36C25019B0060-0001002.pdf
PDF Posted
- Solicitation number
- 36C25019B0060
About this file
This is a solicitation for a construction project to replace two air handling units at the Louis Stokes Cleveland VA Medical Center in Cleveland, Ohio. The project scope includes replacing AHUs 17 and 18, associated ductwork and shafts, with a project magnitude between $5-10 million. The NAICS code is 238220 and it is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. The solicitation will be issued on January 14, 2020 via FBO.gov with a bid opening approximately 30 days later. Interested parties must register at VIP.vetbiz.gov, SAM.gov and be verified as an SDVOSB. The contractor must perform a minimum of 25% of construction work and project duration shall not exceed 665 calendar days from NTP. Bonds will be required and there will be a mandatory site visit. Questions must be submitted in writing by the deadline stated in the solicitation.
36C25019B0060 0001 DRAWINGS - PACKAGE 3.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25019B0060-0002002.pdf | ||
| 36C25019B0060-0002000.docx | DOCX document | |
| 36C25019B0060-0002005.docx | DOCX document | |
| 36C25019B0060-0002004.pdf | ||
| 36C25019B0060-0002006.docx | DOCX document | |
| 36C25019B0060-0002001.docx | DOCX document | |
| 36C25019B0060-0002003.docx | DOCX document | |
| 36C25019B0060-0001000.pdf | ||
| 36C25019B0060-0001001.pdf | ||
| 36C25019B0060-023.docx | DOCX document | |
| 36C25019B0060-024.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JJ
KK
21 23
K1K1
K2K2
H1H1
Z3 Z31
1 RH-1
RH-2
X-RELIEF AIR
HOOD
X-AIR COOLED
CHILLER
X-EXHAUST FAN
X-EXHAUST FAN
X-RELIEF AIR
HOOD
M0.19
M0.19
X-EXHAUST FAN
X-38x38 DN X - 38 x 38 EA
X - 38 x 38 EA
X-AHU-19
X-OA-1
M0.19
M0.19
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:3
:1
P M
2-M-RMB
PARTIAL SEVENTH FLOOR PENTHOUSE
ROOF DUCTWORK PLAN - PHASE 2
JXCDAD08/09/2019
N
# CODED NOTESGENERAL NOTES
1 INSTALL NEW RELIEF AIR HOOD WITH ROOF CURB. REFER TO 7TH FLOOR PENTHOUSE DUCTWORK PLAN FOR CONTINUOUS OF RELIEF AIR DUCTWORK. REFER TO RELIEF AIR HOOD ROOF CURB DETAIL.
1.
2.
GENERAL CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF NEW ROOF CURBS AS NOT TO VOID
EXISTING ROOF WARRANTY. GC SHALL USE FACILITY APPROVED ROOF CONTRACTOR. GC TO
COORDINATE WITH MECHANICAL CONTRACTOR FOR NEW ROOF CURB LOCATIONS.
ALL EXTERIOR DUCTWORK SHALL BE INSULATED WITH 2" THICK POLYISOCYANURATE CLOSED CELL RIGID INSULATION. ON TOP SURFACE, PROVIDE TOP-SIDE REINFORCEMENT PER DETAIL WITH PITCHED MIDDLE.
PROVIDE 30 MIL THICK PVC JACKETING ON EXTERIOR OF INSULATION, WHITE COLOR. DUCT SUPPORTS, UNISTRUT, ETC. SHALL NOT PENETRATE JACKET OR INSULATION.
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE ROOF
DUCTWORK PLAN - PHASE 2
Revisions: Date:
BID ISSUE 08/09/2019
JJ
KK
LL
NN
21 23
MM
K1K1
K2K2
H1H1
Z3 Z3
XR - 6"
XR - 6"
X - 6" CHWS
X - 6" CHWR
X - 6"ø
X - 6"ø CHWS X - 6"ø CHWR
XR - 6"
XR - 6"
XR - 3/4"
X - 4" LPS
X - 3/4" LPR
CAP
M0.19
M0.19
AC-17
X-AHU-19
XR-AC-18
X - 2 1/2" LPS
X - 4" LPS
X - 2" LPR
X - 2" LPR
XR - 4"
XR - 4"
XR - 2"
XR - 2"
XR - 2 1/2"
XR - 2 1/2"
XR - 4"
XR - 2"
XR - 2"
STAIR #5
PENTHOUSE
7C105
PENTHOUSE
7C108
M0.19
M0.19
XR - 6"
XR - 6"
X - 4" HPS*90
X - 2"
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:3
:2
P M
2-MPD-7MB
PARTIAL SEVENTH FLOOR PENTHOUSE
HVAC PIPING DEMOLITION PLAN -
PHASE 2
JXCDAD08/09/2019
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
SEVENTH FLOOR PENTHOUSE HVAC PIPING
DEMOLITION PLAN - PHASE 2 1N
# CODED NOTESGENERAL NOTES
1 REMOVE EXISTING PRE-HEAT STEAM COIL COMPLETE. EXISTING STEAM PIPING AND STEAM CONDENSATE
PIPING SHALL BE REMOVED TO POINT INDICATED, INCLUDING PIPING SUPPORTS.
REMOVE EXISTING CHILLED WATER COILS AND CONDENSATE PIPING COMPLETE. EXISTING CHILLED
WATER PIPING SHALL BE REMOVED TO POINT INDICATED, INCLUDING PIPING SUPPORTS.
REMOVE EXISTING HUMIDIFIER COMPLETE. EXISTING STEAM PIPING AND CONDENSATE PIPING SHALL BE
REMOVED TO POINT INDICATED, INCLUDING PIPING SUPPORTS.
REMOVE X-3/4"Ø LOW PRESSURE CONDENSATE RETURN TO MAIN AND CAP.
REMOVE EXISTING STEAM TRAP INVERTED BUCKET AND MATCH SIZE FOR REPLACEMENT IN NEW PHASE.
REMOVE EXISTING 2-1/2"Ø LOW PRESSURE STEAM PIPING AND ASSOCIATED COMPONENTS TO POINT
INDICATED.
MECHANICAL CONTRACTOR SHALL HIRE FLOWMETER REPRESENTATIVE TO REMOVE AND PRESERVE PIPE TRANSDUCERS AND CABLING FROM EXISTING ULTRASONIC FLOW METER. REFER TO NEW PLANS FOR ADDITIONAL NOTES. FLOWMETER REPRESENTATIVE IS CHALTRON, GAIN APPROVAL FROM COR PRIOR TO
HIRING.
REMOVE EXISTING ISOLATION VALVES AND STRAINERS.
REMOVE AND REROUTE HIGH PRESSURE STEAM PIPING TO ALLOW FOR INSTALLATION OF NEW 8"Ø CHILLED WATER PIPING. NEW HIGH PRESSURE STEAM PIPE SIZE SHALL MATCH EXISTING. COORDINATE HIGH PRESSURE STEAM SHUTDOWN WITH COR, SHUTDOWN SHALL OCCUR DURING WEEKEND HOURS.
1.
2.
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR TRANSPORTING ALL AIR HANDLING UNIT COMPONENTS
THROUGH DOUBLE DOORS TO RIGGING LOCATION ON ROOF. MECHANICAL CONTRACTOR SHALL
COORDINATE WITH RIGGING CONTRACTOR. REFER TO AIR HANDLING UNIT RIGGING PLAN FOR
ADDITIONAL NOTES.STAGING AREA AND PATH SHALL BE PROVIDED WITH 3/4" PLYWOOD WITH RIGID INSULATION TO PROTECT EXISTING ROOF. ANY EXISTING INSULATED PAVERS DAMAGED DURING
CONSTRUCTION SHALL BE REPLACED AT THE CONTRACTOR'S EXPENSE.
WITHIN 7TH FLOOR PENTHOUSE FLOOR TO BOTTOM OF ROOF DECKING IS 22 FEET, CONTRACTOR SHALL
PROVIDE SCAFFOLDING OR ANOTHER MEANS TO COMPLETE WORK.
JJ
KK
LL
NN
21 23
MM
K1K1
K2K2
H1H1
Z3 Z3
M0.19
3/4" LPR
3/4" LPR
M0.19
2 3" LPS
3" LPS
5 6
5 6
6" CHWS
(TOP)
6"CHWR
(BOTTOM)
6" CHWS
6" CHWR
3" LPS
1 1/4" LPR
2 1/2" LPS
X - 2 1/2" LPS
3" LPS
1 1/4" LPR
X - 3"ø LPS
X - 4" LPS
8 7
8 7
STAIR #5
PENTHOUSE
7C105
PENTHOUSE
7C108
AHU-18
M0.19
M0.19
8" CHWS8" CHWR
X - 6" CHWR
X - 6" CHWS
2" HPS*90
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:3
:3
P M
2-MP-7MB
PARTIAL SEVENTH FLOOR PENTHOUSE
HVAC PIPING PLAN - PHASE 2
JXCDAD08/09/2019
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE HVAC
PIPING PLAN - PHASE 2 1N
# CODED NOTESGENERAL NOTES
1 PROVIDE NEW INVERTED BUCKET STEAM TRAP. REFER TO DETAIL FOR REQUIRED VALVES AND FITTINGS.
ROUTE 3"Ø LOW PRESSURE STEAM PIPING THROUGH TOP OF UNIT AND SEAL PENETRATION TO BE AIR TIGHT. PROVIDE NECESSARY FITTINGS TO MAKE CONNECTION TO STEAM HUMIDIFIER. REFER TO DETAIL
FOR REQUIRED VALVES AND FITTINGS.
ROUTE 1-1/4"Ø LOW PRESSURE CONDENSATE PIPING FROM HUMIDIFIER TO EXISTING MAIN. REFER TO
DETAIL FOR REQUIRED VALVES AND FITTINGS.
ROUTE LOW PRESSURE CONDENSATE PIPING FROM LOW PRESSURE STEAM PIPE DIRT LEG UPSTREAM OF
GATE VALVE. REFER TO DETAIL FOR REQUIRED VALVES AND FITTINGS.
ROUTE NEW 3"Ø LOW PRESSURE STEAM PIPING FROM POINT INDICATED TO NEW STEAM PREHEAT COIL.
REFER TO DETAIL FOR REQUIRED VALVES AND FITTINGS.
ROUTE NEW 1-1/4"Ø LOW PRESSURE CONDENSATE PIPING FROM NEW STEAM PREHEAT COIL TO EXISTING
MAIN. REFER TO DETAIL FOR REQUIRED VALVES AND FITTINGS.
ROUTE NEW 6"Ø CHILLED WATER SUPPLY AND 6"Ø CHILLED WATER RETURN PIPING TO NEW CHILLED WATER COILS AND SERVE EACH COIL WITH 4"Ø CHILLED WATER SUPPLY AND 4"Ø CHILLED WATER
RETURN. REFER TO DETAIL FOR REQUIRED VALVES AND FITTINGS.
CONTRACTOR SHALL ROUTE 2"Ø CONDENSATE LINE FROM COOLING COIL DRAIN PAN TO NEAREST FLOOR
DRAIN. PROVIDE TRAP PER DETAIL.
45° ELBOW DOWN TO MAKE CONNECTION TO EXISTING CHILLED WATER PIPING.
MECHANICAL CONTRACTOR SHALL HIRE FLOWMETER REPRESENTATIVE TO REINSTALL PIPE
TRANSDUCERS ON NEW 8"Ø CHWR PIPING, UPDATE FIRMWARE, UPDATE PARAMETERS, CONFIRM EACH FLOW METER CHANNEL IS OPERATING PROPERLY, CONFIRM BACNET CARD IS COMMUNICATING TO BMS AND EXTEND CABLING AS REQUIRED TO/FROM TRANSDUCERS FOR PROPER FLOWMETER OPERATION.
ANY COMPONENTS NOT FUNCTIONING PROPERLY SHALL BE REPLACED. FLOWMETER REPRESENTATIVE IS
CHALTRON, GAIN APPROVAL FROM COR PRIOR TO HIRING.
ROUTE 1"Ø DRAIN LINE FROM OUTDOOR AIR SECTION. PIPING SHALL BE INSULATED WITH ALUMINIUM JACKET. ROUTE TO NEAREST FLOOR DRAIN AND TERMINATE WITH AIR GAP. TRAP PER DETAIL.
1.
2.
WITHIN 7TH FLOOR PENTHOUSE FLOOR TO BOTTOM OF ROOF DECKING IS 22 FEET, CONTRACTOR SHALL
PROVIDE SCAFFOLDING OR ANOTHER MEANS TO COMPLETE WORK.
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR TRANSPORTING NEW AHU-18 COMPONENTS FROM
RIGGING SITE ON 6TH FLOOR ROOF, THROUGH A SET OF DOUBLE DOORS TO FINAL LOCATION WITHIN 7TH
FLOOR PENTHOUSE, MECHANICAL CONTRACTOR SHALL COORDINATE WITH RIGGING CONTRACTOR.
REFER TO AIR HANDLING UNIT RIGGING PLAN FOR ADDITIONAL NOTES. STAGING AREA AND PATH SHALL BE PROVIDED WITH 3/4" PLYWOOD WITH RIGID INSULATION TO PROTECT EXISTING ROOF. ANY EXISTING INSULATED PAVERS DAMAGED DURING CONSTRUCTION SHALL BE REPLACED AT THE CONTRACTOR'S
EXPENSE.
Revisions: Date:
JJ
KK
LL
NN
21 23
MM
K1K1
K2K2
H1H1
Z3 Z3
X-AHU-18
3-MD-7MB
X-AC-17
STAIR #5
PENTHOUSE
7C105
PENTHOUSE
7C1082
3-M-7MB
MB-ROOF
738' - 4 1/4"
MB-ELEV MACH
RM
744' - 4 1/4"
JK
AHU-18
X - 77 x 27 SA
X - 80 x 27 SA
X - 70 x 27 SA
XR - 70 x 28 XR - 82 x 28 XR - 77 x 28
LOD
LOD
LOD
LOD LOD
LOD
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:3
:5
P M
3-MD-7MB
PARTIAL SEVENTH FLOOR PENTHOUSE
DUCTWORK DEMOLITION PLAN -
PHASE 3
JXCDAD08/09/2019
N
# CODED NOTESGENERAL NOTES
1 CONTRACTOR TO REMOVE SECTIONS OF SUPPLY DUCTWORK TIED INTO EAST SUPPLY SHAFT BACK TO EACH NEWLY INSTALLED HEAVY DUTY BALANCE DAMPER. BALANCE DAMPERS SHALL BE LOCKED CLOSED
ONCE AHU-18 IS OPERATIONAL.
1. WITHIN 7TH FLOOR PENTHOUSE FLOOR TO BOTTOM OF ROOF DECKING IS 22 FEET, CONTRACTOR SHALL
PROVIDE SCAFFOLDING OR ANOTHER MEANS TO COMPLETE WORK.
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE
DUCTWORK DEMOLITION PLAN - PHASE 3
Revisions: Date:
BID ISSUE 08/09/2019
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
SUPPLY DISCHARGE SECTION - AHU-18 2
JJ
KK
LL
NN
21 23
MM
K1K1
K2K2
H1H1
Z3 Z3
3-MD-7MB
X-AC-17
1 2
1 2
1 2
77 x 27
80 x 27
77 x 27
STAIR #5
PENTHOUSE
7C105
PENTHOUSE
7C108
3-M-7MB
MB-ROOF
738' - 4 1/4"
MB-ELEV MACH
RM
744' - 4 1/4"
J K
MB-PENT HOUSE
ROOF
761' - 4 1/4"
77 x 27 SA 80 x 27 SA 77 x 27 SA
HEAVY DUTY
BALANCE DAMPER
HEAVY DUTY
BALANCE DAMPER
HEAVY DUTY
BALANCE DAMPER
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:3
:0
P M
3-M-7MB
PARTIAL SEVENTH FLOOR PENTHOUSE
DUCTWORK PLAN - PHASE 3
JXCDAD08/09/2019
N
# CODED NOTESGENERAL NOTES
1 TRANSITION DUCTWORK TO INDICATED SIZE AFTER THE DUCTWORK HAS PENETRATED THE ROOF.
PROVIDE DUCTWORK OFFSET TO ALIGN WITH EXISTING DUCTWORK SHAFTS. ROUTE DUCTWORK DOWN
THROUGH EXISTING AC-17 UNIT CASING, EACH PENETRATION SHALL BE SEALED AIR TIGHT.
PROVIDE 4 FEET OF DUCTWORK BELOW ROOF LINE OF UNIT. PROVIDE HEAVY DUTY BALANCE DAMPER 10'-8" AAF AT EACH STUB . EACH BALANCE DAMPER SHALL BE CLOSED AND LOCKED WHILE AC-17 IS IN
OPERATION.
1. WITHIN 7TH FLOOR PENTHOUSE FLOOR TO BOTTOM OF ROOF DECKING IS 22 FEET, CONTRACTOR SHALL
PROVIDE SCAFFOLDING OR ANOTHER MEANS TO COMPLETE WORK.
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE
DUCTWORK PLAN - PHASE 3 1
Revisions: Date:
BID ISSUE 08/09/2019
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
SUPPLY DISCHARGE SECTION - AHU-17 2
JJ
KK
21 23
K1K1
K2K2
H1H1
Z3 Z3
X-RELIEF AIR
HOOD
X-AIR COOLED
CHILLER
X-EXHAUST FAN
X-EXHAUST FAN
X-RELIEF AIR
HOOD
X-AHU-19
X-RH-1
X-RH-2
X-EXHAUST
FAN
X - 38 x 38
X-38x38 DN
60 x 6060 x 60
X x
X-60"x60"
RETURN
BELOW
x
X - 50 x 70
X x
33333
4 4
4 4
3-M-7MB
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:3
:2
P M
3-M-RMB
PARTIAL SEVENTH FLOOR PENTHOUSE
ROOF DUCTWORK PLAN - PHASE 3
JXCDAD08/09/2019
N
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE ROOF
DUCTWORK PLAN - PHASE 3
# CODED NOTESGENERAL NOTES
1 PRIOR TO ROUTING DUCTWORK DOWN THROUGH ROOF, CONTRACTOR SHALL FIELD MEASURE EXACT LOCATION OF WEST SUPPLY DUCTWORK SHAFT TO ENSURE PROPER ALIGNMENT OF EACH SUPPLY DUCT.
CONTRACTOR TO ROUTE EACH SUPPLY DUCT DOWN THROUGH ROOF TO WEST DUCTWORK SHAFT AND COORDINATE WITH STRUCTURE BELOW. REFER TO DETAIL FOR ROOF DUCTWORK PENETRATION. REFER TO PENTHOUSE DUCTWORK PHASE 3 PLAN FOR CONTINUATION OF DUCTWORK. PROVIDE STRUCTURE
MEMBERS TO FRAME NEW ROOF PENETRATIONS. PROVIDE ROOF PENETRATION CURBS.
CONTRACTOR SHALL PROVIDE PATE RAILS WITH, GALVANIZED STEEL UNISTRUT WITH GALVANIZED STEEL COMPONENTS TO PROPERLY SUPPORT SUPPLY DUCTWORK. REFER TO DETAILS. REFER TO STRUCTURAL
DRAWINGS.
CONTRACTOR SHALL CUSTOM FABRICATE GALVANIZED STEEL WALL BRACKET TO PROPERLY SUPPORT PORTION OF SUPPLY DUCTWORK ROUTED ALONG PENTHOUSE WALL. EACH FABRICATED GALVANIZED STEEL WALL BRACKET SHALL HAVE MINIMUM 1,000 LBS. CAPACITY. PROVIDE GALVANIZED STEEL
HARDWARE.
1.
2.
GENERAL CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF NEW ROOF CURBS AS NOT TO VOID
EXISTING ROOF WARRANTY. GC SHALL USE FACILITY APPROVED ROOF CONTRACTOR. GC TO
COORDINATE WITH MECHANICAL CONTRACTOR FOR NEW ROOF CURB LOCATIONS. STAGING AREA AND PATH SHALL BE PROVIDED WITH 3/4" PLYWOOD WITH RIGID INSULATION TO PROTECT EXISTING ROOF.
ANY EXISTING INSULATED PAVERS DAMAGED DURING CONSTRUCTION SHALL BE REPLACED AT THE
CONTRACTOR'S EXPENSE.
ALL EXTERIOR DUCTWORK SHALL BE INSULATED WITH 2" THICK POLYISOCYANURATE CLOSED CELL RIGID INSULATION. ON TOP SURFACE, PROVIDE TOP-SIDE REINFORCEMENT PER DETAIL WITH PITCHED MIDDLE.
PROVIDE 30 MIL THICK PVC JACKETING ON EXTERIOR OF INSULATION, WHITE COLOR. DUCT SUPPORTS, UNISTRUT, ETC. SHALL NOT PENETRATE JACKET OR INSULATION.
X-AHU-19
X-OA-1
JJ
KK
LL
NN
21 23
MM
K1K1
K2K2
H1H1
Z3 Z3
3-MD-7MB
X - 4" LPS
XR - 4"
X - 4" LPS
X - 6" CHWS
X-AC-17
STAIR #5
PENTHOUSE
7C105
PENTHOUSE
7C108
3-M-7MB
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:5
:2
P M
3-MPD-7MB
PARTIAL SEVENTH FLOOR PENTHOUSE
HVAC PIPING DEMOLITION PLAN -
PHASE 3
JXCDAD08/09/2019
N
# CODED NOTESGENERAL NOTES
1 REMOVE SECTION OF EXISTING 4"Ø LOW PRESSURE STEAM PIPING. PRIOR TO REMOVAL OF PIPING REFER
TO NEW PHASE NOTES.
REMOVE SUSPENDED EXISTING EXPANSION TANK AND ASSOCIATED HANGERS COMPLETE.
APPROXIMATELY 17 FEET AFF.
1. WITHIN 7TH FLOOR PENTHOUSE FLOOR TO BOTTOM OF ROOF DECKING IS 22 FEET, CONTRACTOR SHALL
PROVIDE SCAFFOLDING OR ANOTHER MEANS TO COMPLETE WORK.
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE HVAC
PIPING DEMOLITION PLAN - PHASE 3 1
Revisions: Date:
HH
JJ
KK
LL
NN
21 23
MM
K1K1
K2K2
H1H1
Z3 Z3
3-MD-7MB
X - 4"ø LPSX - 4" LPSX - 4" LPS
X - 3"ø LPS
4" LPS
X - 4" LPS
X-AHU-17
STAIR #5
PENTHOUSE
7C105
PENTHOUSE
7C108
3-M-7MB
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:3
:4
P M
3-MP-7MB
PARTIAL SEVENTH FLOOR PENTHOUSE
HVAC PIPING PLAN - PHASE 3
JXCDAD08/09/2019
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE HVAC
PIPING PLAN - PHASE 3 1N
# CODED NOTESGENERAL NOTES
1 EXISTING LOW PRESSURE STEAM SERVES EXISTING HEATING HOT WATER HEAT EXCHANGERS.
CONTRACTOR SHALL COORDINATE SHUTDOWN WITH COR. TO MINIMIZE SHUTDOWN DURATION
CONTRACTOR SHALL INSTALL NEW 4"Ø LOW PRESSURE ALONG SIDE EXISTING 4"Ø LOW PRESSURE STEAM LINE. ONCE NEW LOW PRESSURE STEAM LINE IS INSTALLED, CONTRACTOR SHALL TIE INTO EXISTING LOW
PRESSURE STEAM LINE AND REMOVE EXISTING UNUSED SECTION .
1. WITHIN 7TH FLOOR PENTHOUSE FLOOR TO BOTTOM OF ROOF DECKING IS 22 FEET, CONTRACTOR SHALL
PROVIDE SCAFFOLDING OR ANOTHER MEANS TO COMPLETE WORK.
JJ
KK
LL
NN
21 23
MM
K1K1
K2K2
H1H1
Z3 Z3
X x
XR - 64 x 48
XR - 64 x 48
XR - 78 x 68 RA
M0.20
X-AHU-18
XR-AC-17
STAIR #5
PENTHOUSE
7C105
PENTHOUSE
7C108
M0.20
M0.20
M0.20
M0.20
A
A
A
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/2
/2
:4
:3
A
M
4-MD-7MB
PARTIAL SEVENTH FLOOR PENTHOUSE
DUCTWORK DEMOLITION PLAN -
PHASE 4
JXCDAD08/09/2019
# CODED NOTESGENERAL NOTES
1 REMOVE EXISTING RETURN FAN COMPLETE, ALONG WITH ASSOCIATED INERTIA PAD AND VFD CONTROL
PANEL.
REMOVE EXISTING RETURN DUCTWORK AND ASSOCIATED HANGERS TO INDICATED POINT.
REMOVE EXISTING RELIEF DUCTWORK AND ASSOCIATED DUCTWORK SUPPORTS. .
CONTRACTOR SHALL REMOVE EXISTING AIR HANDLING COMPLETE, INCLUDING SOUND ATTENUATOR
SECTION AND PRE-FILTER SECTION.
REMOVE EXISTING SUPPLY FAN COMPLETE, ALONG WITH ASSOCIATED INERTIA PAD AND VFD CONTROL
PANEL.
REMOVE SECTION OF RETURN DUCTWORK TO ALLOW FOR THE RELOCATION OF EXISTING ELBOW.
PRIOR TO THE REMOVAL OF AC-17, CONTRACTOR SHALL EXTEND NEWLY INSTALLED SUPPLY DUCTWORK
STUBS AND CONNECT TO EAST SUPPLY DUCTWORK SHAFT. BALANCE DAMPER SHALL BE OPENED.
CONTRACTOR SHALL REMOVE EXISTING SUPPLY AND RETURN FAN VFD'S COMPLETE INCLUDING
ASSOCIATED CONDUIT, UNISTRUT SUPPORT AND CONDUIT SUPPORTS.
REMOVE EXISTING OUTDOOR AIR DAMPER COMPLETE.
REMOVE AND PROTECT EXISTING LOUVER FOR FUTURE INSTALLATION. CONTRACTOR SHALL PROVIDE
TEMPORARY PROTECTION TO PREVENT WATER FROM ENTERING PENTHOUSE.
1.
2.
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR TRANSPORTING ALL AIR HANDLING UNIT COMPONENTS
THROUGH DOUBLE DOORS TO RIGGING LOCATION ON ROOF. MECHANICAL CONTRACTOR SHALL
COORDINATE WITH RIGGING CONTRACTOR. REFER TO AIR HANDLING UNIT RIGGING PLAN FOR
ADDITIONAL NOTES. STAGING AREA AND PATH SHALL BE PROVIDED WITH 3/4" PLYWOOD WITH RIGID INSULATION TO PROTECT EXISTING ROOF. ANY EXISTING INSULATED PAVERS DAMAGED DURING
CONSTRUCTION SHALL BE REPLACED AT THE CONTRACTOR'S EXPENSE.
WITHIN 7TH FLOOR PENTHOUSE FLOOR TO BOTTOM OF ROOF DECKING IS 22 FEET, CONTRACTOR SHALL
PROVIDE SCAFFOLDING OR ANOTHER MEANS TO COMPLETE WORK.
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE
DUCTWORK DEMOLITION PLAN - PHASE 4
1N
# TEMPERATURE CONTROLS CODED NOTES:
A TEMPERATURE CONTROLS CONTRACTOR SHALL REMOVE ALL AC-17 CONTROLS FROM EXISTING
CONTROL PANEL. IF NO OTHER CONTROLS RESIDE WITHIN EXISTING CONTROL PANEL, REMOVE CONTROL PANEL COMPLETE ALONG WITH ALL ASSOCIATED CONTROL WIRING, CONDUIT AND SUPPORT UNISTRUT.
TEMPERATURE CONTROLS CONTRACTOR SHALL MAINTAIN EXISTING INFINET DATA BUS CONTROLLERS. ALL
NEW DATA SHALL BE CONTROLLED THROUGH NATIVE BACNET.
Revisions: Date:
BID ISSUE 08/09/2019
JJ
KK
LL
NN
21 23
MM
K1K1
K2K2
H1H1
Z3 Z3
M0.20
X - 78 x 68
X x
48 x 60
48 x 60 70 x 36
70 x 36
X - 78 x 68
STAIR #5
PENTHOUSE
7C105
PENTHOUSE
7C108
AHU-17
M0.20
M0.20
M0.20
M0.20
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:3
:0
P M
4-M-7MB
PARTIAL SEVENTH FLOOR PENTHOUSE
DUCTWORK PLAN - PHASE 4
JXCDAD08/09/2019
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE
DUCTWORK PLAN - PHASE 4
1N
# CODED NOTESGENERAL NOTES
1 ROUTE NEW 60"x48" RELIEF DUCTWORK FROM AHU-17 RELIEF DUCT CONNECTION TO NEW ROOF
MOUNTED RELIEF HOOD. CONTRACTOR SHALL PROVIDE NECESSARY DUCT FITTINGS TO MAKE
CONNECTION TO NEW RELIEF HOOD AND AHU-17.
ONCE AHU-17 IS ASSEMBLED, CONTRACTOR TO REMOVE SECTIONS OF SUPPLY DUCTWORK TIED INTO
EAST SUPPLY SHAFT TO EACH NEWLY INSTALLED HEAVY DUTY BALANCE DAMPER.
CONTRACTOR SHALL PROVIDE GALVANIZED STEEL UNISTRUT SUPPORT STRUCTURE FOR MOUNTING OF
SUPPLY FAN VFDS. COORDINATE LOCATION VFD LOCATIONS WITH ELECTRICAL CONTRACTOR.
CONTRACTOR SHALL PROVIDE GALVANIZED STEEL UNISTRUT SUPPORT STRUCTURE FOR MOUNTING OF
RETURN FAN VFDS. COORDINATE LOCATION VFD LOCATIONS WITH ELECTRICAL CONTRACTOR.
CONTRACTOR SHALL PROVIDE GALVANIZED STEEL UNISTRUT SUPPORT STRUCTURE FOR MOUNTING OF OUTDOOR AIR FAN VFDS. COORDINATE LOCATION VFD LOCATIONS WITH ELECTRICAL CONTRACTOR.
CLEAN AND REINSTALL EXISTING LOUVERS. PROVIDE CAULK AND FLASHING TO MAKE LOUVERS WEATHER
TIGHT.
PROVIDE NEW TEMPERATURE CONTROL PANEL ENCLOUSURE TO SERVE AHU-17. PROVIDE GALVANIZED
STEEL UNITRUT AND HARDWARE TO SUPPORT CONTROL PANEL ENCLOUSURE.
1.
2.
WITHIN 7TH FLOOR PENTHOUSE FLOOR TO BOTTOM OF ROOF DECKING IS 20 FEET, CONTRACTOR SHALL
PROVIDE SCAFFOLDING OR ANOTHER MEANS TO COMPLETE WORK.
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR TRANSPORTING NEW AHU-18 COMPONENTS FROM
RIGGING SITE ON 6TH FLOOR ROOF, THROUGH A SET OF DOUBLE DOORS TO FINAL LOCATION WITHIN 7TH
FLOOR PENTHOUSE MECHANICAL CONTRACTOR SHALL COORDINATE WITH RIGGING CONTRACTOR.
REFER TO AIR HANDLING UNIT RIGGING PLAN FOR ADDITIONAL NOTES. STAGING AREA AND PATH SHALL BE PROVIDED WITH 3/4" PLYWOOD WITH RIGID INSULATION TO PROTECT EXISTING ROOF. ANY EXISTING INSULATED PAVERS DAMAGED DURING CONSTRUCTION SHALL BE REPLACED AT THE CONTRACTOR'S
EXPENSE.
Revisions: Date:
BID ISSUE 08/09/2019
JJ
KK
21 23
K1K1
K2K2
H1H1
Z3 Z3
X-RELIEF AIR
HOOD
X-AHU-19
X-AIR COOLED
CHILLER
X-EXHAUST FAN
X-EXHAUST FAN
XR-RELIEF AIR
HOOD
XR-RELIEF AIR
HOOD
X-RELIEF AIR
HOOD
X - 60 x 60
X - 60 x 60
X - 40 x 50
X - 40 x 50
X - 40 x 50
X-EXHAUST FAN
X - 50 x 70
X - 50 x 70
X - 40 x 50
X - 40 x 50
X - 40 x 50
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:3
:5
P M
4-MD-RMB
PARTIAL 7TH FLOOR PENTHOUSE
ROOF DUCTWORK DEMOLTION PLAN -
PHASE 4
JXCDAD08/09/2019
N
# CODED NOTESGENERAL NOTES
1 CONTRACTOR SHALL REMOVE EXISTING ROOF MOUTED RELIEF AIR HOOD AND ASSOCIATED ROOF CURB.
ROOF AND METAL ROOF DECKING SHALL BE PATCHED TO MATCH EXISTING.
1.
2.
GENERAL CONTRACTOR IS RESPONSIBLE FOR ROOFING WORK AS NOT TO VOID EXISTING ROOF
WARRANTY. GC SHALL USE FACILITY APPROVED ROOF CONTRACTOR.
STAGING AREA AND PATH SHALL BE PROVIDED WITH 3/4" PLYWOOD WITH RIGID INSULATION TO PROTECT EXISTING ROOF. ANY EXISTING INSULATED PAVERS DAMAGED DURING CONSTRUCTION SHALL BE
REPLACED AT THE CONTRACTOR'S EXPENSE.
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE ROOF
DUCTWORK DEMOLTION PLAN - PHASE 4
JJ
KK
21 23
K1K1
K2K2
H1H1
Z3 Z31
RH-3
RH-4
X-RELIEF AIR
HOOD
X-AIR COOLED
CHILLER
X-EXHAUST FAN
X-EXHAUST FAN
X-RELIEF AIR
HOOD
X - 38 x 38 X-38x38 DN
X-EXHAUST FAN
X - 60 x 60
X - 50 x 70
X - 50 x 70
X-AHU-19
X-OA-1
X x
X - 60 x 60
X x
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:3
:2
P M
4-M-RMB
PARTIAL SEVENTH FLOOR PENTHOUSE
ROOF DUCTWORK PLAN - PHASE 4
JXCDAD08/09/2019
N
# CODED NOTESGENERAL NOTES
1 INSTALL NEW RELIEF AIR HOOD WITH ROOF CURB. REFER TO 7TH FLOOR PENTHOUSE DUCTWORK PLAN FOR CONTINUOUS OF RELIEF AIR DUCTWORK. REFER TO RELIEF AIR HOOD ROOF CURB DETAIL.
1.
2.
GENERAL CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF NEW ROOF CURBS AS NOT TO VOID
EXISTING ROOF WARRANTY. GC SHALL USE FACILITY APPROVED ROOF CONTRACTOR. GC TO
COORDINATE WITH MECHANICAL CONTRACTOR FOR NEW ROOF CURB LOCATIONS. STAGING AREA AND PATH SHALL BE PROVIDED WITH 3/4" PLYWOOD WITH RIGID INSULATION TO PROTECT EXISTING ROOF.
ANY EXISTING INSULATED PAVERS DAMAGED DURING CONSTRUCTION SHALL BE REPLACED AT THE
CONTRACTOR'S EXPENSE.
ALL EXTERIOR DUCTWORK SHALL BE INSULATED WITH 2" THICK POLYISOCYANURATE CLOSED CELL RIGID INSULATION. ON TOP SURFACE, PROVIDE TOP-SIDE REINFORCEMENT PER DETAIL WITH PITCHED MIDDLE.
PROVIDE 30 MIL THICK PVC JACKETING ON EXTERIOR OF INSULATION, WHITE COLOR. DUCT SUPPORTS, UNISTRUT, ETC. SHALL NOT PENETRATE JACKET OR INSULATION.
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE ROOF
DUCTWORK PLAN - PHASE 4
JJ
KK
LL
NN
21 23
MM
K1K1
K2K2
H1H1
Z3 Z3
XR - 3"
XR - 2"
X - 3"ø LPS
X - 4" LPS
XR - 2"
XR - 2"
XR - 3"
XR - 2"
XR - 2"
XR - 2"
XR - 4"
X - 4"ø LPS
XR - 2"
XR - 2"
XR - 4"
STAIR #5
PENTHOUSE
7C105
PENTHOUSE
7C108
XR - 6"
XR - 6"
X - 10" CHWS
X - 10" CHWR
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:3
:3
P M
4-MPD-7MB
PARTIAL SEVENTH FLOOR PENTHOUSE
HVAC PIPING DEMOLITION PLAN -
PHASE 4
JXCDAD08/09/2019
# CODED NOTESGENERAL NOTES
1 REMOVE EXISTING PRE-HEAT STEAM COIL COMPLETE. EXISTING STEAM PIPING AND STEAM CONDENSATE
PIPING SHALL BE REMOVED TO POINT INDICATED, INCLUDING PIPING SUPPORTS.
REMOVE EXISTING CHILLED WATER COILS AND CONDENSATE PIPING COMPLETE. EXISTING CHILLED
WATER PIPING SHALL BE REMOVED TO POINT INDICATED, INCLUDING PIPING SUPPORTS.
REMOVE EXISTING HUMIDIFIER COMPLETE. EXISTING STEAM PIPING AND CONDENSATE PIPING SHALL BE
REMOVED TO POINT INDICATED, INCLUDING PIPING SUPPORTS.
MECHANICAL CONTRACTOR SHALL HIRE FLOWMETER REPRESENTATIVE TO REMOVE AND PRESERVE PIPE TRANSDUCERS AND CABLING FROM EXISTING ULTRASONIC FLOW METER. REFER TO NEW PLANS FOR ADDITIONAL NOTES. FLOWMETER REPRESENTATIVE IS CHALTRON, GAIN APPROVAL FROM COR PRIOR TO
HIRING.
REMOVE EXISTING ISOLATION VALVES AND STRAINERS.
1.
2.
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR TRANSPORTING ALL AIR HANDLING UNIT COMPONENTS
THROUGH DOUBLE DOORS TO RIGGING LOCATION ON ROOF. MECHANICAL CONTRACTOR SHALL
COORDINATE WITH RIGGING CONTRACTOR. REFER TO AIR HANDLING UNIT RIGGING PLAN FOR
ADDITIONAL NOTES. STAGING AREA AND PATH SHALL BE PROVIDED WITH 3/4" PLYWOOD WITH RIGID INSULATION TO PROTECT EXISTING ROOF. ANY EXISTING INSULATED PAVERS DAMAGED DURING
CONSTRUCTION SHALL BE REPLACED AT THE CONTRACTOR'S EXPENSE.
WITHIN 7TH FLOOR PENTHOUSE FLOOR TO BOTTOM OF ROOF DECKING IS 22 FEET, CONTRACTOR SHALL
PROVIDE SCAFFOLDING OR ANOTHER MEANS TO COMPLETE WORK.
N
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE HVAC
PIPING DEMOLITION PLAN - PHASE 4 1
JJ
KK
LL
NN
21 23
MM
K1K1
K2K2
H1H1
Z3 Z3
M0.20
X - 6" CHWR
X - 6"ø CHWS
3/4" LPR
3/4" LPR
6" CHWR
6" CHWS
3" LPS
2 1/2" LPS 2" LPR
X - 2" LPR
6" CHWS
(TOP)
6"CHWR
(BOTTOM)
3/4" LPR3/4" LPR
X - 2" LPR
2" LPR
3" LPS
STAIR #5
PENTHOUSE
7C105
PENTHOUSE
7C108
AHU-17
M0.20
M0.20
M0.20
M0.20
8" CHWR
8" CHWS
X - 10" CHWR
X - 10" CHWS
X - 2" LPR
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R jc a rt e r.
rv t
/8
/2
:3
:4
P M
4-MP-7MB
PARTIAL SEVENTH FLOOR PENTHOUSE
HVAC PIPING PLAN - PHASE 4
JXCDAD08/09/2019
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL SEVENTH FLOOR PENTHOUSE HVAC
PIPING PLAN - PHASE 4 1N
GENERAL NOTES
1.
2.
WITHIN 7TH FLOOR PENTHOUSE FLOOR TO BOTTOM OF ROOF DECKING IS 22 FEET, CONTRACTOR SHALL
PROVIDE SCAFFOLDING OR ANOTHER MEANS TO COMPLETE WORK.
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR TRANSPORTING NEW AHU-17 COMPONENTS FROM
RIGGING SITE ON 6TH FLOOR ROOF, THROUGH A SET OF DOUBLE DOORS TO FINAL LOCATION WITHIN 7TH
FLOOR PENTHOUSE MECHANICAL CONTRACTOR SHALL COORDINATE WITH RIGGING CONTRACTOR.
REFER TO AIR HANDLING UNIT RIGGING PLAN FOR ADDITIONAL NOTES. STAGING AREA AND PATH SHALL BE PROVIDED WITH 3/4" PLYWOOD WITH RIGID INSULATION TO PROTECT EXISTING ROOF. ANY EXISTING INSULATED PAVERS DAMAGED DURING CONSTRUCTION SHALL BE REPLACED AT THE CONTRACTOR'S
EXPENSE.
# CODED NOTES
1 ROUTE 3"Ø LOW PRESSURE STEAM PIPING THROUGH TOP OF UNIT AND SEAL PENETRATION TO BE AIR TIGHT. PROVIDE NECESSARY FITTINGS TO MAKE CONNECTION TO STEAM HUMIDIFIER. REFER TO DETAIL
FOR REQUIRED VALVES AND FITTINGS.
ROUTE 1-1/4"Ø LOW PRESSURE CONDENSATE PIPING FROM HUMIDIFIER TO EXISTING MAIN. REFER TO
DETAIL FOR REQUIRED VALVES AND FITTINGS.
ROUTE LOW PRESSURE CONDENSATE PIPING FROM LOW PRESSURE STEAM PIPE DIRT LEG UPSTREAM OF
GATE VALVE. REFER TO DETAIL FOR REQUIRED VALVES AND FITTINGS.
ROUTE NEW 3"Ø LOW PRESSURE STEAM PIPING FROM POINT INDICATED TO NEW STEAM PREHEAT COIL.
REFER TO DETAIL FOR REQUIRED VALVES AND FITTINGS.
ROUTE NEW 1-1/4" LOW PRESSURE CONDENSATE PIPING FROM NEW STEAM PREHEAT COIL TO EXISTING
MAIN. REFER TO DETAIL FOR REQUIRED VALVES AND FITTINGS.
ROUTE NEW 6"Ø CHILLED WATER SUPPLY AND 6"Ø CHILLED WATER RETURN PIPING TO NEW CHILLED WATER COILS AND SERVE EACH COIL WITH 4"Ø CHILLED WATER SUPPLY AND 4"Ø CHILLED WATER
RETURN. REFER TO DETAIL FOR REQUIRED VALVES AND FITTINGS.
CONTRACTOR SHALL ROUTE 2"Ø CONDENSATE LINE FROM COOLING COIL DRAIN PAN TO NEAREST FLOOR
DRAIN. PROVIDE TRAP PER DETAIL.
MECHANICAL CONTRACTOR SHALL HIRE FLOWMETER REPRESENTATIVE TO REINSTALL PIPE
TRANSDUCERS ON NEW 8"Ø CHWR PIPING, UPDATE FIRMWARE, UPDATE PARAMETERS, CONFIRM EACH FLOW METER CHANNEL IS OPERATING PROPERLY, CONFIRM BACNET CARD IS COMMUNICATING TO BMS AND EXTEND CABLING AS REQUIRED TO/FROM TRANSDUCERS FOR PROPER FLOWMETER OPERATION.
ANY COMPONENTS NOT FUNCTIONING PROPERLY SHALL BE REPLACED. FLOWMETER REPRESENTATIVE IS
CHALTRON, GAIN APPROVAL FROM COR PRIOR TO HIRING.
ROUTE 1"Ø DRAIN LINE FROM OUTDOOR AIR SECTION. PIPING SHALL BE INSULATED WITH ALUMINIUM JACKET. ROUTE TO NEAREST FLOOR DRAIN AND TERMINATE WITH AIR GAP. TRAP PER DETAIL.
Revisions: Date:
FIRE ALARM SYSTEM
RS
CM
MM
FIRE ALARM SYSTEM NOTES:
FIRE ALARM DEVICES SHALL BE BY NOTIFIER AND SHALL BE COMPATIBLE WITH EXISTING NOTIFIER FIRE ALARM
CONTROL SYSTEM.
ALL FIRE ALARM SYSTEM DEVICES SHALL BE CONNECTED COMPLETE TO THE MAIN FIRE ALARM SYSTEM CONTROL PANEL IN ACCORDANCE WITH ENGINEER APPROVED MANUFACTURER'S SHOP DRAWING WIRING DIAGRAMS AND DETAILS. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A FULLY CODE COMPLIANT FIRE ALARM SYSTEM.
DEVICES SHOWN ON PLAN ARE FOR REFERENCE ONLY.
PROVIDE A 2-GANG MINIMUM SIZE BACKBOX FOR ALL OF THE ABOVE FIRE ALARM DEVICES.
ALL FIRE ALARM SYSTEM CONDUCTORS SHALL BE INSTALL IN 3/4" MINIMUM SIZE COMPLETE CONDUIT SYSTEM WITH COLOR CODED WIRING AS INDICATED ON SHOP DRAWINGS - MAINTAIN FACILITY COLOR CODING.
ALL NETWORK AND NETWORK CABLES SHALL BE "COMMUNICATION GRADE" TYPE CABLE.
FURNISH, INSTALL AND CONNECT ALL FIRE ALARM DEVICES IN ACCORDANCE WITH WIRING DIAGRAMS PREPARED BY
SYSTEM VENDOR.
EXISTING FIRE ALARM SYSTEM BY NOTIFIER. REFER TO SPECIFICATIONS SECTION 283100 FOR ELECTRICAL
REQUIREMENTS.
DUCT DETECTOR - ADDRESSABLE INTELLIGENT PHOTOELECTRIC DETECTOR, SAMPLING TUBES AND PROGRAMMABLE RELAY BASE. PROVIDE DUCT DETECTOR TEST/RESET SWITCH WITH REMOTE INDICATOR
LAMP FOR EACH DUCT DETECTOR. (TEST SWITCH MAY NOT BE SHOWN ON PLANS)
24V COMBINATION SMOKE/FIRE DAMPER - FURNISHED AND INSTALLED BY THE MC. EC SHALL PROVIDE 120V CIRCUIT FOR CONNECTION TO ASSOCIATED LOW-VOLTAGE TRANSFORMER, (1) FIRE ALRM CONTROL MODULE,
(1) FIRE ALARM MONITOR MODULE AND ASSOCIATE WIRING, PROGRAMMING, ETC. NECESSARY TO CONNECT
DAMPER COMPLETE TO FIRE ALARM SYSTEM.
CONTROL MODULE - ADDRESSABLE RELAY FOR CONTROL OF SMOKE DAMPERS.
MONITOR MODULE - ADDRESSABLE SUPERVISED FOR MONITORING TAMPER SWITCH , FLOW SWITCH, DAMPER
POSITION,ETC.
D
F1.
F2.
F3.
F4.
F5.
F6.
F7.
ABBREVIATIONS
DEDICATED NEUTRAL CONDUCTORS
AC ABOVE COUNTER AT 9" UNLESS OTHERWISE NOTED
AF AMP FRAME
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AT AMP TRIP
BC BELOW COUNTER AT 18"AFF UNLESS OTHERWISE NOTED
BFC BELOW FINISHED CEILING
CM CEILING MOUNTED
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
IG ISOLATED GROUND
ITD INFORMATION TECHNOLOGY DEPARTMENT
PROVIDE DEFINITION: FURNISH, INSTALL AND CONNECT COMPLETE.
X EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, CONDUIT, ETC. - TO REMAIN
XB INDICATES EXISTING OUTLET, LIGHTING FIXTURE, CONDUIT, ETC - TO BE REMOVED.
PROVIDE BLANK COVER FOR OUTLET AND MAINTAIN CIRCUIT CONTINUITY.
XL NEW LOCATION OF EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC.
XN EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC. - TO BE REPLACED WITH NEW OF
SPECIFIED TYPE
XR EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, CONDUIT, ETC. - TO BE REMOVED COMPLETE-
MAINTAIN CIRCUIT CONTINUITY TO ADJACENT OUTLETS, EXTEND CONDUIT AND WIRING AS
REQUIRED.
XRR EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC. - TO BE REMOVED AND REINSTALLED
AT NEW LOCATION - EXTEND CONDUIT AND WIRING AS REQUIRED
MC MECHANICAL CONTRACTOR
MLO MAIN LUGS ONLY
NEC NATIONAL ELECTRICAL CODE
NF NOT FUSED
OFE OWNER FURNISHED EQUIPMENT
TC TELECOMMUNICATIONS CONTRACTOR
TCC TEMPERATURE CONTROLS CONTRACTOR
TV TELEVISION
VDC VOICE/DATA CONTRACTOR
VFD VARIABLE FREQUENCY DRIVE
WM WIREMOLD
WP WEATHERPROOF ENCLOSURE - NEMA 4
DEDICATED NEUTRAL CONDUCTORS ARE REQUIRED FOR ALL 120V AND 277V BRANCH CIRCUITS. MULTIWIRE BRANCH CIRCUITS
WITH SHARED NEUTRAL CONDUCTORS ARE NOT PERMITTED.
ROUTE NO MORE THAN (3) BRANCH CIRCUIT HOMERUNS PER EACH CONDUIT RUN.
GENERAL ELECTRICAL INSTALLATION NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
ALL MOUNTING HEIGHTS ARE TO CENTER OF DEVICE UNLESS OTHERWISE NOTED.
ALL NEW WALL MOUNTED ELECTRICAL DEVICES ARE TO BE INSTALLED FLUSH IN WALL UNLESS OTHERWISE NOTED. ALL ELECTRICAL CONDUIT SHALL BE CONCEALED BEHIND FINISHED WALLS AND ABOVE FINISHED CEILING UNLESS OTHERWISE NOTED. THE COST TO CUT AND PATCH WALLS SHALL BE THE RESPONSIBILITY OF THE TRADE REQUIRING THE CUTTING.
CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS REQUIRED FOR ELECTRICAL WORK.
CONTRACTOR SHALL REPLACE ANY DAMAGED CEILING TILES.
PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW OR RELOCATED WALL OR CEILING MOUNTED DEVICES WITH
ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS.
COORDINATE ALL SHUT-DOWNS OF EXISTING ELECTRICAL SYSTEMS WITH VA COR A MINIMUM OF FOURTEEN (14) WORKING DAYS IN ADVANCE. ALL SHUT-DOWNS SHALL OCCUR DURING WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON
WEEKDAYS ("OFF-HOURS"). INCLUDE ALL PREMIUM TIME CHARGES IN BID.
ALL NOISE GENERATING OPERATIONS, INCLUDING CUTTING OF CEILINGS, WALLS AND FLOORS, CORING, DRILLING, ETC.
SHALL BE SCHEDULED DURING WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON WEEKDAYS ("OFF-HOURS"). INCLUDING
ALL PREMIUM TIME CHARGES IN BID.
CONTRACTOR SHALL CONNECT ALL MECHANICAL EQUIPMENT COMPLETE PER MANUFACTURER'S WIRING DIAGRAMS AND INSTRUCTIONS. COORDINATE WITH MECHANICAL CONTRACTOR AND VERIFY LOCATION, VOLTAGE, AMPS, NO. OF WIRES, AND PROTECTION REQUIREMENTS PRIOR TO ROUGH-IN. CONTACT ENGINEER WITH ANY DISCREPANCIES FROM DESIGN
DRAWINGS.
PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUIT FOR FINAL CONNECTION TO MECHANICAL EQUIPMENT OR OTHER
EQUIPMENT WHICH MAY PROPAGATE VIBRATION.
ALL FLUORESCENT LAMPS THAT WILL NOT BE REUSED SHALL BE DISPOSED OF IN ACCORDANCE WITH EPA STANDARDS, AND WRITTEN EVIDENCE OF PROPER DISPOSAL SHALL BE FURNISHED TO THE OWNER.
ALL WORK SHALL BE PERFORMED IN STRICT CONFORMANCE WITH THE PHASING REQUIREMENTS OF THE PROJECT. ALL
COSTS ASSOCIATED WITH THESE REQUIREMENTS SHALL BE INCLUDED IN THE BID SUBMITTAL.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY LIGHTING TO ADEQUATELY LIGHT ALL CONSTRUCTION AREAS, TEMPORARILY PARTITIONED AREAS, AND EXIT CORRIDORS MAINTAINED DURING CONSTRUCTION.
DEFINITION: "PROVIDE" - FURNISH, INSTALL AND CONNECT COMPLETE.
PROJECT AND PHASING SCOPE LINES INDICATE WHERE GENERAL CONSTRUCTION BOUNDARIES OCCUR. ELECTRICAL
WORK AND UTILITY TIE-INS MAY OCCUR OUTSIDE OF SCOPE LINES.
MOTOR AND MOTOR CONTROLLERS (FLOOR PLAN VIEW)
COMBINATION FUSED MAGNETIC MOTOR STARTER COMPLETE WITH "HAND-OFF-AUTO" SELECTOR SWITCH AND RED "RUN" PILOT LIGHT IN COVER. NEMA SIZE 0 CONTACTS AND NEMA 1 ENCLOSURE MINIMUM UNLESS
OTHERWISE NOTED.
VARIABLE SPEED DRIVE MOTOR CONTROLLER - (REFER TO SPECIFICATIONS SECTION 262911).
CONTROLLER FURNISHED WITH EQUIPMENT
VSD
POWER DISTRIBUTION EQUIPMENT
208/120V-3PH-4W-SN PANELBOARD UNLESS OTHERWISE NOTED
480/277V-3PH-4W-SN PANELBOARD UNLESS OTHERWISE NOTED
SPECIAL PANEL OR PULLBOX - SIZE AND TYPE AS NOTED
NON-FUSED DISCONNECT SWITCH - SIZE AND TYPE AS NOTED, WITH TYPE RK1 FUSES, "NF" INDICATES NOT FUSED
FUSED DISCONNECT SWITCH - SIZE AND TYPE AS NOTED, WITH TYPE RK1 FUSES
WIRE TERMINATIONS
JJ JUNCTION BOX, CEILING OR WALL MOUNTED, 4" SQ. WITH GROUND LUG, UNLESS OTHERWISE NOTED:
TCP - TEMPERATURE CONTROL PANEL. FURNISHED AND INSTALLED BY MC. EC SHALL PROVIDE 120V
CONNECTION.
MOTOR - HORSEPOWER AND VOLTAGE AS NOTED
3/4" MINIMUM SIZE CONCEALED CONDUIT WITH #12 AWG, THWN STRANDED COPPER CONDUCTORS PLUS SEPARATE #12 GROUND ( ), AND CONDUIT WIRE FILLS IN ACCORDANCE WITH N.E.C. - EMT MAY BE USED IN INTERIOR STUD WALLS, AND ABOVE FINISHED CEILINGS. DEDICATED NEUTRAL CONDUCTORS ARE REQUIRED FOR ALL 120V AND 277V BRANCH CIRCUITS. MULTIWIRE BRANCH CIRCUITS WITH SHARED NEUTRAL CONDUCTORS ARE NOT PERMITTED. ROUTE NO MORE THAN (3) BRANCH CIRCUIT HOMERUNS PER EACH CONDUIT RUN.
GENERAL LEGEND
CODED NOTE - "1" INDICATES NOTE NUMBER
REVISION REFERENCE NUMBER
COLUMN REFERENCE GRID
INDICATES EXISTING CONSTRUCTION WALL TYPE
INDICATES DEMOLITION WALL TYPE
INDICATES NEW CONSTRUCTION WALL TYPE
A
LIGHTING FIXTURES LEGEND
LED LIGHTING FIXTURE CONNECTED TO NORMAL CIRCUIT AS INDICATED - TYPE AS SPECIFIED IN SCHEDULE, "A" INDICATES TYPE, "3" INDICATES CIRCUIT NUMBER ASSIGNMENT, "a" INDICATES LOCAL SWITCHING CONTROL.
CONNECT FIXTURES SO THAT ALL LAMPS ARE CONTROLLED BY
LED LIGHTING FIXTURE - CONNECTED TO EMERGENCY LIFE SAFETY LIGHTING CIRCUIT - TYPE AS SPECIFIED IN
SCHEDULE. "A" INDICATES TYPE. CONNECT AHEAD OF LOCAL SWITCHING.
LED LIGHTING FIXTURE CONNECTED TO NORMAL CIRCUIT AS INDICATED - TYPE AS SPECIFIED IN SCHEDULE, "A" INDICATES TYPE, "3" INDICATES CIRCUIT NUMBER ASSIGNMENT, "a" INDICATES LOCAL SWITCHING CONTROL.
CONNECT FIXTURES SO THAT ALL LAMPS ARE CONTROLLED BY
LED LIGHTING FIXTURE - CONNECTED TO EMERGENCY CRITICAL OR LIFE SAFETY LIGHTING CIRCUIT AS
INDICATED
NL - NIGHT LIGHT
EXIT SIGN - CEILING OR WALL MOUNTED - TYPE AS SPECIFIED IN SCHEDULE OR AS INDICATED ON PLANS
C C
C C aS
A
A aS
D
LIGHTING CONTROLS
120/277V SINGLE POLE 0-10VDC LOW-VOLTAGE LARGE PADDLE SWITCH WITH SMALL DIMMER SLIDER, AUTOMATICALLY RETURNS TO PRESET LEVEL - ENGRAVING LABEL - MOUNTED AT 48" AFF UNLESS OTHERWISE
NOTED. VERIFY ALL SWITCHES ARE COMPATIBLE WITH FIXTURE TYPE.
NOTE: REFER TO "DEVICE AND WALL PLATE DETAIL" FOR ADDITIONAL INFORMATION.
S
SMART BUILDING SYSTEM (SBS) LEGEND
SBS FIBER OPTIC TERMINATION PANEL (FOTP). # INDICATE FOTP ID NUMBER. TYPE AS EXISTING. LOCATION INCLUDES SMART BUILDING SYSTEM FIBER NETWORK TERMINATIONS, SYSTEM SWITCH, AND PATCH PANELS FOR
CAT6 COPPER TERMINATIONS FOR SBS DATA OUTLETS.
SBS DATA OUTLET - EC SHALL PROVIDE 2-GANG WALL MOUNTED BOX WITH SINGLE GANG COVER PLATE MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED AND 1-1/4"C WITH PULLWIRE FROM STUBBED AND BUSHED
FROM BOX TO MIN. 96" ABOVE FINISHED FLOOR AT AN ACCESSIBLE LOCATION.
S - DESIGNATES OUTLET IS PART OF THE SBS NETWORK.
# - DESIGNATES THE NUMBER OF DATA JACKS TO PROVIDE. PROVIDE (1) CAT6 CABLE FROM EACH JACK TO THE FOTP COPPER PATCH PANEL. REFER TO SBS SYSTEM FACEPLATE DETAIL FOR ADDITIONAL INFORMATION.
## - DESIGNATES THE FOTP AT WHICH THE DATA CABLES SHALL BE TERMINATED.
S#.##
FOTP #
ALL CONDUITS SHALL BE INSTALLED COMPLETE WITH PULLWIRE.
THE NUMBER OF CABLES IN ANY PATHWAY SHALL NOT EXCEED 40% FILL.
SMART BUILDING SYSTEM GENERAL NOTES:
A.
B.
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F F
H C
F R c c a m p b e ll.
rv t
/2 /2
:4
:1
P M
E0.1
ELECTRICAL LEGEND AND DETAILS
CPCMPL08/09/2019Revisions: Date:
BID ISSUE 08/09/2019
LIGHTING FIXTURE SCHEDULE
BASIS OF
DESIGN IMAGE
TYPE FIXTURE DESCRIPTION MOUNTING
LAMP DRIVER/BALLAST(S) FIXTURE
TYPE COLOR TEMP
LUMEN MAINTENANCE
RATING
EFFICACY TYPE QUANTITY LUMEN WATTAGE VOLTAGE
A 4"H x 3"W x 4'L, LINEAR LED LIGHTING FIXTURE, DIE-FORMED COLD ROLLED STEEL
HOUSING, WHITE BAKED ENAMEL WHITE ENAMEL FINISH, SQUARE FROSTED LENS,
DAMP LOCATION LISTED. PROVIDE CHAIN HANGING KIT FOR 9'-0" MOUNTING HEIGHT.
SURFACE/CHAIN HUNG LED 3500 K L87@60,000 hrs 104 LPW 0-10V DIMMING 1 4564 37 W 277 V
B
9"W x 11"H x 7"D, LED WALL PACK, ONE-PIECE DIE-CAST ALUMINUM BACK BOX WITH
HINGED DOOR, SEALED LED CHAMBER WITH REFRACTIVE LENS FOR FORWARD THROW,
LED DRIVER MOUNTED TO HOUSING FOR HEAT SINKING, BLACK POWDER COAT FINISH,
1P66 WET LOCATION RATED,
WALL LED 4000 K L70@180,000 HRS 105 LPW NON-DIMMING 1 8500 81 W UNIV
ELECTRICAL DEMOLITION NOTES:
COORDINATE DEMOLITION AND REMOVAL OF EXISTING AIR HANDLING UNITS BETWEEN TRADES. CONTRACTOR IS RESPONSIBLE FOR DISCONNECTING AND REMOVING ALL ELECTRICAL EQUIPMENT THAT IS ABANDONED DUE TO DEMOLITION OF EXISTING AIR HANDLING UNIT'S. LABEL ALL EXISTING CIRCUIT BREAKERS TO REMAIN AS SPARE AFTER DEMOLITION OF EQUIPMENT. PROVIDE UPDATED, TYPED DIRECTORIES FOR ALL PANELBOARDS AND SWITCHGEAR
AFFECTED BY THE SCOPE OF THIS PROJECT.
DURING DEMOLITION WORK, REMOVE ALL OTHER CONDUITS AND CONDUCTORS DETERMINED TO BE ABANDONED IN PLACE
TO FACILITATE INSTALLATION OF NEW MECHANICAL EQUIPMENT AND DUCTWORK..
MECHANICAL WORK PERFORMED ON MULTIPLE FLOORS INCLUDES PARTIAL REMOVAL OF EXISTING CEILINGS TO ALLOW ACCESS TO DUCTWORK AND EQUIPMENT ABOVE. CONTRACTOR SHALL INCLUDE TEMPORARY REMOVAL, RESUPPORT, AND REINSTALLATION OF EXISTING LIGHTING FIXTURES, WIRELESS ACCESS POINTS, FIRE ALARM DEVICES, ETC. AS REQUIRED TO ACCOMMODATE MECHANICAL WORK IN THESE AREAS. REFER TO MECHANICAL DEMOLITION PLANS FOR ADDITIONAL
INFORMATION AND WORK REQUIREMENTS.
1.
2.
3.
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F F
H C
F R c c a m p b e ll.
rv t
/2 /2
:2
:0
P M
E0.2
ELECTRICAL ONE-LINE LEGEND,
SCHEDULES, AND PHASING NOTES
CPCMPL08/09/2019
ELECTRICAL PHASING NOTES
AHU 19 INSTALLATION ( PHASE 1)
1.
2.
3.
4.
5.
6.
AHU 18 INSTALLATION (PHASE 2)
1.
2.
3.
AHU 17 INSTALLATION (PHASE 3)
1.
2.
3.
4.
DISABLE SURGERY CHILLER #1 AT 7TH FLOOR TO LIMIT POTENTIAL LOAD ON PANEL 'DPHL71EQ'
ONE AT A TIME, DISCONNECT (4) EXISTING PUMPS FROM EXISTING PANEL 'DPHL71EQ' AND RE-FEED TO EXISTING PANEL 'DPHL72EQ' AS INDICATED. COORDINATE SHUTDOWNS OF PUMPS WITH FACILITIES.
PROVIDE NEW EQUIPMENT AND FEEDERS FOR CONNECTION OF AIR-HANDLING UNIT 19.
A.
B.
C.
D.
CONNECT ALL AHU 19 FANS (SUPPLY, RETURN, AND OUTSIDE AIR) TO NEW PANEL 'DPHL75EQ'.
CONNECT NEW 480:208/120V-3PH-4W TRANSFORMER WITH INTEGRAL PANELBOARD 'LL75EQ' TO NEW PANEL 'DPHL75EQ' AND CONNECT ALL 120V OR 208V LOADS ASSOCIATED WITH AHU 19 TO NEW CIRCUIT BREAKERS
WITHIN PANEL.
RECONNECT EXISTING CHILLERS #1 AND #2 TO…