36C25018B0222-00005002.pdf
PDF 6 MB Posted
- Attached to
- 552-161: Community Living Center Federal contract opportunity
- Solicitation number
- 36C25018B0222
About this file
36C25018B0222 00005 Addendum #1 - Part 2.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25018B0222-00005005.pdf | ||
| 36C25018B0222-00005004.pdf | ||
| 36C25018B0222-00005001.pdf | ||
| 36C25018B0222-00005000.docx | DOCX document | |
| 36C25018B0222-00005003.pdf | ||
| 36C25018B0222-00004000.docx | DOCX document | |
| 36C25018B0222-00003000.docx | DOCX document | |
| 36C25018B0222-00003001.pdf | ||
| 36C25018B0222-00002000.docx | DOCX document | |
| 36C25018B0222-000.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EEEE
OS
OS
K/3
OS
OS
K/3
OS
OS
OS
DM
OS
DM
3/DM
OS
K/3
OS OS OS
DM
DM
O S
OS
DM
3/DM
3/DM
D M
D M
D M
D M
DM
DM
K/3
DM
L
J J
J J
J J J J
J
J
J
J
J
J
J
J
JJJJ
J
J
J
J
K/3
K/3
KK/3 K/3K
3/DM
D M
D M
PC
3/DM
3/DM
O S
O S
OS
3LC
OS
DM
JJ
WP/GF
W P/G
F
OS
F F
NT
K F F
F
J
S
N 3
A
AM
C
GF
J
B D
A C
HE
I
350EL101
MATCHLINE MATCHLINE
EF2 EF2
EF1 EF2
EF2
EF2
EF2
EF2 EF2
K1a
EF1EF1EF1
EF2 EF2
EF1 EF1
P2
P1
P1
P1 w u
K1a
UC2
UC2
UC2 UC2P4
P4
P4
F1c F1c F1c
F1c F1cF1c
EF2
EF2
F1a
F1a
F1a
C1
C1 C1
C1 C1
C1 C1
C1
C1
C1
C1
K1a
F1b
F1b
P2
A2
W1
K1a
C1 C1 u
UC2
K1b a b a
F1b
C1
C1C1C1C1
2 2
A2
EF2
A2
A2
A2
K1a K1a
CF1
2 2 b
A2
A2
EF2
UC2 UC2
F2a F2a
F2a F2a
F2a F2a
F2b
F2b
F2b
F2b
F2b
F2b F2b
F2b
EF2
EF2
EF2EF2
EF2
EF2
EF2
EF2EF2EF2 EF2EF2
EF2
EF2
EF2 EF2EF2
EF2
EF2
EF2
EF2
EF2EF2
EF2
EF2
EF2
EF2
EF2EF2
EF2 EF2 EF2
EF2
EF2EF2
EF2
CF1
F1b
F1b
F1b
F1b
F1b F1bF1b F1b
F1b F1b
EF2
EF1
EF1
EF1EF1
EF1
EF1
K1a
K1a b b
F1b
F1b
F1b F1b a b b a a a a
K2
EX1
EX1 EX1
EX1
K2
EX1
K2
EX1
EX1
EX1
EX1
EX1
EX2
EX1EX1
a a a b bb b b b
EX1
3/ b
3/ a
EX1
EX1
EX1
K2 K2
K2
K2
EX1
3/a
3/ b
EX1
EX1 EX1
EX1 EX1 EX1
EX2
EF1
w
BEDROOM
BEDROOM
CARE
125C
CL.
125B
BATH
125A BATH
126A
CL.
126B
CARE
126C
ENCLOSED PORCH
BEDROOM
BEDROOM
CARE
133C
CL.
133B
BATH
133A
BATH
134A
CL.
134B
CARE
134C
CORRIDOR
CARE
135C
BEDROOM
BEDROOM
CARE
136C
CL.
136B
BATH
136A
CL.
132A
BATH
135A
CL.
135B
STAFF BREAK
STUDY
LAUNDRY
HAC
CORRIDOR
I.T.
138A
THERAPY/EXERCISE
OFFICE
BEDROOM
BULK STORAGE
CARE
141C
CL.
141B
BATH
141A
CL.
147A
BATH
142A
CL.
142B
CARE
142C
BEDROOM
DEN
CL.
144A
CL.
147B
STAFF TOILET
LIVING ROOM
BEDROOM
BEDROOM
CARE
145C
CL.
145B
BATH
145A
CL
147C BATH
146A
CL.
146B
CARE
146C
CORRIDOR
SCOOTER STORAGE
MECH/ WATER
VESTIBULE
CL.
101A
CLEAN LINEN
CLEAN SUPPLY
SOILED UTILITY
GAS
GAS
CORRIDOR
VESTIBULE
ELECTRICAL
113A
COOLER
N.F.S.
CORRIDOR
103 CORRIDOR
BEDROOM
CARE
121C
BATH
120A
CARE
120C
CL.
122B
MEDICATION
CORRIDOR
122 DINING ROOM
117A
EX1
ECRA1 - 26
ECRA1 - 31
ELSA - 8
ECRA1 - 32
ELSA - 6
ECRA1 - 28
ELSA - 6
ELSA - 6
ELSA - 6
ECRA1 - 28
ELSA - 6
ECRA1 - 28
ECRA1 - 28
ELSA - 6
ECRA1 - 28
ECRA1 - 28
ELSA - 6
ECRA1 - 28
KITCHEN
ECRA1 - 27
NPA1 - 26
EX1
W3
W3
NPA1 - 27
ECRA1 - 29
ECRA1 - 25
NPA1 - 25
NPA2 - 30
UC2
C1
COMMUNICATION
138B
EX1
b a b b b b a
ELECTRICAL
113B
EF2
ELSA - 6
ELSA - 6
NPA2 - 28
l m l m m m m u u u u v v v v w w w ww x x x x x y y y y z z
J b a b
EX1
EX1
a b
EX1
b b
F2b
F2b
P4
UC2
UC2
3/c
W3 c c
W3 c c
ECRA1 - 28
K2
F2b b
F2b b
ECRA1 - 33
EX1
K1a
ELSA - 6
3/ c
(LCPA-2)
(LCPA-2)
(LCPA-2)
(LCPA-2)
ECRA1 - 28
(LCPA-5)
K2
(LCPA-2)
(LCPA-2)
(LCPA-1)
(LCPA-2)
ECRA1 - 28
(LCPA-2)
ECRA1 - 28
(LCPA-2)
K2
(LCPA-2)
(LCPA-1)
(LCPA-1)
NPA2 - 24
u a
ELSA - 6 ELSA - 6
ELSA - 10
10 10
(LCPA-1)
10 10
K2
ECRA1 - 28
(LCPA-2)
a a a a a a
(LCPA-2)
K2
ECRA1 - 28 10
F1b
F1b b b
K2
ECRA1 - 28
(LCPA-1)
L
NPA2 - 26
L
L
L
L L
BEDROOM
121A
BATH
350E507
(10'-4")
(10'-0")
(7'-0")
(11'-0")
(10'-0")
(9'-0")
(7'-0")
(10'-0")
(11'-0")(10'-6")
(10'-0")
(7'-0")
(9'-0")
(10'-0")
12(7'-0")
(8'-0")
(10'-0")
(8'-0")
(10'-0")
12 (8'-0")
(7'-0")
K1a
ELSA - 6
(LCPA-1)
(7'-0")
K1a
ELSA - 6
(LCPA-1)(7'-0") 12
350E507
350E507
350E507
C1a
C1a
A
F1b
F1b
F1b
A1 W1
W1
F1b
F1b
NL1
F1b
F1b
F1b
F1b f g h a b c d c e e dd d d b c a h g g f i d i
A2 c
F1b d
DM
F1b d
NL1
b
DM7
DM
350ET101
350E507
MATCHLINE MATCHLINE
F
CA
K1a K1a
P3
K1a
K1c 15
WP
WP
NPA3 - 11
ECRA1 - 30
ELSA - 6 ELSA - 6
K1c
K1c
K1c
K2 K2
K2
K1a
(LCPA-3)
(LCPA-3)
(LCPA-3)
(LCPA-3)
(LCPA-3)
(LCPA-1)
(LCPA-3)
(LCPA-3)
(LCPA-3)
(LCPA-3)
NPA3 - 16,18
350-EF3
NPA3 - 20
J
J
J
J
K1c
K1c
K1c
K1c
ECRA1 - 30
350E507
LIGHTING CONTROL SCHEDULE (LCPA)
CIRCUIT
SPARE
ECRA2-28
ECRA1-32
AREA
SPARE
SECURITY LIGHTS
COURTYARD LIGHTS
OVERRIDE SWITCH TOD CONTROL NOTES
J --
NOTES:
1 CONTROLLED VA PHOTOCELL.
2 COORDINATE TOD SCHEDULE WITH COR.
4 NPA2-28 CORRIDOR LIGHTS 2x --
5 NPA2-28 CORRIDOR LIGHTS 2y --
6 NPA2-28 CORRIDOR LIGHTS 2z --
7 NPA2-26 CORRIDOR LIGHTS 2u --
8 NPA2-26 CORRIDOR LIGHTS 2v --
9 NPA2-26 CORRIDOR LIGHTS 2w --
10 NPA2-28 PORCH LIGHTS 1m --
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number
Dwg. of on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE,
SUITE 200
MIAMISBURG, OHIO
45342
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
937 461 3290 PHONE
937 461 0260 FAX
jpa@johnpoe.com
100% CONSTRUCTION DOCUMENTS -
Heapy Project No.: 2015-04026 Firm License No.: 01528
Construct CLC Single Story Unit
10.06.2017
FIRST FLOOR PLAN - LIGHTING
350EL101
JRSMSG
15010.00
552-161
Dayton, Ohio
N Scale:
PROJECT
1/8" = 1'-0"
FIRST FLOOR PLAN - LIGHTING
N Scale:
PROJECT
1/4" = 1'-0"
TYPICAL BED ROOM PLAN - LIGHTING
N Scale:
PROJECT
1/8" = 1'-0"
FIRST FLOOR PLAN - ELECTRICAL
NOTES
1. PROVIDE COMBINATION FAN/LIGHTING ELECTRONIC DIMMER.
2. REFER TYPICAL ROOM LAYOUT DETAIL 2 SHEET EL101 FOR LIGHT FIXTURE AND DEVICE
LAYOUT.
3. PROVIDE BUILDING SIDE SHIELDING INSIDE DIFFUSER TO PROTECT FROM GLARE INTO
BEDROOM WINDOWS. SHIELD SHALL ALLOW ENOUGH LIGHT TO ILLUMINATE DIFFUSER ON
SHIELD SIDE BUT SHALL NOT ILLUMINATE BEYOND DIFFUSER.
4. PROVIDE 208V - 1PH, 14-30R RECEPTACLE FOR CONNECTION TO PTAC UNIT. COORDINATE
WITH DIV 23 PRIOR TO INSTALLATION.
5. PROVIDE 120V CONNECTION TO AIR CLEANING UNIT. MOUNT NEXT TO UNIT 6'-6" AFF.
6. PROVIDE 120V SPECIFICATION GRADE PHOTOCELL. MOUNT PHOTOCELL ON WALL IN
WEATHERPROOF CAST IRON BOX.
7. PROVIDE 0-10V SLIDE-TO-OFF DIMMER SWITCH.
8. SWITCH TO CONTROL COURTYARD FIXTURES AS INDICATED.
9. INTERIOR SHELTER LIGHTING SHALL BE WIRED AHEAD OF LCPA CONTROL.
10. DO NOT LOCATE JUNCTION BOXES OR SPLICES ABOVE DRYWALL CEILING. ACCESS
PANELS MAY NOT BE UTILIZED IN BEDROOM. ALL BRANCH CIRCUITRY SHALL BE
ACCESSIBLE ABOVE DROP CEILING AND ABOVE CORRIDOR CEILING. COORDINATE WITH
DIV 01.
11. NOTE OMITTED.
12. MOUNTING HEIGHT IS APPROXIMATE, COORDINATE WITH ARCHITECTURAL ELEVATIONS.
13. CONCEAL FIXTURE IN ROOF EAVE WHERE POSSIBLE WITHOUT COMPROMISING LIGHT
DISTRIBUTION.
14. LIGHT FIXTURE SHALL BE CONTROLLED BY NORMALLY CLOSED LIGHTING CONTRACTOR
MOUNTED IN ELECTRICAL ROOM. LIGHT FIXTURE SHALL BE ON AT DUSK AND OFF AT
DAWN. FIXTURE SHALL BYPASS LIGHTING CONTROL UPON LOSS OF NORMAL POWER OR
ACTIVATION OF FIRE ALARM VIA UL924 LISTED EMERGENCY LIGHTING CONTROL UNIT.
15. MOUNT ON ARCHITECTURAL LUMINATED WOOD LIGHT POLE. REFER TO LIGHTING
SCHEDULE FOR POLE DETAILS.
GENERAL NOTES
A. WHERE MULTIPLE OCCUPANCY SENSORS ARE SHOWN IN A COMMON ROOM OR
CORRIDOR, WIRE SENSORS IN PARALLEL FOR COMMON ZONE CONTROL.
B. WHERE SWITCHES ARE SHOWN IN SPACES CONTROLLED BY OCCUPANCY SENSORS,
WIRE SENSOR RELAY PACK AHEAD OF LOCAL SWITCHING.(EXCEPT LIFE SAFETY
CIRCUITS)
C. PROVIDE DEDICATED NEUTRAL FOR ALL 120V CIRCUITS.
D. COORDINATE ALL LIGHTING FIXTURE LOCATIONS WITH ARCHITECTURAL REFLECTED
CEILING PLANS.
E. OCCUPANCY SENSOR MANUFACTURERS SHALL SUBMIT AN /1/8" SCALE FLOOR PLAN
SHOWING PROPOSED LAYOUT WITH DEVICES CLEARLY IDENTIFIED DURING SHOP
DRAWING REVIEW. OCCUPANCY SENSOR SHOP DRAWING SUBMITTALS MISSING THIS
INFORMATION WILL BE REJECTED. REQUEST AutoCAD FLOOR PLANS WELL IN ADVANCE
OF SHOP DRAWINGS.
F. COORDINATE OCCUPANCY SENSOR AIMING AND PLACEMENT WITH MANUFACTURER
PRIOR TO INSTALLATION.
G. WIRE ALL EXIT SIGNS AHEAD OF LOCAL SWITCHING.
H. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE
TO ALLOW FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING
EQUIPMENT.
I. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.
EACH BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND COMMON/SHARED
GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
J. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND
NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.
K. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO
ARCHITECTURAL DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
L. REFER TO ARCHITECTURAL DRAWINGS FOR RATED WALL LOCATIONS.
M. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES
MOUNTED ABOVE OR BELOW CASEWORK, FURNITURE, LAVATORIES, ETC.
N. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SWITCH COVERPLATES
INDICATING PANEL AND CIRCUIT NUMBER.
N.T.S.Scale:
LIGHTING CONTROL SCHEDULE
sodell Snapshot
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
TT
T
T
T
T
T
T
T
T
T
T T
T
T
TT
T
T
T
T
GF
WP/GF
WP/GF
A
M H
A
M H
W A
S H
W A
S H
GF
GF
GF
GF
GF
G F
R F
TV
W P
/G F
G F
G F T V
M H
C O
W P
/G F
WP/GF
G F
TV
G F
G F
GF
GF
GF
WP/GF
GF
G F
GF
WP/GF
TV
M W
M H
WP/GF
J
J J
J
J
J J
J J
J
J
J
J
G F
JJ JJ
JJ
JJ
J J
J J
J J
J J
J JJ J
J J
J J
J
J J
J
J
J
TV
EMEM
60" MH
J J
J
R F
O M
N I
J
J
J J
JJ
PC
2P
LC
T
96" MH
GF GF
70" MH
J J
J
T
T
2P
J
N C
C P
30A
30A30A
46" MH
M H
F A
C P
M H
S
T
T
T
GF
GF
G F
G F
G F
IC
E
GF
GF
GF
G F
M W
M H R F
R F
G F
G F
J
J
C M
M H
G F
GF
G F
J
J
R F
O M
N I
350EP101
350EP101
GF
T1
GEN-350
PMH "M"
350EP101
4 54 5
4 54 54 5
4 5
4 5
4 5
4 5
4 5
4 5
MATCHLINE MATCHLINE
DDC
350EP101
4 5
MECH/ WATER
SCOOTER STORAGE
LIVING ROOM
VESTIBULE
CLEAN LINEN
CL.
101A
CLEAN SUPPLY
SOILED UTILITY
GAS
GAS
CORRIDOR
VESTIBULE
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
BEDROOM
BEDROOM
CL.
141B
CARE
141C
BATH
141A
CL.
147A
BATH
142A
CL.
142B
CARE
142C
BATH
146A CL.
146B
CARE
146C
BEDROOM
BEDROOM
BATH
145A
CL
147C
CARE
145C CL.
145B
OFFICE
THERAPY/EXERCISE
I.T.
138A
DINING ROOM
117A
ELECTRICAL
113A COOLER
N.F.S.
BEDROOM
BATH
120A
CARE
120C
CARE
121C
BEDROOM
BEDROOM
CARE
125C BATH
125A
CL.
125B
CL.
126BBATH
126A
CARE
126C
CORRIDOR
CORRIDOR
CORRIDOR
STUDY
ENCLOSED PORCH
CORRIDOR
BEDROOM
CL.
133B
BATH
133A
CARE
133C BATH
134A
BEDROOM
CL.
134B
BEDROOM
CL.
135B
CARE
135C
BATH
135A
BEDROOM
BATH
136A
CL.
132A
CL.
136B
CARE
136C
CORRIDOR
LAUNDRY
HAC
MEDICATION
DEN
CL.
144A
CL.
147B
STAFF TOILET
STAFF BREAK
BULK STORAGE
KITCHEN
NPA2 - 1
ECRA1 - 13
NPA2 - 3ECRA1 - 16
NPA2 - 5
ECRA1 - 18
NPA2 - 6
ECRA1 - 19
NPA2 - 9
NPA2 - 8
ECRA1 - 22
NPA3 - 1
ECRA1 - 15
NPA2 - 10
NPA2 - 13
ECRA1 - 24
ECRA1 - 21
NPA2 - 15
NPA2 - 12
NPA2 - 18,20
NPA2 - 14,16
NPA2 - 19
NPA2 - 17
NPA2 - 23
NPA2 - 22
121A
BATH
BEDROOM
ELSA - 5
ELSA - 7
ELSA - 3
NPA2 - 21
ECRA1 - 2 NPA1 - 1,3 ECRA1 - 1
NPA1 - 2,4
ECRA1 - 4 NPA1 - 5,7
ECRA1 - 3 NPA1 - 6,8
ECRA1 - 6
NPA1 - 9,11
ECRA1 - 5
NPA1 - 10,12
ECRA1 - 8
NPA1 - 13,15
ECRA1 - 7
NPA1 - 14,16
ECRA1 - 10NPA1 - 17,19ECRA1 - 9
NPA1 - 18,20
ECRA1 - 12
NPA1 - 21,23
ECRA1 - 11
NPA1 - 22,24
ECRA1 - 17
ELSA - 2
ELSA - 4
ELSA - 2
ELSA - 2 ELSA - 2
ELSA - 4
ELSA - 4
ELSA - 2
ELSA - 2
ECRA3 - 30,32,34
ECRA3 - 39
ECRA1 - 14
ECRA1 - 20
350EP101
NPA3 - 7
NPA3 - 7
NPA3 - 7
NPA3 - 7
NPA3 - 7
NPA3 - 7
ECRA1 - 23
72" MH
NPA2 - 11
14 ELSA - 2
NPA3 - 2
120" MH
NPA3 - 7
ELSA - 4
ELSA - 4
HU3
HU4
HU2
HU1
NPA1 - 28,30,32
NPA1 - 29,31,33
NPA2 - 38,40,42
350-CRP2
350-CRP4
350-CRP3350-CRP1
350-UH2
350-UH2
350-UH1
350-UH1
350-UH1
ECRA3 - 36
NPA3 - 28
ECRA1 - 34ECRA1 - 35
WP
NPA2 - 21
NPA3 - 3
113B
ELECTRICAL
117B
BREAKFAST
BAR
138B
COMMUNICATION
WP
WP
WP
WP
WP
TYP.
F
350E505
S
350E505
T
350E505
U
350E505
G
350E505
G
350E505
T
350E505
S
350E505
F
350E505
ELSA - 2
NPA2 - 32,34,36 15
ECRA2 - 4
ECRA3 - 23
ECRA3 - 25
NPA2 - 4
ECRA3 - 23
ECRA3 - 25
NPA2 - 7
ATS-ELSAATS-ECRA
ECRDPA
ELSA
NDPA
NPA1
NPA2
NPA3
LCPA
ECRA3
ECRA2ECRA1
113A
ELECTRICAL
113B
ELECTRICAL
ECRA2 - 17
350-EUH1
NPA3 - 23,25
B
DHWH1 DHWH1SWTS1
MVP1
MAC1
H W
C P
-1
H W
C P
-1
350-HWP4
350-HWP5
ECRA3 - 1 ECRA3 - 3
ECRA3 - 5,7,9 ECRA3 - 4
ECRA3 - 2
ECRA3 - 12
ECRA3 - 6,8,10
ECRA3 - 11,13,15
ECRA3 - 14
NPA3 - 26
HWB1
HWB2
HWB3
350-HWP1
350-HWP2
350-HWP3
NPA3 - 2748
ECRA1 - 14
350-AC106
ECRA3 - 17,19,21
ECRA3 - 16,18,20
ECRA2 - 36
350-AC138B
2P
ECRA2 - 8
ECRA2 - 1
ECRA2 - 10,12
ECRA2 - 11
ECRA2 - 9
NPA3 - 4
ELSA - 1
138A I.T.
138B
COMMUNICATION
ECRA2 - 15
ECRA2 - 2
ECRA2 - 5
ECRA2 - 14
ECRA2 - 16
ECRA2 - 30,32,34
ECRA2 - 25
NPA3 - 9
ECRA2 - 23 ECRA2 - 18
NPA3 - 6,8
NPA3 - 12 ECRA2 - 21
ECRA2 - 27
ECRA2 - 29,31
NPA3 - 10
ECRA2 - 20,22
NPA3 - 15
NPA3 - 14
NPA3 - 5
PWR &
LTS
NPA3 - 22,24 ECRA2 - 24,26
NPA3 - 19,21
ECRA2 - 33,35
ECRA2 - 28
NPA3 - 17
KITCHEN
117B
BREAKFAST
BAR
N.F.S.
COOLER
ECRA2 - 19
NPA3 - 13
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number
Dwg. of on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE,
SUITE 200
MIAMISBURG, OHIO
45342
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
937 461 3290 PHONE
937 461 0260 FAX
jpa@johnpoe.com
100% CONSTRUCTION DOCUMENTS -
Heapy Project No.: 2015-04026 Firm License No.: 01528
Construct CLC Single Story Unit
10.06.2017
FIRST FLOOR PLAN - POWER
350EP101
JRSMSG
15010.00
552-161
Dayton, Ohio
N Scale:
PROJECT
1/8" = 1'-0"
FIRST FLOOR PLAN - POWER
Scale: 1/4" = 1'-0"2
ENLARGED ELECTRIC ROOM
Scale: 1/4" = 1'-0"3
TYPICAL BED ROOM PLAN - POWER
Scale: 1/4" = 1'-0"4
ENLARGED MECH. ROOM
NOTES
1. ROUGH-IN BOX AND PROVIDE ELECTRICAL CONNECTION TO RANGE HOOD. COORDINATE
MOUNTING WITH ARCHITECT PRIOR TO INSTALLATION.
2. PROVIDE ELECTRICAL CONNECTION TO KITCHEN EQUIPMENT IN LIQUID TIGHT CONDUIT.
3. PROVIDE - 120V SPRING WOUND TIMER INDIVIDUALLY CONNECTED TO SEPARATE CONTACTOR
CONTROLLING POWER TO EQUIPMENT IN KITCHEN. TIMER SHALL BE ADJUSTABLE UP TO AND
INCLUDING 2 HOURS OF OPERATION IN THE "ON" POSITION. PROVIDE WIRING AND CONDUIT TO
LIGHTING CONTACTOR LOCATED IN ELECTRICAL ROOM FOR CONTROL. LABEL EACH SWITCH TO
IDENTIFY EQUIPMENT BEING CONTROLLED. (EX. "OVEN TIMER"). PROVIDE METAL RECESSED
LOCKABLE WALL PLATE COVER FOR TIMERS. PROVIDE 10 KEYS TO COR FOR LOCKABLE COVER.
4. REFER TO TYPICAL BEDROOM LAYOUT DETAIL 3/EP101.
5. DO NOT LOCATE JUNCTION BOXES OR SPLICES ABOVE HARD CEILING. ACCESS PANELS MAY NOT
BE UTILIZED IN BEDROOM. ALL BRANCH CIRCUITRY SHALL BE ACCESSIBLE ABOVE DROP CEILING
AND ABOVE CORRIDOR CEILING. COORDINATE WITH DIV 01.
6. REFER TO DETAIL 3 ON SHEET EL101 FOR COURTYARD POWER DEVICE LOCATIONS.
7. PROVIDE 120V CONNECTION TO GENERATOR BLOCK HEATER.
8. PROVIDE 120V CONNECTION TO GENERATOR BATTERY CHARGER.
9. PROVIDE 120V CONNECTION TO BOILER.
10. PROVIDE GFCI BREAKER IN PANEL.
11. RUN CIRCUITRY TO CONDENSING UNIT CU-1 LOCATED ON ROOF.
12. INSTALL L5-30R TWIST-LOCK TYPE RECEPTACLES ON TOP OF RACK. COORDINATE WITH DIV. 27
PRIOR TO INSTALLATION.
13. PROVIDE 120V CONNECTION TO GENERATOR LIGHTS AND RECEPTACLES.
14. PROVIDE 120V CONNECTION TO DOOR ACCESS CONTROL.
15. PROVIDE 120V CONNECTION TO CONTROL TRANSFORMER FOR AUTO FAUCET. LOCATE
TRANSFORMER ABOVE DROP CEILING. COORDINATE REQUIREMENTS WITH DIV. 22 PRIOR TO
INSTALLATION.
16. RUN CIRCUITRY TO EQUIPMENT CONTROL PANEL.
17. INSTALL L6-30R TWIST-LOCK TYPE RECEPTACLES ON TOP OF RACK. COORDINATE WITH DIV. 27
PRIOR TO INSTALLATION.
18. PROVIDE 120V CONNECTION TO ELECTRIC FIREPLACE. COORDINATE WITH ARCHITECT PRIOR TO
INSTALLATION.
19. MOUNT ELECTRICAL EQUIPMENT UTILIZING GALVANIZED UNISTRUT.
20. PROVIDE CONCRETE BOLLARDS FOR VEHICLE IMPACT PROTECTION. REFER TO DETAIL O ON
SHEET E504.
21. INSTALL RECEPTACLE FOR PATIENT LIFT IN WALL ADJACENT TO LIFT. COORDINATE WITH
ARCHITECT FOR EXACT LOCATION. DO NOT LOCATE ABOVE CEILING.
22. PROVIDE 2-POLE TOGGLE SWITCH TO SERVE AS DISCONNECT MOUNTED NEAR THE UNIT.
23. PROVIDE RECEPTACLES TO SERVE NALCO SYSTEM. COORDINATE EXACT LOCATION OF
RECEPTACLES WITH DIV22 PRIOR TO ROUGH-IN. REFER TO SWTS1 (ONE) DETAIL ON DIV 22
DRAWINGS.
24. PROVIDE SWITCHING AND CONNECTION TO INSINK WASTE DISPOSAL. COORDINATE WITH DIV. 22
PRIOR TO INSTALLATION. DISPOSAL TO BE CONTROLLED BY 30A CONTACTOR LOCATED IN
ELECTRICAL ROOM.
25. PROVIDE CONNECTION TO SCISSOR LIFT. COORDINATE WITH DIV. 01 PRIOR TO INSTALLATION TO
DETERMINE EXACT LOCATION.
26. PROVIDE UNISTRUT FRAME BOLTED TO FLOOR TO MOUNT EQUIPMENT.
27. PROVIDE RECESSED 30A ENCLOSED CIRCUIT BREAKER TO SERVE AS THE MEANS OF DISCONNECT
FOR RETHERM CART. CONCEAL CONDUIT AND CIRCUITRY IN WALL TO RECESSED JUNCTION BOX.
RUN 3 - #10, #10 GND. IN 0.75"C. PROVIDE SEAL TIGHT CONNECTION TO RETHERM CART.
28. PROVIDE 60A, 3-POLE NEMA 3R FUSED DISCONNECT SWITCH, FUSED AT 15A. RUN 3-#10, #10 GND IN 0.75"C.
29. PROVIDE 120V CONNECTION TO GATE MOTOR. MOUNT PUSH BUTTON UP/DOWN CONTROLS
RECESSED AT LOCATION SHOWN. PROVIDE CIRCUITRY FOR CONTROL. COORDINATE WITH DIV 01
PRIOR TO INSTALLATION.
30. PROVIDE 120V CIRCUIT FOR SHADE CONTROL FOR DORMER. PROVIDE CIRCUITRY TO CONTROLLER
WHERE SHOWN. COORDINATE WITH DIV 01 PRIOR TO INSTALLATION.
31. PROVIDE RECESSED MOUNTING FOR SHADE CONTROLLER. COORDINATE WITH DIV 01 PRIOR TO
INSTALLATION. PROVIDE WIRING PER MANUFACTURER INSTRUCTIONS.
32. PROVIDE 50A, 3-POLE NORMALLY OPEN LIGHTING CONTACTOR WALL MOUNTED IN NEMA 1
ENCLOSURE. CONTACTOR SHALL HAVE 120V COIL CONTROLLED BY SPRING WOUND TIMER
LOCATED IN KITCHEN. PROVIDE CONDUIT AND CIRCUITRY TO TIMER. CIRCUITRY TO BE INSTALLED SO THAT CONTACTOR IS NORMALLY OPEN AND CLOSES ONLY WHEN TIMER IS ACTIVATED. LABEL
ENCLOSURE "COOKTOP CONTACTOR".
33. PROVIDE 30A, 3-POLE NORMALLY OPEN LIGHTING CONTACTOR WALL MOUNTED IN NEMA 1
ENCLOSURE JUNCTION BOX WITH COVER. CONTACTOR SHALL HAVE 120V COIL CONTROLLED BY
SPRING WOUND TIMER LOCATED IN KITCHEN. PROVIDE CONDUIT AND CIRCUITRY TO TIMER.
CIRCUITRY TO BE INSTALLED SO THAT CONTACTOR IS CLOSED ONLY WHEN TIMER IS ON. LABEL
ENCLOSURE TO INDICATE EQUIPMENT BEING CONTROLLED (EX. "DISPOSAL CONTACTOR").
34. PROVIDE 50A, 208V-1 PHASE RECEPTACLE FOR DISHWASHER. RUN 2-#8, #10 GRD. IN 1"C.
COORDINATE WITH DIV 01.
35. PROVIDE 50A, 208V-1 PHASE RECEPTACLE FOR COOK TOP. RUN 2-#8, #10 GRD. IN 1"C.
COORDINATE WITH DIV 01. RECEPTACLE TO BE CONTROLLED BY 50A RELAY LOCATED IN
ELECTRICAL ROOM. PROVIDE SHUNT TRIP BREAKER CONTROLLED BY HOOD FIRE SUPPRESSION
SYSTEM. PROVIDE CIRCUITRY AND CONNECTIONS TO HOOD FIRE SUPPRESSION SYSTEM.
36. PROVIDE 30A, 208V-1 PHASE RECEPTACLE FOR OVEN. RUN 2-#10, #10 GRD. IN 0.75"C.
COORDINATE WITH DIV 01. RECEPTACLE TO BE CONTROLLED BY 30A CONTACTOR LOCATED IN
ELECTRICAL ROOM.
37. PROVIDE CONNECTION TO COOLER CONDENSING UNIT. COORDINATE WITH DIV 01.
38. COIL RECIRCULATION PUMP LOCATED BELOW ROOFTOP UNIT.
39. PROVIDE CONCRETE PAD FOR GENERATOR.
40. PROVIDE CONCRETE PAD FOR ELECTRICAL EQUIPMENT.
41. PROVIDE OSHA COMPLIANT PREFABRICATED PLATFORM AND STAIRWAY, 45 DEG. ANGLE OF RISE
TREADS, HEAVY DUTY BAR GRATING, FACTORY WELDED HANDRAIL (ONE SIDE) HELD BACK TO
PERMIT GENERATOR DOOR TO OPEN COMPLETELY, 36"W TREADS (39" OVERALL), SELF
SUPPORTING (DO NOT CONNECT TO TANK / GENERATOR).
42. STUB OUT CONDUIT UNDERGROUND WHERE INDICATED. CAP ENDS OF CONDUIT AND PROVIDE
LOCATING PIN.
43. RUN 4-4" SPARE CONDUITS FROM NDPA FOR PORTABLE GENERATOR FEED. STUB CONDUITS 18"
ABOVE GRADE NEXT TO EXTERIOR WALL WITH RIGID CONDUIT. PROVIDE RIGID CAPS FOR
CONDUIT.
44. PROVIDE FLOOR MOUNTED NEMA 3R, DOCKING STATION. ANCHOR TO CONCRETE PAD. DOCKING
STATION SHALL HAVE FRONT ACCESS ONLY.
45. NOTE OMITTED.
46. PROVIDE STARTERS FOR COIL RECIRCULATION PUMPS.
47. PROVIDE CIRCUITRY TO OUTDOOR CONDENSING UNIT LOCATED ON ROOF. FAN COIL UNIT POWER
SUPPLIED BY CONDENSING UNIT.
48. PROVIDE 120V CONNECTION TO IRRIGATION CONTROLLER. PROVIDE 2" CONDUIT FOR WIRES TO
TURF AREA. REFER TO IRRIGATION DRAWINGS. COORDINATE WITH DIV 01 PRIOR TO ROUGH-IN.
49. PROVIDE 30A, 208V-1 PHASE RECEPTACLE FOR COFFEE MAKER. RUN 2-#10, #10 GND. IN 75"C.
COORDINATE WITH DIV 01 PRIOR TO ORDERING.
50. MOUNT RECEPTACLE IN RECESSED MEDICAL GAS CABINET PROVIDED UNDER DIV 01.
GENERAL NOTES
A. COORDINATE ALL KITCHEN EQUIPMENT DEVICE LOCATIONS WITH ARCHITECTURAL
ELEVATIONS PRIOR TO ROUGH-IN.
B. PROVIDE DEDICATED NEUTRAL FOR ALL 120V-20A CIRCUITS.
C. PROVIDE PRINTED LABELS ON ALL RECEPTACLE AND SWITCH COVERPLATES INDICATING
PANEL AND CIRCUIT NUMBER.
D. EMT CONDUIT SHALL BE 0.75" MINIMUM.
E. REFER TO DIVISION 22/ARCHITECTURAL DRAWINGS FOR LOCATIONS OF ALL PLUMBING
EQUIPMENT.
F. CONTRACTOR SHALL INSTALL ELECTRICAL CONDUIT/FEEDERS TIGHT TO STRUCTURE TO
ALLOW FOR REQUIRED CLEARANCES AROUND OTHER TRADES ABOVE CEILING EQUIPMENT.
G. (1) EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH
BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL AND GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
H. MULTI-GANG BACKBOXES FOR DIFFERENT TYPES OF EMERGENCY AND NORMAL BRANCH
WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.
I. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING.
J. REFER TO ARCHITECTURAL DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
K. REFER TO ARCHITECTURAL DRAWINGS FOR RATED WALL LOCATIONS.
L. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES MOUNTED
ABOVE OR BELOW CASEWORK, FURNITURE, LAVATORIES, ETC.
Scale: 1/4" = 1'-0"5
ENLARGED COMM. ROOM
Scale: 1/4" = 1'-0"6
KITCHEN POWER PLAN
GF
J
B D
A C
HE
I
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
350-RTU4
350-RTU3
350-RTU1
350-RTU2
WP
WP
WP
WP
350-CU106
WP
ECRDPA - 8
ECRDPA - 6
ECRDPA - 7
ECRDPA - 5
ECRA3 - 22,24
C1
C1
C1
O
O
O
O
C1O
C1 O
C1 Q
C1 Q
C1 Q
C1 Q
Q
WP
L1
WP
C1
C1
C1
M
M
M
WP
C1 M
C1 N
C1 N
C1 N
C1N
WP
N
M
L1
L1
C1 M
C1 N
C1 N
C1 M
L1
6 6
TYP.
TYP.
4 TYP.
TYP.
NPA2 - 2
NPA2 - 25 A
NPA3 - 30
NPA3 - 30 NPA3 - 30
NPA3 - 30
ECRA3 - 27,29,31
350-EF1
ECRA3 - 33,35,37
350-EF2
350-CU138B
WP
ECRA3 - 26,28
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number
Dwg. of on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE,
SUITE 200
MIAMISBURG, OHIO
45342
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
937 461 3290 PHONE
937 461 0260 FAX
jpa@johnpoe.com
100% CONSTRUCTION DOCUMENTS -
Heapy Project No.: 2015-04026 Firm License No.: 01528
Construct CLC Single Story Unit
10.06.2017
ROOF PLAN
350EP102
JRSMSG
15010.00
552-161
Dayton, Ohio
N Scale:
PROJECT
1/8" = 1'-0"
ROOF PLAN - LIGHTNING PROTECTION AND POWER
GENERAL NOTES
A. LIGHTNING PROTECTION PLAN SHOWN FOR REFERENCE ONLY. SYSTEM SHALL BE DESIGNED PER
NFPA 780 AND SUBMITTED WITH SHOP DRAWINGS.
NOTES
1. LIGHTNING PROTECTION CONDUCTOR. RUN CONCEALED IN ATTIC.
2. LIGHTNING PROTECTION STRIKE TERMINATION DEVICE.
3. LIGHTNING PROTECTION SYSTEM DOWN CONDUCTOR CONCEALED IN BUILDING AND GROUND ROD.
4. LIGHTNING PROTECTION CONDUCTOR ATTACHED TO EXTERIOR OF WALL WITH LOOP CLIPS.
5. LIGHTNING PROTECTION ROOF CONDUCTOR RUN ON TOP OF FLAT ROOF.
6. MOUNT LIGHTING FIXTURE ON SIDE OF MECHANICAL EQUIPMENT. REFER TO DETAIL.
7. BOND STRUCTURE AT 2 LOCATIONS.
8. RUN CIRCUITRY TO FAN COIL UNIT LOCATED IN COMMUNICATIONS CLOSET.
9. CHAIN MOUNT LIGHTING FIXTURE IN ATTIC WHERE SHOWN. SUPPORT FIXTURE FROM TRUSS DO NOT
SUPPORT FROM ROOF.
10. MOUNT SWITCH AND RECEPTACLE IN SAME ENCLOSURE ON SIDE OF MECHANICAL EQUIPMENT. REFER TO
DETAIL.
11. APPROXIMATE LOCATION OF ROOF MOUNTED ANTENNA FOR ERRCS SYSTEM INCLUDING ROOF
PENETRATION FOR ANTENNA CABLING DOWNLEAD. FIELD VERIFY WITH RADIO SURVEY FOR FINAL LOCATION AND ANTENNA MAST HEIGHT. GROUND ANTENNA, MAST AND MOUNTING SLED AND CONNECT TO
LIGHTNING PROTECTION SYSTEM.
12. THROUGH WALL COMPONENT INSTALLED 8" ABOVE FLAT ROOF THIS LOCATION ONLY.
13. BOND EXHAUST FAN.
14. PROVIDE 120V CONNECTION FOR RTU LIGHTING AND RECEPTACLE.
15. RUN CIRCUITRY TO FAN COIL UNIT LOCATED IN MECHANICAL ROOM.
16. ERRCS DONOR ANTENNA ASSEMBLY TO BE BONDED TO FACILITY LIGHTNING PROTECTION AS REQUIRED.
DETENTION
WQv BASIN
O H
IO
IL
L
IN
O
IS
A
V E
IOWA
AVE.
V E
R M
O N
T
A
V E
IOWA AVE.
O R
E G
O N
A V
E
R E
T A
I N I N
G W
A L
L
P A
R K
IN
G
PARKING
PARKING
POT Sta . 2
4+72.
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
COMMUNITY
BUILDING
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
PIV
PL5
PL3
PL3
PL3
NEW MH #70
NEW MH #71 F
350E505
EX.
MH #45
PMH "M"
PMH "K"
EX.
MH #47
EX. MH #46
EX. MH #48
F
350E505
F
350E505
H
350E505
F
350E505
PL3
PL3
PL3
PL3
PL3
PL5
PL3
PL3PL3
PL3
PL3
TYP.
TYP.
PL3
PL3
EX/R
EX/R
EX/R
EX/R
H
350E505
ELSA - 9
434 433
5 7
5 7
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number
Dwg. of on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE,
SUITE 200
MIAMISBURG, OHIO
45342
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
937 461 3290 PHONE
937 461 0260 FAX
jpa@johnpoe.com
100% CONSTRUCTION DOCUMENTS -
Heapy Project No.: 2015-04026 Firm License No.: 01528
Construct CLC Single Story Unit
10.06.2017
SITE PLAN
350ES101
JRSMSG
15010.00
552-161
Dayton, Ohio
N Scale:
PROJECT
1" = 80'-0"
SITE PLAN
GENERAL NOTES
A. CONTRACTOR SHALL SUBMIT FOR APPROVAL FROM THE COR AND ENGINEER A
SEQUENCE OF CONSTRUCTION NARRATIVE DETAILING THE SEQUENCE OF WORK TO BE
PERFORMED, DATES, TIMES, AND DURATIONS OF OUTAGES FOR TIE-INS. ALL
SHUTDOWN WORK SHALL BE PERFORMED OUTSIDE OF NORMAL WORKING HOURS.
B. LOCATES SHALL BE PROVIDE BY A THIRD PARTY LOCATING SERVICE PRIOR TO
EXCAVATION.
NOTES
1. TIE INTO EXISTING PMH "K" FOR NEW PRIMARY FEED. COORDINATE ANY REQUIRED
SHUT-DOWNS WITH COR 4 WEEKS PRIOR TO PERFORMING WORK.
2. UTILIZE EXISTING SPARE CONDUIT.
3. TIE INTO EXISTING MANHOLE. COORDINATE SHUTDOWNS WITH COR 4 WEEKS PRIOR TO
PERFORMING WORK.
4. RUN DUCT BANK AND PRIMARY CIRCUITS "H" & "E" TO NEW PAD MOUNTED SWITCH.
REFER TO SHEET EP101 FOR LOCATION.
5. REFER TO DETAIL I ON SHEET 350E505.
6. TIE INTO EXISTING CAMPUS LIGHTING CIRCUIT.
7. SAW CUT PAVEMENT AND CURB TO INSTALL NEW DUCT BANK. PATCH ROAD AND
CURB TO MATCH EXISTING.
8. PROVIDE TIER 22, 12"W X 12"L, PULL BOX WITH COVER MARKED "ELECTRIC" ADJACENT
TO LIGHT POLE. REFER TO LIGHTING FIXTURE DETAIL.
9. REMOVE EXISTING POLE LIGHT AND RELOCATE WHERE INDICATED. REROUTE CONDUIT
AND PULL NEW CIRCUITRY TO MAINTAIN CONTINUITY BETWEEN POLE LIGHTS.
10. RELOCATED POLE LIGHT.
11. REMOVE LIGHT FIXTURE AND POLE. TURN OVER TO VA.
12. STUB OUT CONDUIT UNDERGROUND WHERE INDICATED. CAP ENDS OF CONDUIT AND
PROVIDE LOCATING PIN.
13. SIGNALS MANHOLE.
14. PROVIDE NEW DUCT BANK. INSTALL PARALLEL TO EXISTING DUCT BANK.
15. WORK WITHIN AREA TO BE EXCLUDED UNDER DEDUCT ALTERNATE 1.
16. WORK WITHIN AREA TO BE EXCLUDED UNDER DEDUCT ALTERNATE 3.
M P
MP
MPR
M P
R
ABANDONED
MP MPR MP MPR
MH-120
MH-SG16
MH-SG17
MH-302
MH-302A
MH-302B
MH-SG18
MH-SG19
MH-SG20
MH-402A
MH-402
MH-410
MH-410A
MH-410B
MH-305
MH-225
MH-141
MH-SG21
MH-SG23
MH-SG26
MH-SG27
MH
SG282-4"C.
MH
SG15
MH
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
COMMUNITY
BUILDING
(FUTURE)
O H
IO
IL
L
IN
O
IS
A
V E
IOWA
KENTUCKY
AVE.
AVE.
R A
M P
V E
R M
O N
T
A
V E
IOWA AVE.
O R
E G
O N
A V
E
R E
T A
I N I N
G W
A L
L
R E
T A
I N I N
G W
A L
L
RETAIN
IN
G W
ALL
P A
R K
IN
G
PARKING
PARKING
NEW SIG
MH
FUT SIG
MH
FUT SIG
MH
NEW SIG
MH
4-4"C.
NEW 4-4"C.
4-4"C.
FUTURE 4-4"C.
NEW 4-4"C.
NEW 2-4"C.
NEW 2-4"C.
NEW 2-4"C.
NEW 2-4"C.
NEW
CLC
350ES102
350ES102
350ES102 2
350ES102
350ES102
350ES102
350ES102
350ES102
350ES102
350ES102
BLDG 410
BLDG 302
FUTURE 4-4"C.
1 3000 LB. CONCRETE.
2 4" I.D. DUCTS, SCHEDULE 40 PVC. 1-FIBER, 1-
COPPER/COAX.
3 MIN. 3" SPACING BETWEEN CONDUITS AND MIN. 3"
ENCASEMENT (TYPICAL). PROVIDE CONDUIT
SPACERS 6'-0" O.C.
4 RED DYE, RED DUST OR YELLOW MARKER TAPE ON
COMPACTED FILL.
5 INSTALL 3-1.25" INNERDUCTS IN FIBER CONDUIT, LEAVE
1 INNERDUCT EMPTY WITH PULL ROPE.
DETAIL NOTES
1'
-6
TAMPED
BACKFILL
FINISH GRADE
2' -3
C
O V
E R
1'-7"
1 3000 LB. CONCRETE.
2 4" I.D. DUCTS, SCHEDULE 40 PVC. 2-FIBER, 2-
COPPER/COAX.
3 MIN. 3" SPACING BETWEEN CONDUITS AND MIN. 3"
ENCASEMENT (TYPICAL). PROVIDE CONDUIT
SPACERS 6'-0" O.C.
4 RED DYE, RED DUST OR YELLOW MARKER TAPE ON
COMPACTED FILL.
5 INSTALL 3-1.25" INNERDUCTS IN FIBER CONDUIT,
LEAVE 1 INNERDUCT EMPTY WITH PULL ROPE.
DETAIL NOTES
FINISH GRADE
TAMPED
BACKFILL
1'-6"
1' -6
2' -3
C
O V
E R
1' -6
B B
PULLING IRON
0.764 CUBIC METERS (1
CUBIC YARD) 19mm (3/4")
GRAVEL SUMP
GROUND ROD
PER SECTION
26 05 26.
915mm
305mm (12") SUMP
SUMP FRAME &
COVER
CONC.
ENVELOPE
A
A
CABLE STANCHION
GRADE RINGS AS REQ'D TO MATCH
CIVIL FINISHED GRADE ELEVATION.
FINISHED GRADE
(3'-0") m m
(3 '-0
965mm
(3'-2")
965mm
(3'-2")
1930mm
(6'-4") m m
(9 '-4 m m
(5 '-6 m m
(3 '-1
0"
SIGNALS
1524mm
(5'-0") m m
(7 '-4 m m
(8 m m
(6 m m
(1 2"
M
IN
m m
(8
V A
R
IE
S
SECTION "A-A"
TOPVIEW
SECTION "B-B"
m m
(9 '-4 m m (8
'-0 m m
(8 m m
(8 m m
(8
1930mm
(6'-4") 1524mm
(5'-0")
203mm
(8")
305x305mm (12"x12") SUMP
CABLE STANCHION PER
SECTION 26 05 41.
PULLING
IRON
GROUND
ROD
SLEEVE
76mm (3")
SLOPE
SLO
PE
S
LO
P E
A. INCLUDE ALUMINUM LADDER (NOT
SHOWN FOR CLARITY).
GENERAL NOTE:
1. PROVIDE LOCKABLE TYPE MANHOLE
COVER AND RING. LOCKING
MECHANISM SHALL OPERATE VIA
PENTA HEAD SOCKET.
DETAIL NOTE:#
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number
Dwg. of on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE,
SUITE 200
MIAMISBURG, OHIO
45342
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
937 461 3290 PHONE
937 461 0260 FAX
jpa@johnpoe.com
100% CONSTRUCTION DOCUMENTS -
Heapy Project No.: 2015-04026 Firm License No.: 01528
Construct CLC Single Story Unit
10.06.2017
TECHNOLOGY SITE PLAN
350ES102
JDKNTL
15010.00
552-161
Dayton, Ohio
N Scale:
PROJECT
1" = 80'-0"
TECHNOLOGY SITE PLAN
Scale: 1/8" = 1'-0"2
UNDERGROUND DUCTS
Scale: 1/8" = 1'-0"3
UNDERGROUND DUCTS
GENERAL NOTES
A. CONTRACTOR SHALL SUBMIT FOR APPROVAL FROM THE COR AND ENGINEER A
SEQUENCE OF CONSTRUCTION NARRATIVE DETAILING THE SEQUENCE OF WORK TO
BE PERFORMED, DATES, TIMES, AND DURATIONS OF OUTAGES FOR TIE-INS. ALL
SHUTDOWN WORK SHALL BE PERFORMED OUTSIDE OF NORMAL WORKING HOURS.
B. LOCATES SHALL BE PROVIDE BY A THIRD PARTY LOCATING SERVICE PRIOR TO
EXCAVATION.
C. INCLUDE ALL REQUIRED SAW CUTTING, PATCHING AND COMPLETE SURFACE
RESTORATION TO RETURN ALL AFFECTED AREAS TO THEIR PRE-CONSTRUCTION
CONDITION.
PLAN NOTES
1. REFER TO SHEET 350ET102 FOR CONTINUATION.
2. REFER TO SHEET 350ET101 FOR CONTINUATION.
3. EXISTING MANHOLE TO BE UTILIZED FOR NEW CABLE ROUTING.
4. NEW DUCT BANK TO BE INSTALLED PARALLEL WITH EXISTING DUCT BANK AND MATCH EXISTING TOP
ELEVATION.
5. ELECTRICAL MANHOLE.
6. SAW CUT PAVEMENT AND CURB TO INSTALL NEW DUCT BANK. PATCH ROAD AND CURB TO MATCH
EXISTING.
Scale: 3/8" = 1'-0"4
SIGNALS MANHOLE DETAILS
EDC
EDC
EDC
EDC
CC
CC
EDC
CC
CC
CC
CC
CC
CC
CC
CC
CC
CC
CC
9CC
EDC
EDC
EDC
C C
C C
C C
C
C
CC
C C
FAA
N C
C P
KF
F
S
F
KF
F
N
N
N
N
N
NNNN
N
N
N
S
S
S
S
F F
NS
F
F
N T
N
F
S
S
F
F
NS
NDNDND
F
F
F
AM
I
F
NS
K F F
S
F
S
S
F
F
F
NS
S
F
ND
KF
F
F K F F
F
F
F
ND
F
N Z
N Z
N Z
R W
R W
R W R
W
S R
S
F
S
D
D
K F F
K F F
F
N
N
N
N
F
N T
N T
N T
N
N T
N
N
SS
D
D
S
K F F
K
N T N
T
S
IC
V
72" MH
60" MH
V
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
CC
CC
CC
N
N T
F
N T
CR
CR
C R
P
DV
46" MH
P P
W
P P
W
PP W
PP W
C C
P
P
D
D D D
D
SC SC
SC
SC SC
SC SC SC SC
SC
SC SC
SC
SC
SC
SC SC
SC
SC
SC SC
FS
V
V
V
IC
S
D
D
36" MH
P
D
H
D D
D
DD
D
F A
C P
CR
J1D
N
N
N
N
F
D
D D
42" MH
D
EDC
11 CR
EDC
HA
CR
HA
V
72" MH
C R
C R
K C
K C
C R
C R
K C
K C
C R
D
SC
SC
SC
SC
AP
X
AP
X
AP
X
AP
X
AP
X
AP
X
AP
X
AP
X
AP
X
P
CC
AM
C
AM
C
AM
C
AM
C
AM
C
AM
C
S
S
S
S
SS
D
D
A
S
S S
S R
S S
S R
S R
R W
R W
R W
R W
KC
R W
D
K C
S S S
S
AM
C
CC
C C
N
N T
N T
N
M
HA
V 42
69" MH
I
D
J1D
AM
C
C
NS
EDC
CC
CC
EDC
IC
CR
C R
D
EDC
C R
C R
K
CH
A
EDC
HA
H A
H A
H A
EDC
EDC
C R
H A
K C
GF
J
B D
A C
HE
I
350ET101
J
F G
B D
CA
E H
1 2 1 2
1 2
1 2
1 2
1 2 1 2
1 2
1 2 1 21 2
1 2
WP
WP
MATCHLINE MATCHLINE
138A
147E 147D
122C
128A
132D
350E703
Sim
2-4"C.
2-4"c.
BEDROOM
BEDROOM
CARE
125C
CL.
125B
BATH
125A BATH
126A
CL.
126B
CARE
126C
ENCLOSED PORCH
BEDROOM
BEDROOM
CARE
133C
CL.
133B
BATH
133A
BATH
134A
CL.
134B
CARE
134C
CL.
136B
STAFF BREAK
131STUDY
LAUNDRY
HAC
CORRIDOR
OFFICE
BEDROOM
CARE
141C
CL.
141B
BATH
141A
CL.
147A
BATH
142A
CL.
142B
CARE
142C
BEDROOM
DEN
CL.
144A
CL.
147BSTAFF TOILET
LIVING ROOM
BEDROOM
BEDROOM
CARE
145C
CL.
145B
BATH
145A
CL
147C BATH
146A
CL.
146B
CARE
146C
CORRIDOR
SCOOTER STORAGE
MECH/ WATER
VESTIBULE
CL.
101A
CLEAN LINEN
CLEAN SUPPLY
SOILED UTILITY
GAS
GAS
CORRIDOR
VESTIBULE
ELECTRICAL
113A
COOLER
N.F.S.
CORRIDOR
CORRIDOR
BEDROOM
CARE
121C
CARE
120C
CL.
122B
MEDICATION
CORRIDOR
BEDROOM
135B
CL.
135A
BATH
132A
CL.
136A
BATH
BEDROOM
135C
CARE
117A
DINING
ROOM
BULK
STORAGE
CORRIDOR
BEDROOM
CARE
136C
BATH
136A
CL.
132A
BATH
135A
CL.
135B
CARE
135C
CORRIDOR
THERAPY/EXERCISE
WP
138B
BEDROOM
KITCHEN
138B
COMMUNICATION
138A I.T.
113B
ELECTRICAL
120A
BATH
121A
BATH
350ET101
350ET101
112A
112B
103A
103B
115A
VESTIBULE
CORRIDOR
CORRIDOR
N.F.S.
COOLER
113B
ELECTRICAL
113A
ELECTRICAL
CORRIDOR
GAS
SOILED
UTILITY
CLEAN
SUPPLY
CLEAN
LINEN
69" MH
A V
I I
NS
C
69" MH
2" CONUIT SLEEVES, QTY.
AS INDICATED ON PLANS
NL1
A1
F1b F1b
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number
Dwg. of on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE,
SUITE 200
MIAMISBURG, OHIO
45342
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
937 461 3290 PHONE
937 461 0260 FAX
jpa@johnpoe.com
100% CONSTRUCTION DOCUMENTS -
Heapy Project No.: 2015-04026 Firm License No.: 01528
Construct CLC Single Story Unit
10.06.2017
FIRST FLOOR PLAN - SYSTEMS
350ET101
JRS/JDKMSG
15010.00
552-161
Dayton, Ohio
N Scale:
PROJECT
1/8" = 1'-0"
FIRST FLOOR PLAN - SYSTEMS
Scale: 1/4" = 1'-0"2
TYPICAL BED ROOM PLAN - SYSTEMS
NOTES
1. REFER TO TYPICAL ROOM LAYOUT DETAIL 2 SHEET ET101 FOR DEVICE LAYOUT.
2. DO NOT LOCATE JUNCTION BOXES OR SPLICES ABOVE HARD CEILING. ACCESS PANELS
MAY NOT BE UTILIZED IN BEDROOM. ALL BRANCH CIRCUITRY AND COMMUNICATIONS
CABLING SHALL BE ACCESSIBLE ABOVE DROP-IN CEILING AND ABOVE CORRIDOR
CEILING.
3. REFER TO DETAIL 3 ON SHEET EL101 FOR COURT YARD SYSTEMS LAYOUT.
4. 12"X4"DEEP WIRE MESH BASKET TRAY ABOVE CEILING.
5. DATA DROP FOR NETWORK MONITORED AND CONTROLLED FAUCET. PROVIDE
CONNECTIVITY TO FAUCET CONTROLLER AS COORDINATED WITH EQUIPMENT
SUPPLIER. PROVIDE 1-PORT OUTLET ABOVE CEILING WITH PATCH CABLE AS REQUIRED.
6. DOME LIGHT SHALL INDICATE ACTIVATION OF NURSE CALL PULL STATION LOCATED IN
SMOKE HUT.
7. WALL MOUNTED WIRELESS PANIC DURESS SYSTEM REPEATER/ANNUNCIATOR, 46" MH
WITH 1-GANG BOX, 0.75" CONUIT AND WIRING TO MAIN CONTROL UNIT IN I.T. ROOM.
8. RECESS MOUNTED FIRE ALARM REMOTE ANNUNCIATOR.
9. PROVIDE KNOX BOX, KEY PER DAYTON FIRE DEPT.
10. PROVIDE ADDRESSABLE MODULE FOR HOOD SUPPRESSION SWITCH.
11. PROVIDE DEVICE MOUNTING PEDESTAL WITH BASE, 59" TALL, 4X4 STEEL
CONSTRUCTION, DARK BRONZE FINISH, AND MOUNTING HARDWARE FOR SECURITY
DEVICES. EXTEND 1" CONDUIT INTO NEW IT ROOM 138A. UTILIZE OSP RATED CABLING.
12. PROVIDE ADDRESSABLE MODULE FOR ACCESS CONTROL.
GENERAL NOTES
A. ALL NEW VOICE/DATA TO BE CABLED TO COMMUNICATIONS ROOM 138B.
B. REFER TO ARCHITECTURAL PHASING PLAN AND INCLUDE ALL WORK NECESSARY TO
ACCOMMODATE PHASING.
C. REFER TO ARCHITECTURAL DRAWINGS FOR RATED WALL LOCATIONS.
D. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO
ARCHITECTURAL DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.
E. COORDINATE ALL NEW FIRE ALARM/FIRE SUPPRESSION ZONES WITH COR.
F. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS OF DEVICES
MOUNTED ABOVE OR BELOW CASEWORK, FURNITURE, LAVATORIES, ETC.
G. PROVIDE ALL NEW FIRE ALARM BOOSTER PANELS, TRANSPONDER PANELS,
FIBER/COPPER BACKBONE, 120V POWER CIRCUITS, CONDUIT, ETC. AS REQUIRED TO
SERVE NEW DEVICES. COORDINATE ALL NEW EQUIPMENT WITH MANUFACTURER.
Scale: 1/4" = 1'-0"3
PARTIAL PLAN-CORRIDOR 103 SECURITY
Scale: 1/2" = 1'-0"4
TYPICAL PATIENT ROOM ELEVATION
| 350EP101 |
| 350EP102 |
| 350ES101 |
| 350ES102 |
| 350ET101 |