36C24926Q0229 0001.docx

DOCX document 31 KB Posted

Attached to
J041--TVHS VFD Replacement
Solicitation number
36C24926Q0229
Issued by

About this file

This file is an Amendment to a Previous Combined Solicitation containing Questions and Answers for Solicitation 36C24926Q0229 TVHS VFD Replacement. The solicitation is a Request for Quotation issued by the Department of Veterans Affairs Network Contracting Office 9 (Nashville, Tennessee) for the replacement of Variable Frequency Drives (VFDs) at Tennessee Valley Healthcare System's Nashville campus. The contract is a 100% set-aside for Service Disabled Veteran Owned Small Business (SDVOSBC) concerns with a response deadline of June 16, 2026 at 11:00 AM Central Time. The contract period runs from July 1, 2026 through October 31, 2026, with a primary NAICS code of 238220 (Plumbing, Heating, and Air-Conditioning Contractors) and Product/Service Code J041 (Maintenance/Repair/Rebuild of Refrigeration, Air Conditioning, and Air Circulating Equipment).

The amendment addresses 15 questions from potential bidders regarding project specifics. Key clarifications include: this is a new contract with no incumbent contractor; site visits can be arranged by contacting Stephen.Browne@va.gov; licensed electricians and manufacturer-certified VFD/controls technicians are acceptable qualifications; Danfoss VFDs are the required facility standard with specific models determined by equipment size; some VFDs require integral bypass and disconnect packages while others involve dual systems with separate cabinets; locations, point lists, and photographs will be provided upon request; pre-bid site visits are available; fire alarm interfaces are required for specified AHU supply/return and exhaust fan units; witnessed functional testing and commissioning are required; contractor parking is available with VA escort requirements; and one qualified employee may serve multiple project roles provided they remain onsite during installation. The contracting office point of contact is Diane Ziegler (diane.ziegler@va.gov) located at 1639 Medical Center Parkway, Suite 204, Murfreesboro, Tennessee 37129.

View the file

Other files

File Type Posted
S04 Organized Site Visit Sign In Sheet VFD Rep.pdf PDF
36C24926Q0229 0002.docx DOCX document
P07 WD 2015-4647 Rev. 32 DATED 05.13.2026.docx DOCX document
36C24926Q0229.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment to a Previous Combined Solicitation

Amendment to a Previous Combined Solicitation

SUBJECT*
TVHS VFD Replacement

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
37129
SOLICITATION NUMBER*
36C24926Q0229
RESPONSE DATE/TIME/ZONE
06-16-2026 11:00 CENTRAL TIME, CHICAGO, USA
ARCHIVE
30 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N
SET-ASIDE
SDVOSBC
PRODUCT SERVICE CODE*
J041
NAICS CODE*
238220
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Network Contracting Office 9 (90C)

NCO 9

1639 Medical Center Parkway, Suite 204 Murfreesboro TN 37129

POINT OF CONTACT*

Diane Ziegler diane.ziegler@va.gov

PLACE OF PERFORMANCE

ADDRESS
Tennessee Valley Healthcare System Medical Center

1310 24th Ave. South

Nashville TN

POSTAL CODE
37212

COUNTRY

ADDITIONAL INFORMATION

AGENCY’S URL

URL DESCRIPTION

AGENCY CONTACT’S EMAIL ADDRESS

EMAIL DESCRIPTION

DESCRIPTION

The purpose of this amendment is to post Questions and Answers to Solicitation 36C24926Q0229 TVHS VFD Replacements

1. Question: Is this is a brand new contract OR if there is (was) an incumbent performing these services.

Answer: This is a new contract

2. Question: Is there a scheduled site visit or if one can be arranged? We would appreciate any details you could provide, including the date and time, if applicable.

Answer: Site visit will be scheduled and no pictures will be provided. Email Stephen.Browne@va.gov to set up a site visit.

3. Question: Specification Section 5.b requires NICET Level I or NETA Level II certification. Will the Government accept licensed electricians and manufacturer-certified VFD/controls technicians as an equivalent qualification?

Answer: Because this a replacement and the systems are tied to the Fire system. You would need electricians and manufacturer-certified VFD/controls technicians as an equivalent qualification?

4. Question: Please confirm whether electrical one-lines, mechanical and electrical plans, existing VFD schedules, control diagrams, BAS point lists, fire alarm interface diagrams, or record/as-built drawings are available for the listed VFD locations. If available, please provide them with amendment.

Answer: Because this a replacement we can provide locations and point lists, upon request

5. Question: Please confirm whether photos of the existing VFDs, disconnects, bypasses, conduit entries, mounting locations, BAS/control panels, and related fan room and mechanical room conditions can be provided by amendment.

Answer: Because this a replacement we can provide locations and pictures upon request

6. Question: Please confirm whether the Government will schedule a pre-bid site visit or escorted field verification before the quote due date so vendors can review existing VFD locations, mounting conditions, access, conduit entries, control interfaces, and outage constraints.

Answer: Outage constraints can be worked by scheduling after contract is awarded. We can set up a pre bid site visit if needed. (See Question 2)

7. Question: The SOW states the facility standard is Danfoss and the technical evaluation subfactor requires Danfoss-manufactured VFDs. Please identify the required Danfoss model, series, or product line and any required options or accessories.

Answer: The Danfoss model series would be determined by the size required for the equipment

8. Question: The equipment list specifies a disconnect with bypass for each unit. Please clarify whether the bypass is required to be an integral VFD bypass package, a separate disconnect and bypass assembly, or another specific VA-standard configuration.

Answer: Some of the VFDs being replaced are standalone VFDs, these require build in bypass and disconnect. Others are dual systems with added cabinets with disconnects and contactors as interlocks so only one can run at a time.

9. Question: Please provide or clarify the required BAS point list, communication protocol, graphics requirements, trend requirements, alarm requirements, and sequence updates for each VFD.

Answer: Because this a replacement we can provide locations and point lists, upon request

10. Question: Please identify which listed VFDs, AHUs, fans, or pumps require fire alarm interface, shutdown, monitoring, or sequence integration. If available, please provide fire alarm drawings or sequence documentation by amendment.

Answer: Only supply and returns for AHUs and some exhaust fans

FR 3
AHU 9 Supply 1
133129
40
FR 3
AHU 9 Return 1
90770
10
FR 3
AHU 9 Return 2
98773
10
FR 1
AHU 5 Supply 1
96487
40
FR 1
AHU 5 Supply 2
96486
40
FR 17
AHU 54
No #
25
FR 17
RF 54 A
No #
5
FR 17
RF 54 b
No #
5
FR 10
AHU 33
99076
25
FR 4
AHU 22
No #
15
FR 4
RF 22
No #
7.5
FR 11
AHU 26
90743
40
F-8
RF 31
116838
7.5
FR 10
EF72
123027
1.5
FR 10
EF55
123024
2
FR 10
EF64
123023
20
FR 12
AHU 4
No #
5
FR 3
Tertiary Pump
33694
15
F-8
HWP 6
No #
5
FR 9
AHU 32
99075
30
FR 16
AHU 52 Supply
88170
40
FR 16
AHU 52 Return
88174
5
FR 16
AHU 51 Supply
88171
40
FR 16
AHU 51 Return
88175
5

11. Question: Please clarify whether any of the listed AHUs, return fans, exhaust fans, or pumps are part of a smoke control or other life safety sequence that requires special testing, witnessing, or documentation.

Answer: Only the AHUs

12. Question: Please identify any listed equipment serving critical, sensitive, or restricted hospital areas and any outage limitations beyond the general after-hours and weekend coordination requirement.

Answer: AHU 54 would have to be scheduled for after-hours

13. Question: Please clarify whether the Government requires witnessed functional testing for each VFD, BAS point verification, bypass testing, fire alarm interface testing, or other commissioning checkpoints.

Answer: Yes, this part of commissioning

14. Question: Please clarify available loading and unloading areas, freight or service elevator access if applicable, staging limitations, parking limitations, and whether work areas require special access procedures beyond standard badging.

Answer: Contractor parking is available. Contractors for this project will be escorted by VA personnel.

15. Question: Please confirm whether one qualified prime contractor employee may serve in multiple project roles, such as Superintendent, Site Safety and Health Officer, Quality Control Manager, and Project Manager, provided that the individual meets all applicable qualification requirements and can properly perform each required function for the project.

Answer: Provided that this person is onsite during installation.

*= Required Field
Amendment to a Previous Combined Solicitation

Page 1 of

Amendment to a Previous Combined Solicitation

File details come from the government source that posted it. Updated .