Addendum 06-04.05.21.pdf

PDF 469 KB Posted

Attached to
Z1DA--Repair Exterior Walls and Replace Windows - 539-20-103
Solicitation number
36C25021B0012
Issued by

About this file

This document includes an addendum to a solicitation for architectural and engineering services to repair exterior walls and replace windows at the Cincinnati VA Medical Center, as well as the related federal contract opportunity posting. The addendum provides responses to bidder questions, requests for information, and product equivalency requests pertaining to the scope of work, specifications, and drawings. It also details masonry and window replacement requirements. The federal contract opportunity posting specifies this is an invitation for bids for project number 539-20-103 to complete repairs and window replacements at the Cincinnati VA Medical Center with an estimated value between $5 million and $10 million. The solicitation number is 36C25021B0012 and bids are due within 30-45 days of the January 14, 2021 anticipated posting date. The contractor will have 550 days from notice to proceed to complete all work. This opportunity is set aside for service-disabled veteran-owned small businesses.

View the file

Other files

File Type Posted
36C25021B0012 0008.docx DOCX document
Addendum 08-04.14.21.pdf PDF
36C25021B0012 0007.docx DOCX document
36C25021B0012 0006.pdf PDF
Attachment 3 -Contractor EMR Certification Form.pdf PDF
Addendum 05-03.24.21.pdf PDF
36C25021B0012 0005.docx DOCX document
36C25021B0012 0004.docx DOCX document
36C25021B0012 0003.docx DOCX document
Site VIsit Sign-in.pdf PDF
36C25021B0012 0002.docx DOCX document
36C25021B0012 0001.docx DOCX document
Attachment 4 - EMR Attachment.pdf PDF
Attachment 2-Drawings.pdf PDF
Attachment 5-DBA-WD-OH020210082.pdf PDF
Attachment 1-Specifications.pdf PDF
36C25021B0012_1.docx DOCX document
Attachment 3 - RFI Form.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A/E Repair Exterior Walls and Replace Windows

Cincinnati VAMC – Project #539-20-103

Addendum No. 6

April 5, 2021

Addendum No. 6

Cincinnati VAMC – Proj. #539-20-103

3200 Vine Street

Cincinnati, OH 45220

This Addendum supplements and amends the original Drawings and Specifications for the above referenced project. This Addendum shall be forwarded to all Prime Bidders and all appropriate building code authorities. This Addendum shall be taken into account in the preparation of bids and shall become a part of the Contract Documents.

Receipt of this Addendum must be acknowledged on the Bid Form.

This addendum consists of the following items:

General

1. Responses to bidder questions from March 4, 2021 Pre-Bid Walk-thru.

2. Responses to “Requests for Information” (RFI’s).

End of Addendum No. 6

Department of Veterans Affairs Medical Center, 3200 Vine Street, Cincinnati, Ohio

Repair Exterior Walls Replace Windows Project 539-20-103

03/04/21 PRE-BID Questions & Answers

1. Q?: Please clarify Unit Costs related to masonry?

A: Masonry work includes lump sum and unit cost work on each elevation. Lump sum work is generally replacement of most window lintels and replacement of the sealant joints at the ledge angles. Refer to the drawings for the locations and additional work. Unit cost work will be located by THP during the review of the elevation from the swing stage or aerial platform. THP and the contractor will document the location and size of each repair and this will be the basis for payment from the allowance quantities.

2. Q?: Regarding Detail 4, Sheet S200 Ledge Angle Sealant Repair; Hex note No. 1 designates the brick as “new brick”. Where does this occur?

A: Revise hex note no. 1 to read “Existing brick.”

3. Q?: How much time will THP will be on a swing stage. Will THP need to ride the lift all day?

A: THP anticipates 1-2 hours to survey each drop with the contractor. Depending on findings some drops may take longer. Follow up observation trips will occur during construction with similar time need per drop.

End of PRE-BID Questions & Answers

Department of Veterans Affairs Medical Center, 3200 Vine Street, Cincinnati, Ohio

Repair Exterior Walls Replace Windows Project 539-20-103

04/05/21 - ADDENDUM #6

RFI’s and Responses

1. Q?: We are requesting that the Govt add a second site visit due to the recent Change from 3/10 to

3/4.

A: A second Site Visit was scheduled for March 23, 2021 per Amendment #4.

2. Q?: Is FAR 52.229-3 Federal, State, and local taxes applicable to this project?

A: All applicable clauses are listed in the solicitation.

3. Q?: Is there going to be ICRA requirements inside of each room where windows are being replaced? If so, will these be required to be hard barrier or zip poles with plastic?

A: Per Spec 013526; 1.12, B; the primary project scope area for this project is: Class II, however, work outside the primary project scope area may vary. Where dust control is the only hazard, and an agreement is reached with the COR and Medical Center, provide airtight plastic barriers that extends from the floor to ceiling. Seams must be sealed with duct tape to prevent dust and debris from escaping. (Reference Spec 013526; 1.2, C,2). Coordination will be necessary between the

Contractor and the COR to phase work to avoid disrupting occupied rooms.

4. Q?: On Drawing page S200 Detail 4, it states to replace the brick course above and below. At the site visit it was discussed that was wrong and no brick is to be replaced. Please confirm whether we are to replace these courses or not.

A: Regarding Detail 4, Sheet S200 Ledge Angle Sealant Repair, revise hex note no. 1 to read

“Existing brick.” Refer to drawing revisions per Addendum #5.

5. Q?: Is there a standard of Roof Protection that is going to be required from the VA?

A: The VAMC does not have specific roof protection guidelines. The contractor is responsible for providing protection. Construction activities are not to puncture, tear, or damage the roof system, including flashing. Damaged roof areas will be repaired at the VAMC direction and manufacturer requirements at the contractor’s expense. Any damaged roofs under warranty will require repairs that maintain the warranty.

6. Q?: Can the VA provide the Dimensions of the RTU's that will need to have Filters installed?

A: During construction, the Contractor shall provide protection of the outside air intakes of RTU’s and intake building louvers adjacent to masonry work using MERV 8 air filter media rolls. Provide protection to include total OA quantity per attached VA Building 1 – Filters & OA Protection calculations. Replacement of internal RTU filters is not required as part of project scope.

7. Q?: Reference Spec 088000; 1.4, C & 2.5, A: For other VA facility window replacement projects we have been involved with, the blast-resistant windows have been designed to the minimum design provisions of 6.2.2 of the VA Physical Security Design Manual (2015) rather than for a specific threat. Will that be acceptable for this project?

A: This project shall comply with the minimal design requirements of Section 6.2.2 of the Physical

Security Design Manual for Mission Critical Facilities. This section addresses the basic requirements for new fenestration in existing buildings. The new windows shall have standard frames, mullions, and anchorage with laminated glass for inner lites of IGU’s. Consequently, requirements for submission of specific Blast Loading calculations confirming compliance with

ASTM F1642/F2912 can be disregarded. Reference Spec Section 088000 - Paragraphs 2.5-A; and

3.9-A11, B11, and C11. Insulated Laminated Glass assemblies shall otherwise adhere to the

Contract documents and Specifications. Refer to Spec revisions per Addendum #5.

8. Q?: The Attachment 4 EMR Attachment included in the solicitation documents references a different solicitation number. Can you please clarify if we submit this form or if a new one will be issued?

A: VA to issue revised form as part of this Addendum.

9. Q?: Can a second site visit be set up to gain access to the roofs above the work area? If roof access cannot be granted, are there proper anchorage points on roof for safety lines and swing stage equipment.

A: Yes. See response to RFI #1.

10. Q?: Reference Solicitation Section 52.236-27: Can you send us a copy of the minutes/agenda for the Pre-Bid Meeting as well as a copy of the Attendance List?

A: The sign-in list of attendees to the 3/4/21 Pre-Bid Site Visit was posted to beta.SAM.gov online page. Reference uploaded Amendment #3 documents “36C25021B0012+0003” and

“Site+VIsit+Sign-in”. A list of Questions and Answers from the 3/4/21 Pre-Bid Site Visit are included herein.

11. Q?: Product Equivalency Request:

Reference: Spec 085113 – 2.3, A – Fixed Aluminum Exterior Windows

Basis-of-Design: Wausau Window and Wall Systems; 2250i-XLT & 3250i-XLT INVent Series

Proposed Equivalent: Winco Windows; Series 8325F

A: Proposed product is not an approved equal. Justification as follows:

• All windows shall be provided from one manufacturer per Spec 085113 – 2.3; C. Per response to RFI #12 (below), this manufacturer’s Operable Aluminum Interior Psychiatric

Window series is not an approved equal.

12. Q?: Product Equivalency Request:

Reference: Spec 085113 – 2.3, B – Operable Aluminum Interior Psychiatric Windows

Basis-of-Design: Wausau Window and Wall Systems; 2187-DT S.E.A.L Series

Proposed Equivalent: Winco Windows; Series 8800

A: Proposed product is not an approved equal. Justification as follows:

• Manufacturer’s product literature does not indicate this window system complies with

2,000 ft.-lbs. Human Impact force using the scheduled laminated glass access panel as required per Spec 085113 – 2.1; A, 2.

• Design intent is for consistent exterior sight lines on exterior side of all new window units.

It’s not made clear whether this request shall use 2 different window series (either 8325F or 4”-8800 series) or a 8325F / 2-1/4” 8800 series “combination”. These 2 series appear to have slightly different exterior sightlines (2-1/4” vs. 3”). The details provided do not indicate a “combination” assembly is possible.

13. Q?: Reference Spec 085113; 2.5, A, 1, a2: Based on the weight of access panels in the behavioral care windows being beyond OSHA lifting limits for two people, you may consider requiring concealed butt hinges to allow the access panels to swing open rather than lift-out for cleaning and maintenance.

• Hardware:

1. Concealed Hinges at Fixed Lite Access Panels

a. Provide two concealed extruded aluminum “walk-around” butt hinges with stainless steel pins. Provide three hinges on in-swing casement units over 4’-0” in height.

• Will you require access panel operation to meet OSHA lifting requirements?

A: Concealed hinges on interior access panels of Mental Health units are required if weight exceeds OSHA lifting requirements.

14. Q?: Is there anchor points on each roof for swing staging? Can we be provided a drawing laying out all anchor points?

A: No drawings are available of anchor points on existing roofs. Roof access was provided to bidders on March 23 to assess existing conditions for swing stage anchoring per Amendment #4.

15. Q?: Will there be a location on campus for a dumpster?

A: There are only two spots available for all contractors working at the medical campus. The contractor will need to coordinate appropriately with the VA COR.

16. Q?: Reference Spec 013100.01; 1.4, A: Please Confirm the use of Oracle Primavera Submittal

Exchange be a requirement for this project?

A: Per Sub-Paragraph 1.4, A1: Provide Oracle Primavera Submittal Exchange or equivalent web-based project management software. Project Management Software shall include features per

Sub-Paragraph 1.4, A2.

17. Q?: Reference Amendment 4: Will there be interior access available during the second site visit on March 23, 2021?

A: Due to current VAMC health protocols, interior access was limited and only a section of the 8th floor was available during the second site visit.

18. Q?: Will the freight elevator be available to work crews for the movement of materials to the separate floors?

A: Refer to Spec Section 010000 – General Conditions; Sub-paragraph 1.14: “Temporary Use of

Existing Elevators”.

19. Q?: What is the weight capacity of the freight elevator?

A: Weight capacity on freight elevators is 4,500 lbs.

20. Q?: The window that we were shown during the 2nd pre-bid walk was clear of any obstructions

(radiators, furniture, equipment, etc.). Is that indicative of all windows in this project?

A: Window replacements occur in rooms and spaces with varying levels of interior access. Refer to Spec Section 010000 – General Conditions; Sub-paragraph 1.8, A3 – “Disposal and Retention” and sub-paragraph 1.18: “Relocated Items”.

21. Q?: Please verify security - background investigation process for this project. Will this project require SAC or NACI background checks?

A: The VAMC will require a SAC (Special Agreement Check) where an individual’s fingerprints are electronically submitted to OPM by an agency to run a criminal history check

End of ADDENDUM #6 -RFI’s

Ref. Addendum #6, RFI #6

Unit # Unit Location Area Served Stage Filter Size Qty Filter Model Comments

AHU-1 9th Flr. PH East Wing Pre 24x12x22 4 Hi Flo MV9

(Outside) OA 2sf x 4 = 8sf MERV 8

Pre 24x24x22 28 Hi Flo MV9

OA 4sf x 28 =112sf MERV 8

AHU-2 SE Elevator East Wing Pre 24x24x22 20 Hi Flo MV9

PH 10th Flr. OA 4sf x 20 = 80sf MERV 8

AHU-3 NE Elevator East Wing Pre 24x24x22 20 Hi Flo MV9

PH 10th Flr. SPD OA 4sf x 20 = 80sf MERV 8

AHU-4 3rd Flr. Roof ER Pre 24x24x15 10 Hi Flo 12 pkt MV9 through SICU by A394 OA 4sf x 10 = 40sf MERV 8

AHU-5 3rd Flr. Roof NICU Pre 24x24x4 10 Farr 30/30 through SICU SICU OA 4sf x 10 = 40sf MERV 8

Room A394

AHU-7 Rooftop Wing Final 24x24x15 6 Hi Flo ES MV14

OA 4sf x 6 = 24sf MERV 8

Final 24x12x15 2 Hi Flo ES MV14

OA 2sf x 2 = 4sf MERV 8

AHU-8 Rooftop Wing Final 20x24x15 6 Hi Flo ES MV14

OA 3.5sf x 6 = 21sf MERV 8

AHU-9 4th Flr O/S SPS Pre 24x24x22 4 Hi Flo ES MV14

OA 4sf x 4 = 16sf MERV 8

AHU-10 5th Flr Roof Patient Care Pre 24x20x2 6 Farr 30/30

OA 3.5sf x 6 = 21sf MERV 8

AHU-11 5th Flr PH Microbiology Final 24x24x2 2 30/30 Dual 9

OA 4sf x 2 = 8sf MERV 8

AHU-12 5th Flr PH Research Pre 12x24x2 12 Dual 9 access from 4th Floor OA 2sf x 12 = 24sf MERV 8

4th Flr Stairs Pre 20x24x2 4 Dual 9 reverse

SW4 OA 3.5sf x 4 = 14sf MERV 8

AHU-13 4th Flr O/S 3rd Floor Pre 16x25x2 10 Farr 30/30

Rm B-408 OA 3sf x 10 = 30sf MERV 8

Kitchen Pre 16x20x2 10 Farr 30/30

OA 2.5sf x 10 = 25sf MERV 8

AHU-14 2nd Flr Roof Kitchen Pre 12x24x6 1 Rigaflo MV9

Rm B210 OA 2sf x 1 = 2sf MERV 8

Pre 24x24x6 1 Rigaflo MV9

OA 4sf x 1 = 4sf MERV 8

CINCINNATI VA HOSPITAL BLDG 1 - Filters & OA Protection

Cincinnati VAMC – Project #539-20-103

AHU-15 2nd Flr Roof Dining Rm Pre 16x20x2 20 MicroShield MV15

Rm B210 OA 2.5sf x 20 = 50sf MERV 8

AHU-16 1st Floor Gift Shop Pre 16x20x2 4 Farr 30/30

Gift Shop OA 2.5sf x 4 = 10sf MERV 8

Pre 14x20x2 2 Farr 30/30

OA 2sf x 2 = 4sf MERV 8

AHU-17 Basement New Mod Pre 12x24x15 4 Hi Flo ES MV14 by Rm C013 OA 2sf x 4 = 8sf MERV 8

Pre 20x24x15 8 Hi Flo ES MV14

OA 3.5sf x 8 = 28sf MERV 8

AHU-19 Bsmt O/S Morgue Pre 24x24x22 1 Hi Flo ES MV14

Rm A5D OA 4sf x 1 = 4sf MERV 8

Pre 24x20x22 1 Hi Flo ES MV14

OA 3.5sf x 1 = 3.5sf MERV 8

Pre 24x12x22 1 Hi Flo ES MV14

OA 2sf x 1 = 2sf MERV 8

AHU-33 Bldg 1 Rm A035 Frame Rm Pre 16x24x2 8 Farr 30/30

OA 3sf x 8 = 24sf MERV 8

AHU-37 Elev. PH 10th Elevator Rm Pre 24x24x2 2 Farr 30/30

OA 4sf x 2 = 8sf MERV 8

AHU-40 MRI Roof MRI Final 24x24x22 9 Hi Flo ES MV14

Rm A337 OA 4sf x 9 = 36sf MERV 8

AHU-41 MRI Roof MRI Pre 24x24x2 4 30/30 Dual 9

OA 4sf x 4 = 16sf MERV 8

Pre 24x20x2 2 30/30 Dual 9

OA 3.5sf x 2 = 7sf MERV 8

Carbon 24x24x12 4 CitySorb

OA 4sf x 4 = 16sf MERV 8

Carbon 24x20x12 2 CitySorb

OA 4sf x 4 = 16sf MERV 8

AHU-42 3rd Flr MR Pre 20x24x2 6 Pleat

MRI Bldg OA 3.5sf x 6 = 21sf MERV 8

By Rm A305 Pre 12x24x2 3 Pleat

OA 2sf x 3 = 6sf MERV 8

AHU-43 3rd Flr MR Final 24x24x15 10 Hi Flo ES MV14

MRI Bldg OA 4sf x 10 = 40sf MERV 8

By Rm A305 Final 12x24x15 5 Hi Flo ES MV14

OA 2sf x 5 = 10sf MERV 8

AHU-44 5th Flr Roof Pre 16x20x2 8 30/30-AP III

Penthouse OA 2.5sf x 8 = 20sf MERV 8

Trac U. Rooftop Trac Office Pre 20x30x2 2 Farr 30/30

OA 4.5sf x 2 = 9sf MERV 8

RTU-1 10th Flr Roof Elev. Rm Pre 16x20x2 4 Farr 30/30

OA 2.5sf x 4 = 10sf MERV 8

RTU-2 10th Flr Roof Elev. Rm Pre 16x20x2 4 Farr 30/30

OA 2.5sf x 4 = 10sf MERV 8

Intake Electrical Rm Intake N Pre 24x24x2 8 Farr 30/30

OA 4sf x 8 = 32sf MERV 8

Intake S Pre 24x24x2 8 Farr 30/30

OA 4sf x 8 = 32sf MERV 8

Intake E Pre 24x24x2 6 Farr 30/30

OA 4sf x 6 = 24sf MERV 8

Liebert IT Room Liebert Pre 25x16x4 3 Farr 30/30

OA 3sf x 3 = 9sf MERV 8

Liebert IT Room Liebert Pre 25x20x4 6 Farr 30/30

OA 3.5sf x 6 = 21sf MERV 8

LPFU-1 2nd Flr Rf Rm A2012 Pre 24x24x2 2 Farr 30/30

O/S 3rd Flr OA 4sf x 2 = 8sf MERV 8 by AHU-41 Rm A214 HEPA 24x24x12A 2 Absolute XH

OA 4sf x 2 = 8sf MERV 8

OA Louver 4th Flr Mech A3002 OA 63"x63"= 27.6sf MERV 8

North Façade

East of Stair 11

OA Louver 3rd Flr Mech A3002 OA 60"x72" = 30sf MERV 8

Intake Areaway

OA Louver 3rd Flr Mech A3002 OA 120"x96" = 80sf MERV 8

Intake Areaway