This document is an Amendment to Request for Lease Proposal (RLP) No. 36C24W23R0041 issued by the Department of Veterans Affairs for a new Women's Clinic lease in Oklahoma City, OK. The VA is seeking a minimum of 22,299 to a maximum of 24,530 ABOA square feet of contiguous space, not to exceed 30,103 rentable square feet. The RLP has been amended to update the Agency's Requirements in Exhibit B1, clarify the requested square footage, increase the lease term to 20 years (10-year firm, 10-year non-firm), and provide responses to questions received from offerors. The VA has specified the required room types, sizes, and quantities in the Agency's Requirements, which include patient care areas, laboratory, imaging, and support spaces. This is an open market solicitation with no set-aside. The VA expects to award the contract in September 2024.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT NO. 1
TO REQUEST FOR LEASE PROPOSAL NO. 36C24W23R0041
April 8, 2024
Veterans Administration Oklahoma City, OK
Request for Lease Proposal (RLP) 36C24W23R0041 is amended as follows:
• Exhibit B1, Agency’s Requirements, is hereby deleted and replaced with the exhibit attached to this RLP Amendment.
The following is a summary of questions that have been received, along with answers from the Government, which correspond to solicitation 36C24W23R0041:
Q 1. Can the VA provide clarification on the accurate ABOA square footage they are requesting, as there is a discrepancy between the RLP and ASR documents.
A 1. The VA is requesting 22,299 – 24,530 ABOA SF, not to exceed 30,103 Rentable Square Feet. Exhibit B1, Agency’s Specific Requirements has been updated to reflect the requested required square footage.
Q 2. Can the length of the term be increased?
A 2. Yes, we have requested an increase of term of 20-years; 10-years Firm and 10-years Non-Firm.
Q 3. Does the entire space requested need to be contained into one suite?
A 3. RLP Section 1.02.A has been changed to read: The Government is seeking a minimum of 22,299 to a maximum of 24,530 of American National Standards Institute/Building Owners and Managers Association (ANSI/BOMA) Occupant Area (ABOA) square feet (SF) of space within the Area of Consideration set forth below. The Government prefers contiguous space, but will consider separated spaces that will best fit their space plan needs in accordance with Section
2.01 & Section 3.06.O of the RLP and offering the best value to the Government. The Government will not award a lease that exceeds 30,103 rentable square feet. See Section 2 of the Lease for applicable ANSI/BOMA standards
Q 4. Can a TI allowance be provided, and the VA pay the difference?
A 4. See Section 3.07 of RLP for TI Allowance. See Section 3.03, if amortization of TI's is to be used.
Q5. What is the west side boundary of the delineated area?
A5. See Section 1.03 for boundaries; Meridian Blvd is the west boundary.
Q6. Does the VA have a preference of a ground up building or existing building?
A6. No preference. All proposals will be considered and evaluated in accordance to the RLP.
Q7. Can you confirm if this project is a set aside?
A7. This is an Open Market Solicitation, no set-a-side.
Q8. What is the expected award date?
A8. September 2024, if not earlier
------------------------------------------------- END OF RLP CHANGES ----------------------------------------
Authorized By: Craig Wagstaff, Lease Contracting Officer
Please sign below, acknowledging receipt of this amendment, and return to: patti.lorensen@va.gov
RECEIPT OF AMENDMENT NUMBER 1 IS HEREBY ACKNOWLEDGED:
OFFEROR NAME (printed)
OFFEROR SIGNATURE
Women’s Agency Specific Requirements
EXHIBIT B1
Executive Summary The OKCVAHCS is opening a new Women’s Clinic lease with approximately 22,299 to 24,530 ABOA sq. ft of space. The new Women’s lease will expand Women’s Health, Mental health, and Lab Services to increase access to care. Additionally, it will add Telehealth, Lab, Pain Program, Chiropractic, X-Ray, Ultrasound, Mammography, and Veterans Express Care.
Program for Design (PFD - SEPS Report)
Department Functional Area Room Room Code
Qty Area Net Area
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
OUTDOOR PUBLIC
AREA
CBOC Veteran Drop-off, Bldg Sprt
SB101 1 0 0
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
INDOOR PUBLIC
AREA
CBOC Vestibule / Indoor Buffer, Bldg Sprt
SB291 1 100 100
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
VETERAN
WELCOME AREA /
MAIN STREET
CBOC Veteran / Guest Seating, Bldg Sprt
SB003 1 400 400
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
VETERAN
WELCOME AREA /
MAIN STREET
CBOC Bariatric Patient Toilet, Bldg Sprt
SB163 1 75 75
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
VETERAN
WELCOME AREA /
MAIN STREET
CBOC Universal Single Occupant Toilet, Bldg Sprt
SB191 1 65 65
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
VETERAN
WELCOME AREA /
MAIN STREET
CBOC Welcome Station, Clncl Sprt x 3 MSA staff
SC005 1 168 168
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
LABORATORY
MEDICINE AREA
CBOC Bariatric Blood Draw Station, Path Svc
CL822 4 100 400
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
LABORATORY
MEDICINE AREA
CBOC Laboratory Specimen Processing, Path Svc
CL823 1 120 120
EXHIBIT B
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
LABORATORY
MEDICINE AREA
CBOC Laboratory Clean Supply Storage Room, Path Svc
CL831 1 60 60
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
LABORATORY
MEDICINE AREA
CBOC Laboratory Soiled Holding Room, Path Svc
CL832 1 60 60
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
LABORATORY
MEDICINE AREA
CBOC Specimen Collection Toilet, Bldg Sprt
SB198 1 65 65
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
LABORATORY
MEDICINE AREA
CBOC Handwashing Station, Clncl Sprt
SC189 1 10 10
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
PATIENT CARE
AREA
CBOC Optometry Testing Patient Care Room, Eye Clnc
CEY52 1 130 130
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
PATIENT CARE
AREA
CBOC Optometry Patient Care Room, Eye Clnc
CEY53 4 130 520
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
PATIENT CARE
AREA
Optometry Visual Fields Room, Eye Clnc
CEY54 1 130 130
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
PATIENT CARE
AREA
Optometry Photography Room, Eye Clnc
CEY55 1 185 185
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
PATIENT CARE
AREA
Optometry Ultrasound Room, Eye Clnc
CEY56 1 130 130
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
PATIENT CARE
AREA
Optometry Tomography Room, Eye Clnc
CEY61 1 130 130
OUTPATIENT
CLINIC
(CBOC) (265)
PATIENT CARE
AREA
CBOC Eyeglass Fitting &
Dispensing Patient Care Room, Eye Clnc
CEY91 1 180 180
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
PATIENT CARE
AREA
General Patient Care Room, CBOC/vet express
OCB31 3 140 420
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
PATIENT CARE
AREA
CBOC Accessible Patient Height & Weight Station, Clncl Sprt
SC066 2 30 60
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
TEAMWORK
AREA
CBOC Point of Use Equipment Alcove, Clncl Sprt
SC079 1 50 50
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
TEAMWORK
AREA
CBOC Huddle Space, Stff Sprt/Eye clinic/vet express
SS291 2 280 560
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
LOGISTICS AREA CBOC Covered Drop-off / Pick-Up, Bldg Sprt
SB106 1 0 0
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
LOGISTICS AREA CBOC Full Gas Cylinder Storage Room, Lgstcs Svc
SB541 1 40 40
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
LOGISTICS AREA CBOC Empty Gas Cylinder Storage Room, Lgstcs Svc
SB551 1 40 40
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
LOGISTICS AREA CBOC Medical Equipment Storage Room, Lgstcs Svc
SB721 1 80 80
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
LOGISTICS AREA CBOC Clinical Supplies Storage Room, Lgstcs Svc
SB741 1 60 60
OUTPATIENT
CLINIC
(CBOC) (265)
LOGISTICS AREA CBOC Sterile Supplies Storage Room, Lgstcs Svc
SB763 1 60 60
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
LOGISTICS AREA CBOC
Telecommunications Room (TR), OIT
SC391 1 170 170
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
POLICE AREA CBOC Operations Room, Pol Svc
SB811 1 56 56
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
POLICE AREA CBOC Armory / Weapon Storage Room, Pol Svc
SB831 1 60 60
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
MANAGEMENT
AREA
CBOC
Administrative Staff Workstation, Stff Sprt
SS218 4 56 224
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
STAFF WELLNESS
AREA
CBOC Universal Staff Toilet, Bldg Sprt
SB191 1 65 65
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
STAFF WELLNESS
AREA
CBOC Staff Personal Property Locker Alcove, Stff Sprt
SS251 1 40 40
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
STAFF WELLNESS
AREA
CBOC Clinical Neighborhood Staff Multipurpose Room / Breakroom, Stff Sprt
SS262 1 120 120
COMMUNITY
BASED
OUTPATIENT
CLINIC
(CBOC) (265)
MOBILE
TECHNOLOGY
AREA
CBOC Mobile Technology Docking Area, Bldg Sprt
SB218 1 0 0
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
RECEPTION AREA Lactation Room, Wm Vet Svc
CWV11 1 75 75
MODELS 2
AND 3) (258)
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
RECEPTION AREA Wm Vet Svc Waiting, Bldg Sprt
SB003 1 310 310
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
RECEPTION AREA Wm Vet Svc Family Waiting, Bldg Sprt
SB051 1 125 125
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
RECEPTION AREA Wm Vet Svc Family Toilet, Bldg Sprt
SB136 2 80 160
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
RECEPTION AREA Patient Education Workstation, Clncl Sprt
SC172 1 60 60
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
RECEPTION AREA Wm Vet Svc Reception, Clncl Sprt
SC183 1 280 280
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
PATIENT AREA Multipurpose Exam Room, Wm Vet Svc
CWV16 9 140 1260
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
PATIENT AREA Gynecology Exam Room, Wm Vet Svc/2 GYN 1 Rotating speciality room
CWV21 3 140 420
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
PATIENT AREA Cancer Screening Exam Room, Wm Vet Svc
CWV26 1 140 140
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
PATIENT AREA Breast Clinic Exam Room, Wm Vet Svc
CWV31 1 140 140
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
PATIENT AREA Gynecology Procedure Room, Wm Vet Svc
CWV36 2 180 360
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
PATIENT AREA Urology-Gynecology Procedure Room, Wm Vet Svc
CWV41 1 240 240
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
PATIENT AREA Alternative Therapy Procedure Room, Wm Vet Svc
CWV46 2 180 360
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
PATIENT AREA Shared Medical Appointment Room, Wm Vet Svc-MH group room/Move/pelvic floor/pt/tr
CWV51 2 240 480
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
PATIENT AREA Women Veteran Patient Toilet, Bldg Sprt
SB159 2 75 150
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
PATIENT AREA Women Veteran Patient Toilet, Bldg Sprt GYN Patient Toilet/Uro GYN toilet
SB159 2 75 150
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
PATIENT AREA Height / Weight Accessible Station Alcove, Clncl Sprt
SC066 1 60 60
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
PATIENT AREA Tele-Health Room, Clncl Sprt 2 rooms tele/aud PFT telecart/telemental health
SC249 2 120 240
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
IMAGING WOMEN
HEALTH CENTER
(WHC) (MODEL 3
ONLY) PATIENT
AREA
Wm Vet Svc Class 2 Standing Breast Imaging Room, Imgng Svcs
CI056 1 240 240
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
IMAGING WOMEN
HEALTH CENTER
(WHC) (MODEL 3
ONLY) PATIENT
AREA
Wm Vet Svc Class 2 Standing Breast Imaging System Component Alcove, Imgng Svcs
CI057 1 20 20
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
IMAGING WOMEN
HEALTH CENTER
(WHC) (MODEL 3
ONLY) PATIENT
AREA
Wm Vet Svc Class 2 Standing Breast Imaging Automated Supply Dispenser Unit (ASDU) Alcove, Imgng Svcs
CI058 1 20 20
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
IMAGING WOMEN
HEALTH CENTER
(WHC) (MODEL 3
ONLY) PATIENT
AREA
Wm Vet Svc Breast Imaging ABUS Scanning Room, Imgng Svcs
CI067 1 230 230
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
IMAGING WOMEN
HEALTH CENTER
(WHC) (MODEL 3
ONLY) PATIENT
AREA
Wm Vet Svc Bone Densitometry Scanning Room, Imgng Svcs
CI076 1 220 220
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
IMAGING WOMEN
HEALTH CENTER
(WHC) (MODEL 3
ONLY) PATIENT
AREA
Wm Vet Svc PACS Viewing Room, Imgng Svcs
CI501 1 120 120
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
IMAGING WOMEN
HEALTH CENTER
(WHC) (MODEL 3
ONLY) PATIENT
AREA
Portable Imaging Equipment Storage Room, Wm Vet Svc
CWV81 1 120 120
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
IMAGING WOMEN
HEALTH CENTER
(WHC) (MODEL 3
ONLY) PATIENT
AREA
Wm Vet Svc Imaging Patient Waiting, Bldg Sprt
SB003 1 110 110
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
IMAGING WOMEN
HEALTH CENTER
(WHC) (MODEL 3
ONLY) PATIENT
AREA
Wm Vet Svc Imaging Patient Dressing Cubicle, Bldg Sprt
SB137 4 35 140
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
IMAGING WOMEN
HEALTH CENTER
(WHC) (MODEL 3
ONLY) PATIENT
AREA
Wm Vet Svc Imaging Patient Toilet, Bldg Sprt
SB201 2 60 120
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
SUPPORT AREA Equipment Storage Room, Wm Vet Svc
CWV61 1 100 100
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
SUPPORT AREA Wm Vet Svc Housekeeping Aides Closet (HAC), Bldg Sprt
SB244 1 60 60
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
SUPPORT AREA Wm Vet Svc Clean Utility Room, Lgstcs Svc
SB737 1 100 100
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
SUPPORT AREA Wm Vet Svc Soiled Utility Room, Lgstcs Svc
SB743 1 80 80
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
SUPPORT AREA Wm Vet Svc Clean Linen Alcove, EMS
SC467 1 40 40
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
SUPPORT AREA Wm Vet Svc Medication Room, Phrm Svc
SV583 1 75 75
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
AND 3) (258)
STAFF AND
ADMINISTRATIVE
AREA
Wm Vet Svc Benefits Advisor Office, Stff Sprt
SS203 1 100 100
WOMEN
VETERANS
CLINICAL
SERVICE
(WVCS) (FOR
MODELS 2
STAFF AND
ADMINISTRATIVE
AREA
Wm Vet Svc Administration Workstation, Stff Sprt
SS218 24 56 1344
IMAGING
SERVICES
(295)
IMAGING
SERVICES
RECEPTION AREA
Imgng Svcs Reception, Clncl Sprt
SC183 1 85 85
IMAGING
SERVICES
(295)
GENERAL
RADIOLOGY
AREA
General Radiology Patient Dressing Room, Bldg Sprt
SB138 1 60 60
IMAGING
SERVICES
(295)
GENERAL
RADIOLOGY
AREA
General Radiology Patient Personal Property Locker Alcove, Bldg Sprt
SB139 1 20 20
IMAGING
SERVICES
(295)
GENERAL
RADIOLOGY
AREA
General Radiology Team Room, Clncl Sprt
SC243 1 360 360
IMAGING
SERVICES
(295)
IMAGING
SERVICES
SUPPORT AREA
Equipment Storage Room, Imgng Svcs
CI301 1 120 120
IMAGING
SERVICES
(295)
IMAGING
SERVICES
SUPPORT AREA
Imaging Sterile Consumables (Soft Goods) Storage Room, Imgng Svcs
CI304 1 80 80
IMAGING
SERVICES
(295)
IMAGING
SERVICES
SUPPORT AREA
Lead Apron Alcove, Imgng Svcs
CI521 1 15 15
IMAGING
SERVICES
(295)
IMAGING
SERVICES
SUPPORT AREA
Imgng Svcs Clean Utility Room, Lgstcs Svc
SB737 1 100 100
IMAGING
SERVICES
(295)
IMAGING
SERVICES
SUPPORT AREA
Imgng Svcs Soiled Utility Room, Lgstcs Svc
SB743 1 120 120
IMAGING
SERVICES
(295)
IMAGING
SERVICES
SUPPORT AREA
Imgng Svcs Mobile Patient Lift Alcove, Clncl Sprt
SC093 1 20 20
IMAGING
SERVICES
(295)
IMAGING
SERVICES
SUPPORT AREA
Imgng Svcs Mobile Ultrasound Alcove, Clncl Sprt
SC096 1 30 30
IMAGING
SERVICES
(295)
IMAGING
SERVICES
SUPPORT AREA
Imgng Svcs Wheelchair / Stretcher Alcove, Bldg Sprt
SC252 1 50 50
IMAGING
SERVICES
(295)
IMAGING
SERVICES
SUPPORT AREA
Imgng Svcs Clean Linen Alcove, EMS
SC467 1 20 20
IMAGING
SERVICES
(295)
IMAGING
SERVICES STAFF
AND
ADMINISTRATIVE
AREA
PACS Digital Quality Control Workroom, Imgng Svcs
CI403 1 150 150
IMAGING
SERVICES
(295)
IMAGING
SERVICES STAFF
AND
ADMINISTRATIVE
AREA
PACS Administrator Workroom, Imgng Svcs
CI404 1 150 150
IMAGING
SERVICES
(295)
IMAGING
SERVICES STAFF
AND
ADMINISTRATIVE
AREA
PACS 3D
Workstation, Imgng Svcs
CI405 1 56 56
Building Totals: Room Qty: 146
1.0 QUALITY OF SPACE
1.0.1 The tenant improvement design and construction shall be executed in strict accordance with the latest editions of Veterans Health Administration (VHA) A/E Minimum Submission Requirements, Design Guides/Manuals, VHA Master Construction Specifications, International Building Code (IBC), International Mechanical and Plumbing Codes, and all applicable National Fire Protection Agency (NFPA) regulations, specifically NFPA 101 Life Safety Code.
1.0.2 The leased facility will closely align with the SEPS space utilization requirements outlined above, while also accommodating a range of additional needs. The following list highlights specific areas of focus, though it does not encompass all of the room requirements:
• Waiting Room o Electrical convenience outlets, cable outlet and data for televisions o Auto door opener for main entry doors o VA approved vinyl signage for entry doors o Sounds Reduction ceiling tiles, flooring, etc
• Receptionist Area o Buzzer for door magnetic door lock at door to corridor.
o Electrical for copier, electric outlets at workstation along with telephone and data outlets.
o Built-in Millwork o Solid glass window with 4-inch gap at bottom and speaking hole in the middle for each reception window. 3/8” Glass minimum o Sound reduction ceiling tiles, walls, and doors
• X-Ray/Ultrasound Rooms/Panoramic/Cephalometric/Radiology o All walls lined with lead lined gypsum board and lead lined gypsum board ceiling.
o Electrical as required for x-ray equipment, telephone and data outlets.
• Treatment Rooms o Lessor to provide and install all cabinets and millwork. This includes exam chair requirements such as electrical, conduit for data to side millwork computer stations to connect to exam chair, computers, and otoscope. Also includes all cabinetry both uppers and lowers, sinks and plumbing.
o Electrical, phone outlets, and data outlets.
o Sinks in each exam room o Soap dispenser, paper towel, Sharps containers in each exam room o Otoscopes provided by tenant; installed by lessor in each exam room
• Lab o Ventilation – 6 exchanges per hour rate.
o Compressed air. 2 quick connect access points and 2 regular connections.
o Electrical outlets along the bench. To be defined with electrical/data port placement procedures.
o Electrical outlets, telephone and data outlets for 2 workstations.
o Ceiling exhaust vent approved for lab areas o Mechanical: Mini Split o Deionized water unit with separate spout to sink.
o Eye wash station
• Med Storage Room o Data and telephone outlets o Sink with cabinet.
o Emergency backup power to Omni Cell.
o Dedicated circuit for Omni Cell.
o Mini split- Temperature and humidity control.
• Soiled Utility Room o Sink with eyewash station o Negative air pressure for room o Automatic door opener with motion operated sensors.
o Minimum electrical
• Clean Storage o Minimum electrical o Temp/humidity control- Mini split o Furnishings by Tenant
• Equipment Storage o Adequate electrical outlets.
o Data needed for Glucometer.
• Staff Workstation Area o Power, data & telephone outlets
• Team Room o Power, data & telephone outlets
• Mental Health Rooms o Power, data & telephone outlets o Built in ceiling White Noise machine.
o Sound absorbing technology for ceiling tiles, walls, and doors
• Admin Offices o Power, data & telephone outlets o Sound absorbing technology for ceiling tiles, walls, and doors
• Restrooms o Baby Changing station in all family restrooms.
o Auto Door openers for all shared restrooms
• Miscellaneous:
o Mini Split HVAC units needed in IT closet, med room(s), clean storage, sterile storage and lab. Other rooms will be discussed as needed.
o Dirty rooms need to have negative air pressure.
o Sterile supply rooms need to have positive air pressure.
o No door shall be less than 36” in width for ADA compliance. If a push bar is installed, 36” in the clear is required.
o If bathroom wall tile splits the mirror, the tile behind the mirror needs to be left out so the mirror sits flush against the wall.
o Major clinical hallways should have alcove space to support medical equipment storage, scales, blood pressure, EKG machine and other equipment as needed.
1.0.3 The site, site improvements, building, interior spaces and finishes, and Lessor-furnished equipment and special construction shall be provided in accordance with this Exhibit, all applicable Federal requirements, local Building Codes and ordinances, and applicable utility company requirements.
1.0.4 Site, site improvements, building, interior construction, and equipment shall comply with General Design Criteria, including Codes and Standards, criteria unique to VA, Fire, and Life Safety requirements, Environmental requirements, Accessibility Standards, OSHA requirements, and Energy Efficiency and Sustainable Design.
1.1 GENERAL DESIGN CRITERIA
1.1.1 NFPA 101 primarily addresses life safety and fire protection features, while the IBC addresses a wide range of considerations, including, but not limited to, structural strength, seismic stability, sanitation, adequate light and ventilation, and energy conservation. VA buildings must meet the requirements of NFPA 101 and documents referenced by NFPA 101 in order to comply with the accreditation requirements of the Joint Commission. Therefore, designs shall comply with the requirements of NFPA 101 and documents referenced therein. Design features not addressed by NFPA 101 or documents referenced therein shall comply with the requirements of the IBC.
1.1.2 Fire protection implementation guidance to the A/E with respect to the National Fire
Protection Agency (NFPA) Fire Codes is provided as follows:
1) VA has adopted the National Fire Codes (NFC) published by the National Fire Protection Association (NFPA), which establish a minimum acceptable level of life safety and property protection. Life safety requirements are specifically addressed in the Life Safety Code, NFPA 101. Where conflicts exist between codes, the A/E shall follow the code specified in the text under the subject section of the VA Fire Protection Design Manual. Fire Protection design shall be based on the latest editions of the NFC at the Date of Award of the contract to the Architectural Engineering (A/E) firm. Under special circumstances, the VA will require compliance with a more recent code edition when significant changes to the code have occurred between the Date of Award to the A/E and the Date of Award to the prime contractor for construction.
Note: Special circumstances would include a situation where a designed project sat “on the shelf” for an extended period of time, or where a significant change to the code was made and where incorporating that change would improve safety in the opinion of the AHJ.
2) The A/E shall use the Department of Veterans Affairs Fire Design Manual, Seventh Edition, 2015 in conjunction with the Scope of Work paragraph in the
Architect/Engineer (A/E) Package and PG-18-15, Minimum Requirements for A/E Submissions, which defines the information to be shown on drawings and work to be completed at each stage of design. In addition, coordinate with requirements from other applicable VA Design and Construction Criteria, VA Design Manuals, and VA Design Guides.
3) The A/E shall posses the knowledge of applicable fire protection criteria such as the respective Network Safety Manager, Network Safety and Fire Protection Engineer (SFPE), or solicit the services of a third-party qualified fire protection engineering consultant during design in order to insure the project as designed by the A/E complies with such criteria. In the event the A/E will solicit the services of a third-party, it is required they are obtained early in the design process. The third-party entity shall be involved in reviewing the design, but may also be involved with reviewing contractor’s submissions, conducting pre-occupancy life safety inspections, and/or witnessing final fire protection acceptance testing.
4) For code interpretation and enforcement, the Authority Having Jurisdiction (AHJ) for all VA projects is ultimately the Deputy Under Secretary for Health for Operations and Management (10N), with the Safety and Fire Protection Engineer (10NA8) acting as the VA Fire Marshal.
5) The existing fire rated features and fire protection changes will be shown on a separate drawing sheet by the A/E, and stamped by a Fire Protection Engineer (FPE) in the contract documents.
NOTE: The above list is intended to serve as a starting point for design and does not represent the only information in identifying the project scope.
1.1.3 Lessor shall provide architectural design services for Tenant Improvements (TI) in accordance with VA Architectural Design Manual.
http://www.cfm.va.gov/til/dManual/dmARhosp.pdf.
1.1.4 The Lessors A/E shall provide Interior Design Services in accordance with VA Interior
Design Manual, For New Construction and Renovations of Hospitals and Clinics http://www.cfm.va.gov/til/dManual/dmIDhonh.pdf. The interior designer shall have NCIDQ Certification and be able to demonstrate a minimum 3-years of healthcare project experience. Interior design services shall include furniture selection and layout of the PACT Team Work Zone, Teamwork Support Zone, and Patient Transition Areas.
1.1.5 The Lessor’s Interior Designer will provide room-by-room furniture and equipment layouts outlining exam table, patient lifts, privacy curtains, stool, work station and media-mounts, wall mounted items, casework, bookcases, and room furniture locations so Lessors MEP design team can determine plumbing, electrical power, and data drop locations.
1.1.6 The Lessors A/E shall provide design services that utilize and incorporate VA
Prototypes for Standardized Design and Construction Community – Based Outpatient Clinics, latest edition. http://www.cfm.va.gov/til/Prototype/CBOCPrototype- 00-TOC.pdf.
1.1.7 The Lessor’s design team shall utilize and incorporate all VHA’s facility design http://www.cfm.va.gov/til/dManual/dmARhosp.pdf http://www.cfm.va.gov/til/dManual/dmIDhonh.pdf http://www.cfm.va.gov/til/Prototype/CBOCPrototype-00-TOC.pdf http://www.cfm.va.gov/til/Prototype/CBOCPrototype-00-TOC.pdf concepts and models into the new leased space design and provide required tenant improvements that meet the specific model requirements to support but not limited to PACT teams, Dental, Radiology/imaging and a variety Mental Health and Tele- Health Services.
PACT Space Module Design Guide dgPACT.pdf (va.gov)
Imaging Services Design Guide (Rev. 8/1/2023) dgImaging.pdf (va.gov)
Mental Health Outpatient Services design guide dgMHOP.pdf (va.gov)
Signage Design Manual cfm.va.gov/til/dManual/dmSignage.pdf
Parking Design Manual dmParking.pdf (va.gov)
Telecommunications Spaces OIT-InfrastrucStdTelecomSpaces-v4-0.pdf (va.gov)
Physical Medicine and Rehab dgPMRS.pdf (va.gov)
Physical Security design dmPhySec.pdf (va.gov)
1.1.8 The lessor shall provide new furnishings such as welded sheet and luxury tile flooring, ceilings, painting, office and exam room drapery tracks, accessories, and window furnishings.
1) Lessor shall provide upper and lower wood casework and solid surface counter tops for conference, staff break room, physical therapy, exam rooms, lab draw, and other areas as needed.
2) Provide upper and lower manufactured metal casework for Blood Draw Lab.
3) Lessor shall provide built-in millwork/casework with lockable doors and drawers for reception, mail/copier work room, and conference room.
4) Lessor to supply electric sit-to-stand desk options for all solid surface/built-it desks options
5) Lessor shall provide employee lockers for staff rest/locker rooms.
6) Lessor shall provide electrical convenience outlets, cable outlet and data for television in waiting areas, conference rooms, and group rooms.
7) Lessor shall provide built-in millwork with solid surface counters but not limited to in all clinical exam, lab draw, radiology, physical therapy, etc.
8) Lessor to supply electrical and data lines as needed in all rooms for computer, telephone, and medical equipment.
9) Lessor to supply Solid glass window with 4-inch gap at bottom and speaking hole https://www.cfm.va.gov/til/dGuide/dgPACT.pdf https://www.cfm.va.gov/til/dGuide/dgImaging.pdf https://www.cfm.va.gov/til/dGuide/dgMHOP.pdf https://www.cfm.va.gov/til/dManual/dmSignage.pdf https://www.cfm.va.gov/til/dManual/dmParking.pdf https://www.cfm.va.gov/til/dguide/OIT-InfrastrucStdTelecomSpaces-v4-0.pdf https://www.cfm.va.gov/til/dGuide/dgPMRS.pdf https://www.cfm.va.gov/til/PhysicalSecurity/dmPhySec.pdf in the middle (min. 3/8” tempered glass) for all check-in/out reception areas.
10) Lessor to supply medical grade sinks in all clinical areas.
11) Lessor to supply TV service (Cable, Direct TV, Dish, etc.)
12) Lessor to provide own private/secure internet service for lessor needs. Must meet VA OIT standards.
13) Lessor to provide guest internet service.
14) Lessor to supply door hardware/system such as but not limited to: Auto door openers, hands-free motion opener, maglocks, VA approved badge entry throughout clinic as needed by VA. See Security section below.
15) Lessor to supply X-Ray/Ultrasound Rooms/Panoramic/Cephalometric rooms with lead lined walls, ceilings and doors.
1.2 DESIGN TEAM QUALIFICATIONS
1.2.1 Provide a resume for each individual or firm on the Lessor’s design team. Identify key personnel that are to be committed to the project. Provide a description of outstanding commitments for each firm and key personnel. As a minimum, the design team shall include entities providing the following services: Architecture, Civil Engineering, Mechanical Engineering, Fire Protection, Electrical Engineering, Interior Design, and appropriate Low Voltage Engineering (Structured Telecommunications Cabling, Security, Audio Visual, and Special Systems).
1.2.2 Provide a copy of the license or certification of the individual(s) and/or firm(s), providing architectural and engineering design services, proving their ability to practice in the state where the facility is located. Low-voltage designers shall be BICSI-certified for structural cabling and shall have OEM credentials for the Special Systems Specific Requirements.
1.2.3 Lessor shall maintain the same design team for the duration of the design development and construction process. Design team firm and key personnel shall not be changed without prior approval by the Contracting Officer.
1.3 CONTRACTOR QUALIFICATION
1.3.1 Provide a completed GSA Form 527, "Contractor’s Qualifications and Financial Information" for the General Contractor, Mechanical Contractor, and Electrical Contractor; except Section V need not be completed. In Section VII of Form 527, provide a description of outstanding commitments, names and qualifications of key personnel, and any other information related to experience, competency, performance capabilities, and three (3) Past Performance’ evaluations with construction projects similar in scope to that which is required herein.
1.3.2 Provide a copy of the license in the state where the facility is located for the individual(s) and/or firm(s) proposed as contractors. If the Lessor is also the Contractor, information provided in response to Past Performance and Financial
Resources above need not be duplicated.
2.0 BUILDING ENTRANCES AND EXITS
2.0.1 Public access to the facility should be restricted to a limited number of entrances. The public entrance is to the main lobby of the facility. Staff entrances shall be located independently of main entrance lobbies and be convenient to staff parking. Design access from drop-off to lobby to prevent a straight line of travel. Provide sufficient size to accommodate several people with mobility aids.
2.0.2 Entrance doors to the lobby shall be visible to or monitored by security personnel or system. Access from the lobby to elevators, stairways, and corridors shall be controlled. Separate the public lobby from adjacent areas with partitions that extend to the underside of the floor above. Glazing in the lobby area shall be laminated glass.
2.0.3 Public doors shall be capable of being remotely locked and unlocked from the reception desk in the main lobby. Secondary public entrance doors shall prevent unauthorized access. Staff entrance door hardware shall include mechanical and electronic badge locks.
2.0.4 Means of egress doors that do not also function as entrances shall be provided with delayed action and alarmed emergency egress hardware. Delayed egress and alarmed exits shall comply with applicable codes and regulations. Means of egress shall not be obstructed by installation of security devices such as guard stations, screening equipment, or other security devices.
2.0.5 Access for Emergency Responders: The Fire Command Center (FCC) and secure house key box for emergency responders shall be located near the main entrance door. The entrance shall be controlled and monitored by Security Surveillance Television (SSTV).
2.0.6 SSTV cameras shall be provided to monitor activities in the lobbies of new and existing life- safety protected facilities and shall be located to provide views of approaching pedestrian and vehicular traffic, drop-off areas, building entrances, and departing pedestrian and vehicular traffic. Provide SSTV cameras at locations with alarmed exits, at loading docks, and other areas subject to pilferage. Install door status monitors at doors intended to be used only for emergency egress.
2.1 BUILDING ENVELOPE
2.1.1 Building envelope shall meet the latest edition of the Architectural Design Manual for
New Hospitals refers to ASHRAE 189.1-2009, Standard for the Design of High- Performance Green Buildings. The complete standard has not been adopted by the VA, but the Architectural Design Manual requires compliance with the building envelope requirements. The prescriptive assembly maximum U-values and insulation minimum R-values stated in ASHRAE 189.1-2009 shall be incorporated into the opaque elements of the building envelope of new facilities.
2.2 EXTERIOR SIGNAGE
2.2.1 Lessor shall develop and provide a complete exterior signage program to include identification, directional, informational, and regulatory signage. Signage must comply with local municipality’s codes and specifications. Careful consideration of the location of monument signs shall be taken to avoid sight triangle encroachment.
Exterior signage shall include all Mandatory VA signage such as no weapons signage at all VA entrances.
2.2.2 Lessor shall provide ground mounted, illuminated, horizontal monument sign to identify the Outpatient Clinic main entrance. The Lessor shall provide foundations and electrical power as necessary. Base shall be concrete or masonry and shall be compatible with building design and landscaping scheme. Monument sign shall be a minimum of 4’-0" high x 8’-0" wide. VA will furnish message layout, content, and colors for the monument sign. Graphic process shall be routed out copy backed with white, translucent acrylic.
2.2.3 Lessor Shall provide flagpole at the location. The flag of the United States of America will be provided be by the lessor, as part of the shell rent, and replaced at all times during lessor term when showing signs of wear. The flag will be displayed twenty-four hours a day and be properly illuminated during the hours of darkness.
2.2.4 Lessor shall develop and submit a signage plan for review and approval by the
Contracting Officer during design development. Lessor shall provide illuminated, wall mounted building identification signs of dimensional powder coated aluminum letters and numerals with VA logo. Letters and numerals shall be minimum 12 inches high.
Logo shall be of design provided by VA and shall be minimum 27 inches high. Sign messages shall be as follows:
Facility Name: Oklahoma City Women’s Clinic VA logo shall precede facility name.
Address sign shall consist of numerals for the building street address.
2.2.5 Wall mounted building signs shall be prominently located to be visible from street approach in accordance with VA-approved building elevations.
2.3 INTERIOR SIGNAGE
2.3.1 Lessor shall develop and submit a signage plan for review and approval by the Contracting Officer during design development. Interior signage systems shall include identification, directional, informational, and code required signage. The Lessor shall furnish and install interior signs for all rooms, areas, conditions or features in the facility. Comply with accessibility standards. For informational purposes, Offerors are advised that VA has an established signage program, VA Signage Design Guide, which may be found at http://www.cfm.va.gov/til/aeDesSubReq.asp.
2.4 NOISE TRANSMISSION CONTROL GENERAL
2.4.1 Provide sound-resistant construction at the rooms and areas listed in paragraphs below. Submit details of sound resistant construction with Second Design Development Submittal. Include test reports for designs or systems to be used.
Construct partition, ceiling, and floor systems to provide necessary performance.
http://www.cfm.va.gov/til/aeDesSubReq.asp
Special attention shall be given to prevent possible flanking paths for noise transmission. Verification of noise transmission control shall be included in building commissioning.
2.4.2 Sound damping in meditation rooms, quiet rooms, and similar areas shall be provided
PG-18-14, Room Finishes, Doors, and Door hardware Schedules.
2.4.3 Where an area generating unusual noise or vibration is located adjacent to occupied spaces, the Lessor’s A/E shall obtain the services of a professional acoustical consultant to design the sound suppression measures required to produce a comfortable working environment in the adjacent spaces.
2.4.4 NOISE CONTROL (NC): The sound resistant enclosures (partitions, doors, duct system) of the spaces listed below shall be designed to suppress generated noise and provide a satisfactory degree of acoustical isolation for adjacent occupied spaces. The minimum NIC ratings shall be achieved:
1. Multipurpose Rooms: NC 35
2. Mental Health Group Therapy rooms: NC 35
3. PACT Team: NC 35
4. Conference rooms: NC 35
5. Consultation offices: NC 30
6. Examination and treatment rooms: NC 30
7. Individual offices in Mental Health and Behavioral Sciences Service: NC 30
8. Tele-Health rooms: NC 30
3.0 FIRE PROTECTION
3.0.1 Lessor shall provide fire protection systems in accordance with the latest edition of
VA Fire Protection Design Manual. http://www.cfm.va.gov/til/dManual/dmFire.pdf.
3.0.2 Hazardous and high hazard areas within the outpatient clinic shall be protected as prescribed in NFPA 101, Life Safety Code and local building codes and ordinances.
Areas identified as high hazard shall be protected by not less than a minimum 1-hour fire enclosure with C- labeled doors and automatic sprinklers.
3.0.3 Storage rooms of 50 or more square feet [15.24 sq m] net area shall be considered hazardous areas and comply with appropriate occupancy chapter requirements of
NFPA 101.
3.0.4 Location, construction, and arrangement of compressed medical gas storage areas shall comply with NFPA 99.
3.1 WATER SUPPLY FOR FIRE PROTECTION
3.1.1 Assess adequacy of the water supply. The Lessor must verify the locations involved as well as the quality and accuracy of the data. Perform water supply flow testing.
3.1.2 Fire flows shall be available as required by NFPA 13 for the required occupancy classification. The Lessor shall verify and submit documentation of the fire department’s capability of handling the manual firefighting requirements to the http://www.cfm.va.gov/til/dManual/dmFire.pdf
Contracting Officer prior to occupancy by the Government.
3.2 AUTOMATIC SPRINKLER SYSTEMS
3.2.1 Design wet pipe sprinkler systems, unless installed in areas subject to freezing. Dry pendant or sidewall sprinklers are preferred in lieu of dry pipe or antifreeze systems.
Propylene glycol shall be used should antifreeze systems need to be installed when permitted by local authorities. Do not use pre-action type systems.
3.2.2 The installation shall comply with the requirements of NFPA 13. Sprinklers shall be provided throughout the building. Rooms containing bulk supply storage shall be classified as defined by NFPA 13. Do not use shelving which obstructs sprinkler water from penetrating down through racks.
3.2.3 Install quick response sprinklers (QRS) in all areas, except where specifically prohibited (e.g., high temperature areas as defined in NFPA 13, elevator shafts, or elevator machine rooms). On retrofit projects, replace existing standard sprinklers with QRS.
3.2.4 Install standard sprinklers with intermediate temperature rating 200 °F [93 °C] or higher in elevator shafts, elevator pits, and elevator machine rooms. Install sprinklers in elevator shafts and pits only where required by NFPA 13. (Comply with necessary power shutdown requirements.)
3.2.5 The installation of flow control (on/off) sprinkler heads is not permitted. Provide non-ferrous piping for all areas within Magnetic Resonance Imaging (MRI) suites.
3.2.6 Coordinate with architectural, mechanical and electrical work and show smoke zone boundaries, hazard classification, density, and other special requirements on drawings.
3.2.7 Coordinate sprinkler zones with fire or smoke (compartments) and fire alarm evacuation zones. Provide a flow switch, isolation valve, tamper switch, and pressure gauge for each zone. Notification shall comply with NFPA 72.
3.2.8 Determine and identify on drawings the location of fire pump, risers, all valves, fire department connections, drains, and points of connection with underground fire service main.
3.2.9 Provide seismic protection in areas of Moderate High, High, and Very High
Seismicities (See VA Seismic Design Requirements (H-18-8)).
3.2.10 For the leased facilities, commissioning of the fire protection systems shall be implemented to verify the intent of the design by inspecting and testing the systems.
3.3 FIRE ALARM SYSTEMS
3.3.1 Fire alarm systems shall be provided as required by NFPA 101 or the locally adopted codes.
3.3.2 Wiring for fire alarm systems shall be as follows: Initiating Device Circuits – Style B
(Class B), Signaling Line Circuits – Style 4.0 (Class B), Notification Appliance Circuits
– Style Y (Class B), and Communications between fire alarm control units – Style 7 (Class A). Where there are conflicts with local codes, the most stringent requirements shall be enforced.
3.3.3 Initiation devices shall be provided in accordance with NFPA 101, NFPA 72, NFPA 90A, and ASME 17.1 or ASME 17.3, as applicable.
3.3.4 Audible fire alarm notification appliances shall be provided in accordance with NFPA 72 and NFPA 101.
3.3.5 Visual fire alarm notification appliances shall be provided in mechanical rooms, public restrooms, and public accessible areas such as corridors, auditoriums, cafeterias, assembly rooms, canteens, retail stores, and other publicly accessible rooms of more than 750 square feet [228.6 square meters] of area.
3.3.6 Coordinate fire alarm zones with the location of smoke compartments and sprinkler zones. The fire alarm system shall be monitored by a listed remote central station.
3.4 FIRE EXTINGUISHERS
3.4.1 Portable fire extinguishers and recessed cabinets shall be provided, inspected, and maintained by the Lessor. Lessor is responsible for monthly routine inspection with signoff and annual full inspection in accordance with National Fire Protection Association (NFPA) 10, Standard for Portable Fire Extinguishers.
3.4.2 Recessed cabinets shall be provided in occupied areas with appropriate signage and identification. Size fire extinguisher cabinets to accommodate a 2.5 gallon [9.5 liters] pressurized water extinguisher. Recessed cabinets shall be conspicuously marked.
4.0 PHYSICAL SECURITY
4.1.1 The Lessor shall provide Federal Security Level 2 which is reasonably deters unauthorized entry to the space leased during non-duty hours and deters loitering or disruptive acts in and around the space leased. The Lessor shall ensure that security camera's and lighting are not obstructed.
4.1.2 OPERATIONS AND ADMINISTRATION: LESSOR TO WORK WITH VA
POLICE The Lessor shall cooperate and work with the buildings’ VA Police throughout the term of the lease.
4.1.3 ACCESS TO BUILDING INFORMATION
Building Information – including mechanical, electrical, vertical transport, fire and life safety security system plans and schematics, computer automation systems and emergency operations procedures – shall be strictly controlled. Such information shall be released to authorized personnel only, approved by the Government, by the development of an access list and controlled copy numbering. The Contracting Officer may direct that the names and location of the Government tenants are not disclosed in any publicly accessed document or record. If that is the case, the Government may request that such information not be posted in the building directory.
Lessor shall have emergency plans and associated documents readily available in the event of an emergency.
4.1.4 Lessor shall provide Security Systems to include Intrusion Detection System (IDS), Physical Access Control System (PACS), Security Surveillance (SSTV), Nurse Call, and Public-Address Improvements. Systems shall be designed and install in accordance with VA Design Manuals, VA Master Construction Specifications, and VA Handbook 0730/4 Security and Law Enforcement.
https://www.va.gov/vapubs/search_action.cfm?formno=730&SortBy=Pub_Type_ Desc.
All PACs readers must be HSPD-12 and Lennel Software compliant for the PIV cards:
1) Wall Mount Reader: Identiv uTrust TS Contact, dual authentication.
8116ABP0L2B uTrust TS Wall mount SC (Contact Smart Card) HF/LF Pigtail Wiegand Lenel Reader
READER-SUR CHARGE Reader Temporary reader surcharge for access control readers
2) Dual Reader Interface Module: Part#: LNL-1320-S3: Mfr: Lenel S2
Dual Reader Interface Module (Series 3 Supports OSDP Readers) 12/24 VDC, 2 Reader interface, W/M, 8 inputs, 6 (5A) form C relays, RoHS, CE, C-Tick and UL294 certified.
2) Mag Lock with Z brackets
Alarm Controls 600lb single Magnetic Lock – Model 600lb GRA-48ZW44 Alarm Controls Three piece Z bracket for use on in-swing doors GRA-
48ZW50(AM6370)
3) Push to Exit square green button
Alarm Controls 48ZW53
4.1.5 Physical Access Control System: Compliance with Federal Standards. New installations or retrofitted access control systems will be compliant with technology described in Federal Information Processing Standard (FIPS) Publication 201, Personal Identity Verification of Federal Employees and Contractors, and the document "PACS Implementation Guidance, Version 2.2 (July 30, 2004), published by the Physical Access Interagency Interoperability Working Group of the GSA Government Smart Card Interagency Advisory Board. This requires that such systems will meet the ISO/IEC 14443 a, Parts 1-4 standard for contactless (proximity) card systems, or the ISOIIEC 7816 Standard for contact-type cards. **Lessor to provide Andover Continuum with latest firmware revision or equal.
https://www.va.gov/vapubs/search_action.cfm?formno=730&SortBy=Pub_Type_Desc https://www.va.gov/vapubs/search_action.cfm?formno=730&SortBy=Pub_Type_Desc
4.1.6 DURESS ALARM: The Lessor shall design, install, and maintain a duress alarm system as described. THE GOVERNEMNT SHALL PROVIDE A SCOPE OF WORK FOR A DURESS ALARM SYSTEM. Technical review shall be coordinated with the Government Security Representative, at the direction of the Contracting Officer, prior to installation. System testing and acceptance shall be conducted by the Government prior to occupancy. This system shall comply with the Architectural Barriers Act, section F230.0.
The Lessor in consultation and coordination with the security provider and Government Security Representative shall conduct security system performance testing annually. Testing must be based on established, consistent VA specific protocols, documentation and furnished to the Contracting Officer. Components which fail or require maintenance, or which fail during testing should be serviced in accordance with the Security System Maintenance Criteria listed below.
4.1.7 Physical Access Control System (PACS): Shall include, but not be limited to: card readers, keypads, electromagnetic locks and strikes, and electronic security management system (SMS). PACS devices shall be used for the purpose of controlling access and monitoring building entrances, sensitive areas, mission critical asset areas, and alarm conditions from an access control perspective. This includes maintaining control over defined areas such as site access points, parking lot areas, building perimeter, and interior areas that are monitored from a centralized SCC.
PACS shall be able to be fully integrated with other security subsystems using direct hardwire or computer interface.
4.1.8 Security Surveillance Television (SSTV): Shall be provided to monitor building entrances, restricted areas, mission critical asset areas, and alarm conditions. SSTV system shall be used for surveillance and observations of defined exterior areas, such as site and roadway access points, parking lots, and building perimeter, and interior areas from a centralized police operations room or security control center.
The design, installation, and use of SSTV cameras shall support the visual identification and surveillance of persons, vehicles, assets, incidents, and defined locations.
4.1.9 The Intrusion Detection System (IDS): Shall include motion detection, glass break, and door contact sensors, among other devices. These devices provide alternative methods to detect actual or attempted intrusion into protected areas through the use of alarm components, monitoring, and reporting systems. The IDS shall have the capability of being integrated with PACS, and SSTV systems. All IDS shall meet UL 639 Intrusion Detection Standard. The IDS shall be used to monitor the site perimeter, building envelope and entrances, and interior building areas where access is restricted or controlled.
4.1.10 Electronic Security Management System (SMS): The SMS shall allow the configuration of an enrollment and badging, alarm monitoring, administrative, asset management, digital video management, intrusion detection, visitor enrollment, remote access level management, and integrated security workstations or any combination thereof. Entry control software shall allow for programming of the PACS via a CPU. All software shall be updated per manufacturer’s instructions. Network interface devices shall consist of all hardware and software required to allow for full interface with other security subsystems via a CPU.
4.1.11 Police Operations Room and Holding Room: Police operations room shall be located on the first floor of the building adjacent to the highest potential trouble area, such as emergency or urgent care room, or lobby and shall be located to allow appropriate response and deployment to respond to a security related event. Holding room shall be located within or adjacent to the police operations room. When the police operations room is adjacent to or opens onto areas occupied by unscreened public, such as lobbies, emergency rooms, and public corridors, construction, including partitions from slab to slab, doors, windows, and other openings separating the unit from such spaces, shall be 1-hour fire resistive, UL level 3 ballistic-resistant.
SSTV surveillance shall be provided of the entire room through an opening glazed with transparent polycarbonate in a steel frame firmly anchored…