36C24926Q0053 0001 Questions and Answers .pdf

PDF 41 KB Posted

Attached to
Updated J065--Provide and Install Dental Vac Replacement at TVHS Murfreesboro, TN
Solicitation number
36C24926Q0053
Issued by

About this file

This document is a set of questions and answers regarding a dental vacuum system replacement. The document details key technical specifications and site conditions for a proposed RV5-2T vacuum system installation. Specific details include confirmation of a dedicated 20-amp electrical breaker, sufficient mechanical room space for an Infiniti tank, and the system's capacity to support 5 treatment rooms/dental chairs. Access to the mechanical space is noted as being via an external staircase outside the building, which provides context for installation considerations. The responses indicate that supporting photographic documentation of the current setup was provided in a separate PDF attachment.

View the file

Other files

File Type Posted
36C24926Q0053 0002 Questions and Answers.pdf PDF
36C24926Q0053 0002.pdf PDF
Existing Equipment Reference.pdf PDF
36C24926Q0053 0001.pdf PDF
WDOL 15-4647 R30 12.3.25.pdf PDF
36C24926Q0053 final.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. Could you provide photos of the mechanical room and the current vacuum system setup that will be replaced?

Answer: Pictures of current setup and the general area are attached in PDF format.

2. Is the existing system connected to a dedicated 20-amp breaker?

Answer: Yes.

3. Is there sufficient room in the mechanical area to install the Infiniti tank?

Answer: Yes.

4. How many treatment rooms is the proposed RV5-2T expected to support for vacuum service?

Answer: There is a total of 5 rooms/dental chairs.

5. Is there normal access to this space? Rather than access through rooftop or other difficult area?

Answer: PDF attachment shows the staircase entrance to this Mechanical

Space. This Mechanical Space is only accessible from outside of the building, down the staircase.