THE OWNER DESIRES TO SALVAGE. ALL REMAINING ITEMS INDICATED TO BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR AND LEGALLY DISPOSED OF IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. ALL ITEMS TO REMAIN IN SPACE SHALL BE PROTECTED THROUGHOUT BY THE CONTRACTOR THROUGHOUT CONSTRUCTION. NEW FURNITURE TO BE FURNISHED AND INSTALLED

BY THE OWNER UNLESS NOTED OTHERWISE.

CONTRACTOR SHALL PROVIDE DUST-REMOVAL WALK-OFF MATS (TACKY MAT) AT ALL CONSTRUCTION ENTRY

POINTS.

CONTRACTOR SHALL PROVIDE HEPA FILTERED NEGATIVE AIR MACHINE(S) TO MAINTAIN NEGATIVE PRESSURE IN WORK AREAS ENSURING NO DUST OR FUMES WILL BE TRANSFERRED TO OCCUPIED AREAS.

PROVIDE VISUAL PRESSURE MONITORING DEVICE AT DUST-PROOF BARRICADE TO CONFIRM PRESSURE.

DUST MONITORING SHALL BE BY OWNER. SEE SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS"

ATTACHMENT AND 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS.

ALL DEMOLITION WORK BEING DONE OUTSIDE TEMPORARY PARTITIONS IS TO BE APPROPRIATELY SEALED OFF TO PREVENT THE TRANSMISSION OF DUST AND DEBRIS. WORK SHALL BE DONE TO MINIMIZE DISRUPTION TO VISITORS, PATIENTS, AND STAFF. COORDINATE LOCATION OF BARRIERS WITH OWNER.

THE HOSPITAL'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN THE

PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.

FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.

WHERE NEW DOORS ARE INDICATED IN EXISTING WALL ASSEMBLIES, CUT OPENINGS IN EXISTING WALL.

REFER TO DOOR SCHEDULE FOR DIMENSIONS. PREPARE OPENINGS FOR NEW DOOR, INCLUSIVE OF THE ADDITION OF JAMB AND HEAD STUD REINFORCEMENT (I.E. DOUBLE STUDS, HEADERS) AND PATCH ADJACENT

WALLS TO MATCH EXISTING.

ALL FLOOR, WALL, CEILING, AND MISC. FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION SHALL BE OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND/OR AS REQUIRED BY CODE. ALL EXISTING FIRE-RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING NOT COMPROMISED. FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRESTOPPING, FIRE RATED DOORS, AND MISC. FIRE RESISTIVE

REQUIREMENTS SHALL BE LEFT UNCONCEALED AS REQUIRED FOR INSPECTION BY THE VA COR.

DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR DURING OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF DEBRIS FROM THE PROJECT AREA.

ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE OWNER'S OPERATIONS AS DETERMINED BY THE COR. ALL WORK IN PUBLIC CORRIDORS SHALL BE PERFORMED OFF-HOURS UNLESS

OTHERWISE APPROVED BY THE COR.

EXISTING FLOOR SLABS ARE 2 HR FIRE RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, CONTRACTOR SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE COMPROMISED, AND CONTRACTOR SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD.

CONTRACTOR SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS.

FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, CONTRACTOR SHALL PATCH CONCRETE SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING OR APPROVED 2 HR RATED

INFILL FIRESTOP ASSEMBLY WHEN APPROVED BY THE COR.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

SYMBOL LEGEND:

INDICATES EXISTING DOOR

INDICATES NEW DOOR

EXISTING WALLS TO REMAIN

NEW WALLS

WALLS TO BE REMOVED FULL HEIGHT U.N.O.

DASHED LINES INDICATE ITEMS TO BE DEMOLISHED

HATCHED AREA OUTSIDE OF PROJECT SCOPE.

ACCESS INTO CEILING SPACES MAY OCCUR, REFER

TO MEP DWGS.

FIRE-RATED PLASTIC SHEETING/METAL STUD WALL TEMPORARY PARTITION WALL W/3'-0" X 7'-0"

SCWD DOOR FOR CONTRACTOR ACCESS ONLY. WALL AND DOOR TO BE REMOVED UPON

COMPLETION OF WORK U.N.O. PATCH/REPAIR EXISTING CONDITIONS AS REQUIRED UPON

REMOVAL OF ALL TEMPORARY CONSTRUCTION. REFER TO TEMPORARY CONSTRUCTION BARRIER

DETAIL ON SHEET AS-600. SCHEDULE NOTE: CONSTRUCTION OF TEMPORARY BARRIERS SHALL BE

PERFORMED AFTER NORMAL BUSINESS HOURS UNLESS OTHERWISE APPROVED BY THE COR.

TEMPORARY ZIP WALL PROTECTION TO BE PROVIDED AROUND CONSTRUCTION AREA PER VA

SAFETY STANDARDS. INSTALLATION OF ZIP WALL MAY NEED TO OCCUR AFTER RELOCATION OF

CASEWORK/FURNITURE. GC TO COORDINATE SEQUENCING OF INSTALL WITH COR

GENERAL CONSTRUCTION PARTITION NOTE: WHERE TEMP. CONST. PARTITIONS CONFLICT

W/EX. LIGHTS/DIFFUSER/MEP ITEM LOCATIONS (INDICATED ON CEILING DEMOLITION PLANS), GC

SHALL COORD. W/COR TO EITHER TEMPORARILY REMOVE SUCH ITEMS, OR ADJUST LOCATION

OF CONST. PARTITION ACCORDINGLY TO ALLOW ITEMS TO REMAIN IN PLACE. TEMPORARY

REMOVAL/REINSTALLATION SHALL BE PERFORMED BY THE CONTRACTOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: NICK CARROZZA

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

E T

G

DE

I

RET

S

HCRA

I

KACZMAR

STANLEY

NO. 4988

T

E R

S

AT

E

I

T C

J.

O

O

FO

H

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

MECHANICAL/TECH. ENGINEERING:

HEAPY

THE HANNA BUILDING

1422 EUCLID AVE. STE. 1162

CLEVELAND, OH 44115

P. 216.862.5846

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

ELECTRICAL ENGINEERING:

FFE, INC.

110 BOGGS LN, SUITE 170

SPRINGDALE, OH 45246

P. 513.522.0956

HAZ. MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOC., INC.

30628 DETROIT RD. #258

WESTLAKE, OH 44145

P. 216.781.0060

STRUCTURAL ENGINEERING:

THORSON BAKER & ASSOC.

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

BID ISSUE SUBMISSION

C U s e rs \d a v e \D o c u m e n ts \V

A M

P

S le e p

L a b H o m e O x y g e n

R d a k a p la n .r v t

/2

/2

:5

:3

A

M

AS-X-2.0

SECOND FLOOR EXISTING CONDITIONS PLAN RENOVATE SLEEP AND HOME

OXYGEN AREAS

10701 EAST BLVD. CLEVELAND, OHIO

541-21-104

5.20.22 CJK DAK

SCALE: 3/32" = 1'-0"

2ND FLOOR EXISTING CONDITIONS PLAN

NORTH

Revisions: Date:

SCHEMATIC DESIGN 9.2.20

DESIGN DEVELOPMENT 11.13.20

65% CDs SUBMISSION 3.26.21

100% CDs SUBMISSION 5.5.21

24 25 26 27 29 30 33 34 35 36

EE

G1

H

J

K

L

L1

L2

N

P

Q

R

T

V

F

D

C1

G

L3

S

U

24b 25a 26a 28a 30a 38

M

Equip.

Closet 2C144A

E.P. Lab 2C144

Storage 2C143

Lockers 2C142

Toilet 2C141

Corridor 2C140

Control 2C145A

Control 2C145B

Scrub 2C145

Office 2C146

Intervention 2C148

Cath. Lab 2C147

Equip.

Closet 2C147A

Soiled Utility 2C149

G.I. Office 2C438

ICU

Cleveland

Clinic Resident

2C439

Cardiothoracic 2C440

TELECOMM

2C134

CORRIDOR

2C100C

OPEN

OFFICE

AREA

2C136

Sub-Sterile 2C235

Procedure 2C233

STAIR #9

2C202

PACU EMS

2C234

PACU

CUBICLE 1

2C237A

PACU

CUBICLE 2

2C237B

PACU

CUBICLE 4

2C237D

PACU

CUBICLE 5

2C237E

PACU

CUBICLE 6

2C237F

PACU

CUBICLE 7

2C326A

PACU

CUBICLE 8

2C326B

PACU

CUBICLE 9

2C326C

PACU

CUBICLE

2C326D

PACU

ADMIN.

CENTER

2C323

PACU

PASSAGE

2C323A

PACU

TOILET

2C322

PACU

CUBICLE

2C326E

PACU

STORAGE

2C328

PACU

CUBICLE

2C326F

PACU

CUBICLE

2C326G

PACU

CUBICLE

2C326H

PACU

SOILED

UTILITY

2C321

OXYGEN

STORAGE

(CLEAN)

2B121A

PACU

MEDS

2C324

PACU

NOUR.

2C325

HOME

OXYGEN

CLINIC

2B119

CLEAN

UTILITY

2B120

OFFICE/CONSULT

2B122 OFFICE/CONSULT

2B123

OFFICE/CONSULT

2B124

ELECT.

ROOM

2B125

ELEC.

ROOM

2B126

RECEPTION/WAITING

2B141

PFT LAB

2B142

TOILET

2B143

PFT LAB

2B144

PFT LAB

(CPET)

2B145

Administration Center 2B336

Passage 2B330

Meds 2B339 Cubicle 6

2B336A

Cubicle 7 2B336B

Clean Utility 2B338

Soiled 2B337

Seclusion 2 2B333B

Seclusion 3 2B333C

Seclusion 4 2B333D

Seclusion 5 2B333E

Linen 2B338A

Chute 2B335

Seclusion 1 2B333A

Water Processing/ Equip. Rm

2B332A

Toilet 2B334

Water Processing/ Equipment

Room 2B332

Closet 2B324A

Office 2B325A

Office 2B325B

Office 2B325C

Stair #11 2B146

CORRIDOR

2B134

SLEEP

LAB

2B133

TOILET/SHOWER

2B133A

OFFICE

2B132

OFFICE

2B131

OFFICE

2B130

SLEEP

LAB

2B135

TOILET/SHOWER

2B135A

OFFICE

2B136

SLEEP

LAB DAY

TESTING

2B137

Stair #8 2B138

OFFICE

2B139

PCAS/CHECK-IN

2B140

OFFICE

2B127

FELLOWS

OFFICE

2B128

OFFICE

2B129

CORRIDOR

2B100B

CORRIDOR

2B100A

HAC

2C224

CLOSET

2B126A

EMS

2C416

Office 2C417

Elect.

2C140A

Chute 2C134A

CONTROL

STATION

2B134A

ALCOVE

2B143A

Corridor 2B480A

HOME

OXYGEN

OFFICE

2B121E

HOME

OXYGEN -

EXAM

2B121C

HOME

OXYGEN -

ENTRY

2B121

Staff Lounge

2B411

Exam 3 2B421

Corridor 2B419

Exam 1 2B422

Storage 2B435

Family/ Consult

2B437

Corridor 2500H

OR-7

General

OR-6

General

Electric

EMS

Anesthesia Storage

EMS

2508A

Sub Sterile

JC

2B201

Rehab Office 2B203

Psychology Office 2B204

Psychology Office 2B206

Psychology Office 2B207

Psychology Office 2B209

Surgical Lounge

2B211

Corridor 2B200C

CORRIDOR

2C100C

OFFICE

2C137

OFFICE

2C138

OFFICE

2C139

UPS

ROOM

2C135

Penthouse 2B480

PHASE II SCOPE OF WORK BOUNDARY

P H

A S

E I

I S C

O P

E O

F W

O R

K B

O U

N D

A R

Y

P H

A S

E I

I S C

O P

E O

F W

O R

K B

O U

N D

A R

Y

PHASE II SCOPE OF WORK BOUNDARY

HOME

OXYGEN

OFFICE

2B121D

S

S

S

S

S

S

SD

W

W

W

W W W

W

W

W

S

2" BUILDING

EXPANSION JOINT

S

PHASE I SCOPE OF WORK BOUNDARY

PACU

CLEAN

2C330A

ELEC.

2C327

S

PACU

CUBICLE 3

2C237C

S

S

S

S

W

W

W

GENERAL NOTES:

CONSIDER ALL AREAS OWNER-OCCUPIED UNLESS NOTED OTHERWISE.

ALL WALLS ARE DRAWN AND DIMENSIONED TO A 5" NOMINAL WIDTH TYPICAL UNLESS OTHERWISE NOTED.

ALL DIMENSIONS ARE CLEAR DIMENSIONS FROM FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.

CONTRACTOR (I.E. FIRE PROTECTION, HVAC, FIRE ALARM, ELECTRICAL, ETC.) TO INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE

CODES.

PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING CONDITIONS.

WHERE NEW UTILITIES ARE TO BE INSTALLED IN EXISTING PARTITIONS, CONTRACTOR SHALL REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME AND PATCH AND REPAIR WITH NEW TO

MATCH EXISTING CONDITIONS UPON COMPLETION OF UTILITY INSTALLATION.

ALL DAMAGE TO EXISTING AREAS OCCURING AS A RESULT OF CONSTRUCTION SHALL BE REPAIRED AS REQUIRED BY THE CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL, CEILING, AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL BE REPLACED BY THE

CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.

ALL NEW PENETRATIONS IN FIRE-RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF ASSEMBLY AS

REQUIRED.

NEW AND EXISTING FURNITURE SHOWN FOR REFERENCE ONLY. THE OWNER SHALL REMOVE, PRIOR TO CONSTRUCTION, ALL ITEMS THAT THE OWNER DESIRES TO SALVAGE. ALL REMAINING ITEMS INDICATED TO BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR AND LEGALLY DISPOSED OF IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. ALL ITEMS TO REMAIN IN SPACE SHALL BE PROTECTED THROUGHOUT BY THE CONTRACTOR THROUGHOUT CONSTRUCTION. NEW FURNITURE TO BE FURNISHED AND INSTALLED

BY THE OWNER UNLESS NOTED OTHERWISE.

CONTRACTOR SHALL PROVIDE DUST-REMOVAL WALK-OFF MATS (TACKY MAT) AT ALL CONSTRUCTION ENTRY

POINTS.

CONTRACTOR SHALL PROVIDE HEPA FILTERED NEGATIVE AIR MACHINE(S) TO MAINTAIN NEGATIVE PRESSURE IN WORK AREAS ENSURING NO DUST OR FUMES WILL BE TRANSFERRED TO OCCUPIED AREAS.

PROVIDE VISUAL PRESSURE MONITORING DEVICE AT DUST-PROOF BARRICADE TO CONFIRM PRESSURE.

DUST MONITORING SHALL BE BY OWNER. SEE SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS"

ATTACHMENT AND 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS.

ALL DEMOLITION WORK BEING DONE OUTSIDE TEMPORARY PARTITIONS IS TO BE APPROPRIATELY SEALED OFF TO PREVENT THE TRANSMISSION OF DUST AND DEBRIS. WORK SHALL BE DONE TO MINIMIZE DISRUPTION TO VISITORS, PATIENTS, AND STAFF. COORDINATE LOCATION OF BARRIERS WITH OWNER.

THE HOSPITAL'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN THE

PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.

FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.

WHERE NEW DOORS ARE INDICATED IN EXISTING WALL ASSEMBLIES, CUT OPENINGS IN EXISTING WALL.

REFER TO DOOR SCHEDULE FOR DIMENSIONS. PREPARE OPENINGS FOR NEW DOOR, INCLUSIVE OF THE ADDITION OF JAMB AND HEAD STUD REINFORCEMENT (I.E. DOUBLE STUDS, HEADERS) AND PATCH ADJACENT

WALLS TO MATCH EXISTING.

ALL FLOOR, WALL, CEILING, AND MISC. FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION SHALL BE OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND/OR AS REQUIRED BY CODE. ALL EXISTING FIRE-RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING NOT COMPROMISED. FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRESTOPPING, FIRE RATED DOORS, AND MISC. FIRE RESISTIVE

REQUIREMENTS SHALL BE LEFT UNCONCEALED AS REQUIRED FOR INSPECTION BY THE VA COR.

DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR DURING OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF DEBRIS FROM THE PROJECT AREA.

ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE OWNER'S OPERATIONS AS DETERMINED BY THE COR. ALL WORK IN PUBLIC CORRIDORS SHALL BE PERFORMED OFF-HOURS UNLESS

OTHERWISE APPROVED BY THE COR.

EXISTING FLOOR SLABS ARE 2 HR FIRE RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, CONTRACTOR SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE COMPROMISED, AND CONTRACTOR SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD.

CONTRACTOR SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS.

FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, CONTRACTOR SHALL PATCH CONCRETE SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING OR APPROVED 2 HR RATED

INFILL FIRESTOP ASSEMBLY WHEN APPROVED BY THE COR.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

CEILING SYMBOL LEGEND:

EXISTING 2 X 2

CEILING TILE

AREAS TO REMAIN

EXISTING 2 X 4

CEILING TILE

AREAS TO REMAIN

SCOPE OF WORK

AREA

GYPSUM BOARD

CEILING/SOFFIT -

PAINTED FINISH

2 X 4 LIGHT

FIXTURE

2 X 2 LIGHT FIXTURE

RECESSED CAN

LIGHT FIXTURE

RETURN AIR

DIFFUSERS

SUPPLY AIR DIFFUSERS

SECURITY CAMERA

S RECESSED SPEAKER

W WIRELESS ACCESS POINT

SD SMOKE DETECTOR

GENERAL NOTE: ACCESS INTO CEILINGS OUTSIDE OF TEMPORARY CONSTRUCTION BARRIERS AS A PART OF A CONSTRUCTION PHASE MAY OCCUR. REFER TO MEP DRAWINGS FOR ABOVE-CEILING DEMOLITION THAT OCCURS OUTSIDE THE TEMPORARY CONSTRUCTION BARRIER EXTENTS. CONTRACTOR SHALL PROVIDE TEMPORARY PROTECTION MEASURES IN SUCH AREAS TO PROTECT EXISTING CONDITIONS. COORD. REQUIREMENTS W/VA

COR

CONTINUOUS LINEAR COVE

LIGHT

CORRIDOR WALL

SCONCE

CLG. MTD. PATIENT BED

LIFT - FURNISHED/INSTALLED

BY VA. GC TO PROVIDE

JUNCTION BOX ONLY - SEE

ELEC. DWGS.

WALL-MTD. SINK LIGHT

FIXTURE

NURSE CALL ALERT LIGHT

WALL-MTD. TV ON SWING-

ARM MOUNT,

FURNISHED/INSTALLED BY

VA. CONTRACTOR TO

PROVIDE SOLID IN-WALL

BLOCKING BETWEEN 6'-0"

& 7'-0" AFF

U

V CLG. MOUNTED UV LIGHT

FIXTURE, FURNISHED BY

VA, INSTALLED BY GC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: NICK CARROZZA

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Louis Stokes Cleveland

VA Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

E T

G

DE

I

RET

S

HCRA

I

KACZMAR

STANLEY

NO. 4988

T

E R

S

AT

E

I

T C

J.

O

O

FO

H

1468 WEST 9TH STREET #400

CLEVELAND, OH 44113

P. 216.687.1555 F. 216.687.1558

MECHANICAL/TECH. ENGINEERING:

HEAPY

THE HANNA BUILDING

1422 EUCLID AVE. STE. 1162

CLEVELAND, OH 44115

P. 216.862.5846

COST ESTIMATING:

MCGUINESS UNLIMITED, INC.

15724 STILLWOOD AVE.

CLEVELAND, OH 44111

P. 440.667.5120

ELECTRICAL ENGINEERING:

FFE, INC.

110 BOGGS LN, SUITE 170

SPRINGDALE, OH 45246

P. 513.522.0956

HAZ. MATERIALS

ASSESSMENT:

STEPHEN J. SEBESTA &

ASSOC., INC.

30628 DETROIT RD. #258

WESTLAKE, OH 44145

P. 216.781.0060

STRUCTURAL ENGINEERING:

THORSON BAKER & ASSOC.

3030 WEST STREETSBORO RD.

RICHFIELD, OH 44286

P. 330.659.6688

BID ISSUE SUBMISSION

C U s e rs \d a v e \D o c u m e n ts \V

A M

P

S le e p

L a b H o m e O x y g e n

R d a k a p la n .r v t

/2

/2

:5

:4

A

M

AS-XC-2.0

SECOND FLOOR EXISTING REFLECTED

CEILING PLAN

RENOVATE SLEEP AND HOME

OXYGEN AREAS

10701 EAST BLVD. CLEVELAND, OHIO

541-21-104

5.20.22 CJK DAK

SCALE: 3/32" = 1'-0"

2ND FLOOR EXISTING REFLECTED CEILING PLAN

NORTH

Revisions: Date:

SCHEMATIC DESIGN 9.2.20

DESIGN DEVELOPMENT 11.13.20

65% CDs SUBMISSION 3.26.21

100% CDs SUBMISSION 5.5.21

27 29 30 33 34

G1

H

J

K

F

D

26a 28a 30a

H

T

1'-1"

@ 7'-2" HT.

3'-10"

NO DEMO

SCOPE

HOME

OXYGEN

CLINIC

2B119

25 26 27 29 30

K

L1

30a

CLOSET

2B126A

CORRIDOR

2B100B

1A

1A

2 2

1A

3 3

M

IN

GC ACCESS

DOOR

SEE SHEET AS-D-2.2

ALIGN

55'-9" +/-

GC SHALL LOCATE EAST TEMP. WALL IN

FIELD TO ENSURE THAT EX. DOUBLE

EGRESS DOORS (ON HOLD-OPENS) CAN

FULLY OPEN AS SHOWN

2 2

MAINTAIN EX. PLUMBING

ENCLOSURE

ENTIRE

ROOM

ENTIRE

ROOM

ENTIRE

ROOM

ENTIRE

ROOM

ENTIRE

ROOM

ENTIRE

ROOM

ENTIRE

ROOM

7'-2" HT.

4'-4" 9"

7'-2" HT.

3'-4"1

2"

SPECIAL PHASING NOTE: DOOR

REMOVAL AND WALL DEMOLITION

ALONG THIS PORTION OF

CORRIDOR WALL SHALL BE

DEFERRED TOWARDS THE END OF

PHASE 2 AT A TIME WHEN THE

TEMPORARY CONSTRUCTION

PARTITION LOCATED TO THE WEST

CAN BE TAKEN DOWN (SINK

REMOVAL CAN BE DONE PRIOR).

THE INTENT IS TO PERMIT SAFE

USAGE OF THE EXISTING DOUBLE

EGRESS AND SAFE PASSAGE OF

STRETCHERS, BOTH OF WHICH

WOULD BE AFFECTED BY THE

PRESENCE OF TWO (2)

CONSTRUCTION PARTITIONS. UPON

REMOVAL OF WEST CONST.

PARTITION, GC SHALL SET UP A NEW

PARTITION AROUND THESE

DOORS/CORRIDOR WALLS FOR

DEMOLITION & IMPROVEMENTS.

MAINTAIN…