This file is an Amendment to a Previous Combined Solicitation containing Questions and Answers for Solicitation 36C24926Q0229 TVHS VFD Replacement. The solicitation is a Request for Quotation issued by the Department of Veterans Affairs Network Contracting Office 9 (Nashville, Tennessee) for the replacement of Variable Frequency Drives (VFDs) at Tennessee Valley Healthcare System's Nashville campus. The contract is a 100% set-aside for Service Disabled Veteran Owned Small Business (SDVOSBC) concerns with a response deadline of June 16, 2026 at 11:00 AM Central Time. The contract period runs from July 1, 2026 through October 31, 2026, with a primary NAICS code of 238220 (Plumbing, Heating, and Air-Conditioning Contractors) and Product/Service Code J041 (Maintenance/Repair/Rebuild of Refrigeration, Air Conditioning, and Air Circulating Equipment).
The amendment addresses 15 questions from potential bidders regarding project specifics. Key clarifications include: this is a new contract with no incumbent contractor; site visits can be arranged by contacting Stephen.Browne@va.gov; licensed electricians and manufacturer-certified VFD/controls technicians are acceptable qualifications; Danfoss VFDs are the required facility standard with specific models determined by equipment size; some VFDs require integral bypass and disconnect packages while others involve dual systems with separate cabinets; locations, point lists, and photographs will be provided upon request; pre-bid site visits are available; fire alarm interfaces are required for specified AHU supply/return and exhaust fan units; witnessed functional testing and commissioning are required; contractor parking is available with VA escort requirements; and one qualified employee may serve multiple project roles provided they remain onsite during installation. The contracting office point of contact is Diane Ziegler (diane.ziegler@va.gov) located at 1639 Medical Center Parkway, Suite 204, Murfreesboro, Tennessee 37129.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S04 Organized Site Visit Sign In Sheet VFD Rep.pdf | ||
| 36C24926Q0229 0002.docx | DOCX document | |
| P07 WD 2015-4647 Rev. 32 DATED 05.13.2026.docx | DOCX document | |
| 36C24926Q0229.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Amendment to a Previous Combined Solicitation
Amendment to a Previous Combined Solicitation
| SUBJECT* |
| TVHS VFD Replacement |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 37129 |
| SOLICITATION NUMBER* |
| 36C24926Q0229 |
| RESPONSE DATE/TIME/ZONE |
| 06-16-2026 11:00 CENTRAL TIME, CHICAGO, USA |
| ARCHIVE |
| 30 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
| SET-ASIDE |
| SDVOSBC |
| PRODUCT SERVICE CODE* |
| J041 |
| NAICS CODE* |
| 238220 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
Network Contracting Office 9 (90C)
NCO 9
1639 Medical Center Parkway, Suite 204 Murfreesboro TN 37129
POINT OF CONTACT*
Diane Ziegler diane.ziegler@va.gov
PLACE OF PERFORMANCE
| ADDRESS |
| Tennessee Valley Healthcare System Medical Center |
1310 24th Ave. South
Nashville TN
| POSTAL CODE |
| 37212 |
COUNTRY
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
DESCRIPTION
The purpose of this amendment is to post Questions and Answers to Solicitation 36C24926Q0229 TVHS VFD Replacements
1. Question: Is this is a brand new contract OR if there is (was) an incumbent performing these services.
Answer: This is a new contract
2. Question: Is there a scheduled site visit or if one can be arranged? We would appreciate any details you could provide, including the date and time, if applicable.
Answer: Site visit will be scheduled and no pictures will be provided. Email Stephen.Browne@va.gov to set up a site visit.
3. Question: Specification Section 5.b requires NICET Level I or NETA Level II certification. Will the Government accept licensed electricians and manufacturer-certified VFD/controls technicians as an equivalent qualification?
Answer: Because this a replacement and the systems are tied to the Fire system. You would need electricians and manufacturer-certified VFD/controls technicians as an equivalent qualification?
4. Question: Please confirm whether electrical one-lines, mechanical and electrical plans, existing VFD schedules, control diagrams, BAS point lists, fire alarm interface diagrams, or record/as-built drawings are available for the listed VFD locations. If available, please provide them with amendment.
Answer: Because this a replacement we can provide locations and point lists, upon request
5. Question: Please confirm whether photos of the existing VFDs, disconnects, bypasses, conduit entries, mounting locations, BAS/control panels, and related fan room and mechanical room conditions can be provided by amendment.
Answer: Because this a replacement we can provide locations and pictures upon request
6. Question: Please confirm whether the Government will schedule a pre-bid site visit or escorted field verification before the quote due date so vendors can review existing VFD locations, mounting conditions, access, conduit entries, control interfaces, and outage constraints.
Answer: Outage constraints can be worked by scheduling after contract is awarded. We can set up a pre bid site visit if needed. (See Question 2)
7. Question: The SOW states the facility standard is Danfoss and the technical evaluation subfactor requires Danfoss-manufactured VFDs. Please identify the required Danfoss model, series, or product line and any required options or accessories.
Answer: The Danfoss model series would be determined by the size required for the equipment
8. Question: The equipment list specifies a disconnect with bypass for each unit. Please clarify whether the bypass is required to be an integral VFD bypass package, a separate disconnect and bypass assembly, or another specific VA-standard configuration.
Answer: Some of the VFDs being replaced are standalone VFDs, these require build in bypass and disconnect. Others are dual systems with added cabinets with disconnects and contactors as interlocks so only one can run at a time.
9. Question: Please provide or clarify the required BAS point list, communication protocol, graphics requirements, trend requirements, alarm requirements, and sequence updates for each VFD.
Answer: Because this a replacement we can provide locations and point lists, upon request
10. Question: Please identify which listed VFDs, AHUs, fans, or pumps require fire alarm interface, shutdown, monitoring, or sequence integration. If available, please provide fire alarm drawings or sequence documentation by amendment.
Answer: Only supply and returns for AHUs and some exhaust fans
| FR 3 |
| AHU 9 Supply 1 |
| 133129 |
| 40 |
| FR 3 |
| AHU 9 Return 1 |
| 90770 |
| 10 |
| FR 3 |
| AHU 9 Return 2 |
| 98773 |
| 10 |
| FR 1 |
| AHU 5 Supply 1 |
| 96487 |
| 40 |
| FR 1 |
| AHU 5 Supply 2 |
| 96486 |
| 40 |
| FR 17 |
| AHU 54 |
| No # |
| 25 |
| FR 17 |
| RF 54 A |
| No # |
| 5 |
| FR 17 |
| RF 54 b |
| No # |
| 5 |
| FR 10 |
| AHU 33 |
| 99076 |
| 25 |
| FR 4 |
| AHU 22 |
| No # |
| 15 |
| FR 4 |
| RF 22 |
| No # |
| 7.5 |
| FR 11 |
| AHU 26 |
| 90743 |
| 40 |
| F-8 |
| RF 31 |
| 116838 |
| 7.5 |
| FR 10 |
| EF72 |
| 123027 |
| 1.5 |
| FR 10 |
| EF55 |
| 123024 |
| 2 |
| FR 10 |
| EF64 |
| 123023 |
| 20 |
| FR 12 |
| AHU 4 |
| No # |
| 5 |
| FR 3 |
| Tertiary Pump |
| 33694 |
| 15 |
| F-8 |
| HWP 6 |
| No # |
| 5 |
| FR 9 |
| AHU 32 |
| 99075 |
| 30 |
| FR 16 |
| AHU 52 Supply |
| 88170 |
| 40 |
| FR 16 |
| AHU 52 Return |
| 88174 |
| 5 |
| FR 16 |
| AHU 51 Supply |
| 88171 |
| 40 |
| FR 16 |
| AHU 51 Return |
| 88175 |
| 5 |
11. Question: Please clarify whether any of the listed AHUs, return fans, exhaust fans, or pumps are part of a smoke control or other life safety sequence that requires special testing, witnessing, or documentation.
Answer: Only the AHUs
12. Question: Please identify any listed equipment serving critical, sensitive, or restricted hospital areas and any outage limitations beyond the general after-hours and weekend coordination requirement.
Answer: AHU 54 would have to be scheduled for after-hours
13. Question: Please clarify whether the Government requires witnessed functional testing for each VFD, BAS point verification, bypass testing, fire alarm interface testing, or other commissioning checkpoints.
Answer: Yes, this part of commissioning
14. Question: Please clarify available loading and unloading areas, freight or service elevator access if applicable, staging limitations, parking limitations, and whether work areas require special access procedures beyond standard badging.
Answer: Contractor parking is available. Contractors for this project will be escorted by VA personnel.
15. Question: Please confirm whether one qualified prime contractor employee may serve in multiple project roles, such as Superintendent, Site Safety and Health Officer, Quality Control Manager, and Project Manager, provided that the individual meets all applicable qualification requirements and can properly perform each required function for the project.
Answer: Provided that this person is onsite during installation.
| *= Required Field |
| Amendment to a Previous Combined Solicitation |
Page 1 of
Amendment to a Previous Combined Solicitation