Drawing Title
Approved:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
CHALMERS P. WYLIE VA AMBULATORY CARE CENTER
Bldg 3 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
CONSULTANTS:
1221 N. Pennsylvania Street, Ste. 200 Indianapolis, IN 46202 317.800.6388
WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERINGC
U s e rs
\m v a n d e rw o u d e \D o c u m e n ts
\1 .1
.1
V
A C o lu m b u s F a llD e te rr e n t B id -A rc h v m v a n d e rw o u d e .r v t
FINAL BID DOCUMENTS
GI000
STWMJV
TITLE PAGE
04/04/2019
757-20-204ADD FALL DETERRENT
TO PARKING GARAGE
855 Grandview Avenue, 3rd Floor Columbus, OH 43215
Phone: (614) 443-1178 Fax: (614) 443-1594
Email: dynamix@dynamix-ltd.com
Facility Engineering Consultants
Engineering Ltd.
Contact:Contact: Contact:
DYNAMIX ENGINEERING LTD.
Doug Smith, PE.
MEP Engineer
855 Grandview Ave.
Columbus, OH 43215 p: 614.443.1178 e: dsmith@dynamix-ltd.com
MECHANICAL,
ELECTRICAL &
PLUMBING
STRUCTURAL
ENGINEERDEPT. OF VETERANS
AFFAIRS
CHALMERS P. WYLIE
AMBULATORY CARE CENTER
Jennifer N. Miller
General Engineer
420 North James Road Columbus, OH 43219-1834 p: 614.388-7332 f: 614.257.5312 e: Jennifer.Miller197e76@va.gov
OWNER
GUIDON DESIGN INC.
Stewart Whitcomb, AIA Architect
1221 N. Pennsylvania St Ste. 200 Indianapolis, IN 46202 p: 317.800.6388 e: swhitcomb@guidondesign.com
ARCHITECT
Contact:
GUIDON DESIGN INC.
Mark VanderWoude, PE Structural Engineer
1221 N. Pennsylvania St Ste. 200 Indianapolis, IN 46202 p: 317.800.6388 e:mvanderwoude@guidondesign.com
VICINITY MAP
LOCATION MAP
Columbus VA ACC
Project Location
ADD FALL DETERRENT TO
PARKING GARAGE
FINAL BID DOCUMENTS
DEPT. OF VETERANS AFFAIRS
CHALMERS P. WYLIE
VA AMBULATORY CARE CENTER
COLUMBUS, OHIO
SHEET LIST - ADD FALL DETERRENT TO PARKING GARAGE
SHEET NUMBER SHEET NAME
GI000 TITLE PAGE
GI100 ABBREVIATIONS, SYMBOLS, AND CODES
GI111 STRUCTURAL GENERAL NOTES
AS300 FALL DETERRENT ELEVATIONS
AS600 FALL DETERRENT DETAILS
Engineering service
757-20-204
Engineering Office
PROJECT DESCRIPTION:
ADD NEW FALL DETERRENT FENCING TO THE
EXISTING PARKING GARAGE ON LEVELS B & C.
Farid Mehr, PE Engineering Services
STO
P
VAN VAN
V A
N
VAN VAN
STOP
ARCHITECTURAL ABBREVIATIONS
A/C AIR CONDITIONING
ACOUS ACOUSTICAL
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH
DISABILITIES ACT
A&E ARCHITECT AND ENGINEERS
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITIES HAVING
JURISDICTION
AHU AIR HANDLING UNIT
ALT ALTERNATIVE
ALT TRANS ALTERNATIVE TRANSPORTATION
ALUM ALUMINUM
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AVG AVERAGE
BB BULLETIN BOARD
BD BOARD
BG BUMPER GUARD
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BO BOTTOM OF
BRG BEARING
CB CATCH BASIN
CBB CEMENTITIOUS BACKER
BOARD
CER CERAMIC
CF CUBIC FEET
CFCI CONTRACTOR FURNISH
CONTRACTOR INSTALL
CFM CUBIC FEET PER MINUTE
CG CORNER GUARD, CEILING
GRILLE
C & G CURB & GUTTER
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNITS
CO CLEANOUT(S)
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
CP CONCRETE PIPE
CPT CARPET
CRS COLD ROLLED STEEL
CS CAST STONE
CSB CONCRETE SPLASH BLOCK
CSI CONSTRUCTION
SPECIFICATIONS INSTITUTE
CT CERAMIC TILE
CTR CENTER
CU FT CUBIC FEET
CUH CABINET UNIT HEATER
CY CUBIC YARD
D DRYER
DEG DEGREE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DISP DISPENSER
DIV DIVISION
DN DOWN
DR DOOR
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
E EAST
(E) EXISTING
EA EACH
EF EXHAUST FAN
EIFS EXTERIOR INSULATION
AND FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATED
ETS EXPOSED TO STRUCTURE
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FF & E FURNITURE FIXTURES & EQUIPMENT
FIN FINISH
FIXT FIXTURE
FL FLOW LINE
FLR FLOOR
FLUORFLUORESCENT
FO FINISH OPENING
FOS FACE OF STUD
FR FIRE RATED
FSP FIRE STANDPIPE
FT FOOT / FEET
FTG FOOTING
FURR FURRING
FV FIELD VERIFY
FVC FIRE VALVE CABINET
FWC FABRIC WALLCOVERING
QA QUALITY ASSURANCE
QT QUARRY TILE
R R-VALUE (INSULATION),
RADIUS, RISER
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RE: REFERENCE
REBAR REINFORCING BAR
REC RECESSED
RECPT RECEPTACLE
REF REFRIGERATOR
REG REGISTER
REINF REINFORCE
REQD REQUIRED
RESIL RESILIENT
REV REVISION
RH ROOF HATCH
RM ROOM
RO ROUGH OPENING
RT RUBBER STAIR TREAD
S SOUTH
SAF SEAMLESS ACRYLIC FLOORING
SAP SUSPENDED ACOUSTICAL
PANELS
SAT SUSPENDED ACOUSTICAL TILE
SB SPLASHBLOCK
SC SEALED CONCRETE, SOLID
CORE
SCHED SCHEDULE
SCP SCUPPER
SD SOAP DISPENSER
SEAL SEALER
SECT SECTION
SF SQUARE FOOT
SF CMU SPLIT-FACE CMU
SHR SHOWER
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SL SLOPE
SLV SHORT LEG VERTICAL
SND SANITARY NAPKIN DISPOSER
SNV SANITARY NAPKIN VENDOR
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SUSP SUSPENDED
SV SHEET VINYL
SYM SYMMETRICAL
SYS SYSTEM
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GD GARBAGE DISPOSAL
GF CMU GROUND FACE CMU
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GI GALVANIZED IRON
GL GLASS
GL BLK GLASS BLACK
GLU LAM GLUE LAMINATED WOOD
GND GROUND
GT GROUT
GYP BD GYPSUM BOARD
HAZ MAT HAZARDOUS MATERIALS
HB HOSE BIB
HC HOLLOW CORE
HCP HANDICAPPED
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
HGT HEIGHT
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR, HANDRAIL
HT HEIGHT
HVAC HEATING, VENTILATING & AIR
CONDITIONING
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IG INSULATING GLASS
IN INCH
INCAN INCANDESCENT
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INV INVERT
ITG INSULATED TEMPERED GLASS
JAN JANITOR
J-BOX JUNCTION BOX
JT JOINT
L LONG
LAV LAVATORY
LB(S) # POUND(S)
LF LINEAL FEET
LLV LONG LEG VERTICAL
LT LIGHT
LVR LOUVER
T TREAD
TB TACKBOARD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TBD TO BE DETERMINED
TD TUBULAR DAYLIGHTING DEVICE
TEL TELEPHONE
TEMP TEMPERATURE
TG TEMPERED GLASS,
TONGUE & GROOVE,
TRANSFER GRILLE
THRU THROUGH
TO TOP OF
TOC TOP OF CONCRETE
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TTD TOILET TISSUE DISPENSER
TV TELEVISION
TYP TYPICAL
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
URN URINAL
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WDP WOOD PANELING
WDW WINDOW
WF WIDE FLANGE
WGL WIRED GLASS
WH WATER HEATER
WR WASTE RECEPTACLE,
WATER RESISTANT
WS WATER STOP
WSCT WAINSCOTT
WT WEIGHT
WWF WELDED WIRE FABRIC
M & BH MOP AND BROOM HOLDER
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MEPF MECHANICAL, ELECTRICAL, PLUMBING,
FIRE PROTECTION (CONDUIT)
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MSB MOP SERVICE BASIN
MTD MOUNTED
MTL METAL
N NORTH
NA NOT APPLICABLE
NECY NECESSARY
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER,
OVERFLOW DRAIN
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED
OWNER INSTALLED
OH OPPOSITE HAND
OPN OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
P PLASTIC
PARTN PARTITION
PBD PARTICLE BOARD
PCC PRECAST CONCRETE
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PR PAIR
PRCST PRECAST
PREFAB PREFABRICATED
PROP PROPERTY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT
PT CONC POST-TENSIONED CONCRETE
PTD PAPER TOWEL DISPENSER
PTL PORCELAIN TILE
PVC POLYVINYL CHLORIDE
XX-XX
XX
X
X XXXX
X
X
X XXXXX
WALL IDENTIFIER
FRAME IDENTIFIER
EQUIPMENT IDENTIFIER
REVISION INDICATOR
ROOM NAME
BUILDING SECTION
REFERENCE
SECTION REFERENCE
BUILDING ELEVATION
REFERENCE
PARTIAL ELEVATION
REFERENCE
ELEVATION INDICATION
ARCHITECTURAL DRAWING SYMBOLS
DRAWING NUMBER
SHEET WHERE DETAIL
IS LOCATED
DRAWING NUMBER
SHEET WHERE DETAIL
IS LOCATED
DRAWING NUMBER DETAIL
SHEET WHERE DETAIL
IS LOCATED
NORTH
NORTH ARROW
HANDICAP
SYMBOL
1337A
PROPOSED DOOR
AND DOOR
NUMBER
COLUMN GRID
IDENTIFIER
MATCH LINE
FIRE EXTINGUISHER,
WALL MOUNT
AUTOMATED EXTERNAL
DEFIBRILLATOR
FEC
AED
ROOM IDENTIFIER
SHEET LOCATION
ROOM NUMBER
VIEW NUMBER
XX ALTERNATE NOTE
DETAIL REFERENCE
EXISTING COLUMN
GRID IDENTIFIER
1 View Name A101 1/8" = 1'-0"
ROOM NAME
S1
BUILDING
OBJECT
REFERENCED
FINISH
FLOOREL. = 100'-0"
FINISH
FLOOREL. = 100'-0"
EXISTING ELEVATION
INDICATION
8'-0" AFF SPOT ELEVATION
INDICATION
SPECIALTIES AND
EQUIPMENT IDENTIFIER
XX
OBJECT
REFERENCED
MATCHLINE
NOT ALL SYMBOLS MAY BE USED
RIGID INSULATION
BLOCKING OR SHIMMING
FINISH WOOD
ROUGH WOOD FRAMING CERAMIC TILE
PLYWOOD
PARTICLE BOARD
ACOUSTIC TILE
EARTH
CONCRETE
GRAVEL STEEL
CONCRETE
MASONRY UNIT
ALUMINUM
BRASS / BRONZE
BATT INSULATION
MATERIALS LEGEND
GYPSUM BOARD
SAND / MORTAR / PLASTER /
CEMENT
GYP. BD. CLG.
OPEN GRID CLG.
PRECAST CONCRETE
BRICK
ACOUSTIC TILE
STRUCTURAL COLUMN
RE: STRUCTURAL
DRAWINGS AND DIMENSIONS
5. THE DRAWINGS AND SPECIFICATIONS, INCLUDING
DRAWINGS PREPARED BY SPECIFIC ENGINEERING
DISCIPLINES (SUCH AS STRUCTURAL, ELECTRICAL)
ARE COMPLEMENTARY; ITEMS SHOWN IN ANY ONE
LOCATION IN THE DRAWINGS SHALL BE CONSIDERED
TO BE REQUIREMENTS OF THE CONTRACT FOR
CONSTRUCTION. IN THE EVENT OF AN
INCONSISTENCY BETWEEN THE DRAWINGS AND
SPECIFICATIONS, OR WITHIN EITHER DOCUMENT, THE
CONTRACTOR SHALL SEEK CLARIFICATION OR
INTERPRETATION FROM THE COR PRIOR TO BIDDING.
WHERE INCONSISTENCIES ARE NOT CLARIFIED PRIOR
TO BIDDING, AND WHERE THE ACTUAL SOLUTION OR
INTENT CANNOT BE REASONABLY INFERRED, THE
CONTRACTOR SHALL PROVIDE THE BETTER QUALITY
OR GREATER QUANTITY OF WORK.
6. USE OF THE WORD "VERIFY" POINTS OUT A
SITUATION WHICH MUST BE CONFIRMED PRIOR TO
PROCEEDING WITH THE WORK, FABRICATION OF
EQUIPMENT, OR ORDERING MATERIAL. NOTIFY THE
COR OF ANY DISCREPANCY
7. THE GENERAL CONTRACTOR SHALL BE
RESPONSIBLE FOR NOTIFYING THE COR IMMEDIATELY
SHOULD ANY DISCREPANCIES BE FOUND IN THE
DRAWINGS AND SPECIFICATIONS.
8. THE GENERAL CONTRACTOR IS RESPONSIBLE
FOR CHECKING ALL FIELD CONDITIONS AND
DIMENSIONS AS THEY RELATE TO THIS PROJECT.
SHOULD DISCREPANCIES EXIST BETWEEN THE WORK
INDICATED AND ACTUAL FIELD CONDITIONS NOTIFY
THE COR PRIOR TO PROCEEDING WITH THE WORK.
9. DO NOT SCALE THE DRAWINGS. DRAWING SCALES
AS INDICATED ARE FOR REFERENCE ONLY AND ARE
NOT INTENDED TO ACCURATELY DEPICT ACTUAL OR
DESIGNATED CONDITIONS. WRITTEN DIMENSIONS
SHALL GOVERN.
1. THESE DOCUMENTS WERE PRODUCED USING THE
CONSTRUCTION SPECIFICATIONS INSTITUTE'S
UNIFORM DRAWING SYSTEM AND THE NATIONAL CAD
STANDARD AS GUIDES.
2. ANY INDICATION OF PROJECT LIMITS OR LINES OF
DEMARCATION ARE SHOWN FOR THE CONVENIENCE
OF THE CONTRACTOR, AND ARE NOT TO BE TAKEN
LITERALLY. ACTUAL CONTRACT LIMITS ARE TO BE
DETERMINED BY THE CONTRACTOR AND APPROVED
BY THE COR BEFORE ACTUAL CONSTRUCTION WORK
BEGINS.
3. DRAWINGS ARE PREPARED USING DIMENSIONS
AND PRODUCT CONFIGURATIONS OR DETAILS OF
SPECIFIC MANUFACTURERS. DIMENSIONS AND
DETAILS FOR SPECIFIC PRODUCTS MAY CHANGE
BEFORE THEY ARE ACTUALLY INCORPORATED INTO
THE WORK, AND PRODUCTS BY OTHER
MANUFACTURERS MAY ALSO BE ACCEPTABLE.
THEREFORE, ACTUAL INSTALLATION DETAILS AND
DIMENSIONS MAY DIFFER FROM THOSE SHOWN.
CONTRACTOR SHALL VERIFY INSTALLATION
REQUIREMENTS FOR ALL PRODUCTS TO BE
INCORPORATED IN THE WORK AND IS RESPONSIBLE
FOR ACCOMMODATING AND COORDINATING
CHANGES TO OTHER MATERIALS OR PRODUCTS THAT
ARE NECESSARY BECAUSE OF THESE DIFFERENCES.
4. THE DRAWINGS, SPECIFICATIONS AND
ATTACHMENTS ARE SEPARATED INTO DISCIPLINES
FOR THE CONVENIENCE. THE SEPARATIONS USED
HEREIN ARE USED ONLY FOR THE PURPOSES OF
CONVENIENCE AND REFERENCE AND IN NO WAY DO
THEY DEFINE OR LIMIT THE SCOPE OR INTENT OF ANY
PART OF THE DRAWINGS, OR OF THE DRAWINGS AND
SPECIFICATIONS AS A WHOLE. THE FACT THAT THE
DRAWINGS ARE SEPARATED IN NO WAY SUGGESTS
THAT THE WORK IS NOT TO BE CONSTRUCTED AS A
COMPLETE, INTEGRATED AND UNIFIED WHOLE.
GOVERNING CODES:
NFPA 101, Life Safety Code, 2018 edition (LSC)
IBC 2018
NFPA 88A Standard for Parking Structures 2019 NFPA 780 Standard for the Installation of Lightning
Protection Systems 2017 Edition
VA DESIGN MANUALS:
VA Parking Design Manual & Demand Model, April 2013 VA Architectural Design Manual, August 2014 VA Electrical Design Manual, December 2015 VA Structural Design Manual, February 2014 VA Physical Security Design Manual - Life Safety, 2015
GENERAL REQUIREMENTS
1. ATTENTION ALL USERS OF THESE DRAWINGS,
GENERAL CONTRACTORS, SUB CONTRACTORS,
MANUFACTURERS, SUPPLIERS: CAREFULLY AND
THOROUGHLY REVIEW THESE GENERAL NOTES. IT IS
YOUR RESPONSIBILITY TO KNOW AND ADHERE TO
THESE REQUIREMENTS.
2. DO NOT PRESUME THAT YOUR SCOPE OF WORK IS
SINGULARLY DEFINED. YOUR SCOPE OF WORK IS
DEFINED THROUGHOUT THE ENTIRE SET OF DRAWINGS,
SPECIFICATIONS AND ATTACHMENTS ARE NOT
CONTAINED IN JUST ONE SERIES OF DRAWINGS OR
DIVISION OF SPECIFICATIONS. YOU MUST REVIEW THE
ENTIRE SET OF CONTRACT DOCUMENTS TO DETERMINE
YOUR SCOPE OF WORK.
3. EVERY EFFORT HAS BEEN MADE TO MAKE THESE
DOCUMENTS CONCISE AND COORDINATED, TO DEFINE
WORK IN THE MOST LOGICAL PLACE AND TO ELIMINATE
REDUNDANCY. KEEP IN MIND HOWEVER THAT YOUR
SCOPE OF WORK CAN BE CONTAINED IN VARIOUS
PLACES, WITH VARYING DESCRIPTIONS. DO NOT
CONSIDER THAT THERE IS ONE CUSTOMARY PLACE TO
LOCATE YOUR WORK. THERE IS A DANGER OF OMITTING
WORK FROM YOUR SCOPE BECAUSE THE ENTIRE SET OF
DOCUMENTS WAS NOT REVIEWED.
4. ELECTRICAL ELEMENTS SHOW INFORMATION IN A
DIAGRAMMATIC FASHION WITHOUT DIMENSIONING. THE
GENERAL CONTRACTOR IS TO COORDINATE THE
LOCATIONS OF ALL MECHANICAL AND ELECTRICAL
EQUIPMENT WITH RESPECT TO THE ARCHITECTURAL
AND STRUCTURAL DETAILING OF SHAFTS, CHASES, AND
SUCH.
5. THE CONTRACTOR SHALL VISIT THE SITE AND
BECOME FAMILIAR WITH SITE CONDITIONS AS THEY MAY
AFFECT CARRYING OUT THE WORK AS DESCRIBED IN
THESE CONTRACT DOCUMENTS. THE CONTRACTOR
SHALL INVESTIGATE, VERIFY, AND BE RESPONSIBLE FOR
ALL CONDITIONS OF THE PROJECT, AND NOTIFY THE
COR OF ANY CONDITIONS THAT REQUIRE MODIFICATION
BEFORE PROCEEDING WITH THE WORK.
GENERAL NOTES:
6. THE CONTRACTOR SHALL PROVIDE ALL
MATERIALS, EQUIPMENT, LABOR, AND SERVICES
NECESSARY TO COMPLETE THE SAFETY
ENHANCEMENT WORK IN AN OPERATIVE AND
FULLY FUNCTIONAL MANNER.
7. ALL PERSONS DIRECTLY OR INDIRECTLY
ASSOCIATED WITH THE PROJECT SHALL BE
FAMILIAR WITH THE RULES AND REGULATIONS OF
THE OCCUPATIONAL SAFETY AND HEALTH ACT,
AND IMPLEMENT THOSE RULES AS THEY APPLY TO
THIS PROJECT.
8. ALL WORK PERFORMED SHALL BE IN
ACCORDANCE WITH THE BUILDING CODES AS
NOTED ON GENERAL INFORMATION (GI) SHEETS
AND AS BELOW.
9. CONTRACTOR SHALL SUBMIT CONFORMATION
OF ORDERED MATERIALS OR ITEMS NECESSARY
TO COMPLETE THE PROJECT WITH PROJECTED
DELIVERY DATE GREATER THAN FOUR WEEKS.
10. ALL SUBCONTRACTORS SHALL SUBMIT SHOP
DRAWINGS AS REQUIRED FOR APPROVAL PRIOR
TO COMMENCING ANY WORK.
11. THE GENERAL CONTRACTOR SHALL BE
RESPONSIBLE FOR THE COORDINATION OF ALL
TRADES AND THE PREVENTION OF CONFLICT
BETWEEN ALL TRADES.
12. THE GENERAL CONTRACTOR SHALL BE
RESPONSIBLE FOR LOCATING AND PROTECTING
ALL UTILITY LINES. LOCATIONS SHOWN ARE
APPROXIMATE. REPAIR ALL DAMAGE TO UTILITY
LINES CAUSED BY CONSTRUCTION OPERATIONS
AT NO COST TO THE OWNER.
Existing building complies with:
ASCE-07-16
ACI 318-14
AISC 360-10
PCI MNL 120-10, Design Handbook
NFPA 70/NEC
NFPA 88A Standard for Parking Structures 2011 International Plumbing Code 2010 ADA Standards for Accessible Design Architectural Barriers Act (ABA) 2006
C. FIRE RESISTANCE RATED SEPARATIONS
The Garage has been designed as nonseparated mixed uses. Incidental uses do not occur so no fire rated separation is required between occupancies. Interior building elements that require fire resistance ratings are listed below, and all are installed to meet these requirements:
BUILDING ELEMENT FIRE RESISTANCE RATING CODE REFERENCE
Exit stair enclosures Open, 0 (1,2) NFPA 88A, 4.1.5
NFPA 101, 42.8.1.1
Exit stair enclosures Open, 0 (1,2) NFPA 88A, 4.1.5
NFPA 101, 42.8.1.1
Ramps Open,0 (1,2) NFPA 101 42.8.3.1.1 (3)
Mechanical Exhaust and Supply duct NFPA 101, 42.8.3.1.2 systems where the duct system is 0 IBC 708.2 located within the garage and serves Excep. 15 only the garage
Other shafts which connect 2 or more stories Open, 0 (1) NFPA 101 42.8.3.1.2
Elevator machine rooms 0 IBC 3006.4 Excep. 2
Emergency generator (if provided) 2
THE WORK IS NOT TO CHANGE, COMPROMISE OR AFFECT FIRE RATED SEPARATIONS IN ANY WAY.
DAMAGED FIRE RATINGS SHALL BE REPAIRED AT NO ADDITIONAL COST TO THE OWNER.
Fire barriers will extend from the top of the floor below to the underside of the floor or roof deck above. The openings and penetrations in required exit enclosures will be protected with self-closing or automatic-closing opening protectives.
Openings in fire resistance rated walls will be protected in accordance with the following:
COMPONENT WALLS AND PARTITIONS FIRE DOOR
ASSEMBLIES (HR) IBC 709 (MIN) IBC 715
Elevator Hoistways, Elevator Machine Rooms 1 60
2 90 Vertical Shafts (including enclosed exit stairways) 1 60
2 90 Exterior walls and walls of shafts and hoistways (HR) IBC 602 and 705. Penetrations in exterior walls with Fire Separation Distance (X) > 30' 0 00
Piping, conduit, and wire penetrations of fire rated construction will be protected by materials or systems of the same hourly rating listed by Underwriters Laboratories (UL), Factory Mutual (FM), or a National Recognized Testing Laboratory (NRTL). Duct, air transfer openings, and other penetrations through floors, shaft enclosures and other fire rated construction will be protected in accordance with the IBC.
D. BUILDING PLACEMENT
NO CHANGE
E. INTERIOR FINISH
NO CHANGE
F. EGRESS LIGHTING AND EXIT SIGNAGE
NO CHANGE
G. MEANS OF EGRESS
NO CHANGE
H. EMERGENCY ELEVATOR OPERATION
Planned and Future elevator will have a smoke/heat detector, located in its respective lobby, on each floor level. Upon activation of a lobby or machine room smoke detector, the elevators served by that lobby or machine room will be recalled to the main level of the building, one at a time. In the event that the alarm is on this designated level, the elevators will be recalled one at a time to an alternate level. It is proposed to recall only the elevator or group of elevators served by the affected lobby or elevator machine room.
After returning to the appropriate level, the elevators will stop, the doors will open, and the elevators will be rendered inoperable without the use of the fireman's key or until such time that they are manually reset to the normal operating mode. This mode of operation is provided for fire department use to allow for access to all levels served by the elevators.
NO CHANGE
K. PORTABLE FIRE EXTINGUISHERS
1. Portable fire extinguishers will be provided throughout the garages as required by IFC section 906.1 and spaced in accordance with NFPA 10, 2010 edition.
NO CHANGE
A. OCCUPANCY CLASSIFICATION
1. The parking garage is classified as Ordinary Hazard storage facilities, and Group S-2 Occupancy.
2. Definitions:
1. Enclosed Parking Structure: Any parking structure that is not an open parking structure.
2. Open Parking Structure: A parking structure that meets the requirements of NFPA 88A Section 4.7.1 as referenced by NFPA 101 Section 42.
i. Each parking level shall have wall openings to the atmosphere for an area of not less than 1.4 square feet for each linear foot of the exterior perimeter.
ii. Opening shall be distributed over a minimum of 40% of the building perimeter or uniformly over two opposing sides.
iii. Interior wall lines and columns shall be at least 20% open, with openings distributed to provide ventilation.
3. Ramp Type Parking Structure: A parking Structure that utilizes sloped ramps for vertical vehicle circulation.
B. CONSTRUCTION CLASSIFICATION
1. The parking garage is to be constructed in accordance with the provisions of NFPA 88A as defined in NFPA
220. Construction type for a building exceeding 25 feet in height shall be Type I, Type II(2) or Type II(1) . An open parking garage of these construction types may be unlimited in height and area.
2. The Parking Garage has two levels above grade and is classified as an OPEN PARKING STRUCTURE. The construction classification is Type IB based upon the occupancy and area of the building.
3. Primary structural elements of Type II (2)buildings will be 2-hour rated, primary structural elements supporting a roof only will be 1-hour rated, and all floor construction will have a fire resistance rating of 2- hours. Primary structural elements of Type II(1) buildings will be 1-hour rated. Primary structural elements supporting a roof only will be 1- hour rated, and all floor construction will have a fire resistance rating of 1- hours.
4. Primary structural members are considered to be bearing walls, columns, and the girders, beams, trusses and spandrels having direct connections to columns and bracing members designed to carry gravity loads. The members of floor or roof panels which have no connection to the columns and do not carry a gravity load are considered secondary members and are not part of the structural frame of a building.
CODE ANALYSIS
A
B
C
D
1 2
E
3 4 5 6 7 8 9 11 12 13 14 15 16 1810
F
40115S 50080 2
DIAGONAL DISTANCE = 361' - 6"
EXIT SEPARATION DISTANCE = 303' - 6"
F E
C
F E
C
F E
C
F E
C
CONTRACTORS PERMITTED TO USE
NORTH PARKING STALLS FOR STAGING AND
STORAGE. COORDINATE WITH COR AND SPEC.
CONTRACTORS PERMITTED TO USE
UNDER-RAMP STORAGE FOR STAGING AND
STORAGE. COORDINATE WITH COR AND SPEC.
SECURE STORAGE
OUT OF SCOPE
ENCLOSED STAIRS
OUT OF SCOPE
DO NOT OBSTRUCT
EGRESS
Drawing Title
Approved:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
CHALMERS P. WYLIE VA AMBULATORY CARE CENTER
Bldg 3 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
CONSULTANTS:
1221 N. Pennsylvania Street, Ste. 200 Indianapolis, IN 46202 317.800.6388
WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERINGC
U s e rs
\m v a n d e rw o u d e \D o c u m e n ts
\1 .1
.1
V
A C o lu m b u s F a llD e te rr e n t B id -A rc h v m v a n d e rw o u d e .r v t
FINAL BID DOCUMENTS
GI100
AROSTW
ABBREVIATIONS,
SYMBOLS, AND CODES
04/04/2019
757-20-204ADD FALL DETERRENT
TO PARKING GARAGE
855 Grandview Avenue, 3rd Floor Columbus, OH 43215
Phone: (614) 443-1178 Fax: (614) 443-1594
Email: dynamix@dynamix-ltd.com
Facility Engineering Consultants
Engineering Ltd.
1" = 40'-0"GI100
FALL DETERRENT CODE PLAN1
Drawing Title
Approved:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
CHALMERS P. WYLIE VA AMBULATORY CARE CENTER
Bldg 3 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
CONSULTANTS:
1221 N. Pennsylvania Street, Ste. 200 Indianapolis, IN 46202 317.800.6388
WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERINGC
U s e rs
\m v a n d e rw o u d e \D o c u m e n ts
\1 .1
.1
V
A C o lu m b u s F a llD e te rr e n t B id -A rc h v m v a n d e rw o u d e .r v t
FINAL BID DOCUMENTS
GI111
DRKSTW
STRUCTURAL
GENERAL NOTES
04/04/2019
757-20-204ADD FALL DETERRENT
TO PARKING GARAGE
855 Grandview Avenue, 3rd Floor Columbus, OH 43215
Phone: (614) 443-1178 Fax: (614) 443-1594
Email: dynamix@dynamix-ltd.com
Facility Engineering Consultants
Engineering Ltd.
GENERAL
THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE METHODS, MEANS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCE TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION OF
NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS, TIEDOWNS, ETC.
THE DRAWINGS SHALL BE USED IN CONJUNCTION WITH CIVIL, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS AND
SPECIFICATIONS.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE FULL WRITTEN MATERIAL SPECIFICATIONS (IF ANY) FOR THE PROJECT. IF A DISCREPANCY OCCURS BETWEEN THE NOTES AND THE FULL SPECIFICATIONS, THE MORE STRINGENT
REQUIREMENT SHALL APPLY.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN ON THE DRAWINGS, SHALL BE MADE WITHOUT
THE APPROVAL OF THE STRUCTURAL ENGINEER.
CONTRACTOR TO COORDINATE ALL EQUIPMENT, ROOF DRAINS, CHASES, AND OTHER ITEMS CONNECTED TO THE STRUCTURE BEFORE
FABRICATION BEGINS.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE HIM TO FABRICATE, ERECT AND CONSTRUCT ALL PARTS OF THE WORK IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE STRUCTURAL ENGINEER. DRAWINGS
SUBMITTED WITHOUT CONTRACTOR'S REVIEW WILL BE RETURNED UNCHECKED.
SUBMIT ELECTRONIC VERSIONS OF SHOP DRAWINGS. SUBMIT SHOP DRAWINGS IN PDF FORMAT.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. STRUCTURAL STEEL (INCLUDING DESIGN CALCULATIONS SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT IS CONSTRUCTED FOR ALL CONNECTIONS NOT SPECIFICALLY DETAILED ON THE DRAWINGS.
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN THOSE SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
MANUFACTURER'S TRADE NAMES AND NUMBERS USED HEREIN ARE ONLY TO IDENTIFY COLORS, FINISHES, TEXTURES, AND PATTERNS AS A BASIS OF DESIGN. PRODUCTS OF AUTHORIZED EQUAL MANUFACTURER'S EQUIVALENT TO COLORS, FINISHES, TEXTURES, AND PATTERNS OF MANUFACTURERS LISTED THAT MEET REQUIREMENTS OF TECHNICAL SPECIFICATIONS IN EVERY RESPECT MAY BE ACCEPTABLE WITH SUBMITTAL OF A COMPLETED SUBSTITUTION REQUEST CONTAINING ALL PRODUCT DATA, TESTING AND ACTUAL
SAMPLES, AND UPON APPROVAL IN WRITING BY CONTRACTING OFFICER.
SUBMIT ELECTRONIC VERSIONS OF PRODUCT DATA IN PDF FORMAT TO THE STRUCTURAL ENGINEER AND COR FOR REVIEW.
1. EXPANSION ANCHORS
2. ADHESIVE ANCHORS
EXPANSION ANCHORS
EXPANSION ANCHORS SHALL BE CARBON STEEL ANCHORS AS MANUFACTURED BY HILTI FASTENING SYSTEMS OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER AND SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
EXPANSION ANCHORS SHALL NOT BE INSTALLED IN CONCRETE UNTIL IT HAS ATTAINED ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE
STRENGTH.
ADHESIVE ANCHORS
ADHESIVE ANCHORS SHALL BE HILTI "HIT HY200" FOR SOLID SUBSTRATE AND HILTI "HIT HY70" FOR HOLLOW SUBSTRATE OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNLESS NOTED OTHERWISE ON PLANS. ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS BY INSTALLERS TRAINED BY THE MANUFACTURER'S
REPRESENTATIVE.
MINIMUM EMBEDMENT DEPTH SHALL BE 8 BOLT DIAMETERS UNLESS NOTED OTHERWISE.
NON-SHRINK GROUT
GROUT SHALL BE A NON-METALLIC, SHRINKAGE RESISTANT (WHEN TESTED IN ACCORDANCE WITH THE LATEST EDITION OF ASTM C827 OR CRD-C621), PREMIXED, NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING PORTLAND CEMENT, SILICA SANDS, SHRINKAGE COMPENSATING AGENTS AND FLUIDITY IMPROVING COMPOUNDS. GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (F'C) OF
5,000 PSI IN 28 DAYS.
STRUCTURAL STEEL
STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO THE ANSI/AISC 360 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, LATEST EDITION WITH AMENDMENTS, AND THE AISC 303 CODE OF STANDARD PRACTICE FOR
STEEL BUILDINGS AND BRIDGES, LATEST EDITION WITH AMENDMENTS.
STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992, 50 KSI.
STRUCTURAL STEEL PLATES AND ROLLED SHAPES OTHER THAN WIDE-FLANGE SHAPES SHALL CONFORM TO ASTM A36, UNLESS NOTED
OTHERWISE.
STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A500, GRADE B.
STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, GRADE B.
ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36, UNLESS NOTED OTHERWISE.
STEEL STUDS SHALL CONFORM TO ASTM A108.
BOLTED CONNECTIONS SHALL CONFORM TO THE SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS, APPROVED BY THE RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS OF THE ENGINEERING FOUNDATION. BOLTED CONNECTIONS FOR STRUCTURAL STEEL MEMBERS SHALL BE MADE WITH 3/4" DIAMETER A325 BOLTS, UNLESS NOTED OTHERWISE.
BOLTED CONNECTIONS SHALL BE TIGHTENED TO THE SNUG TIGHT CONDITION, EXCEPT BOLTED CONNECTIONS IN BRACE ELEMENTS
ARE TO BE FULLY PRETENSIONED WITH CLASS A FAYING SURFACES.
WELDING PROCEDURES SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN WELDING SOCIETY'S STRUCTURAL WELDING
CODE FOR STEEL ANSI/AWS D1.1.
WELDED CONNECTIONS USING ASTM A992 STEEL AS A BASE METAL SHALL BE MADE WITH E70XX LOW HYDROGEN ELECTRODES.
UNLESS OTHERWISE SHOWN OR NOTED ON THE DRAWINGS, OTHER WELDED CONNECTIONS MAY BE MADE WITH STANDARD E70XX
ELECTRODES.
STRUCTURAL STEEL THAT RECEIVES FINISH PAINT SHALL BE SHOP-PRIMED WITH A RUST-INHIBITING PRIMER, UNLESS NOTED OTHERWISE ON THE DRAWINGS. CONTRACTOR SHALL VERIFY PRIMER IS COMPATIBLE WITH FINISH COAT SYSTEM SPECIFIED BY THE
ARCHITECT. COORDINATE FINISH PAINTING REQUIREMENTS WITH THE ARCHITECT.
STRUCTURAL STEEL THAT IS NOT EXPOSED IN THE FINISHED CONSTRUCTION AND DOES NOT RECEIVE FINISH PAINT SHALL NOT BE
SHOP-PRIMED, UNLESS NOTED OTHERWISE ON THE DRAWINGS.
STRUCTURAL STEEL NOTED TO BE GALVANIZED SHALL BE HOT-DIP GALVANIZED IN CONFORMANCE WITH ASTM A123.
DO NOT PAINT OR GALVANIZE THE FOLLOWING SURFACES:
1. SURFACES TO BE WELDED.
2. SURFACES TO RECEIVE BOLTED SLIP-CRITICAL CONNECTIONS.
3. SURFACES TO RECEIVE SHEAR STUD CONNECTIONS.
4. SURFACES TO RECEIVE SPRAYED-ON FIREPROOFING.
ALL ABRASIONS TO GALVANIZED SURFACES OR SURFACES TO RECEIVE AN ARCHITECTURAL FINISH COAT SHALL BE TOUCHED-UP AFTER ERECTION IS COMPLETE. FOR PAINTED STEEL, USE A PRIMER EQUIVALENT TO THE SHOP PAINT. FOR GALVANIZED STEEL, USE
A ZINC-RICH COLD-GALVANIZING PAINT.
DESIGN CONNECTIONS NOT SHOWN IN ACCORDANCE WITH THE ASD SPECIFICATION AND MANUAL OF STEEL CONSTRUCTION. UNLESS NOTED OTHERWISE ON THE DRAWINGS, DESIGN BEAM CONNECTIONS NOT SHOWN, TO SUPPORT A MINIMUM OF A 10 KIP SHEAR REACTION. PROVIDE NO LESS THAN 2 BOLTS IN ANY SINGLE LINE OF BOLTS, UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.
GALVANIZE ALL EXPOSED STEEL.
EXISTING CONDITIONS
WORK SHOWN ON THESE PLANS ASSUMES THAT THE ORIGINAL CONSTRUCTION WAS PERFORMED IN ACCORDANCE WITH THE ORIGINAL PARKING GARAGE DRAWINGS INCLUDING (BUT NOT LIMITED TO) DIMENSIONS, ELEVATIONS, MEMBER SIZES, MATERIALS, DETAILS, ETC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY OF ANY DISCREPANCIES OR CONFLICTS.
WHERE NEW WORK IS TO BE FITTED TO OLD WORK, THE CONTRACTOR SHALL CHECK ALL DIMENSIONS AND CONDITIONS IN THE FIELD, AND REPORT ANY ERRORS OR DISCREPANCIES TO THE STRUCTURAL ENGINEER PRIOR TO THE FABRICATION AND ERECTION OF ANY
NEW MEMBERS.
EXISTING MATERIALS TO BE REMOVED AND REINSTALLED AS PART OF THE PROJECT, THAT BECOME DAMAGED, SHALL BE REPLACED
WITH NEW MATERIAL OF EQUAL QUALITY AND APPEARANCE, AT THE CONTRACTORS EXPENSE.
ALL WORK SHALL BE PREFORMED WITHOUT DAMAGE TO ADJACENT RETAINED WORK. ADJACENT EXISTING CONSTRUCTION SHALL BE
PROTECTED FROM DUST, DIRT, AND DEBRIS ACCUMULATION AT ALL TIMES.
LEVEL A
EL. = 100' - 0"
LEVEL B
EL. = 111' - 4"
LEVEL C
EL. = 122' - 8"
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 18101.5 17.315.5 17
AS600
7' - 8" 5' - 4" 7' - 8" 7' - 8" 5' - 4" 7' - 8" 7' - 8" 5' - 4" 7' - 8" 5' - 4" 6' - 2" 5' - 5" 5' - 5" 7' - 8" 7' - 8" 5' - 4" 5' - 2"
2' - 0" 1' - 0" 2' - 0"
6' - 8" 5' - 4" 6' - 2" 7' - 8" 5' - 4" 7' - 8" 7' - 8" 5' - 4" 7' - 8" 7' - 8" 5' - 4" 7' - 8" 7' - 8" 5' - 4" 7' - 8" 8' - 0"
3' - 5 3/4" VIF
4' - 4"
7' - 8"7' - 6"5' - 6"
AS600
AS600
SIM.
SIM.
SIM.
NEW HSS 12x6x1/2 COLUMNS AND BEAM. BRACE TO METAL STAIR STRUCTURE W/ HSS 6x6x5/6 HORIZONTAL MEMBERS.
PROVIDE FULL-BUTT WELD TO COLUMNS.
AT THIS COLUMN COORDINATE STEEL TUBES
WITH EXISTING LIGHT POLE.
1' - 9 1/2"
/8
/4
V .I .F
PROVIDE STEEL PLATES
PER 15/AS600 AND 16/AS600
V
IF
NOTE: NOMINAL DIMENSIONS SHOWN AT LEVEL C OF THIS ELEVATION ARE FOR FALL DETERRENCE AND FROM CENTER-LINE TO CENTER-LINE OF STEEL TUBE OR CONCRETE COLUMN.
CONTRACTOR SHALL COORDINATE STEEL COLUMN FABRICATOR AND CONNECTIONS WITH WOVEN WIRE MANUFACTURER.
COLUMNS AT COLUMN LINES E5 THROUGH E14 INCLUDE LIGHTNING PROTECTION AIR TERMINALS TO BE RELOCATED, SEE DETAIL 4 AND 5 ON AS600
PROVIDE STEEL TUBE AND FALL DETERRENT IN-SWING GATE PER 10/AS600 ANGLE DETAIL.
HARDWARE SET HW-G3. MOUNT GRADE/FLOOR HARDWARE INTO TOP OF CONCRETE WALL
11' - 6 13/16"20' - 8"20' - 8"20' - 8"20' - 8"19' - 2"3' - 0"19' - 2"30' - 0"20' - 8"20' - 8"20' - 8"20' - 8"
1 1 1 1 1 1 1 1
1 1 1
22' - 6"11' - 2"11' - 4"
VIF
4' - 11 1/2"6' - 6"5' - 4"7' - 8"7' - 10"
AS600
7' - 8" 5' - 4" 7' - 8" 7' - 8" 5' - 4" 7' - 8" 7' - 8" 5' - 4" 7' - 8" 5' - 4" 6' - 2" 5' - 5" 5' - 5" 7' - 8" 7' - 8" 5' - 4" 5' - 2"
2' - 0" 1' - 0" 2' - 0"
6' - 8" 5' - 4" 6' - 2" 7' - 8" 5' - 4" 7' - 8" 7' - 8" 5' - 4" 7' - 8" 7' - 8" 5' - 4" 7' - 8" 7' - 8" 5' - 4" 7' - 8" 8' - 0"
3' - 5 3/4" VIF
AS600
LEVEL A
EL. = 100' - 0"
LEVEL B
EL. = 111' - 4"
LEVEL C
EL. = 122' - 8"
345678911121314151618 10
1.5
AS600
AS600
AS600
AS600
AS600
SEE DETAIL 7/AS600
FOR CORNER DETAIL,
TYP.
SEE DETAIL 7/AS603
FOR CORNER DETAIL,
TYP.
PROVIDE STEEL PLATES
PER 15/AS600 AND 16/AS600
(PLATES ARE BASE BID, NOT
ALTERNATE ITEMS.)
18'-8" VIF
/8
/2
17'-2" VIF
/8
4' - 7"4' - 8"4' - 8"
VIF
4' - 9"
2' - 0" VIF
VIF
4' - 9 1/2"
4' - 6"4' - 8"
VIF
4' - 8 1/2"
VIF
2' - 0"
VIF
3' - 8"4' - 8"
1' - 0"
4' - 8"4' - 8"
NOTE: NOMINAL DIMENSIONS SHOWN IN THIS ELEVATION ARE FOR FALL DETERRENCE AND FROM CENTER-LINE TO CENTER-LINE OF STEEL TUBE OR FACE OF CONCRETE COLUMN. CONTRACTOR SHALL COORDINATE STEEL COLUMN FABRICATOR AND CONNECTIONS WITH WOVEN
WIRE MANUFACTURER.
COLUMNS AT COLUMN LINES B4 THROUGH B11, A15 THROUGH A17, B17 AND B18 INCLUDE LIGHTNING PROTECTION AIR TERMINALS TO BE
RELOCATED, SEE DETAIL 4 AND 5 ON AS600
FALL DETERRENCE BEYOND
(SEE OTHER ELEVATIONS)
EXISTING CHAIN LINK FENCE
20' - 8"20' - 8"20' - 8"
TYPICAL
20' - 8"30' - 0"19' - 2"3' - 0"19' - 2"20' - 8"20' - 8"20' - 8"20' - 8"29' - 0"2' - 0"14' - 0"
8'-8"
VIF
5'-11 5/8" 8' - 3" 8' - 0" 8' - 0" 6' - 11 1/2" 4' - 0" TYP
1 1 1
2' - 1" VIF
4' - 3"4' - 3"4' - 3"
VIF
4' - 3"1' - 1" 2' - 0"
4' - 4"4' - 3"
3' - 3 1/2"3' - 3 1/2"
4' - 3"4' - 3"
VIF
4' - 4"
2' - 1" VIF
4' - 3"4' - 3"4' - 3"4' - 4"
2' - 0" VIF
4' - 8"4' - 8"
1' - 10"
4' - 8"4' - 8"
2' - 0"
4' - 9"4' - 8"
1' - 8"
4' - 8"4' - 9"
2' - 0"
5' - 0"4' - 4"4' - 8"4' - 8"
4' - 5"
VIF
4' - 2"4' - 5" 4' - 4"4' - 6"4' - 6"
1' - 4" VIF
4' - 6"4' - 6"4' - 4" 4' - 3"4' - 6"
1' - 1" VIF
4' - 6"4' - 4" 4' - 6"4' - 6"
11"
4' - 6"4' - 3" 4' - 4"4' - 6"
1' - 0"
4' - 6"4' - 4" 4' - 3"4' - 6"1' - 1"4' - 6"4' - 4"
V
IF
V
IF
/4
V
IF
/4
VIF
6' - 0 1/2"
T Y
P
FALL DETERRENCE VIEWED ON
EDGE (SEE PLAN 5/AS300)
SIM.
TYP.TYP.
4' - 0"
T Y
P TYP
4' - 0"
VIF
4' - 9 3/4"
TYP
4' - 0"
T Y
P
TYP
4' - 0"
EJ
AS600
AS600
AS600
LEVEL A
EL. = 100' - 0"
LEVEL B
EL. = 111' - 4"
LEVEL C
EL. = 122' - 8"
LEVEL D
EL. = 134' - 0"
ABCDEF
AS600
AS6009
AS600
AS600
AS600
AS600
V .I .F
.TYP
V
IF
SEE DETAIL 6/AS600 FOR
CORNER DETAIL, TYP.
SEE DETAIL 6/AS600 FOR CORNER DETAIL,
INSIDE CORNER IS SIMILAR
NOTE: NOMINAL DIMENSIONS SHOWN IN THIS ELEVATION ARE FOR FALL DETERRENCE AND FROM CENTER-LINE TO CENTER-LINE OF STEEL TUBE OR CONCRETE COLUMN. CONTRACTOR SHALL COORDINATE STEEL COLUMN FABRICATOR AND CONNECTIONS WITH WOVEN WIRE MANUFACTURER.
45' - 0"62' - 0"62' - 0"
/2
1 1 1 1 1
TYP
4'-8" 8'-8" 8'-8" 8'-8" 8'-8" 8'-3"
VIF
1'-1"
2'-2 1/2" VIF
VIF
1'-0"
VIF
3'-0"
VIF
1'-0"VIF
1'-0"3'-6" 3'-11" 3'-11"
VIF
1'-0"
TYP
4'-8"
TYP
TYP
TYP
LEVEL A
EL. = 100' - 0"
LEVEL B
EL. = 111' - 4"
LEVEL C
EL. = 122' - 8"
A B C D E F
PROVIDE 12x6 STRUCTURAL TUBING WELD TO STEEL
POSTS, BRACE TO METAL STAIR W/ 6X6 STEEL
TUBING, - SEE SOUTH ELEVATION 1/AS300
FALL DETERRENCE BEYOND
(SEE OTHER ELEVATIONS)
62'-1"
6' - 6"
FALL DETERRENCE VIEWED ON
EDGE (SEE PLAN 5/AS300)
T .O
A
N G
L E
V
.I .F
NOTE: NOMINAL DIMENSIONS SHOWN IN THIS ELEVATION ARE FOR FALL DETERRENCE AND FROM CENTER-LINE TO CENTER-LINE OF STEEL TUBE OR FACE OF CONCRETE COLUMN.
CONTRACTOR SHALL COORDINATE STEEL COLUMN FABRICATOR AND CONNECTIONS WITH WOVEN WIRE MANUFACTURER. VERIFY EXISTING CONCRETE DIMENSIONS IN FIELD.
4' - 7 1/2"
62' - 3" 44' - 0" 18' - 0"
1 1 1 1 1
VIF
3' - 2"
VIF
8'-6" VIF
1'-3 1/2"
VIF
4'-11 3/4"
TYP
8'-4"
TYP
8'-4"
TYP
8'-4"
TYP
8'-4"
VIF
4'-6 3/4"
VIF
8'-3 3/4"
VIF
1'-5"
VIF
4'-9 7/8"
AS600
AS600
AS600
AS600
AS600
AS600
LIGHTNING PROTECTION AIR
TERMINALS TO BE RELOCATED,
SEE DETAIL 4 AND 5 ON AS600
PROVIDE FALL DETERRENT FENCE TO 8'-6" PER
5/AS600 AND 8/AS600. WELD FULL WIDTH OF TUBE
STEEL TO METAL STAIR AT BOTH FLANGES OF STEEL
SUPPORTING DECK.
4' - 4"
2' - 11" VIF
4' - 4"
ALTERNATES:
1. OMIT MATERIAL, LABOR AND SCHEDULE TO PROVIDE FALL
DETERRENCE AT B DECK IN THE INDICATED STRUCTURAL BAYS.
NOTE: NOT ALL ALTERNATE SYMBOLS WILL BE USED ON EACH SHEET
ADDITIONAL SCOPE NOTES
1. EXISTING PARKING GARAGE ON SITE WILL BE MADE
AVAILABLE FOR PRE-BID TOUR AND OBSERVATION.
2. PROVIDE NEOPRENE WASHERS OR SEALANT ALL
JOINTS, CRACKS OR CONNECTIONS WHICH OCCUR
WHERE DISSIMILAR MATERIALS INTERSECT
PERPENDICULAR TO EACH OTHER, UNLESS INDICATED
OTHERWISE ON THE DRAWINGS.
3. PROVIDE PRE-GALVANIZED (AKA GALVANIZED
BEFORE WEAVE) WIRE MESH 1”X 1”, 11 GA. WIRE WITH
BAR-FRAME THAT DRAINS ACCUMULATED
PRECIPITATION TO FORM PANELS OF NOMINAL SIZES
INDICATED.
4. PROVIDE ADDITIONAL JOINTS AND FASTENERS AS
REQUIRED PER MANUFACTURE'S RECOMMENDATIONS.
INDICATE WITHIN SHOP DRAWING SUBMITTAL FOR
APPROVAL.
5. HANDLE ALL GALVANIZED MATERIAL WITH CARE. IF
GALVANIZED COATING IS DAMAGED DURING
INSTALLATION, CONTRACTOR MUST REPLACE OR
REPAIR THE MATERIAL AT NO COST TO OWNER.
6. PROVIDE ATTIC STOCK OF WIRE MESH PANELS WITH
SPARE PARTS( BOLTS, WASHERS, NUTS AND 1 1/2" X 1
1/2" 3/16 BENT ANGLES) OF QUANTITY INDICATED AND
MATCHING FIELD VERIFIED SIZES OF INSTALLED:
TWO 4'-4" @ 4'-9" TALL
FOUR 8'-4" @ 4'-9" TALL
TWO 1'-4" @ 8'-0" TALL
FOUR 4'-4" @ 8'-0" TALL
TEN 3/16 BENT ANGLES @ 8' LONG
PROVIDE FOUR 8'-0" TALL STEEL TUBE COLUMNS AND
FOUR 4'-9" TALL STEEL TUBE COLUMNS AS DETAILED
ON AS/600.
LENGTHS LISTED ARE NOMINAL, COORDINATE ACTUAL
LENGTHS WITH ADJACENT COLUMN PER DETAILS 1, 2,
AND 6 /AS600
E
1615.5
L5X5X5/16
L X
X
/1
L5X5X5/16
L X
X
/1
10' - 9"
AS600
GALV. WIRE MESH 1" X 1" SQUARE
OPENING W/ PVC- COATED 'BAR'-FRAME.
MATERIAL TO MATCH VERTICAL BARRIERS
AS600
Sim
AS600
Sim
AS600
18 AS600
Sim
NOTE: PROVIDE RAIN WEEPS IN ALL TUBE AND ANGLE
STEEL AS REQUIRED WHERE WATER WILL
ACCUMULATE
ISOMETRIC PHASING VIEW
LEVEL A
100'-0" GRADE
LEVEL B
111'-4"
LEVEL C
122'-8"
BASE BID - LEVEL C + RAMP:
PHASE 1
ALTERNATE BID ITEM -
LEVEL B: PHASE 2
STORAGE AND STAGING
AREA - LEVEL A.
COORDINATE WITH VA/COR
CONTRACTORS SHALL COORDINATE OBSTRUCTED
PARKING SPACES WITH COR.
VA ANTICIPATES 10 PER DAY,
BUT WILL PERMIT MORE TO ACCELERATE THE WORK.
PROVIDE CONTROL OF
PERIMETER AS SPECIFIED IN
SECTION 013526 - SAFETY
REQUIREMENTS
Drawing Title
Approved:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
CHALMERS P. WYLIE VA AMBULATORY CARE CENTER
Bldg 3 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
CONSULTANTS:
1221 N. Pennsylvania Street, Ste. 200 Indianapolis, IN 46202 317.800.6388
WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERINGC
U s e rs
\m v a n d e rw o u d e \D o c u m e n ts
\1 .1
.1
V
A C o lu m b u s F a llD e te rr e n t B id -A rc h v m v a n d e rw o u d e .r v t
FINAL BID DOCUMENTS
AS300
STWARO
FALL DETERRENT
ELEVATIONS
04/04/2019
757-20-204ADD FALL DETERRENT
TO PARKING GARAGE
855 Grandview Avenue, 3rd Floor Columbus, OH 43215
Phone: (614) 443-1178 Fax: (614) 443-1594
Email: dynamix@dynamix-ltd.com
Facility Engineering Consultants
Engineering Ltd.
3/32" = 1'-0"AS300
SOUTH ELEVATION1
3/32" = 1'-0"AS300
NORTH ELEVATION2
3/32" = 1'-0"AS300
EAST ELEVATION3
3/32" = 1'-0"AS300
WEST ELEVATION4
PROVIDE THE PAIR OF GATES WITH THE FOLLOWING:
PADLOCK WITH NEW CYLINDER PER KEYWAY UPGRADES, REQUEST KEYWAY
UPGRADE SPECIFICATIONS/DETAILS FROM COR/VA.
SIX (6) BOLT-ON HEAVY DUTY 3000 LBS HINGES W/ 120 DEGREE MOVEMENT.
PROVIDE 3" 90 DEGREE ANGLE BRACKET AND MATCHING 2.5"H x 1.5"W x 2"D
HASP WITH HOLE TO MATCH PADLOCK. WELD TO GATE FRAME AT 6'-0" AFF.
PROVIDE DROP BOLT, G90 GALV., 5/8" DIA OF 19" L (MIN) WITH 12" VSA
ALUMINUM HOUSING, BOLT TO STEEL TUBE PROVIDE HEAD-BLOCK FOR SELF-
LOCKING.
PROVIDE 1" OD. ASTM A500 PIPE AS DROP BOLT RECEIVING TUBE. PROVIDE
PIPE CONNECTION TO GATE AND CONCRETE WALL PER SPECIFICATION 05 50
00 IN THE REFERENCE DOCUMENTS.
ADDITIONAL REQUIREMENTS PER 08 71 00, HARDWARE SPECIFICATIONS OF
EXISTING PROJECT 757-201 CONSTRUCT PARKING GARAGE
HW-G3 (HARDWARE SET GATE TYPE 3)
1/4" = 1'-0"AS300
ENLARGED EAST TOWER ROOF PLAN5
GALV. WIRE MESH 1" X 1" SQUARE
OPENING OF 11 GA. GALV. WIRE W/ "BAR"
FRAME. SHOP BOLT OR WELD BAR FRAME
TO WIRE MESH
S E
E E
L E
V A
T
IO
N S
S E
E E
L E
V A
T
IO
N S
STEEL PLATE AND ANGLE, BELOW. PER
STRUCTURAL SECTIONS 11, 12, AND 13
AS600
EXISTING CAST-IN PLACE
WALL, BELOW
3x4x1/4 GALV. STEEL ANGLE, PROVIDE
1" SLOT THROUGH-BOLT W/ NEOPRENE
WASHERS TO BAR FRAME, TYP.
INTERIOREXTERIOR
3x4x1/4 GALV. STEEL ANGLE BRACKET, THROUGH-BOLT TO STRUCTURAL TUBE, WITH TAMPER RESISTANT FASTENER, TYP.
ETR
10"
STRUCTURAL TUBE, ALIGN
TO FACE OF CONCRETE, TYP.
M
IN
TYP.
3"
INTERIOREXTERIOR
ETR
10"
STEEL BENT PLATE, BELOW. BOLT TO
CONCRETE, WELD TO TUBE TYP.
CAST-IN PLACE WALL AND
COLUMN, BELOW
3x4x1/4 STEEL ANGLE, PROVIDE 1" SLOT
FOR THROUGH-BOLT TO BAR FRAME,
W/ NEOPRENE WASHERS TYP.
THROUGH-BOLT TO STRUCTURE TUBE,
ROUNDED HEADS ONLY WITHIN GAP, TYP.
M
IN
/2
M A
X C
L R
M
IN
/2
PROVIDE 24" TALL 16 GA. GALVANIZED
STEEL 'CAP GUARD' AT COLUMN CAPS TO
COVER SIDES, ANCHOR TO CONCRETE
COLUMN AND STEEL TUBES.
E Q
E Q
S E
E E
L E
V A
T
IO
N S
E E
E L
E V
A T
IO
N
GALV. WIRE MESH 1" X 1" SQUARE
OPENING OF 11 GA. GALV. WIRE W/
"BAR" FRAME, SHOP ASSEMBLED
TO STEEL ANGLES, TYP.
GALV. WIRE MESH 1" X 1" SQUARE
OPENING OF 11 GA. GALV. WIRE W/
"BAR" FRAME, SHOP ASSEMBLED
TO STEEL ANGLES, TYP.
ETR
2'-0".EXISTING CAST-IN
PLACE WALL
V .I .F
S E
E E
L E
V O
N A
S
STEEL PLATE AND ANGLE BEYOND.
REF.: 13/AS600
STRUCTURAL STEEL TUBE
3x4x1/4 STEEL ANGLE @ 4'-0" O.C. MAX.
BOLT TO BAR-FRAME, THROUGH-BOLT
TO STRUCTURE TUBE.
INTERIOREXTERIOR
M A
X
GALV. WIRE MESH 1" X 1" W/ "BAR" FRAME.
GALV. BENT ANGLE 1 1/2 X 1 1/2
X 3/16"
EXISTING CAST-IN
PLACE WALL
STEEL PLATE BEYOND. REF.:
13/AS600
INTERIOREXTERIOR
GALV. BENT ANGLE 1 1/2 X 1 1/2
X 3/16"
1' -5
M
IN
CONNECT EXISTING LIGHTING PROTECTION SYSTEM
WHERE INSTALLED, BOND LIGHTNING PROTECTION
W/ FITTING
3x4x1/4 STEEL ANGLE @ 2'-0" O.C. MAX
BEYOND. BOLT TO BAR FRAME, THROUGH-
BOLT TO STRUCTURE TUBE, TYP.
.0
NOTE: FOR FURTHER MATERIAL CALL OUTS REFER TO DETAIL 5 - AS600
GALV. WIRE MESH 1" X 1" W/ "BAR" FRAME.
GALV. BENT ANGLE 1 1/2 X 1 1/2
X 3/16"
GALV. WIRE MESH 1" X 1" W/ "BAR" FRAME.
EXTEND LIGHTNING PROTECTION
SYSTEM, RE-INSTALL EXISTING AIR
TERMINAL WHERE THEY OCCUR W/
THERMALBOND PER NFPA 780.
ETR
2'-0"
EXISTING CAST-IN
PLACE WALL
GALV. STEEL 4X4X1/2 HSS,
UNO, TYP.
INTERIOREXTERIOR
STEEL 16 GA. GALV.
STEEL GUARD W/ SIDE
FLANGE, FIT TO
CONCRETE COLUMN
TOP ON THREE SIDES.
PROVIDE RAIN WEEP IN
EACH COLUMN.
FULL WELD MITER
CONNECTION TO
4X4X1/2
WELDED CAP
M
IN
1'-0" MAX
.0
EXISTING TRAFFIC
BARRIER CABLES
INTERIOREXTERIOR
STEEL TUBING SUPPORT BEYOND.
REF.: 12/AS600
GALV. WIRE MESH 1" X 1", W/ 'BAR'
FRAME
CONNECT EXISTING LIGHTING PROTECTION
SYSTEM WHERE INSTALLED, BOND LIGHTNING
PROTECTION W/ FITTING
EXISTING CAST-IN
PLACE SLAB
STEEL PLATE BEYOND, REF.: 12/AS600
A B
O V
E D
E C
K
1' -5
T Y
P
M A
X
EXTEND LIGHTNING PROTECTION
SYSTEM, RE-INSTALL EXISTING AIR
TERMINAL WHERE THEY OCCUR W/
THERMALBOND PER NFPA 780.
GALV. BENT ANGLE 1 1/2 X 1 1/2
X 3/16"
GALV. WIRE MESH 1" X 1", W/ 'BAR'
FRAME
GALV. WIRE MESH 1" X 1", W/ 'BAR'
FRAME
SEE ELEVATIONS
V .I .F
S E
E
/A S
PREVIOUSLY INSTALLED
CAST-IN PLACE WALL
TUBE STEEL. SEE ELEVATIONS FOR
SPACING, TYP.
ANCHOR TUBE STEEL TO
CONCRETE
RE: 12/AS600
3x4x1/4 STEEL ANGLE BRACKET, TYP.
BOLT W/ ACORN NUT & NEOPRENE
WASHER BETWEEN FRAME AND
STEEL.
1" TYP
GALV. WIRE MESH 1" X 1" SQUARE
OPENING
GALV. 'BAR'
FRAME
GALV. 'BAR'
FRAME
GALV. BENT
ANGLE
PREVIOUSLY INSTALLED
CAST-IN PLACE WALL, TYP.
M A
X
SEE ELEVATIONS
S E
E E
L E
V
EXISTING CAST-IN PLACE WALL
TUBE STEEL, TYP. REF.; 14/AS600.
SEE ELEVATIONS FOR SPACING.
GALV. WIRE MESH 1" X 1" SQUARE
OPENING
3x4x1/4 STEEL ANGLE BRACKET, TYP.
BOLT W/ ACORN NUT & NEOPRENE
WASHER BETWEEN FRAME AND
STEEL.
1" TYP
24" STEEL PLATE, WELDED TO TUBE
STEEL. ANCHOR TO CONCRETE WALL.
REF.: 12/AS600
GALV. "BAR" FRAME
GALV. 'BAR' FRAME
GALV. BENT ANGLE 1 1/2 X 1 1/2
GALV. BENT ANGLE 1 1/2 X 1 1/2
SHOP-WELD TO BAR FRAMES
4" TYP. 4" TYP.
INTERIOREXTERIOR
ETR
10"
GALV. WIRE MESH 1" X 1"
SQUARE OPENING
STEEL ANGLE BELOW, PER STRUCTURAL
SECTIONS AS600
CAST-IN PLACE WALL, BELOW
ANGLE, PROVIDE 1" SLOT FOR THROUGH-
BOLT TO 'BAR' FRAME, W/ NEOPRENE
WASHERS TYP.
GALV. "BAR" FRAME
GALV. BENT ANGLE BELOW, SEE
AS600 SECTIONS
THROUGH-BOLT TO STRUCTURE TUBE,
FLAT HEADS ONLY WITHIN GAP.
PROVIDE HW-G3 HARDWARE AS
INDICATED ON AS300
S E
E E
L E
V A
T
IO
N S
E E
E L
E V
A T
IO
N
S
STEEL ANGLE BELOW.
IN-SWING STEEL 5X5X5/16 TUBING FRAMED GATE.
MATCH SECTION IN HEIGHT WITH STRAIGHT
PROFILE (REF 14/AS600 FOR BACK BEND). SEE
AS300 ELEVATIONS FOR WIDTH TO CL.
AS600
(ABOVE)
NOTE: ALL EXPOSED STEEL
SHALL BE GALVANIZED
ETR
2'-0"
EXISTING CAST-IN
PLACE WALL
INTERIOREXTERIOR
1/4 4" MIN
1/2" x 6" (HORIZ) x 8" (VERT) x
REQ'D BENT PLATE W/ (2) 5/8" DIA.
EXPANSION ANCHORS @ 3" MIN.
SPACING WITH 5" MIN. EMBED
HSS5x5x5/16 TUBE
.0
PROVIDE RAIN WEEP
WHERE WATER MAY COLLECT IN STEEL.
DO NOT PROVIDE SEALANT BETWEEN
PLATES AND EXISTING CONCRETE , TYP.
HSS4x4x1/2
1/2" x 4" (HORIZ) x 8" (VERT) x REQ'D GALV.
BENT PLATE W/ (2) 1/2" DIA. EXPANSION
ANCHORS @ 3" SPACING W/ 4" MIN. EMBED.
3/8 3" MIN.
7/8" x 10" (HORIZ) x 1'-2"
(VERT) GALV. PLATE W/
(4) 1/2" DIA. EXPANSION
ANCHORS W/ 3 1/4" MIN.
EMBED.
GALV. PLATES. DO NOT INSTALL SEALANT
BETWEEN PLATES AND CONCRETE.
PROVIDE RAIN WEEP
WHERE WATER MAY
COLLECT IN STEEL.
DO NOT PROVIDE SEALANT
BETWEEN PLATES AND
EXISTING CONCRETE , TYP.
1' - 0" ETR
STEEL TUBE JAMB POST BEYOND.
PRE-GALV. WIRE MESH 1" X 1"
SQUARE OPENING W/ GALV.
'BAR' FRAME
PRE-GALV. WIRE MESH 1" X 1"
SQUARE OPENING W/ GALV.
'BAR' FRAME
A B
O V
E D
E C
K
'-3
GALV. BENT 4 X 6
X 3/16 ANGLE
INTERIOREXTERIOR
3x4x1/4 STEEL ANGLE
BRACKET, TYP.
15.00°
INTERIOR
EXTERIOR
GALV. WIRE MESH 1" X 1" W/ SQUARE
OPENING W/ GALV. 'BAR' FRAME
STEEL PLATE BELOW, W/ 2 BENT LEGS.
BOLT TO CONCRETE, WELD TO TUBES.
CAST-IN PLACE WALL AND
COLUMN, BELOW
3x4x1/4 STEEL ANGLE, PROVIDE 1" SLOT FOR
THROUGH-BOLT TO 'BAR' FRAME, W/
NEOPRENE WASHERS TYP.
THROUGH-BOLT TO STRUCTURE TUBE,
ROUNDED HEADS ON WOVEN WIRE SIDE,
TYP.
PROVIDE 24" TALL 16 GA. GALVANIZED
STEEL ANGLED 'CAP GUARD' AT COLUMN
CAPS TO COVER SIDES, ANCHOR TO
CONCRETE AND STEEL COLUMNS.
REVERSE AT INSIDE CORNER.
/2
4 1/2" 2" 1"
GALV. STEEL BENT PLATE, BELOW. BOLT
TO CONCRETE, WELD TO TUBE.
INSIDE CORNER DETAIL IS SIMILAR; PROVIDE "L" SHAPED FOOTPRINT FOR 'CAP GUARD'
INSTEAD OF SQUARE. SLOPE TO DRAIN AND PREVENT FOOT-HOLDS. WIRE MESH PANELS
AND ANGLES W/ BOLT-SLOT REVERSED.
TOP SECTION MESH IN KICK-BACK SECTION SHALL HAVE 'BAR'-FRAME & WIRE MESH MITERED
FOR A 45 DEGREE CORNERS AND SHOP WELDED. BOTH TUBES OF COLUMNS SHALL BE MITERED
22.5 DEGREES FROM A PLANE PERPENDICULAR TO OPPOSING CORNER AXIS, AND SHOP
ASSEMBLED FOR 45 DEGREE ROTATION IN PLAN.
ANCHOR WIRE MESH W/ 3X4X1/4 GALV. BENT PLATES W/ SLOTS IN SHORT LEG, BENT TO 45
DEGREES.
SEE ELEVATIONS
S E
E E
L E
V A
T
IO
N S
6 1/2" M A X
. VIF
MITERED GALV. STEEL TUBES TO ROTATE IN
PLAN AND SUPPORT BENT ANGLES (ABOVE)
9 10
PLATE FLUSH W/ COLUMN
FACE. DO NOT BOLT INTO
SECOND COLUMN.
A,B,E
1/4" x 3'-0" STAINLESS STEEL
PLATE W/ 3/4" DIA. EXPANSION
ANCHORS (2 1/2" MIN. EMBED.)
SEE 15/AS600 FOR SPACING
NOTES:
1. INSTALL PLATES AT THE FOLLOWING (5 )LOCATIONS: LEVEL B,
COLUMNS A-9/A-10, B-9/B-10, AND E-9/E-10; LEVEL C, COLUMNS
B-9/B-10 AND E9/E10
2. INSTALL PLATE ON INNER FACE OF COLUMNS, FACING PARKING
AREA.
9 10 3' - 0"
A
T L
E V
E L C
A T
L E
V E
L B
1' - 0"1' - 0"1' - 0"
M A
X
G
A P
SLAB
6"
1/4" x 3'-0" STAINLESS
STEEL PLATE
T Y
P
1/4 3"
3/4" x 6" (HORIZ.) x
1'-6" (VERT.) PLATE
(GALV) W / (4) 1/2" DIA.
EXPANSION ANCHORS
W/ 2 1/2" EMBED.
NOTE: CONTRACTOR TO COORDINATE BOLT LOCATIONS AND AVOID
CONFLICT WITH EXISTING REINFORCEMENT AND TENSION CABLES IN
CONCRETE. OWNER WILL PROVIDE SHOP DRAWINGS AND DOCUMENTS
L6x3 1/2x1/2 x 6" LONG
GALV. STEEL ANGLE
W/ (2) 1/2" DIA. EXP.
ANCHORS W/ 2 1/2"
EMBED
3/8"
1/2" DIA. EXPANSION ANCHOR @ 18" O.C.
PROVIDE GALV. WASHER TO FILL 3/8" GAP
BETWEEN ANGLE AND CONCRETE
GALV. HSS 4x4x1/4 FRAME FOR
WIRE MESH PANEL.
L5x5x5/16 GALV. STEEL ANGLE
REINFORCED
CONCRETE BEAM - SEE
PLAN
1/4 2@12
EXISTING ROOFING, FLASHING AND DECK,
PROTECT OR REPAIR AT NO ADDITIONAL
COST TO OWNER.
GALV. WIRE MESH 1" X 1" SQUARE
OPENING W/ GALV. 'BAR'-FRAME BOLT
W/ GALV. BOLT, ACORN HEAD &
NEOPRENE WASHER AT 24" MAX. O.C.
SHOP DRILL WEEPS @ 24"
O.C., ALIGN THROUGH
ANGLE AND HSS 4X4X1/4
15.5
1/4 2"
L3x3x1/4 WELDED
ANGLE CONNECTION
AT L5x5
INTERSECTIONS
1 1/2" = 1'-0"AS600
TYPICAL STEEL POST PLAN DETAIL1
1 1/2" = 1'-0"AS600
PLAN DETAIL AT CONCRETE COLUMNS2
1" = 1'-0"AS600
SECTION W/O BACK BEND3
1" = 1'-0"AS600
DETERRENT SECTION AT C DECK4
1" = 1'-0"AS600
TYP. POST SECTION AT COLUMNS9
1" = 1'-0"AS600
DETERRENT SECTION AT CABLE BARRIER5
3/4" = 1'-0"AS600
TYP. AT B DECK OR W/ STRUCTURE ABOVE7
3/4" = 1'-0"AS600
TYPICAL LEVEL C ELEVATION81 1/2" = 1'-0"AS600
IN-SWING GATE HINGE DETAIL101" = 1'-0"AS600
STRUCT. SECTION AT COLUMNS11
1" = 1'-0"AS600
STRUCT. SECTION AT WALL/COLUMNS13
1" = 1'-0"AS600
TOP SECTION AT GATE, TYP.14
1 1/2" = 1'-0"AS600
PLAN DETAIL AT COLUMN CORNERS6
1/2" = 1'-0"AS600
EXPANSION JT PLATE DETAIL16
1/2" = 1'-0"AS600
EXPANSION JT PLATE DETAIL15
3/4" = 1'-0"AS600
STRUCT. SECTION AT DECK12
3/4" = 1'-0"AS600
STRUCTURAL SECTION17
3/4" = 1'-0"AS600
CONN. DETAIL18
NOTE: STEEL COLUMNS SHALL BE SHOP
GALVANIZED. COORDINATE GALVANIZING W/
BONDING AT ANY EXISTING LIGHTNING PROTECTION
INSTALLATION, WHICH MAYBE INCOMPLETE
Drawing Title
Approved:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawi…