36C25018B0222-00005001.pdf

PDF 5 MB Posted

Attached to
552-161: Community Living Center Federal contract opportunity
Solicitation number
36C25018B0222
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25018B0222 00005 Addendum #1 - Part 1.pdf

View the file

Other files for this federal contract opportunity

Other files attached to 552-161: Community Living Center, newest first.
File Type Posted
36C25018B0222-00005004.pdf PDF
36C25018B0222-00005005.pdf PDF
36C25018B0222-00005002.pdf PDF
36C25018B0222-00005000.docx DOCX document
36C25018B0222-00005003.pdf PDF
36C25018B0222-00004000.docx DOCX document
36C25018B0222-00003001.pdf PDF
36C25018B0222-00003000.docx DOCX document
36C25018B0222-00002000.docx DOCX document
36C25018B0222-000.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

General

1. Bidder Question: Regarding the IRRIGATION PLANS – There is no scale shown on 3501R101, 3501R102 (irrigation plans). Please advise.

o Answer: Plans are scaled at 1/8” = 1’-0”.

2. Bidder Question: Are trusses required to be fire rated? Please advise.

o Answer: As indicated in code notes on Sheet 350G101, exterior bearing walls, interior bearing walls, columns, beams, girders, trusses and roof/ceiling assemblies are to be 1 Hour protected.

o Answer: Note 9.39 on wall sections sheets calls out two layers of 5/8” gypsum board at bottom or trusses and joists. This creates the necessary 1 hour protection at underside of rated ceiling/roof assembly.

o Answer: See Specification Section 09 29 00, Paragraph 3.2/G (revised below) for direction on how to install the two layers of gypsum board at underside of roof structure.

3. Bidder Question: Cabinetry – is there a color spec’d on the cabinetry? Please advise.

o Answer: Color as indicated in Section 09 06 00, Paragraph 2.9/B

4. Bidder Question: Is there a product spec for the ceiling mounted patient lift system shown in spec section 11 73 00?

o Answer: Section 11 73 00, Paragraph 2.1/A clearly indicates lift system shall be by Guldmann.

5. Bidder Question: Is there a product spec for the Fireplaces in spec section 10 30 90-2?

o Answer: Section 10 30 90 is a performance specification. Any product that meets the requirements of this section will be accepted.

6. Bidder Question: The following items have been identified to be obtained from a mandatory Ability One source in compliance with* FAR clause 52.208-9, Contractor Use of Mandatory Sources of Supply or Services: DIVISION 08 – OPENINGS, 08 71 00 DOOR HARDWARE; SKILCRAFT Brand Exit Devices, Door Controls – Closers, Mortise Locks & Latches. Pricing and availability may be obtained from SKILCRAFT PDQ at 1- 855-NIB-SPEC (1-855-652-7732) or SKILCRAFT.ASP@VISIONCORPS.NET.

mailto:SKILCRAFT.ASP@VISIONCORPS.NET o Answer: There is a J&A on file for Corbin Russwin lock sets, therefore Corbin Russwin must be used. Other hardware types such as closers will need to submitted and evaluated for specification compliance after contract award.

7. Bidder Question: Provide sub-base mounted fuel oil tank, double wall constructed of steel plate of thickness required by applicable standards and shall be UL 2085 – Is this a site requirement for the UL 2085 tank or can a UL142 Double Wall fuel tank be used as a value engineering?

o Answer: The UL 2085 is a physical security requirement. Provide per specifications.

8. Bidder Question: Refer to drawings for capacity. – I did not see on any of the drawings the capacity – 24/48 or larger?

o Answer: 96 hour run time tank is required.

9. Bidder Question: Tank shall be UL listed and labeled. UL 2085 for “Protected

Secondary Containment Generator Base Tank” (Measured at Site), 2 hour fire protected rating, ballistic resistance test certification and vehicle impact resistance test certification. Looking at the drawings you also have bollards around the enclosure and tank to protect any vehicle impact – o Answer: Yes, bollards are also required by our physical security design manual. Provide per drawings.

10. Bidder Question: On the generator – Do you want that to be PMG?

o Answer: Yes.

11. Bidder Question: The engine generator and related equipment shall be housed in an outdoor weatherproof, critical grade, walk-in enclosure – Typically the enclosure for these sizes are “skin tight” and not walk-in. Again a value engineering opportunity.

o Answer: Our electrical maintenance section prefers the walk-in type and we have several on the installation. Provide per specifications.

12. Bidder Question: Enclosure shall be walk-in type and sound-attenuated (maximum 85 dBA at 1525 mm (5 feet) from any side, top and bottom to no more than 75 dBA when measured at 15 M (50 feet). Please find attached the spec sheet for the SA Enclosure for the C13 and the quietest we can go is 70dBA @ 23’ at 100% load.

o Answer: Cut sheet provided seems to exceed the specification requirements for the 50’ SPL.

13. Bidder Question: There is an emergency call button on the back patio behind the Living room RM 102. The plans do not show a dome lamp for the emergency button on the patio and we think it should. Should I provide a dome lamp or not.

o Answer: Yes, provide a dome lamp.

14. Bidder Question: When is the start date for project to start? This could affect completion in 365 days. If project cannot start till August for Indiana Bat protection.

Trees must come down first to prepare site for building before winter sets in.

o Answer: The start date has not yet been determined. We will take tree removal into consideration when the approved contractor schedule is developed.

15. Bidder Question: Are these CAD files available for the site portion of this project? This will assist in the take-off.

o Answer: No, typically we don’t receive CAD drawings from the A&E during bidding. Drawings will be available after award, if contractor signs design team waivers. Also Note:

▪ a. The pdf site plans are to scale, see scaling bars at the left margin.

▪ b. If you are using a quantity takeoff software that requires CAD documents there are software programs available which can convert PDF to CAD formats. (Recommend you try sites such as dotsoft.com)

16. Bidder Question: Bidder Question: How are calls going to be displayed to the staff?

The plans do not show a master station. The specifications call for a master station.

Please indicate the location of the master station.

o Answer: Provide master station in Office 139. Location to be confirmed with VA prior to rough-in.

17. Bidder Question: In talking with the “RADA” fixture supplier, we have been informed that RADA is not available (still in testing stage) and they are not sure when they will be available.

o Answer: Use Chicago, see SSJ

Specifications

1. Section 09 29 00 GYPSUM BOARD. Delete Paragraph 2.2 RESILIENT FURRING

CHANNELS

2. Section 09 29 00 GYPSUM BOARD. Revise Paragraph 3.2/G as follows:

G. At underside of roof structure (trusses, joists, beams, etc.)

1. Base layer 5/8” Type X gypsum wallboard applied at right angles to joist or truss 24” o.c. with 1 ¼” Type S or Type W drywall screws 24” o.c.

2. Face layer 5/8” Type X drywall base applied at right angles to joists or truss through base layer with 1 7/8” Type S or Type W screws 12” o.c. at joints and intermediate joist or truss. Face layer Type G drywall screws placed 2” back on either side of face layer end joints, 12” o.c.

3. Section 22 40 00 – Revised specification attached. Revised specification to indicate Chicago Faucets Model #116.113.AB.1, less battery back-up, and with chrome-plated trim plate for P418 and P419 lavatories.

Drawings

4. 350C301 - Clarification: Keynote 4 on Sheet 350C301 indicates: “Vectren to supply and install natural gas main, meter/regulator, refer to MEP Plans for Building Connection. Include all Vectren costs in bid.” Contractor shall include in bid an allowance of $140,000.00 to pay Vectren for Aide to Construction costs associate with the new gas main design and installation. Contractor shall make application to Vectren for the gas main on the owner’s behalf.

5. 350PP101 – Revised drawing attached. Revised Plan Note #11 to indicate requirement for transformer, power wiring and electrical boxes, conduit, and low-voltage wiring for lavatories.

6. 350P601 – Revised drawing attached. Revised Plumbing Fixture Schedule to indicate Chicago Faucets Model #116.113.AB.1, less battery back-up, and with chrome-plated trim plate for P418 and P419 lavatories.

7. 350M401- Drawing resubmitted for line weights and clarity.

8. 350MH101- Drawing resubmitted for line weights and clarity.

9. 350MH102- Drawing resubmitted for line weights and clarity.

10. 350MP101- Drawing resubmitted for line weights and clarity.

11. 350EL101- Drawing resubmitted for line weights and clarity.

12. 350EP101- Drawing resubmitted for line weights and clarity.

13. 350EP102- Drawing resubmitted for line weights and clarity.

14. 350ES101- Drawing resubmitted for line weights and clarity.

15. 350ES102- Drawing resubmitted for line weights and clarity.

16. 350ET101- Drawing resubmitted for line weights and clarity.

B F

P B

F P

P

P

M

BFP

TP

T P

T P

TP

B F

P

B F

P

B F

P P

P

M

BFP

TP

T P

B F

P

TP

T P

P802

0.75"

0.75"

P802

0.75"

P802

P802

0.75"

P524

P505

P808 P808

P502

P418 P505

P419

P103

3" VTR

CO CO

CO

CO CO

3" VTR

CO

P524

3" VTR

V

P419

FD1

P103

P419 P701

P419

P103

FD1

P701

P419

V

V

V

V

V

V

P419

FD1

P103

P419

P701

P419 P103

FD1 P701

P419

MA

MV

O2

O

M V

M A

ZVC

MA

O2

MV

O2

MVMA

O

M V

M A

0.5"

0.5"

0.75"

0.5"

0.75"

0.5"

P419

P701

FD1

P103 P419

P419 P103

FD1

P419

P701

M A

M V

O

M A

M V

O

P419 P419

FD1

P103

P701P419

FD1

P701P419

COCO

P419

FD1

P103 P419

P419

P701

P103

FD1

P701

P419

P524

P419

FD1

P103

P701 P419 P419

P103

FD1

P701 P419V

V

V

STM

S T

M

STM

S T

M

OD1

RD1

RD1

RD1

OD1

RD1

OD1

OD1

TEST-Y & CO

3" VTR

3" VTR

V

V

V

V V

V

V

0.5"

0.75"

0.5"

0.5"0.75"

0.5"

0.5" 0.75"

0.5"

0.5"0.75"

0.5"

0.5" 0.75"

0.5"

0.5"

0.75" 0.5"

0.5"1"0.5"

V V

V

0.75"0.75"

V

V

0.75"

1"

0.75"

0.5"

0.75"0.5"

0.5"

0.75" 0.5"

0.5" 0.75"

0.5"

0.5"

1"

0.5"

4" DS (2,180 SF)

FD1

FD1

CO

CO

P103

2"0.75"

2"0.75"

1"2"

1"2"

1"2"

1"2"

1"

2"

1"2"

1"1.25"

1.25" 1"

1.5"

1.25"

1"

1"

1.25"

1.25"1"1.25"1.5"

1.5"

1.5"

1.5"

2"

2"1.5"

1.5"

2.5" 0.75"

350PP101

350PP101

V

V

350PP101

350PP101

CO

CO

CO

CO

CO

P524

CO

OD OD

CO

CO

1"

O2

MVMA

O

M V

M A

3"

3"

3"

3"

S T

M

3"

3"

3" DS (1,090 SF)

CO

CO

CO

S T

M

3"

3" DS (1,090 SF)

10 10

138A I.T

P524

P525

3" G

G

TEST-Y & CO

TEST-Y & CO

121B

CL.

121A

BATH

BATH

120A

120B

CL.

OD

OD

3"

3"

- 1,090 SF

- 1,090 SF

OD

O D

3"

3"

3"

201,090 SF -

AAP - 23

*BARIATRIC

ROOM

OD OD

3" 3"

201,090 SF -

113B

ELECTRICAL

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

117-1

DINING

ROOM - 1

STUDY

BEDROOM

BEDROOM

THERAPY/EXERCISE

CIRCULATION

STAFF

BREAK

KITCHEN

BEDROOM

BEDROOM144

DEN

LIVING

ROOM

113A

ELECTRICAL

N.F.S.

MECH/WATER

BEDROOM145

BEDROOM

VESTIBULE

CLEAN

LINEN

CLEAN

SUPPLY

SOILED

UTILITY

CORRDIOR

CIRCULATION

CORRIDOR

STAFF

TOILET

117-1

COMMUNICATION

BULK

STORAGE

OFFICE

LAUNDRY

HAC

CIRCULATION

MEDICATION

COOLER

BEDROOM

BEDROOM

125C

CARE

126C

CARE

126A

BATH

125A

BATH

CORRIDOR

P419

P419

FD1

P701

P103 P103

FD1

P701

P419 P419

0.5"0.75"

0.5"

0.5"

0.75"

0.5"

0.5" 0.5" 0.5"

0.5"

0.5" 0.5" 0.5" 1.25"

1.5"

1.5" 1.5"

1.25"

1"

1" 1.25"

0.5" 0.5"

0.5"

0.5"

0.5"0.5"

MA

MV

O2

M A

M V

O

COCO

0.5" 0.5"

1.25"1.25" 1.25"

V

V

V V

V

V

V

V

CO

11 11

B

MECH/

WATER

CO

MAC1

MVP1

FD1

FD1

FD1

FD2

FD2

FD1

FD1

350P601

SWTS1

VR

VR

CWS

3"

4"

CO

DHWXT1

DHWRP1

M V

M A

1"

0.75"

P418 P505

V

153 GPM -

3"

G

3"

3"

G

3"

- 400 CFH

- 400 CFH

- 400 CFH

- 150 CFH

150 CFH -

3"

O D

3"

O D

20 - (1,090 SF)

2"

2"

P702

0.5"0.5"0.5"

0.5" 0.5" 0.5"

0.5"

1.5" 1.5"

1.5"

0.5"

2.5"

2.5"

3"

1"

O

DHWH1

DHWH2

LAUNDRY

HAC

P505

P502

P808 P808

FD1

1" 1.25"

0.5"

1.25" 1" 0.75"

0.75"0.75"0.75"

0.75"

0.75"

V

V

STAFF

TOILET

P419

P103

FD1

2"

0.75"

2" 0.75"

0.5"

0.5" 1.25"

1.25"

P

DHW

P

DCW

P

5 GPH

CHEMICAL

DOSING

PACKAGE SRE2000 NSF

GENERATOR

SODIUM CHLORITE

SUPPLY (HYG-25) -

SOFTENER BRINE

TANK

DRIP/SPILL

CONTAINMENT -

10" CARTRIDGE

FILTER -

REGULATOR -

CONTROLLER &

SENSOR ASSEMBLY -

DCW

FLOW SENSOR -

NALCO 3DT 360

FOR ENVIROX -

- 10" CARTRIDGE

FILTER

GLOBAL GATEWAY -

- REGULATOR

- REGULATOR

- 20" CARTRIDGE

FILTER

FLOW

METER

COMPUTER -

- CONTROLLER &

SENSOR ASSEMBLY

FLOOR DRAIN -

0.5"

0.75"

0.5" 0.5"

0.75"

0.5" 0.5"- DRIP/SPILL

CONTAINMENT

- CONCRETE PAD

FLOOR

DCW MAIN

RECIRCULATED

DHW MAIN

*COORDINATE SIZING, MOUNTING

HEIGHTS, CLEARANCES,

FLOW RATES, UTILITY REQUIREMENTS,

INSTALLATION, AND CONNECTIONS

WITH NALCO.

3 3

1 1

1 1

DETAIL NOTES

1 PROVIDED BY DIVISION 22.

2 SUPPLIED BY NALCO, INSTALLED BY DIVISION 22.

3 SUPPLIED AND INSTALLED BY NALCO. DIVISION 22

IS RESPONSIBLE FOR RECEIVING ALL "NALCO"

COMPONENTS ONSITE, TRANSPORTING TO MECHANICAL

ROOM, UNPACKING ALL COMPONENTS, AND REMOVING

PACKAGING FROM SITE.

4 BRINE TANK SUPPLIED AND INSTALLED BY NALCO.

DIVISION 22 SHALL PROVIDE 100 LBS. OF WATER

SOFTENER GRADE SALT PELLETS (NOT GRANULES)

WITH NO ADDITIVES.

5 SODIUM CHLORITE DRUM WITH SPILL CONTAINMENT

BY NALCO. DIVISION 22 SHALL PROVIDE SODIUM

CHLORITE.

*NALCO WILL MAKE FINAL MISC.

TUBING & ELECTRICAL

CONNECTIONS BETWEEN MAJOR

ENVIROX EQUIPMENT AND

DIVISION 22 INSTALLED UTILITIES.

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE,

SUITE 200

MIAMISBURG, OHIO

45342

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

JPA Project No.

937 461 3290 PHONE

937 461 0260 FAX

jpa@johnpoe.com

100% CONSTRUCTION DOCUMENTS -

Heapy Project No.: 2015-04026 Firm License No.: 01528

Construct CLC Single Story Unit

10.06.2017

FIRST FLOOR PLAN

350PP101

DPBWSM

15010

552-161

Dayton, Ohio

N Scale:

PROJECT

1/8" = 1'-0"

FIRST FLOOR PLAN

GENERAL NOTES

NOTES

A REFER TO SHEET 350P001 FOR GENERAL NOTES, LEGEND, AND INDEX OF DRAWINGS.

1 COMBINATION WATER SERVICE PIPING UP THROUGH FLOOR SLAB. REFER TO

DETAIL 2/350FS100.

2 FIRE RISER. REFER TO DETAIL 6/350P601 AND 2/350FS100.

3 FLANGE SERVING DOMESTIC WATER SERVICE. REFER TO DETAIL 2/350FS100.

4 SECONDARY DOMESTIC WATER METER. REFER TO DETAIL 6/350P601.

5 TRAP PRIMER. REFER TO DETAIL 2/350P601.

SCALE: 1/4" = 1'-0"

TYPICAL PATIENT ROOM

SCALE: 1/4" = 1'-0"

MECHANICAL ROOM

SCALE: 1/4" = 1'-0"

HAC/LAUNDRY ROOM

SCALE: 1/4" = 1'-0"

STAFF TOILET

6 HEATING HOT WATER BOILER. REFER TO DIVISION 23 DRAWINGS.

7 DUPLEX REDUCED PRESSURE TYPE BACKFLOW PREVENTERS. REFER TO

DETAIL 6/350P601.

8 0.75-INCH SIZE REDUCED PRESSURE TYPE BACKFLOW PREVENTER TO

SERVE MECHANICAL MAKE-UP WATER SYSTEM.

9 PROVIDE VALVE AND CAP AT POINT OF CONNECTION TO MECHANICAL MAKE-

UP WATER SYSTEM. REFER TO DIVISION 23 DRAWINGS FOR CONTINUATION

OF PIPING.

10 NO WATER OR STORM PIPING SHALL BE LOCATED ABOVE THIS ROOM.

11 PROVIDE A BOX-MOUNTED TRANSFORMER LOCATED ABOVE

THE CEILING AND LOW VOLTAGE WIRING TO CONTROL SENSOR

OPERATED FAUCET ON FIXTURE(S) BELOW. 120V-1PH POWER

WILL BE LOCATED IN A WIRING BOX ABOVE THE CEILING WITH

A 0.75" CONDUIT STUBBED ABOVE THE CEILING AND

EXTENDED DOWN TO AN ELECTRICAL WALL BOX LOCATED

BELOW EACH LAVATORY (REFER TO DIVISION 26 DRAWINGS).

12 PATIENT LIFT RAILING AND STRUCTURAL SUPPORTS.

13 SINGLE-SIDED, MODULAR MEDICAL GAS SERVICES ASSEMBLY WITH

MEDICAL GAS OUTLETS AND VACUUM SLIDE HIDDEN BEHIND A MOVABLE

PICTURE.

14 MEDICAL GAS PIPING (SIZED AS INDICATED) EXTENDS DOWN IN WALL TO

SERVE SINGLE-SIDED, MODULAR MEDICAL GAS SERVICES ASSEMBLY.

15 BALANCING VALVE SET TO INDICATED FLOW RATE. REFER TO DETAIL

4/350P601 FOR BALANCING VALVE INSTALLATION REQUIREMENTS.

16 WATER CONNECTION BOX TO SERVE COFFEE MAKER.

17 WATER CONNECTION BOX TO SERVE WATER DISPENSER.

18 NATURAL GAS METER / REGULATOR ASSEMBLY PROVIDED BY

VECTREN. CONNECT TO OUTLET OF METER / REGULATOR AND

EXTEND PIPING (SIZE AS INDICATED) INTO BUILDING.

VECTREN CONTACT: BRIAN VOLPATTI @ 937-312-2560.

19 NATURAL GAS CONNECTION TO ITEM OF EQUIPMENT, CAPACITY AS

INDICATED. REFER TO DETAIL 3/350P601.

20 LOCATION OF EMERGENCY OVERFLOW DRAIN TERMINATION WITH

DOWNSPOUT NOZZLE. REFER TO DETAIL 5/350P601.

21 2-INCH SIZED REDUCED PRESSURE TYPE BACKFLOW PREVENTER TO

SERVE IRRIGATION WATER PIPING SYSTEM.

22 2-INCH IRRIGATION WATER PIPING SYSTEM CONNECTION. REFER TO

IRRIGATION PLANTING PLAN FOR ADDITIONAL INFORMATION.

23 EXTEND WIRING FROM GAS SPECIFIC SENSOR LOCATED AT REMOTE

PIPING SENSOR INSTALLATION OR ZONE VALVE BOX SENSOR

INSTALLATION TO AREA ALARM PANEL.

24 EMERGENCY THERMOSTATIC MIXING VALVE.

CAPACITY: 3 GPM @ 10 PSI DROP

EXTEND 0.5-INCH TEMPERED WATER PIPING TO SERVE P702.

25 EXTEND 1.5" MEDICAL AIR COMPRESSOR INTAKE PIPING UP THROUGH

ROOF.

26 EXTEND 2" MEDICAL VACUUM PRODUCER EXHAUST PIPING UP THROUGH

ROOF.

27 CAP EXISTING O2 PIPING TO ACCOMMODATE FUTURE EXTENSION OF

O2 SYSTEM.

28 2" STANDPIPE SERVING HUMIDIFER.

SCALE: NONE

SWTS1

Revisions Date

6 Addendum #1 04.18.2018

5 Bid Documents 10.06.2017

4 100% Construction Documents 06.30.2017

3 95% Owner Review 01.06.2017

2 Design Development 09.26.2016

1 Schematic Design 06.29.2016

MARK LOCATION

MECH RMDHWH1

SERVED

BLDG

AND/OR

AREA

SERVICE

AND/OR

SYSTEM

TYPE GAL (L)

CAPACITY

STORAGE

GAL/HR (L/HR)

(39 DEG C.) RISE

RECOVERY @ 70 DEG F.

SETTING

RELIEF VALVE

PSIG (KPa) TYPE

INLET PRESSURE FLOW

IN WG (PA) CFH (L/H)

FUEL ELECTRICAL MOTOR

NOMINAL POWER (EA.)

HP (kW)

PHASE VOLT

NOTES

CLC BLDG DHW TANK 100 379 255 963 NAT. GAS 7 1744 150 4248 - - - - 1 120

MECH RMDHWH2 CLC BLDG DHW TANK 100 379 255 963 NAT. GAS 7 1744 150 4248 - - - - 1 120

MARK LOCATION

MECH RMDHWRP1

SERVED

BLDG

AND/OR

AREA

SERVICE

AND/OR

SYSTEM

TYPE

FLUID

GPM (L/s) FT

CIRCULATING FLUID

FT DEG F (DEG C) SP. GR. EFF

FUEL ELECTRICAL MOTOR

NOMINAL POWER (EA.)

HP (kW)

PHASE VOLT

NOTES

CLC BLDG DHW CENT

DOM

6 0.38 15 N/A 140 60 1 70 - - 1 115 CONSTANT

FLOW

(KPa)

HEAD NPSH AVAILABLE TEMPERATURE

MIN. % RPM

MAX

CONTROL

SPEED

(KPa)

WATER

45 N/A 1/12 1750

MARK LOCATION

MECH RMDHWXT1

TYPE

NOTES

THERMAL

MIN. MAX.

DEG. F (DEG C)

SYSTEM TEMP RANGE

60 16 140 60

DEG. F (DEG C)

IN TANK

INITIAL PRESSURE

PSIG (kPa)

PRESSURE

MAX OPERATING

PSIG (kPa)

(kPa)

RELIEF VALVE PSIG

PSIG (kPa)

MIN TANK VOLUME

GAL (L)

MIN ACCEPT VOLUME

GAL (L)

PIPE SIZE TO TANK

IN (mm)

EXPANSION

50 350 80 550 100 690 2 8 0.90 3.6 0.75 19.1

MARK LOCATION

MECH RMMVP1

SERVED

BLDG

AND/OR

AREA

SERVICE

AND/OR

SYSTEM

TYPE GAL (L) in Hg SCFM

ELECTRICAL POWER

POWER EACH

HP (kW)

PHASE VOLT

NOTES

CLC BLDG

MEDICAL

80 302.8 19 13 3 208

RECEIVER SIZE

(KPa)

VACUUM PRESSURE PRESSURE (SI)

STANDARD

64.3 6.12 3 1800

VACUUM

CFM DELIVERY @

(L/s)

NO. PUMPS RPM

VACUUM

DUPLEX

OIL-LESS ROTARY

2 1,22.237

MARK LOCATION

MECH RMMAC1

SERVED

BLDG

AND/OR

AREA

SERVICE

AND/OR

SYSTEM

TYPE GAL (L) PSIG CFM

ELECTRICAL POWER

POWER EACH

HP (kW)

PHASE VOLT

NOTES

CLC BLDG

MEDICAL

80 302.8 60 10.4 3 208

RECEIVER SIZE

(KPa)

DISCHARGE PRESSURE INLET AIRFLOW

STANDARD

413 3.9 3 3600

(L/s)

NO. PUMPS RPM

AIR

DUPLEX

OIL-LESS SCROLL

2 1,22.237

MARK LOCATION

MECH RMSWTS1

SERVED

BLDG

AND/OR

AREA

SERVICE

AND/OR

SYSTEM

TYPE GPM (L/s)

FLOW RATE

CONTINUOUS

GAL/DAY (L/DAY)

NOTES

CLC BLDG DCW DIOXIDE 5 0.32 20,000 75,708 1,2,3,4,5,6,7,8

CHLORINE

SYMBOL C.I.

BODY STRAINER / GRATE TOP FINISH

- -FD1

FD2

S.S. C.R. BRASS RD. SQ. ADJUST. FLAT RECESS DOME BRONZE C.I. C.R. S.S.

NICKEL

SYMBOL DESCRIPTION DRAINS

FIXTURE UNITS DRAINAGE CONNECTION

4 5/- - 2" - -P103

HEIGHT

18" TO RIM

MOUNTING

C/H

WATER

SUPPLY

COLD HOT TEPID OUTLET VENT DIRECT INDIRECT

1" - - - - 4"

P502 FLOOR SET 3 2.25/2.25 1.5"0.5" - - 3" 0.5" - -

- -P419 - - 1 - - - -

P418 34" TO RIM 1 0.6/0.6 0.5" 0.5"

0.6/0.6 0.5" 0.5"

1.5"1.5"

1.5"1.5" - -

P505 34" TO RIM 3 2.25/2.25 0.5" 0.5" - -- - 1.5"1.5"

P524 - - 2 1/1 1.5" - -0.5" 0.5" - - 1.5"

P525 - - 2 1/1 1.5" - -0.5" 0.5" - - (2) 1.5"

P701 44" VALVE

P702 42"

2 1/1 1.5" - -0.5" 0.5" - - 2"

0 0 1.5" - -- - - - 0.75" 1.5"

- - 3/0 - - - -P802 24" 0.75" - - - - - - - -

P808 2 1/1 0.5" 0.5" - - 2" 1.5" - -

RD1

OD1

GAS FIRED WATER HEATER SCHEDULE

PLUMBING PUMP SCHEDULE

DOMESTIC WATER THERMAL EXPANSION TANK SCHEDULE

VACUUM PUMP SCHEDULE

AIR COMPRESSOR SCHEDULE

SECONDARY WATER TREATMENT EQUIPMENT SCHEDULE

DRAIN SCHEDULE

FIXTURE SCHEDULE

EQUIPMENT SCHEDULE NOTES:

1 PROVIDE HOUSEKEEPING PAD & DRAIN PAN AND EXTEND DRAIN PIPING TO FLOOR DRAIN.

EQUIPMENT SCHEDULE NOTES:

1 PIPE MOUNTED PUMP.

EQUIPMENT SCHEDULE NOTES:

1 PIPE MOUNTED TANK.

EQUIPMENT SCHEDULE NOTES:

1 PROVIDE HOUSEKEEPING PAD AND EXTEND DRAIN PIPING TO FLOOR DRAIN.

EQUIPMENT SCHEDULE NOTES:

1 PROVIDE HOUSEKEEPING PAD.

2 PACKAGED UNIT WITH SINGLE-POINT CONNECTION.

2 PACKAGED UNIT WITH SINGLE-POINT CONNECTION.

EQUIPMENT SCHEDULE NOTES:

1 INCLUDES TREATMENT FOR DOMESTIC COLD WATER AND DOMESTIC HOT WATER SYSTEMS.

2 EQUIPMENT SHALL BE NSF-61 CERTIFIED.

3 EQUIPMENT SHALL HAVE FULLY AUTOMATIC CONTROLLERS.

4 EQUIPMENT SHALL INCLUDE COMMISSIONING AND START-UP.

5 PROVIDE CHLORITE SPILL KIT.

6 PROVIDE SODIUM CHLORITE DRUM WITH SPILL CONTAINMENT.

7 PROVIDE CONTINUOUS MONITORING SYSTEM WITH WALL-MOUNTED PANEL WITH MULTI-CHANNEL MEASURING AND CONTROL SYSTEM.

SYSTEM SHALL INCLUDE SAMPLING LINES, PROBE AND PROBE HOLDERS, AND PRESSURE TRANSMITTER. SYSTEM SHALL INCLUDE CONTROLS

FOR BAS CONNECTIVITY AND BE COMPATIBLE WITH DVAMC'S CURRENT SYSTEM. SYSTEM SHALL MONITOR WATER PRESSURE, DISSOLVED

SOLIDS IN WATER BY CONDUCTIVITY, TEMPERATURE, pH OF WATER, AND OXIDANT RESIDUAL.

8 SECONDARY WATER TREATMENT SYSTEM SHALL BE NALCO SRE2000NSF CHLORINE DIOXIDE GENERATOR WITH 5 GPH CHEMICAL DOSING

DESCRIPTION

3" MEDIUM DUTY / DOUBLE DRAINAGE / VANDAL RESISTANT (TYPE C) / TRAP PRIMER CONNECTION

WATER CLOSET / WALL HUNG / ELONGATED BOWL / ADA / 1.28 GPF

REMARKS

BATTERY POWERED, SENSOR OPERATED FLUSH VALVE

MOP SINK / 24"x24x12" / 6"DROP FRONT / TERRAZZO PAIL HOOK FAUCET / VACUUM BREAKER / CROSS HANDLES

HARD-WIRED / SENSOR OPERATED / GOOSENECK SPOUT

LAVATORY / C'TOP / ADA / NON-AERATED / CHICAGO FAUCET MODEL

#116.113.AB.1 / LESS BATTERY BACK-UP / CHROME PLATED TRIM PLATE

LAVATORY / WALL HUNG / 20" X 18" / ADA / NON-AERATED / CHICAGO FAUCET

MODEL #116.113.AB.1 / LESS BATTERY BACK-UP / CHROME PLATED TRIM PLATE

HARD-WIRED / SENSOR OPERATED / GOOSENECK SPOUT / LAV SHIELD

SERVICE SINK / WALL MOUNTED GOOSENECK SPOUT / WRIST BLADE HANDLES

SINK INTEGRAL W/ C'TOP/ ADA SINGLE LEVER HANDLES / GOOSENECK SPOUT / ADA

SINK INTEGRAL W/ C'TOP / ADA / TWO COMP'T SINGLE LEVER HANDLES / GOOSENECK SPOUT / ADA

SHOWER VALVE & HEAD ASSEMBLY / ENCLOSURE BY GENERAL TRADES / ADA

EYE / FACEWASH / WALL-MOUNTED / PLASTIC BOWL

PRESSURE BALANCING / HAND HELD HOSE / VACUUM BREAKER

EYE/FACEWASH / TEPID WATER FROM EMERGENCY THERMOSTATIC MIXING VALVE

WALL HYDRANT / FREEZE PROOF NON-FREEZE / INTEGRAL VACUUM BREAKER

DOMESTIC WATER SUPPLY / DRAIN BOX

48" TO

C.L.

QUARTER TURN VALVE / INTEGRAL VACUUM BREAKER

4" MEDIUM DUTY / DOUBLE DRAINAGE / 12" X 12" X 8" FLOOR SINK / (TYPE R) / TRAP PRIMER CONNECTION

3" FLANGED W/ADJ. DRAINAGE COLLAR / SUMP RECEIVER / BEARING PAN / DECK CLAMP

3" FLANGED W/ADJ. DRAINAGE COLLAR / SUMP RECEIVER / BEARING PAN / DECK CLAMP / 3" STANDPIPE

PACKAGE - REFER TO SPECIFICATION SECTION 22 11 00 - 2.13 AND DETAIL 6/350PP101.

TRAP PRIMER, WITH DISTRIBUTION

UNIT WHEN SERVING MULTIPLE

DRAINS. LOCATE ABOVE CEILING

IN FINISHED AREAS.

0.5''SUPPLY SHALL BE

OFF TOP OF MAIN

COLD WATER MAIN

T P

T P

WALL

FINISHED CEILING

WHERE APPLICABLE

FLOOR DRAINS

FLOOR

TP

PIPING TO FLOOR DRAINS

SHALL BE RUN BELOW FLOOR,

UNLESS NOTED OTHERWISE.

INSTALL PIPING CONCEALED

IN WALL IN FINISHED AREAS.

INSTALL PIPING TIGHT TO WALL

SURFACE IN UNFINISHED AREAS.

MIN. 45 DEGREES

BRANCH OR RUNOUT

TO STATION OUTLET,

INLET OR SPECIAL STATION

MAIN OR BRANCH PIPING

PIPE SIZE AS

INDICATED

ON PLANS

SHUT-OFF VALVE

EQUIPMENT CONNECTION

PIPE SIZE

EQUIPMENT

CONNECTION

UNION

PIPE CAP

3'' MIN.

UNION

BALL VALVE (SEE SPECS)

CHECK VALVE (SEE SPECS)FLOW CONTROLLER (SEE SPECS)

UNION

BALL VALVE (SEE SPECS)

EXTERIOR WALL SYSTEM

ZURN NO. ZS199-DC

304 STAINLESS STEEL

DOWNSPOUT COVER

CAULK UNDER AND AROUND

SCUPPER DRAIN PRIOR TO

INSTALLATION

OVERFLOW

STORM PIPE

WITH INSULATION

1 AIR GAP OVER FLOOR DRAIN.

2 COMBINATION TEMPERATURE-PRESSURE RELIEF VALVE.

3 MINIMUM 27'' HEAT TRAP

4 VACUUM RELIEF VALVE.

5 AIR GAP OVER FLOOR.

6 SET WATER TEMPERATURE TO DISTRIBUTE OUT AT

130 DEG. F WITH A 5 DEG. F. TEMPERATURE DIFFERENCE.

DTCS1

DHWH2

DHWXT1

DHWH1

.3

T

P

T

P

NOTES

P/T

P/T

ROOF

CAP

INLET SCREEN

(TYP.)

24" TYP.

MIN. 10'-0" ROOF

CAP

INLET SCREEN

(TYP.)

24" TYP.

MIN. 10'-0"

1.5" 1.5"

1.5"

1.5"

1.5"

0.75"

1.5"

1.5"

2.5"

1.5"

1.5"

1.5"1.5"

1.5" 1.5"

0.75" 0.75"

0.75"

0.75"

0.75"

0.75"

NG

NG NG

N

GN

G

3" 3"

1.5"

1.5"

SCH 40 PVC OR IN COMPLIANCE

WITH MANUFACTURER'S

REQUIREMENTS. REFER TO

SPECIFICATION (TYP.)

DOUBLE WALL FLUE PIPING.

AL294C OR STAINLESS STEEL

INNER LINER, AND ALUMINIZED

STEEL OUTER JACKET. REFER

TO SPECIFICATION (TYP.)

OUTER JACKET OF COMPONENTS OUTSIDE

THE BUILDING SHALL BE TYPE 304 STAINLESS STEEL

REFER TO SPECIFICATION (TYP.)

DHWRP1

Level 1 100' - 0"

Bearing 111' - 6"

Level 1 100'-0"

Bearing Point 111'-6"

FLAT ROOF

112'-5 7/8"

P

P

BALL VALVE

CHECK

VALVES

STRAINERS

REDUCED PRESSURE

TYPE BACKFLOW PREVENTERS

(EXTEND DISCHARGE PIPING

TO FLOOR DRAIN)

WATER

METER

FLANGE

BY F.S.C. FLOOR DRAIN

FLOOR

DRAIN

FLOOR

SV

FS

DOUBLE CHECK

DETECTOR ASSEMBLY

SV

SV

TRAP PRIMER

2" SIZED REDUCED PRESSURE

TYPE BACKFLOW PREVENTER

TO SERVE IRRIGATION SYSTEM

(EXTEND DISCHARGE PIPING

TO FLOOR DRAIN)

0.5"

0.5"

2"

3"

3"

3"

2"

3"

NOTE:

1 REFER TO FLOOR PLANS FOR REQUIRED NUMBER OF

VALVES, VALVE SERVICES AND SIZES AT EACH INDIVIDUAL LOCATION.

VACUUM GAUGE

PRESSURE

GAUGE, TYPICAL

MEDICAL GAS OR VACUUM

PIPING TO/FROM STATION

INLETS AND OUTLETS

SYSTEM AND SERVICE

AREA LABEL, TYPICAL

MEDICAL GAS OR VACUUM

PIPING TO/FROM

DISTRIBUTION SYSTEM

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE,

SUITE 200

MIAMISBURG, OHIO

45342

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

JPA Project No.

937 461 3290 PHONE

937 461 0260 FAX

jpa@johnpoe.com

100% CONSTRUCTION DOCUMENTS -

Heapy Project No.: 2015-04026 Firm License No.: 01528

Construct CLC Single Story Unit

10.06.2017

SCHEDULES, DETAILS, &

DIAGRAMS

350P601

DPBWSM

15010

552-161

Dayton, Ohio

SCALE: NONE

TRAP PRIMER

SCALE: NONE

BRANCH TAKE-OFF PIPING - MEDICAL GAS

SCALE: NONE

TYPICAL EQUIPMENT GAS CONNECTION

SCALE: NONE

FLOW CONTROLLER ASSEMBLY

SCALE: NONE

SECONDARY ROOF DRAIN COVER

SCALE: NONE

DOMESTIC WATER HEATER PIPING

SCALE: NONE

WATER SERVICE

SCALE: NONE

MEDICAL GAS ZONE VALVE

Revisions Date

6 Addendum #1 04.18.2018

5 Bid Documents 10.06.2017

4 100% Construction Documents 06.30.2017

3 95% Owner Review 01.06.2017

2 Design Development 09.26.2016

1 Schematic Design 06.29.2016

B F

P

B F

P P

P

M

BFP

TP

T P

B F

P

T

T

T

T

SCALE: NONE

DIAPHRAGM EXPANSION TANK

PITCH UP 1.6%

SLOPE (MIN.)

CONNECTOR PIPE

NORMALLY OPEN GATE

VALVE IN VERTICAL

(REMOVE HANDLE)

MANUAL AIR VENT

PRESSURE GAGE

HWR

50 PSI

FLOOR

0.75" TO HUMIDIFIERS

(SEE FLOOR PLAN)

-A

S

MAKE UP ASSEMBLY

1"

0.75"

EXTEND TO FLOOR DRAIN

0.75"

FUNNEL

0.5"

0.75"

-W

F

HWS

HWR

FLOOR

FROM SYSTEM

TO SYSTEM

2.5"

2.5"

H W

S

CHEMICAL

POT FEEDER

2.5"

THERMOMETER

THERMOMETER

0.75"

1"

0.75"

0.75"

PRESSURE GAGE

350-P4

0.5"

2.5"

PRESSURE GAGE

350-P5

0.5"

2.5"

2.5"

1"

2.5"

350-BHW1 350-BHW2 350-BHW3

350-P1 350-P2 350-P3

1 1 1

1 WALL MOUNTED HIGH EFFICIENCY BOILER SIZED FOR

50% OF BUILDING LOAD.

2 PRIMARY PUMP FURNISHED WITH BOILER. SHIPPED

LOOSE.

3 BYPASS VALVE-NORMALLY CLOSED.

4 EXTEND SAFETY RELIEF VALVE DISCHARGE TO FLOOR

DRAIN.

5 PRESSURE REDUCING VALVE SET AT 12 PSI.

6 HIGH CAPACITY AUTO AIR VENT. EXTEND DISCHARGE

TO FLOOR DRAIN.

7 INSTALL TOP OF CHEMICAL POT FEEDER TANK NO

MORE THAN 3'-0" ABOVE FLOOR.

8 1" REDUCED PRESSURE TYPE BACKFLOW PREVENTER.

REFER TO PLUMBING DRAWINGS. EXTEND DRAIN PIPE

TO FLOOR DRAIN.

9 PROVIDE HOSE CONNECTION AND SCREW-ON CAP.

10 ALLOW SPACE FOR INSULATING FILTER AND PIPING.

11 PROVIDE ANGLE FRAME TO SUPPORT PUMP OFF

FLOOR.

2 2 2

0.75"

H W

S

0.75"

2.5"

2.5"

H W

S

HWS

HWR

H W

R

2" 2.5" 2"

2"

2"

2"

NOTES

HEATING HOT WATER SYSTEM SCHEMATIC

B

MECH/

WATER

SCOOTER

STORAGE

B

350-UH-1

350-AC106

350-BHW3

350-BHW2

350-BHW1

350-P4

350-AS1

350-P5

350-UH-3

350-UH-2

H W

S

H W

R

350M401

350M401

1"1"

0.75"

0.75"

2.5"

2.5"

1"

HWS

M U

M U

H W

R

H W

S

HWR

HWS

HWR

R

H W

S

HWS

350-EH2

350-AP1

350-EF3

350-PTAC1

Level 1 100'-0"

Bearing Point 111'-6"

SWTS1

HWS

HWS

2.5"

1"

2.5" - HWS

2.5" - HWR

0.75" - MU

DHWH1 DHWH2

Level 1 100'-0"

Bearing Point 111'-6"

350-BHW1 350-BHW2 350-BHW3350-P4

350-P5

350-AS1

H W

S

DHWH1

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE,

SUITE 200

MIAMISBURG, OHIO

45342

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

JPA Project No.

937 461 3290 PHONE

937 461 0260 FAX

jpa@johnpoe.com

100% CONSTRUCTION DOCUMENTS -

Heapy Project No.: 2015-04026 Firm License No.: 01528

Construct CLC Single Story Unit

10.06.2017

ENLARGED MECHANICAL ROOM

AND SMOKING SHELTER PLAN

350M401

WJSBGA

15010

552-161

Dayton, Ohio

N Scale:

PROJECT

1/2" = 1'-0"

ENLARGED MECHANICAL ROOM PLAN

N Scale:

PROJECT

1/4" = 1'-0"

SHELTER PLAN

GENERAL NOTES

A. REFER TO SHEET 350M001 FOR LEGEND, ABBREVIATIONS AND ADDITIONAL GENERAL NOTES.

PLAN NOTES

1. PROVIDE WALL BRACKETS AND MOUNT UNIT AT APPROXIMATELY 7'-0" AFF.

2. REFER TO HEATING HOT WATER SYSTEM SCHEMATIC ON THIS SHEET FOR REQUIREMENTS

OF THIS ROOM.

3. PROVIDE REFRIGERANT PIPING AND ACCESSORIES PER MANNUFACTURER'S

RECOMMENDATIONS. APPROXIMATE ROUTE SHOWN.

4. EXTEND REFRIGERANT THRU ATTIC AND ONTO ROOF. REFER TO SHEET 350MH102 FOR

CONTINUATION.

5. MOUNT UNIT TO WALL ABOVE DOOR PER MANUFACTURER'S RECOMMENDATIONS. EXTEND

CONDENSATE DRAIN PIPING TO FLOOR DRAIN. PROVIDE CLEAN-OUTS AT EACH CHANGE OF

DIRECTION.

6. EXTEND 1" BOILER MAKE-UP WATER PIPING TO EQUIPMENT.

SCALE: 1/4" = 1'-0"

WATER TREATMENT SECTION PLAN

SCALE: 1/4" = 1'-0"

BOILER SECTION PLAN

sodell Snapshot

T

T

T

T

T T

T

T

T

T

T

T

T

T

T

T

TT

T

T

T

T

T

T

T

T

T

T T

T

T

TT

T

T

T

T

GF

J

B D

A C

HE

I

MEDICATION

GAS

KITCHEN

COOLER 115

N.F.S.

LAUNDRY

113B

ELECTRICAL

122B

CL.

CLEAN

LINEN

CLEAN

SUPPLY

101A

CL.

VESTIBULE

CORRIDOR

GAS

VESTIBULE

SOILED

UTILITY

CORRIDOR

HAC

126A

BATH

117A

DINING

ROOM

132B

CL.

135A

BATH

136A

BATH

OFFICE

142A

BATH

141A

BATH

125A

BATH

133A

BATH

134A

BATH

146A

BATH147C

CL

145A

BATH

BEDROOM

BEDROOM

CORRIDOR

144A

CL.

BEDROOM

BEDROOM

BEDROOM

BEDROOM

120A

BATH

121A

BATH

BEDROOM

BEDROOM

MECH/

WATER

SCOOTER

STORAGE

BEDROOM

BEDROOM

BEDROOM

BEDROOM

DEN

THERAPY/EXERCISE

CORRIDOR

STUDY

STAFF

BREAK

138B

COMMUNICATION

BULK

STORAGE

CORRIDOR

CORRIDOR

CORRIDOR

6ø

CD1

65 CFM

8ø

CD1

210 CFM

10ø

CD1

340 CFM

8ø

CD1

210 CFM

8ø

CD1

215 CFM

10ø

CD1

250 CFM

12ø

CD1

470 CFM

6ø

CD1

200 CFM

10x6

265 CFM

TR1

BOG: 10' - 7"

6ø

CD1

90 CFM

14x6

350 CFM

TR1

BOG: 10' - 9"

14x6

350 CFM

TR1

BOG: 10' - 9"

8ø

CD3

195 CFM

8ø

CD3

190 CFM

8ø

CD3

190 CFM

8ø

CD3

195 CFM

8ø

CD3

140 CFM

8ø

CD3

145 CFM

8ø

CD3

165 CFM

8ø

CD3

160 CFM

8ø

CD3

155 CFM

8ø

CD3

155 CFM

8ø

CD3

160 CFM

8ø

CD3

160 CFM8ø

CD1

235 CFM

8ø

CD3

190 CFM

8ø

CD3

190 CFM

8ø

CD3

190 CFM

8ø

CD3

190 CFM

6ø

CD1

50 CFM

8ø

CD3

200 CFM

8ø

CD3

200 CFM

8ø

CD3

200 CFM

8ø

CD3

200 CFM

8ø

CD3

200 CFM

8ø

CD3

200 CFM

8ø

CD3

200 CFM

8ø

CD3

200 CFM

8ø

CD1

200 CFM

8ø

CD1

200 CFM

8ø

CD1

200 CFM

350-TU-4-07

350-TU-4-08

350-TU-4-06

350-TU-4-05

350-TU-4-04

350-TU-4-02

350-TU-4-09

350-TU-3-03

350-TU-3-01

350-TU-3-04

350-TU-3-05

350-TU-3-06

350-TU-1-02

350-TU-1-06

350-TU-1-04

350-TU-1-07

350--TU-1-08

350-TU-2-01

350-TU-2-02

350-TU-2-05

24x12

135 CFM

CR1

D

350-TU-1-05

350-TU-1-01

8ø

CD1

180 CFM

350-TU-3-02

350-TU-4-01

R

D ø

20x16 x1

8x8

20x16 x1

6x10 x1 x1 x1 x8

14x10

14x8 x1 x1

12x6

12x6

8x x8 12 x8

12x6

8ø

10x10

24x12

310 CFM

CG2

8ø

24x12

310 CFM

CG2

x86x10

12x12

90 CFM

CR2

12x12

90 CFM

CR2

22x8

22x8

8ø

24x12

310 CFM

CG2

24x12

310 CFM

CG2

6x10

8ø 8ø

8ø

8ø

8ø

8ø

10x10

10x10

12x12

90 CFM

CR2

12x12

90 CFM

CR2

24x12

295 CFM

CG2

24x12

295 CFM

CG2

8ø 8ø

8ø 8ø

10x10 10x10

24x12

235 CFM

CG2

8ø

8ø

8ø

8ø

12x12

90 CFM

CR2

12x12

90 CFM

CR2

24x12

195 CFM

CG2

10x6

12x12

90 CFM

CR2

12x12

90 CFM

CR2

8ø

8ø 10x6

24x12

230 CFM

CG2

12x12

90 CFM

CR2

12x12

90 CFM

CR2

24x12

220 CFM

CG2

24x12

290 CFM

CG2

24x12

290 CFM

CG2

10x6

8ø

8ø

10x10

10x10 10x10 12x12

90 CFM

CR2

12x12

90 CFM

CR2

350-UH-3

350-UH-2

350-UH-5

350-UH-4

16x14

24x12

125 CFM

CG1

12x10

6x8

350-TU-2-06

24x24

505 CFM

CG2

138A I.T.

8ø

CD3

180 CFM

8ø

(2) CD3

185 CFM

6ø

CD1

50 CFM

6ø

CD1

50 CFM

x1

10x6

265 CFM

TR1

BOG: 10' - 7"

LIVING

ROOM

D

D

24x12

300 CFM

CG2

8ø

CD2

220 CFM

14x18

565 CFM

BG1

14x18

530 CFM

BG1

BOG: 1' - 0"

24x12

40 CFM

CG1

24x12

40 CFM

CG1

16x8

325 CFM

TG1

D

12x12

90 CFM

CR1

24x12

395 CFM

CG1

24x12

250 CFM

CG1

R

D

6x12

8x8

60 CFM

BG1

BOG: 0' - 7"

8ø

CD3

150 CFM

8ø

CD3

150 CFM

8ø

CD1

200 CFM

x1 x8 x1

R

ENCLOSED

PORCH

350-EUH-1

6x50

700 CFM

BG1

BOG: 1' - 3"

14x12

12x10

8x106x10

24x24

525 CFM

CG1

R

24x12

90 CFM

CG1

D

R x1 x1

24x12

300 CFM

CG1

16x16

D

20x14

12x8

14x10

6x10

350-TU-2-04

x6 x1

16x8 16x10

350-TU-2-03

12x16 10x10 x1

12x10

6x50

8ø

8ø

8ø

8ø

6ø

(2) CD4

90 CFM

R

10x6

10x6

250 CFM

TR1

BOG: 10' - 7"

10x6

250 CFM

TR1

BOG: 10' - 7"

350-RTU-3

ABOVE

350-RTU-1

ABOVE

350-RTU-2

ABOVE

350-RTU-4

ABOVE

16"x16"

UP TO

350-EF2

16" x 20"

UP TO

350-EF1

R 8x8

8x8

200 CFM

TR1

24x12

270 CFM

CG1

D

14x12

16x18

350MH101

350MH101

350MH101

350MH101

8ø

CD2

385 CFM

8ø

CD2

385 CFM

16x8

325 CFM

TG1

8x8

60 CFM

BG1

BOG: 0' - 7"

12x8

TG1

18x10 x8

8x6

60 CFM

TR1

8x6

170 CFM

TR1

x1 x1

8ø

CD2

215 CFM 7

R

24x12

200 CFM

CG1

24x12

125 CFM

CG1

350-AC138B

R

18x10

24x24

245 CFM

CR1

24x24

100 CFM

CR1

132A

CL.

147A

CL.

113A

ELECTRICAL

STAFF

TOILET

D

12x10

10x8

12x612x6

10x8

12x6

12x6

R

D

R

R 10x10 x1

10x8

12x10 x1

12x8

8x8

12x6

12x6 x6

16x10

12x6 x1

6x

8x

24x12

385 CFM

CG1

24x12

385 CFM

CG1

x6

8x6

8x6 x8

8ø 8ø

10x8

12x6

12x6

350-TU-3-07

10x6

10x614x10

6x8

10x12

10x10

10x10

10x10

10x10

10x10

10x10

(TYP)

(TYP)

4 (TYP)4(TYP)

(TYP)

R

5(TYP)

(TYP)

(TYP)

(TYP)

8ø

(2) CD3

175 CFM

350-TU-3-07

(TYP) (TYP)

4 (TYP)

12x10

4 4

10x6

230 CFM

TR211

12x6

350-TU-4-03

350-TU-1-03

D

14x6

350 CFM

TR1

14x6

350 CFM

TR1

6x50

700 CFM

BG1

350-EF1

350-TU-2-02

350-TU-2-03

350-TU-2-04

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE,

SUITE 200

MIAMISBURG, OHIO

45342

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

JPA Project No.

937 461 3290 PHONE

937 461 0260 FAX

jpa@johnpoe.com

100% CONSTRUCTION DOCUMENTS -

Heapy Project No.: 2015-04026 Firm License No.: 01528

Construct CLC Single Story Unit

10.06.2017

FIRST FLOOR PLAN - DUCTWORK

350MH101

WJSBGA

15010

552-161

Dayton, Ohio

N Scale:

PROJECT

1/8" = 1'-0"

FIRST FLOOR PLAN - DUCTWORK

GENERAL NOTES

A. REFER TO SHEET 350M001 FOR LEGEND, ABBREVIATIONS AND ADDITIONAL GENERAL NOTES.

PLAN NOTES

1. REFER TO SHEET 350MH401 FOR WORK IN THIS AREA.

2. PROVIDE DRYER WALL BOX BEHIND DRYER FOR DIRECT CONNECTION OF DRYER VENT.

EXTEND 3"x10" DUCT FROM DRYER BOX ABOVE CEILING. TRANSITION TO 4" DIA DUCT, EXTEND

THRU ROOF. REFER TO SHEET 350MH102 FOR CONTINUATION AND REFER TO DETAIL ON

SHEET 350M502.

3. EXTEND DUCT UP TO RTU. REFER TO SHEET 350MH102 FOR CONTINUATION.

4. LOCATE MANUAL DAMPERS ABOVE ACCESSIBLE CEILING.

5. MAINTAIN ADEQUATE WORKING CLEARANCE FOR ATU CONTROL PANEL.

6. PROVIDE HUMIDIFIER DISPERSION TUBE PER MANUFACTURER'S RECOMMENDATIONS.

PROVIDE STAINLESS STEEL DUCTWORK MINIMUM 8" UPSTREAM AND 24" DOWNSTREAM.

7. ROUTE DUCTWORK TO MISS LIGHTS.

8. PROVIDE FLEXIBLE DUCT AT INLET AND OUTLET.

9. AIR DEVICE SHALL BE UTILIZED TO ACCESS ATU. PROVIDE MOUNTING FRAME AND LAY-IN

TYPE AIR DEVICE TO ALLOW EASY REMOVAL. PROVIDE LONG ENOUGH RUN OF FLEX DUCT

FOR AIR DEVICE TO BE SET ON TOP OF ATU DURING SERVICE.

10. PROVIDE CABLE OPERATED DAMPER. MOUNT ACTUATOR NEAR ATU SERVING THIS SPACE.

11. PROVIDE KITCHEN HOOD WITH INTEGRAL FIRE SUPPRESSION SYSTEM PER SPECIFICATIONS.

Scale: 1/4" = 1'-0"4

DINING ROOM WEST

Scale: 1/4" = 1'-0"2

DINING ALCOVE NORTH

Scale: 1/4" = 1'-0"3

KITCHEN WEST

Scale: 1/4" = 1'-0"5

NFS - SOUTH

GF

J

B D

A C

HE

I

350MH102

350-RTU2

350-RTU1 350-RTU3

350-RTU4

350-CU-138B

350-EF2

350-EF1

350MH102

16x20

DN

16x16 DN 10

3 3

1" DN12

1" DN

1" DN 12

1" DN

4" 2

350-CU106

R

4 7

R

4 9DN

4 6

'-0

M

IN

OUTSIDE AIR INTAKE

OUTSIDE AIR INTAKE

'-0

M

IN

'-0

M

IN

'-0

M

IN

OUTSIDE AIR INTAKE

OUTSIDE AIR INTAKE

Level 1 100'-0"

Bearing Point 111'-6"

FLAT ROOF

112'-5 7/8"

350-RTU1

x1

22x8 350-TU-1-01

350MH101

350MH101

350-RTU2

350-EF1

350-TU-1-06

350-TU-2-01

Level 1 100'-0"

Bearing Point 111'-6"

FLAT ROOF

112'-5 7/8"

350-RTU3 350-RTU4

350-EF2

350-CU-138B

350-TU-3-07

350-TU-4-01

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE,

SUITE 200

MIAMISBURG, OHIO

45342

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

JPA Project No.

937 461 3290 PHONE

937 461 0260 FAX

jpa@johnpoe.com

100% CONSTRUCTION DOCUMENTS -

Heapy Project No.: 2015-04026 Firm License No.: 01528

Construct CLC Single Story Unit

10.06.2017

ROOF PLAN

350MH102

WJSBGA

15010

552-161

Dayton, Ohio

GENERAL NOTES

A. REFER TO SHEET 350M001 FOR LEGEND, ABBREVIATIONS AND ADDITIONAL GENERAL NOTES.

PLAN NOTES

N Scale:

PROJECT

1/8" = 1'-0"

ROOF PLAN

1. EXTEND BOILER FLUE THROUGH ROOF. PROVIDE CAP, ROOF PENETRATION CURB AND

ACCESSORIES PER MANUFACTURER'S RECOMMENDATIONS. FLUE MATERIAL SHALL BE

AL29-4C.

2. ROUTE COMBUSTION AIR AND FLUE DUCTS THROUGH ATTIC.

3. MAINTAIN EQUIPMENT MANUFACTURER'S REQUIRED SERVICE/AIR FLOW CLEARANCES.

4. PROVIDE REFRIGERANT PIPING AND ACCESSORIES PER MANUFACTURER'S

RECOMMENDATIONS. APPROXIMATE ROUTE SHOWN.

5. PROVIDE EQUIPMENT/PIPE SUPPORT CURB PER DETAIL ON SHEET 350M501.

6. EXTEND REFRIGERANT PIPING DOWN THRU ROOF. PROVIDE PIPE PENETRATION ROOF

CURB. REFER TO SHEET 350MP101 FOR CONTINUATION.

7. EXTEND PIPING THRU ATTIC.

8. SEAL PENETRATION WEATHERTIGHT.

9. REFER TO SHEET 350MP101 FOR CONTINUATION.

10. TRANSITION DUCT TO FULL SIZE OF EQUIPMENT CONNECTION. REFER TO SHEET

350MH101 FOR CONTINUATION.

11. TRANSITION DUCT TO FULL SIZE OF UNIT CONNECTION. PROVIDE FLEXIBLE DUCT

CONNECTOR. REFER TO SHEET 350MH101 FOR CONTINUATION.

12. EXTEND HEATING HOT WATER SUPPLY AND RETURN PIPING TO RTU COIL PER UNIT

MANUFACTURER'S RECOMMENDATIONS. REFER TO SHEET 350MP101 FOR

CONTINUATION.

13. TERMINATE DRYER VENT THRU ROOF WITH NON-RESTRICTIVE EXTRA CLEARANCE HIGH

PROFILE DRYER VENT TERMINATION. TERMINATION SHALL HAVE A MAXIMUM AIR FLOW

RESTRICTION OF 0.02" W.C.

14. EXTEND BOILER COMBUSTION AIR INTAKE THROUGH ROOF. PROVIDE ROOF

PENETRATION CURB. TERMINATE WITH GOOSENECK FITTING PER MANUFACTURER'S

RECOMMENDATIONS. INTAKE MATERIAL SHALL BE SCHEDULE 40 PVC.

SCALE: 1/4" = 1'-0"

350-RTU1 & 350-RTU2 EAST SECTION

SCALE: 1/4" = 1'-0"

350-RTU3 & 350-RTU4 EAST SECTION

HEAT PUMP CONDENSING SECTION

FILTERS

POWERED EXHAUST

100% ECONOMIZER

HOT WATER HEATING COIL

DX HEAT PUMP COIL

TYPICAL RTU CONFIGURATION

T

T

T

T T

T

T

T

T

T

T

T

T

T

T

TT

T

T

T

T

T

T

T

T

T

T T

T

T

TT

T

T

T

T

MEDICATION

GAS

KITCHEN

COOLER

N.F.S.

LAUNDRY

113B

ELECTRICAL

122B

CL.

CLEAN

LINEN

CLEAN

SUPPLY

101A

CL.

VESTIBULE

CORRIDOR

GAS

VESTIBULE

SOILED

UTILITY

CORRIDOR

HAC

126A

BATH

117A

DINING

ROOM

132B

CL.

135A

BATH

136A

BATH

147A

CL.

OFFICE

142A

BATH

125A

BATH

133A

BATH

134A

BATH

146A

BATH

147C

CL

145A

BATH

BEDROOM

BEDROOM

CORRIDOR

144A

CL.

BEDROOM

BEDROOM

BEDROOM

BEDROOM

120A

BATH

121A

BATH

BEDROOM

BEDROOM

MECH/

WATER

SCOOTER

STORAGE

BEDROOM

BEDROOM

BEDROOM

BEDROOM

350-TU-4-07

350-TU-4-08

350-TU-4-06

350-TU-4-05

350-TU-4-04

350-TU-4-02

350-TU-4-09

350-TU-3-03

350-TU-3-01

350-TU-3-04

350-TU-3-05350-TU-3-06

350-TU-1-02

350-TU-1-06

350-TU-1-04

350-TU-1-07 350--TU-1-08

350-TU-2-01

350-TU-2-02

350-TU-2-05

350-TU-1-05

350-TU-1-01

350-TU-3-02

J

F G

B D

CA

E H

350-UH-3

350-UH-2

0.

H W

S 0.

H

W R

1" - HWS

1" - HWR

1"

1"

H W

S

0.75"

1.5"

H W

R H

W S

2"

0.75"

1"

H W

S 1"

H

W R

1"

0.75"

1"1"

350-TU-4-01

2" - HWR

2" - HWS350-UH-5

350-UH-4

350-TU-2-06

STAFF

BREAK

CORRIDOR

STUDY

CORRIDOR 132

CORRIDOR

CORRIDOR

138B

COMMUNICATION

BULK

STORAGE

THERAPY/EXERCISE

CORRIDOR

DEN

141A

BATH

CORRIDOR

CORRIDOR

1.25" - HWR

1.25" - HWS

350-UH-1

1"

350-EUH-1

350-AC106

350-AC138B

UP TO ROOF

C.O.

C.O.

D

D

0.75"

1"

0.75" - HWS

0.75" - HWR

1.

5"

H

W R

1.

5"

H

W S

1.25" - HWR

1.25" - HWS

1.25" - HWR

1.25" - HWS

0.75"

350-CRP4

1.25"1.25"

2.5"2.5"

2.5"2.5"

350-RTU-4

ABOVE

350-RTU-2

ABOVE

350-RTU-3

ABOVE

350-RTU-1

ABOVE

350-EH2

350-CRP2

350-CRP1

1"

H W

R

0.75"0.75"

DP6

DP

H W

R H

W S

H W

S H

W R

5350-CRP-3

350-TU-2-04

350-TU-2-03

350-TU-3-07

350-EH-4

2"

350-EH-3

2"

2"

2"

350-TU-4-03

1"

MU

0.5" 0.75"

M U

MU

0.75"

1.5"1.5"

1.5"1.5"

0.5"

M U

350-TU-1-03

350-EH-1

M U

0.5"

350-TU-3-07

0.5"

M U

M U0.5"

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number

Dwg. of on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE,

SUITE 200

MIAMISBURG, OHIO

45342

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

JPA Project No.

937 461 3290 PHONE

937 461 0260 FAX

jpa@johnpoe.com

100% CONSTRUCTION DOCUMENTS -

Heapy Project No.: 2015-04026 Firm License No.: 01528

Construct CLC Single Story Unit

10.06.2017

FIRST FLOOR PLAN - PIPING

350MP101

WJSBGA

15010

552-161

Dayton, Ohio

N Scale:

PROJECT

1/8" = 1'-0"

FIRST FLOOR PLAN - PIPING

GENERAL NOTES

A. REFER TO SHEET 350M001 FOR LEGEND, ABBREVIATIONS AND ADDITIONAL GENERAL NOTES.

PLAN NOTES

1. REFER TO SHEET 350M401 FOR WORK IN THIS AREA.

2. EXTEND PIPING UP TO ROOFTOP UNIT PER DETAIL ON SHEET 350M502.

REFER TO SHEET 350MH102 FOR CONTINUATION.

3. PROVIDE REFRIGERANT PIPING AND ACCESSORIES PER MANUFACTURER'S

RECOMMENDATIONS. APPROXIMATE ROUTE SHOWN.

4. EXTEND CONDENSATE DRAIN PIPING DOWN WALL AND DISCHARGE INTO.

MOP SINK. PROVIDE CLEANOUTS AT EACH CHANGE IN DIRECTION.

5. PROVIDE HUMIDIFIER DISPERSION TUBE PER MANUFACTURER'S

RECOMMENDATIONS.

6. PROVIDE DDC DIFFERENTIAL SENSOR FOR CONTROL OF HOT WATER

SECONDARY PUMPS.

7. PROVIDE DDC BAS CONTROL PANEL AT THIS LOCATION.

2015-04026_350PP101 - FIRST FLOOR PLAN
Sheets
350P601 - SCHEDULES, DETAILS, & DIAGRAMS
350PP101 - FIRST FLOOR PLAN
2015-04026_350P601 - SCHEDULES, DETAILS, & DIAGRAMS
Sheets
350P601 - SCHEDULES, DETAILS, & DIAGRAMS
350PP101 - FIRST FLOOR PLAN
350M401
350MH101
350MH102
350MP101