Load (Roof) Anchor Inspection & Certification (Memphis VAMC) **Combined Synopsis/Solicitation** AMENDMENT-1

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
37129
SOLICITATION NUMBER*
36C24923Q0002
RESPONSE DATE/TIME/ZONE
08-26-2022 10:00 CENTRAL TIME, CHICAGO, USA
ARCHIVE
60 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N
SET-ASIDE
SBA
PRODUCT SERVICE CODE*
H999
NAICS CODE*
541380
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Network Contracting Office 9 (90C)

NCO 9

1639 Medical Center Parkway, Suite 400 Murfreesboro TN 37129

POINT OF CONTACT*

Contract Specialist Lara J Hampton Lara.Hampton@va.gov 615-225-6576

PLACE OF PERFORMANCE

ADDRESS
Department of Veterans Affairs

Memphis Veterans Affairs Medical Center

1030 Jefferson Avenue

Memphis TN

POSTAL CODE
38104
COUNTRY
USA

ADDITIONAL INFORMATION

AGENCY’S URL
https://www.va.gov
URL DESCRIPTION
Department of Veterans Affairs
AGENCY CONTACT’S EMAIL ADDRESS
Lara.Hampton@va.gov
EMAIL DESCRIPTION
Contract Specialist Email Address

Amendment to a Previous Combined Solicitation

Amendment to a Previous Combined Solicitation

DESCRIPTION

*= Required Field
Amendment to a Previous Combined Solicitation

Page 1 of

Amendment to a Previous Combined Solicitation

Vendor Questions/Government Responses Vendor Question: Do you have any specs or prints for the above anchor solicitation? Government Response: see below (NO Blueprints available) Testing Prescriptions: The technician utilizes a force implementation system to place benchmark loads on designated equipment for a period of two minutes. A test is considered successful if the unit remains elastic through the course of the test without showing excessive deflection.

· Fall arrest anchorage testing procedure: The technician placed a calibrated digital Hydrajaws with a chain ratchet, inline between the 2 anchorage points and applied a

11.2 kN (2,500 lbs) load, pulling the anchorages toward one another for duration of 2 minutes. Deflection and yield were measured and recorded.

Test Limitations: The test results and data analysis expressed herein is not a warranty that the components tested are necessarily defect-free. RTA takes no responsibility for and makes no claims or opinions with respect to any latent or concealed defects or other defects which may be visible, but which may exist prior to or as of the date of the test.

Equipment inspection: The technician conducted a visual inspection of exposed, visible, and accessible components for any obvious signs of wear, loose or damaged mountings, scarring, cracking, rust, damage, bending, distortion, or corrosion. They additionally reviewed any equipment label, tags, signage or user instructions made available to them.

Comments:

1. Anchorages are tested to 2,500 lbs./11.2 kN for a 5,000 lbs. ultimate load.

Page 1 of Page 1 of

Photos r

,,.r:•

Figures 1, 2 & 3: Typical pull testing setup, anchorages #1 to #2, and #9 gauge

Figure #4: Showing the southern atrium opening in the center

Figure #5: Looking east, from the SE corner of Bed Tower