C27_Drawings_621-22-113 - Replace Bldg 160 Domestic Water Piping.pdf

PDF 14 MB Posted

Attached to
Z2DZ--621-22-113 - Replace Bldg 160 Domestic Water Piping
Solicitation number
36C24923B0011
Issued by

About this file

This document provides details on a federal contract opportunity to replace domestic water piping at a Veterans Affairs medical center. The Department of Veterans Affairs Network Contracting Office 9 Central Region will solicit bids for construction services through an Invitation for Bids on or around April 28, 2023. The project involves replacing copper and plastic domestic water pipes in Building 160 at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The contract is set aside for a Service-Disabled Veteran-Owned Small Business and has an estimated value between $2-5 million. The period of performance is 423 calendar days from notice to proceed. Bidders must be verified as SDVOSBs by the VA Center for Veterans Enterprise and registered in the System for Award Management at the time of bid submission to be deemed responsive. Questions must be submitted in writing to the contracting specialist by email with the project number and solicitation number in the subject line.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT

SITE

N

NORTH

LOCATION MAP

MOUNTAIN

HOME

NASHVILLE KNOXVILLE

MEMPHIS

TENNESSEE

CHATTANOOGA

PROJECT

LOCATION

1. THESE NOTES ARE FOR THE CONTRACTOR, AND ALL ASSOCIATED

SUBCONTRACTORS, MANUFACTURERS, AND SUPPLIERS.

2. SHOULD DISCREPANCY EXIST BETWEEN THE DRAWINGS AND

SPECIFICATION, THE CONTRACTOR AND/OR SUBCONTRACTOR SHALL

MAKE MENTION TO THE OWNER FOR DIRECTION PRIOR TO PROCEEDING

WITH WORK.

3. THE PLANS AND DETAILS ARE REPRESENTATIVE IN NATURE, AND ARE

PROVIDED TO SHOW THE RELATIONSHIP BETWEEN SPECIFIED

MATERIALS. FOR CLARITY, ALL SPECIFIED MATERIALS REQUIRED FOR

USE MAY NOT BE SHOWN ON DETAILS, AND CONTRACTOR SHALL

ENSURE THAT CONSTRUCTION, INSTALLATION, AND APPLICATION OF

MATERIALS IS DONE IN ACCORDANCE WITH SPECIFICATION.

4. ALL MEASUREMENTS AND EXISTING CONDITIONS MUST BE VERIFIED

PRIOR TO ORDERING MATERIALS AND/OR PROCEEDING WITH WORK.

5. ALL CROSS-SECTIONAL DETAILS REPRESENT TYPICAL CONDITIONS, AND

THOSE CROSS-SECTIONAL DETAILS SHALL BE APPLIED IN MERIT TO

APPLICABLE AREAS EVEN THOUGH NOT SPECIFICALLY MARKED ON

DRAWINGS OR REFERRED TO IN SPECIFICATIONS.

6. ALL MANUFACTURER'S RECOMMENDATIONS MUST BE STRICTLY

ADHERED TO, UNLESS MORE STRINGENT REQUIREMENTS LIE WITHIN

THE SPECIFICATION OR DRAWINGS.

7. THE NEW CEILING AND WALL CONSTRUCTION SHALL MATCH EXISTING

CEILINGS AND WALL CONSTRUCTION WHERE CEILINGS AND WALLS ARE

DEMOLISHED TO REPLACE/ADD PLUMBING ELEMENTS

8. KITCHEN SHALL REMAIN OPERATIONAL EXCEPT DURING NIGHT TIME.

G.C. SHALL COORDINATE ACCEPTABLE DOWN TIME WITH VA.

ALLOWABLE WORKING HOURS ARE 7 DAYS A WEEK 9PM-4AM UNLESS

OTHERWISE APPROVED.

9. PHASING OF ALL WORK SHALL BE COORDINATED WITH COR.

DRAWING NOTES

JURISDICTION: COUNTY

ALL CODES TO INCLUDE CURRENT TENNESSEE AMENDMENTS

ALL CONSTRUCTION, ADDITIONS, ALTERATIONS, REPAIRS,

REPLACEMENT, AND MOVEMENTS SHALL COMPLY WITH THE 2018

INTERNATIONAL EXISTING BUILDING CODE (IBC) AND ALL LOCAL CODES.

ALL INSTALLATIONS OF ELECTRICAL SYSTEMS SHALL COMPLY WITH THE

2017 NATIONAL ELECTRICAL CODE (NFPA 70) INCLUDING ALTERATIONS,

REPAIRS, REPLACEMENT, EQUIPMENT, APPLIANCES, FIXTURES AND

FITTINGS.

ALL INSTALLATIONS OF MECHANICAL SYSTEMS SHALL COMPLY WITH THE

2018 INTERNATIONAL MECHANICAL CODE, INCLUDING ALTERATIONS,

REPAIRS REPLACEMENT OF MECHANICAL SYSTEMS.

ALL INSTALLATIONS OF PLUMBING SYSTEMS SHALL COMPLY WITH THE

2018 INTERNATIONAL PLUMBING CODE, INCLUDING ALTERATIONS,

REPAIRS, REPLACEMENT, EQUIPMENT, APPLIANCES, FIXTURES AND

FITTINGS.

ALL CONSTRUCTION, ALTERATIONS, MOVEMENT, ENLARGEMENT,

REPLACEMENT, AND REPAIR SHALL COMPLY WITH ALL CURRENT

EDITIONS AND REVISIONS OF THE 2018 INTERNATIONAL FIRE CODE

INCLUDING ALL FIRE CODES ADOPTED BY THE STATE OF TENNESSEE.

ALL CONSTRUCTION, ALTERATIONS MOVEMENT, ENLARGEMENT,

REPLACEMENT, AND REPAIR SHALL COMPLY WITH THE THE AMERICAN

NATIONAL STANDARD FOR PHYSICALLY HANDICAPPED PEOPLE (ANSI

A117.1) AND THE AMERICANS WITH DISABILITIES ACT (ADA 2010).

ALL DESIGN AND MATERIALS SHALL COMPLY WITH THE 2015

INTERNATIONAL ENERGY CONSERVATION CODE.

PROJECT

AREA

JAMES H. QUILLEN VA

MEDICAL CENTER

CODE REFERENCE

A SEPARATE PROJECT MANUAL (SPECIFICATION) IS:

INCLUDED

NOT INCLUDED

AS PART OF THIS PROJECT.

SPECIFICATIONS

REPLACE BUILDING 160

DOMESTIC WATER PIPING

JAMES H. QUILLEN VA MEDICAL

CENTER, LAMONT AND VETERANS

WAY MT. HOME, TN 37684

Raymond Project #: 1418.035 VA Project #: 621-22-113 o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

Raymond-Pond 8A II JV, LLC 1035 Green Street Suite A | Conyers, Georgia 30012

Office: (919) 872-7866

CONSULTANTS:

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

SDVOSB

CVE

FINAL CONSTRUCTION DRAWINGS FOR BID

Department of Veterans Affairs

Office of Construction and Facilities Management

AE REPLACE BLDG 160

DOMESTIC WATER PIPING

CONTR. No. #36C24919D0021

MOUNTAIN HOME, TN

621-22-113

2023-05-04

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

DRAWING INDEX

Sheet Number Sheet Title ISSUE DATE REV NO. LATEST

ISSUE

G-001 COVER SHEET 2023-05-04 -- --

P-001 GENERAL INFORMATION 2023-05-04 -- --

P-002 PHASING PLAN 2023-05-04 -- --

P-003 PHASING PLAN 2023-05-04 -- --

PD101A SUB-BASEMENT CENTER CORE - DEMO 2023-05-04 -- --

PD101B SUB-BASEMENT EAST - DEMO 2023-05-04 -- --

PD101C SUB-BASEMENT WEST - DEMO 2023-05-04 -- --

PD111A FIRST FLOOR CENTER CORE - DEMO 2023-05-04 -- --

PD121A SECOND FLOOR CENTER CORE - DEMO 2023-05-04 -- --

PD131A THIRD FLOOR CENTER CORE - DEMO 2023-05-04 -- --

PD141A FOURTH FLOOR CENTER CORE - DEMO 2023-05-04 -- --

PD401 ENLARGED PLUMBING EQUIPMENT ROOM - DEMO 2023-05-04 -- --

PD402 FIRST FLOOR KITCHEN PLAN - DEMO 2023-05-04 -- --

PD403 SHEET PHOTOS 2023-05-04 -- --

PP101A SUB-BASEMENT CORE CENTER - NEW WORK 2023-05-04 -- --

PP101B SUB-BASEMENT EAST - NEW WORK 2023-05-04 -- --

PP101C SUB-BASEMENT WEST - NEW WORK 2023-05-04 -- --

PP111A FIRST FLOOR CENTER CORE - NEW WORK 2023-05-04 -- --

PP121A SECOND FLOOR CENTER CORE - NEW WORK 2023-05-04 -- --

PP131A THIRD FLOOR CENTER CORE - NEW WORK 2023-05-04 -- --

PP141A FOURTH FLOOR CENTER CORE - NEW WORK 2023-05-04 -- --

PP401 ENLARGED PLUMBING EQUIPMENT ROOM - NEW WORK 2023-05-04 -- --

PP402 FIRST FLOOR KITCHEN PLAN - NEW WORK 2023-05-04 -- --

P-601 DETAILS AND SCHEDULES 2023-05-04 -- --

05/04/23 o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

Raymond-Pond 8A II JV, LLC 1035 Green Street Suite A | Conyers, Georgia 30012

Office: (919) 872-7866

CONSULTANTS:

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

SDVOSB

CVE

FINAL CONSTRUCTION DRAWINGS FOR BID

Department of Veterans Affairs

Office of Construction and Facilities Management

AE REPLACE BLDG 160

DOMESTIC WATER PIPING

CONTR. No. #36C24919D0021

MOUNTAIN HOME, TN

621-22-113

2023-05-04

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

1. PLUMBING WORK SHALL BE IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE, INTERNATIONAL PLUMBING CODE, AND INTERNATIONAL FUEL GAS CODE. ADDITIONALLY, FOLLOW UFC 1-200-1, UFC 1-200-02, AND UFC 3-420-01.

2. SLOPES AND INVERT ELEVATIONS SHALL BE ESTABLISHED BEFORE ANY PIPE IS INSTALLED IN ORDER TO MAINTAIN PROPER SLOPES. ANY DISCREPANCIES SHALL BE REPORTED TO CONTRACTING OFFICER'S REPRESENTATIVE. ALL PIPING SHALL BE LOCATED AND DETERMINED WHEN TO BE INSTALLED TO AVOID CONFLICT WITH OTHER TRADES.

3. PIPING SHALL BE CONCEALED UNLESS OTHERWISE NOTED.

4. COORDINATE LOCATION OF PIPING WITH ALL MECHANICAL AND ELECTRICAL EQUIPMENT. NO PIPING SHALL BE INSTALLED ABOVE ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT OR PANELS. COMPLY WITH ARCHITECTURAL PLANS FOR EXACT LOCATION OF PLUMBING FIXTURES, COMPLIANCE TO ADA CLEARANCES, AND FINISHES.

5. PROVIDE REQUIRED WATER, WASTE, AND VENT PIPING, FITTINGS, AND INSULATION, AND MAKE FINAL CONNECTIONS TO EQUIPMENT. THESE PLANS ARE SCHEMATIC AND DIAGRAMMATIC ONLY. THEY DO NOT SHOW ALL REQUIRED BENDS, OFFSETS, VALVES, AND MISCELLANEOUS FITTINGS FOR A COMPLETE INSTALLATION. ALL PIPING, EQUIPMENT, AND CONNECTIONS SHALL BE INSTALLED IN ACCORDANCE WITH SPECIFICATIONS, LOCAL CODES AND ORDINANCES, AND

MANUFACTURER'S INSTRUCTIONS.

6. DO NOT SCALE DRAWINGS. REFER TO ARCHITECTURE DRAWINGS FOR EXACT DIMENSIONS, FIXTURE LOCATIONS, ROOM NAMES, AND NUMBERS.

7. WHERE POSSIBLE, INSTALL SHUT-OFF VALVES AND EQUIPMENT REQUIRING MAINTENANCE, CLEANING AND ADJUSTMENT ABOVE ACCESSIBLE CEILINGS OR IN SERVICE AREAS SUCH AS JANITOR'S CLOSETS. IN OTHER LOCATIONS, PROVIDE ACCESS PANELS IN INCONSPICUOUS LOCATIONS WITH FINISH TO MATCH ARCHITECTURAL.

8. ALL HOSE BIBBS, WALL HYDRANTS, AND VALVES WITH THREADED HOSE CONNECTIONS SHALL BE EQUIPPED WITH

VACUUM BREAKER.

9. PROVIDE INSULATION, PIPE IDENTIFICATION, AND OTHER REQUIREMENTS AS LISTED IN SPECIFICATIONS.

10. ALL PIPING ABOVE GRADE SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING

TILES OR BE SUPPORTED FROM CEILING TILES.

11. WATER PIPING ROUTED ABOVE CEILINGS AND IN EXTERIOR WALLS SHALL BE ROUTED ON HEATED SIDE (UNDERSIDE)

OF CEILING INSULATION AND HEATED SIDE (INSIDE) OF WALL INSULATION.

12. LOCATE ALL SECTIONAL OR MAIN CONTROL VALVES WITHIN 1'-0" FROM ACCESS PANELS, CEILING TILES, OR OTHER

POINT OF ACCESS.

13. PROVIDE WATER HAMMER ARRESTORS SIZED PER PLUMBING DRAINAGE INSTITUTE SPECIFICATIONS ON ALL DOMESTIC WATER LINES SERVING FLUSH VALVE FIXTURES, WASHING MACHINES SUPPLIES, PRV STATIONS, AND OTHER

INSTALLATIONS WITH QUICK CLOSING VALVES.

14. PROVIDE A MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL PIPING SYSTEMS

CROSSING BUILDING EXPANSION JOINTS.

15. ALL PLUMBING EQUIPMENT AND SYSTEMS SHALL BE GUARANTEED FOR A MINIMUM PERIOD OF ONE YEAR AFTER

OWNER'S FINAL ACCEPTANCE.

16. ALL PIPE PENETRATIONS OF FIRE AND/OR SMOKE-RATED ASSEMBLIES SHALL BE FIRE-STOPPED AS REQUIRED TO RESTORE ASSEMBLY TO ORIGINAL INTEGRITY. FIRE BARRIER PRODUCTS SHALL BE AS MANUFACTURED BY 3M COMPANY, CP25 CAULK, CS195 COMPOSITE PANEL, FS195 WRAP/STRIP, OR PSS 7900 SERIES SYSTEMS AS RECOMMENDED BY MANUFACTURER FOR PARTICULAR APPLICATION, OR EQUIVALENT SYSTEM AS APPROVED BY

LOCAL CODE OFFICIALS.

17. ALL WATER CLOSET FLUSH VALVE LEVERS SHALL BE LOCATED ON THE APPROACH SIDE OF THE WATER CLOSET.

18. ALL COLD WATER, HOT WATER, AND DRAIN PIPING AT HANDICAPPED FIXTURES SHALL BE INSULATED WITH HANDI-LAV

GUARD MODELS 102 AND 105 (OR APPROVED EQUAL) INSULATION KITS.

19. NOT ALL PLUMBING ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.

20. ALL SPRINKLER PIPING ABOVE THE CEILING IS PLASTIC. THE CONTRACTOR IS TO USE EXTREME CAUTION IN WORKING AROUND THE SPRINKLER PIPING. CONTRACTOR SHALL REPAIR/REPLACE IF DAMAGED DURING CONSTRUCTION.

GENERAL PLUMBING NOTES

- UNION

- REDUCER OR INCREASER

- BRANCH FROM BOTTOM OF PIPE

- BRANCH FROM TOP OF PIPE

- PIPE ELBOW DN

- PIPE ELBOW UP

- CHECK VALVE

- CONTROL VALVE - 2 WAY

- INLINE PUMP

- BALL VALVE

- GATE VALVE

- BALANCING VALVE

- PIPE CAP

- PIPE BREAK

- PIPE FLOW ARROW

- POINT OF NEW CONNECTION

- LIMIT OF REMOVAL

- KEYED NOTE

- REVISION/KEYED NOTE

- PIPING AND EQUIPMENT FOR REMOVAL

- HOSE BIBB

- WALL HYDRANT

- STRAINER WITH BLOWDOWN

WH

- DOMESTIC HOT WATER PIPING

- DOMESTIC HOT RECIRCULATION WATER PIPING

- DOMESTIC COLD WATER PIPING

PLUMBING LEGEND

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISH FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

AP ACCESS PANEL

ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION & AIR

CONDITIONING ENGINEERS

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS

AWWA AMERICAN WATERWORKS ASSOCIATION

BFP BACK FLOW PREVENTER

BOR BASE OF RISER

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

COR CONTRACTING OFFICER REPRESENTATIVE

CPVC CHLORINATED POLYVINYL CHLORIDE

CU COPPER

CV CONTROL VALVE

CW COLD WATER (DOMESTIC)

DFU DRAINAGE FIXTURE UNIT

DN DOWN

DWG DRAWING

DWH DOMESTIC WATER HEATER

ETR/(E) EXISTING TO REMAIN

EXIST EXISTING

FU FIXTURE UNITS

FV FLUSH VALVE

GAL GALLON

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

HW HOT WATER (DOMESTIC)

HWC HOT WATER CIRCULATION (DOMESTIC)

IPC INTERNATIONAL PLUMBING CODE

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION

P PUMP

PDI PLUMBING AND DRAINAGE INSTITUTE

PRV PRESSURE REDUCING VALVE

PSIG POUNDS PER SQUARE INCH GAUGE

PVC POLYVINYL CHLORIDE

TMV THERMOSTATIC MIXING VALVE

TYP TYPICAL

UPC UNIFORM PLUMBING CODE

WSFU WATER SUPPLY FIXTURE UNIT

PLUMBING ABBREVIATIONS

DEDUCT ALTERNATES

1. OMIT NEW PIPING TO ISOLATION VALVES IN THE CORRIDOR AND FIXTURES IN THE TWO FOURTH FLOOR CENTER CORE RESTROOMS N401 AND P400. INSTALL NEW PIPING AND VALVES IN THE REMAINDER OF THE FOURTH FLOOR CORE AS

SHOWN. SEE DRAWING SHEETS PD141A AND PP141A

2. OMIT NEW PIPING TO ISOLATION VALVES IN THE CORRIDOR AND FIXTURES IN THE TWO THIRD FLOOR CENTER CORE LARGE RESTROOMS N301 AND P300 AND TWO SMALL RESTROOMS N305A AND P301. INSTALL NEW PIPING AND VALVES IN THE REMAINDER OF THE THIRD FLOOR CORE AS SHOWN.SEE DRAWING SHEETS PD131A AND PP131A

3. OMIT NEW PIPING TO ISOLATION VALVES IN THE CORRIDOR IN THE TWO SECOND FLOOR CENTER CORE LARGE RESTROOMS N201 AND P200 AND PIPING TO ISOLATION VALVES IN THE CORRIDOR AND FIXTURES IN THE THREE SMALL RESTROOMS N203, P202, AND P204A. INSTALL NEW PIPING AND VALVES IN THE REMAINDER OF THE SECOND FLOOR

CORE AS SHOWN. SEE DRAWING SHEETS PD121A AND PP121A

LOCKER

UPUP

UP

DN

UP

UP UP

PLATFORM

DN

DN

DN

TRASH

COMP

TC-1

OVERHEAD DOOR

OVERHEAD DOOR

MALE/ FEMALE

TOILET

P087

TOILET

OFFICE

P072

INCENTIVE THERAPY

P003

CORRIDOR

CORRIDOR

CORRIDOR

TOILET

CORRIDORCORRIDOR

WAITING AREA

WAITING AREA

CORRIDOR

SIG

P071

CORRIDOR

CORRIDOR CORRIDOR

CORRIDOR

CORRIDOR

ELEVATOR

LOBBY

EL001

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDORCORRIDOR

STAIR

N0-2

STO

N064

TOILET

N062

MALE

TOILET

N066

BATTERY

RM

N068

FMS

LOUNGE

P095

FEMALE

TOILET

P093

STAIR

NO-1

STO

P089

TOILET

RECREATION /

MULTI-PURPOSE

AREA

N001

HAC

N065

TOILET

N063

MECH

N060

MECH

N056A

FMS STOR

N056

SIG

N058

ELEC EQUIP RM

N054

CLEAN

LINEN

N052

SOILED

LINEN

COLLECT

N050EMPLOYEE FITNESS

N027A

MENS TOILET

N011

EMS

OFFICE

N061

EMS

OFFICE

N059

EXERCISE RM

N055

MEDITATION RM

N051

DOM CHAPLAINS

OFFICE

N049

LOCKER

FEMALE

TOILET

N047

HAC

N045

RECEIVING

N046

TRASH

RM

N054B

TRASH

CHUTE

C3

SVC

ELEVATOR

S1

COLD STORAGE

N046A

STAIR

NO-3

MENTAL HEALTH

MEETING RM

N044

MENTAL HEALTH

OFFICE

N044A

TUB

RTPD MED

DIRECTOR OFFICE

N042

OFFICE

N040

BAL

OFFICE

N038

TOILET

OFFICE

N036

SOCIAL WORKER OFFICE

N034

TOILET

PRTP / PRRC

SOCIAL WORKER

NO32

OFFICE

N030

OFFICE

N028

PRTP NURSE PRACTITIONER

N026

TOILETBALTOILET

OFFICE

N024

OFFICE

N022

TOILET

OFFICE

N020

OFFICE

N018

PRTP

CLERK ELEC

STAIR

N0-4

TOILET

UTIL

LAUNDRY

N012

CLOTHING RM

N010

RECREATION STORAGE /

SEWING RM

N008

OFFICE

N006

TOILET

OFFICE

NOO4

NOO2

TUB

VEST

NC008

TUB

FRONT DESK

P001

GROUP RM

P005

TV

LOUNGE

P007

ARTS AND

CRAFT

STORAGE

P009

SLEEP RM

P011

TOILET

SLEEP RM

P013

SLEEP RM

P015

SLEEP RM

P017

TOILET

ELEC

P014

STAIR

NO-5

REC

OFFICE

N001A

ELEVATOR

P3

ELEVATOR

P4

ELEVATOR

P2

ELEVATOR

P1

FILES

P002A

BREAK AREA

P002J

CUBICLE

P002Y

CUBICLE

P002E

CUBICLE

P002D

CUBICLE

P002C

CUBICLE

P002BCUBICLE

P002I

CUBICLE

P002H

CUBICLE

P002G

CUBICLE

P002F

OFFICE CUBICLE

P002K

CUBICLE

P002LCUBICLE

P002M

CUBICLE

P002N

CUBICLE

P002P

P002Z

TOILET

P080

HAC

P082

CONSOLIDATED

LIBRARY

P026

CONG

BATH

P010

TOILET

TV

LOUNGE

P078

STOR

P026A

TUB

P076

MED LIBRARIAN

OFFICE

P074

MULTI-

PURPOSE

RM/KIT

P070

P068

TUB

TOILET

TUB

CONG

BATH

P064

PSYCHOLOGY SVC

P073

GROUP RM

P069

CLEAN

LINEN

P062

ELEC

P056

STORAGE

P067

HAC

P063

GROUP RM

P065

SLEEP RM

P019

SLEEP RM

P021

TOILET

TOILET

SLEEP RM

P023

BAL

SLEEP RM

P025

TOILET

SLEEP RM

P027SLEEP RM

P029

SLEEP RM

P031

TOILET

SLEEP RM

P033

SLEEP RM

P035

BAL

SLEEP RM

P037SLEEP RM

P039

TOILET

SLEEP RM

P041

TOILET

SLEEP RM

P043ASLEEP RM

P043

STAIR

NO-6

TOILET

MECH

P075

SLEEP RM

P061

SLEEP RM

P059

SLEEP RM

P057

SLEEP RM

P055

TOILET

SLEEP RM

P053

BAL

TOILET

SLEEP RM

P051

TOILET

SLEEP RM

P049

SLEEP RM

P047

DOM ASST

P045

BATH

N016

W

W

W

W

W

W

W

W

W

W

W

W

W

W

D

D

D

D

D

D

LAUNDRY

N012

D D D D D D D

PHASE 1

PHASE 3

PHASE 4

PHASE 2PHASE 5

PHASE 2

PHASE 6

PHASE 10

PHASE 7

PHASE 9

PHASE 8

PHASE 7

o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

Raymond-Pond 8A II JV, LLC 1035 Green Street Suite A | Conyers, Georgia 30012

Office: (919) 872-7866

CONSULTANTS:

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

SDVOSB

CVE

FINAL CONSTRUCTION DRAWINGS FOR BID

Department of Veterans Affairs

Office of Construction and Facilities Management

AE REPLACE BLDG 160

DOMESTIC WATER PIPING

CONTR. No. #36C24919D0021

MOUNTAIN HOME, TN

621-22-113

2023-05-04

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

KEY PLAN

N

SCALE:

DOMESTIC BASEMENT FLOOR PHASING PLAN

1/16" = 1'-0" P-002

E1

GENERAL NOTES:

HOURS VARIES SEE PHASING NOTES.

RISER WORK ONCE INITIATED MUST BE COMPLETED FROM GROUND FLOOR TO 4TH

FLOOR DURING PHASE 2. TEMPORARILY CONNECT TO EXISTING UNTIL SUBSEQUENT

PHASES BEGIN.

A. CONTRACTOR SHALL PROVIDE TEMPORARY BYPASS HOT AND COLD WATER

LINES TO ENSURE DOWN STREAM SERVICES ARE UNINTERRUPTED DURING

CONSTRUCTION PHASES. PEX AND PRESS OR CRIMP FITTINGS ACCEPTABLE

FOR TEMPORARY WORK.

PHASE 1:

INCLUDES ALL WORK IN PLUMBING MECHANICAL ROOM N056A. NO WORK AT

DOMESTIC HOT WATER HEAT EXCHANGER. EXTENT OF WORK IS NOTED IN THE

DEMO AND NEW WORK SHEETS PD401 AND PP401. THIS WORK CAN BE

PERFORMED ANY TIME. COORDINATE ALL WATER OUTAGES WITH COR. ALL

SHUTDOWNS SHALL BE DURING OFF-PEAK HOURS AND SCHEDULED TO

MINIMIZE DOWN TIME.

PHASE 2:

INCLUDES N-SIDE MAIN CORRIDOR WORK FROM CENTER CORE TO THE

INTERSECTION OUTSIDE THE TRASH CHUTE/ROOM AREA TO THE SOUTHEAST.

INCLUDING SINKS & DRINKING FOUNTAINS IN AND AROUND EXERCISE ROOMS

N055, TOILET N062, STORAGE N064, MALE TOILET N066, BATTERY ROOM N068

AND THE RISERS. RISERS WILL HAVE BARRIERS ON ALL FLOOR THROUGH THE

DURATION OF PROJECT. THIS WORK CAN BE PERFORMED ANY TIME.

COORDINATE ALL WATER OUTAGES WITH COR.

PHASE 3:

INCLUDES THE TRASH CHUTE/ROOM AREA AND THE ADJOINING CORRIDOR

INTERSECTION. NIGHT WORK ONLY. MUST BE COMPLETE EACH MORNING AND

RETURNED TO SERVICE. ALTERNATIVELY, WORK MAY BE CONDUCTED 24HRS

OVER A WEEKEND STARTING FRIDAY 8PM - MONDAY 5AM.

PHASE 4:

INCLUDES N-SIDE SOUTH CORRIDOR RUNNING EAST TO WEST AND ALL

ADJOINING ROOMS. THIS WORK CAN BE PERFORMED ANY TIME. COORDINATE

ALL WATER OUTAGES WITH COR.

PHASE 5:

INCLUDES N-SIDE WEST CORRIDOR RUNNING NORTH TO SOUTH AND ALL

ADJOINING ROOMS.

PHASE 6:

INCLUDES CENTER CORE AREA FROM NORTH CENTER MAIN CORRIDOR NEAR

THE RISERS TO THE OFFICES AND VESTIBULE TO THE SOUTH AND ALL

ADJOINING ROOMS TO THE NORTHWEST. NIGHT WORK ONLY. MUST BE

COMPLETE EACH MORNING AND RETURN TO SERVICE. WORK MAY BE

CONDUCTED @$ HOURS OVER A WEEKEND STARTING FRIDAY 8 PM TO MONDAY

5 AM.

PHASE 7:

INCLUDES P-SIDE MAIN CORRIDOR WORK FROM CENTER CORE TO THE END OF

THE CORRIDOR TO THE SOUTHWEST, ALL ADJOINING ROOMS TO THE

NORTHWEST AND THE CORRIDOR CONNECTION TO PHASE 8. THIS WORK CAN

BE PERFORMED ANY TIME. COORDINATE ALL WATER OUTAGES WITH COR.

PHASE 8:

INCLUDES P-SIDE WEST CORRIDOR RUNNING NORTHEAST TO SOUTHWEST AND

ALL ADJOINING ROOMS. THIS WORK CAN BE PERFORMED ANY TIME.

COORDINATE ALL WATER OUTAGES WITH COR.

PHASE 9:

INCLUDES P-SIDE SOUTH NORTH CORRIDOR RUNNING EAST TO WEST AND ALL

ADJOINING ROOMS. THIS WORK CAN BE PERFORMED ANY TIME. COORDINATE

ALL WATER OUTAGES WITH COR.

PHASE 10:

INCLUDES P-SIDE EAST CORRIDOR RUNNING NORTH TO SOUTH AND ALL

ADJOINING ROOMS. THIS WORK CAN BE PERFORMED ANY TIME. COORDINATE

ALL WATER OUTAGES WITH COR.

KEYED NOTES:#

1. PHASE 2 BUILD DUST ENCLOSURE ALL THE WAY UP TO FOURTH FLOOR TO

CHANGE OUT RISERS. THIS WILL STAY IN PLACE UNTIL THE WORK IS DONE.

AREA TURNED OVER TO THE CONTRACTOR

FOR DAY WORK.

WORK ANYTIME SCHEDULE WATER

SHUT DOWNS WITH COR

NIGHT WORK AND PUT CEILINGS BACK

UP AT END OF WORK SHIFT

UP

DN

UP

DN

UNDER CONSTRUCTION

CHASE

CORRIDOR

HAC/

SAN

SUPPLY

N100C

CORRIDOR

NFS

STORAGE

N178

TOILET

N176STO

P177

CORRIDOR

CORRIDOR

STAFF

ELEVATOR

LOBBY

EL101

NFS SECERATARY

OFFICE

N182

MALE

TOILET

N180

STAIR

NO-2

DIET

OFFICE

P181FEMALE

TOILET

P179

STAIR

NO-1

PRODUCTION MGR

OFFICE

N100G

REFR

N100D

REFRIG

N100F

PGM SUPPORT

CLERK OFFICE

N100E

ELEVATOR

P2

ELEVATOR

P1

ELEC

N102

ELEVATOR

P4

ELEVATOR

P3

FOOD SVC

SUPV

N100L

FOOD SVC

SUPV

N100K

DIET CHANCE

OFFICE

N100B

OFFICE

N100A

NON-FOOD

STORAGE

N100M

N100L

TOILET

N108

HAC

N106

OFFICE

N179

SUPPLY RM

DRY FOOD

STORAGE

N100H

INGREDIENT CONTROL

OFFICE

N100U

OFFICE

N100T

MENTAL HEALTH CLINIC

PSYCHIATRIST OFFICE

TOILET

P175

PHASE 11

PHASE 15

UP

DN

UP

DN

UNDER CONSTRUCTION

EXAM

N207

CORRIDOR

VEST

L201

CORRIDORCORRIDOR

MED

PREP

N200

STAIR

NO-1

TOILET

P202

FEMALE

TOILET

P200

CHECK-IN

AREA

L202

ELEVATOR

LOBBY

ELEVATOR

P4

ELEVATOR

P3

OUTPATIENT

LAB

PROCESSING

N202

OFFICE

N200A

VENDING

N204

VEND

N204

EXAM RM

N281

LAB

TOILET

BUSINESS OFFICE

DOM ADMISSIONS

N202

P204A

MALE

TOILET

N201

STAIR

NO-3

WHEEL CHAIR STORAGE

N205

TOILET

N203

EXAM

N209

LPN

P244K

OFFICE

P244J

OFFICE

P244H

STAFF

LOUNGE

P265

CONFERENCE

P263

OFFICE

P201

ELEVATOR

P1

ELEVATOR

P2

P204

P206

PHASE 12

UP

DN

UP

DN

TOILET

N305A

TOILET

P304A

VISITOR/

SOCIALIZATION

ACTIVITIES AREA

OFFICE

N300J

C O S

OFFICE

N300C

OEF/DIF/OND

PGM MGR

OFFICE

N305

STORAGE

N303

STAIR

NO-2MALE

TOILET

N301

TEAM CLERKS

P302

UA

P303

CORRIDOR

HOPTEL

LODGING

P306

P304

STORAGE

P302

STAIR

NO-1 FEMALE

TOILET

P300

ELEVATOR

P3

ELEVATOR

P4

PRIMARY CARE

ADMINISTRATION

P301

OFFICE

P301A

OFFICE

P301B

ELEVATOR

LOBBY

ELEVATOR

P1

OFFICE

P301C

OFFICE

P301D

OFFICE

P301E

CHIEF PRIMARY

CARE OFFICE

P301F

SECY

COS

N300D

ELEVATOR

P2

SEC

WAIT

N300

PHASE 13

DN

UP

DN

DESK

COUNTER

N405A

EVIDENCE-BASED

DTSD

TELEMENTAL

HEALTH

PSYCHOLOGIST

OFFICE

P404

N405

CORRIDOR

ELEVATOR

LOBBY

STORAGE

N403

STAIR

NO-2MALE

TOILET

N401

VISITOR

L401

CHECK-IN

DOMICILIARY

NURSE

P402

EXAM RM

STORAGE

P402

STAIR

NO-1 FEMALE

TOILET

P400

STAIR

NO-7

ELEVATOR

P4

ELEVATOR

P3

ELEVATOR

P1

ELEVATOR

P2

MECH

N400

TOILET

OFFICE

P406

BOPC

OFFICE

P478

WORKER OFFICE

N407

PHASE 14

o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

Raymond-Pond 8A II JV, LLC 1035 Green Street Suite A | Conyers, Georgia 30012

Office: (919) 872-7866

CONSULTANTS:

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

SDVOSB

CVE

FINAL CONSTRUCTION DRAWINGS FOR BID

Department of Veterans Affairs

Office of Construction and Facilities Management

AE REPLACE BLDG 160

DOMESTIC WATER PIPING

CONTR. No. #36C24919D0021

MOUNTAIN HOME, TN

621-22-113

2023-05-04

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

KEY PLAN

N

SCALE:

DOMESTIC FIRST FLOOR PHASING PLAN

1/16" = 1'-0" P-003

F1

SCALE:

DOMESTIC SECOND FLOOR PHASING PLAN

1/16" = 1'-0" P-003

C1

SCALE:

DOMESTIC THIRD FLOOR PHASING PLAN

1/16" = 1'-0" P-003

F5

SCALE:

DOMESTIC FOURTH FLOOR PHASING PLAN

1/16" = 1'-0" P-003

C5

GENERAL NOTES:

HOURS VARIES SEE PHASING NOTES.

RISER WORK ONCE INITIATED MUST BE COMPLETED FROM GROUND FLOOR TO 4TH

FLOOR DURING PHASE 2. TEMPORARILY CONNECTION TO EXISTING UNTIL

SUBSEQUENT PHASES BEGIN.

A. CONTRACTOR SHALL PROVIDE TEMPORARY BYPASS HOT AND COLD WATER

LINES TO ENSURE DOWN STREAM SERVICES ARE UNINTERRUPTED DURING

CONSTRUCTION PHASES. PEX AND PRESS OR CRIMP FITTINGS ACCEPTABLE

FOR TEMPORARY WORK.

PHASE 11:

INCLUDES FIRST FLOOR CENTER CORE AREA AND RISERS*. CORRIDOR WORK

TO BE PERFORMED AT NIGHT. STAIRWELLS AND RESTROOMS CAN

TEMPORARILY BE CLOSED.

PHASE 12:

INCLUDES SECOND FLOOR CENTER CORE AREA AND RISERS*. CORRIDOR

WORK TO BE PERFORMED AT NIGHT. STAIRWELLS AND RESTROOMS CAN

TEMPORARILY BE CLOSED.

PHASE 13:

INCLUDES THIRD FLOOR CENTER CORE AREA AND RISERS*. CORRIDOR WORK

TO BE PERFORMED AT NIGHT. STAIRWELLS AND RESTROOMS CAN

TEMPORARILY BE CLOSED.

PHASE 14:

INCLUDES FOURTH FLOOR CENTER CORE AREA AND RISERS*. CORRIDOR WORK

TO BE PERFORMED AT NIGHT. RESTROOM WORK CAN BE COORDINATED

DURING DAY TIME. RESTROOMS AND STAIRWELLS CAN BE TEMPORARILY

CLOSED FOR CONSTRUCTION BUT NOT ALL AT ONCE.

PHASE 15:

INCLUDES FIRST FLOOR KITCHEN AREA. ALL WORK MUST BE PERFORMED AT

NIGHT. ALL SERVICE RESTORED AND CLEANED BY MORNING. WORK

KEYED NOTES:#

1. PHASE 2 BUILD DUST ENCLOSURE ALL THE WAY UP TO FOURTH FLOOR TO

CHANGE OUT RISERS. THIS WILL STAY IN PLACE UNTIL THE WORK IS DONE.

NIGHT WORK AND PUT CEILINGS BACK

UP AT END OF WORK SHIFT

RESTROOMS CAN ONLY BE SHUT DOWN 1 AT A TIME.

STAIRWELLS CAN ONLY BE SHUT DOWN 1 AT A TIME.RESTROOMS CAN ONLY BE SHUT DOWN 1 AT A TIME.

STAIRWELLS CAN ONLY BE SHUT DOWN 1 AT A TIME.

RESTROOMS CAN ONLY BE SHUT DOWN 1 AT A TIME.

STAIRWELLS CAN ONLY BE SHUT DOWN 1 AT A TIME.

RESTROOMS CAN ONLY BE SHUT DOWN 1 AT A TIME.

STAIRWELLS CAN ONLY BE SHUT DOWN 1 AT A TIME.

MALE/ FEMALE

TOILET

P087

INCENTIVE THERAPY

P003

CORRIDOR CORRIDOR

CORRIDOR

ELEVATOR

LOBBY

EL001

CORRIDOR

STAIR

N0-2

STO

N064

TOILET

N062

MALE

TOILET

N066

BATTERY

RM

N068

FMS

LOUNGE

P095

FEMALE

TOILET

P093

STAIR

NO-1

STO

P089

TOILET

RECREATION /

MULTI-PURPOSE

AREA

N001

RECREATION STORAGE /

OFFICE

N006

TOILET

OFFICE

NOO4

NOO2

TUB

VEST

NC008

TUB

FRONT DESK

P001

GROUP RM

P005

REC

OFFICE

N001A

ELEVATOR

P3

ELEVATOR

P4

ELEVATOR

P2

ELEVATOR

P1

FILES

P002A

BREAK AREA

P002J

CUBICLE

P002Y

CUBICLE

P002E

CUBICLE

P002D

CUBICLE

P002C

CUBICLE

P002BCUBICLE

P002I

CUBICLE

P002H

CUBICLE

P002G

CUBICLE

P002F

OFFICE CUBICLE

P002K

CUBICLE

P002LCUBICLE

P002M

CUBICLE

P002N

CUBICLE

P002P

LAUNDRY

3/4"

1" 1"

1-1/2" 1-1/2"

CW

CW

HW

HW

C

1" HW

2-1/2" CW2" CW

1" HW

1-1/2" 1-1/2"

CW

3/4"

2" HWC UP REMOVE

3" HW UP REMOVE

6" CW UP TO REMAIN

1" 140 HWC UP REMOVE

2" 140 HW UP REMOVE

1/2"

2"

2"

1/2" 1/2"

1/2"1/2" 3/4" 3/4"

1/2" 1/2"

P-103

P-418

P-103

P-604

P-417 P-417 P-103

P-604

P-103 P-201

P-202

P-103

P-502

P-302

P-418

P-103

P-604 P-103

P-418P-302

P-418

P-103

P-103 P-418

P-604

3/4" 2"

1/2" HWC

2" CW

P-604

1/2" CW

1/2"

P-707

1 1

3 2

1" HWC

3" CW

1/2" HWC

1" HW

1-1/4" CW1-1/2" CW1/2" HWC

3/ 4"

H W

C 1-

1/ 4"

H W2- 1/

2" C

W

3/ 4"

H W

C 1-

1/ 4"

H W2- 1/

2" C

W

1" HWC

1-1/2" HW

1" HWC

2" HW

2" HWC

4" HW

1" 140 HWC

2" 140 HW

2" HWC

4" HW

(E) 6" CW

1" 140 HWC

2" 140 HW

2" 140 HW

1" HWC

1-1/2" HW

3" CW (E) 6" CW3" CW3" CW3" CW

2" HW

1-1/4" CW

1-1/4" CW

1-1/4" CW

1-1/4" HW

1-1/2" CW

WATER PIPES IN BOX AREA ARE

ABOVE LARGE DUCTWORK.

EXISTING DUCTWORK SHALL BE

REMOVED AND REINSTALLED.

REMOVE

THE P-414

1-1/4" HW & CW

P-808

P-418 o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

Raymond-Pond 8A II JV, LLC 1035 Green Street Suite A | Conyers, Georgia 30012

Office: (919) 872-7866

CONSULTANTS:

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

SDVOSB

CVE

FINAL CONSTRUCTION DRAWINGS FOR BID

Department of Veterans Affairs

Office of Construction and Facilities Management

AE REPLACE BLDG 160

DOMESTIC WATER PIPING

CONTR. No. #36C24919D0021

MOUNTAIN HOME, TN

621-22-113

2023-05-04

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

KEY PLAN

N

SCALE:

SUB-BASEMENT CENTER DOMESTIC FLOOR PLAN-DEMO

1/8" = 1'-0" PD101A

F1

GENERAL NOTES:

1. THE EXTENT OF PLUMBING FIXTURE DEMO WORK SHALL BE

COORDINATED WITH THE PLUMBING FIXTURE SCHEDULE AND

DEDUCT ALTERNATES TAKEN.

2. ALL WATER PIPING IS GENERALLY SHOWN ABOVE CEILING AND/OR

WITHIN WALLS, UNLESS OTHERWISE NOTED.

3. REFER TO PLUMBING FIXTURE SCHEDULE FOR FIXTURE

CONNECTION SIZES.

4. COORDINATE ALL WORK WITH OTHER TRADES.

5. ALL CHAIR CARRIERS TO REMAIN AND INSTALL NEW FASTENERS TO

ANCHOR NEW PLUMBING FIXTURES.

1. UNDER BASE BID FIXTURE P-801 IS TO BE REPLACED.

2. UNDER BASE BID THE TUB P-302 IS TO REMAIN AND ONLY FAUCET

AND SHOWER HEAD TO BE REPLACED.

3. UNDER BASE BID FIXTURE P-502 IS TO REMAIN AND ONLY THE

FAUCET IS TO BE REPLACED

4. 1/2" HW AND CW DROPS TO P-804. REMOVE PIPING. SEE PHOTO

#2601.

5. 1/2" STOP VALVE FOR CONNECTION TO ICE MACHINE. SEE

PHOTOS #2597 AND #2598.

6. STAINLESS-STEEL COUNTER TOP AND SINK TO REMAIN.

EXISTING FAUCET TO REMAIN. REMOVE PIPING TO WATER

FILTERS AND ALL PIPING DOWN STREAM OF THE WATER FILTERS.

SEE PHOTO #2591 AND #2592.

7. SINK IN AREA HAS BEEN REMOVED. REMOVE WATER PIPES AS

SHOWN. SEE PHOTO #2587.

8. REMOVE PIPING TO EXISTING P-707 SAFETY SHOWER MIXING

VALVE. SAFETY SHOWER AND MIXING VALVE TO REMAIN. SEE

PHOTO #2584.

9. UNDER BASE BID FIXTURE P-417 IS TO BE REPLACED. FIXTURE IS

A ROUND CHINA DROP IN BOWL. COUNTER TOP IS TO BE

CLEANED. SEE PHOTO #2581 FOR A TYPICAL ARRANGEMENT.

# KEYED NOTE

FO

R

CO

NT

IN

UA

TI

ON

S

EE

P D1

B

FO

R

CO

NT

IN

UA

TI

ON

S

EE

P D1

C

#2601

#2597

#2598

#2591

#2592

#2587

#2584

#2581

1. REFER TO PLAN: REMOVE EXISTING GYPSUM WALL BOARD /

WALLCOVERING AND ASSOCIATE CONSTRUCTION AS NECESSARY

TO ACCESS AND COMPLETE INDICATED WORK. INFILL OPENING

TO MATCH EXISTING ADJACENT CONSTRUCTION AND FINISHES.

DO NOT DISTURB EXISTING FINISHES ON UNDISTURBED SIDE OF

PARTITION.

2. REFER TO PLAN: REMOVE AND SALVAGE FOR REUSE EXISTING

CEILING GRID AND TILE AS NECESSARY TO ACCESS WORK.

REINSTALL GRID AND TILE TO MATCH EXISTING ADJACENT

CONSTRUCTION. PROVIDE NEW MATERIALS TO REPLACE

DAMAGED MATERIALS; DO NOT REUSE DAMAGED MATERIALS.

3. REFER TO PLAN: REMOVE AND SALVAGE FOR REUSE EXISTING

CEILING GRID AND WATER RESISTANT TILE AS NECESSARY TO

ACCESS WORK. REINSTALL GRID AND TILE TO MATCH EXISTING

ADJACENT CONSTRUCTION. PROVIDE NEW MATERIALS TO

REPLACE DAMAGED MATERIALS; DO NOT REUSE DAMAGED

MATERIALS.

4. IN ALL INSTANCES OF DEMOLITION, PREPARE EXISTING

CONSTRUCTION TO REMAIN TO RECEIVE NEW WORK AS

INDICATED.

5. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE

EXTENT OF DEMOLITION NECESSARY TO ACCESS CONCEALED

WORK. IN ALL INSTANCES, DEMOLITION MUST BE HELD TO THE

MINIMUM EXTENT NECESSARY.

6. IN ALL INSTANCES OF REPAIR/RESTORATION NEW WORK/INFILL

MUST MATCH EXISTING ADJACENT CONSTRUCTION.

7. IN ALL INSTANCES OF REPAIR/RESTORATION PROVIDE NEW

MATERIALS TO REPLACE DAMAGED MATERIALS; DO NOT REUSE

DAMAGED MATERIALS.

8. ARCHITECTURAL KEYNOTES ON PLAN REPRESENT WHICH SIDES

OF THE WALL WILL NEED TO BE OPENED FOR THE INSTALLATION

OF NEW PIPE WORK. REFER TO ARCHITECTURAL NOTE # ON

WHAT FINISH WILL NEED TO BE REPLACED. VERIFY WITH

EXISTING ADJACENT CONDITIONS TO MATCH ACCORDINGLY.

WALL IS COMPOSED OF METAL STUDS.

9. DO NOT DEMOLISH / REMOVE ANY EXISTING WALL TILE UNLESS

STATED BY THE ARCHITECTURAL KEYNOTE ON PLAN.

ARCHITECTURAL NOTE#

LOCKER

UP

UP

PLATFORM

DN

TRASH

COMP

TC-1

OVERHEAD DOOR

OVERHEAD DOOR

TOILET

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDORCORRIDOR

HAC

N065

TOILET

N063

MECH

N060

MECH

N056A

FMS STOR

N056

SIG

N058

ELEC EQUIP RM

N054

CLEAN

LINEN

N052

SOILED

LINEN

COLLECT

N050EMPLOYEE FITNESS

N027A

MENS TOILET

N011

EMS

OFFICE

N061

EMS

OFFICE

N059

EXERCISE RM

N055

MEDITATION RM

N051

DOM CHAPLAINS

OFFICE

N049

LOCKER

FEMALE

TOILET

N047

HAC

N045

RECEIVING

N046

TRASH

RM

N054B

TRASH

CHUTE

C3

SVC

ELEVATOR

S1

COLD STORAGE

N046A

STAIR

NO-3

MENTAL HEALTH

MEETING RM

N044

MENTAL HEALTH

OFFICE

N044A

TUB

RTPD MED

DIRECTOR OFFICE

N042

OFFICE

N040

BAL

OFFICE

N038

TOILET

OFFICE

N036

SOCIAL WORKER OFFICE

N034

TOILET

PRTP / PRRC

SOCIAL WORKER

NO32

OFFICE

N030

OFFICE

N028

PRTP NURSE PRACTITIONER

N026

TOILETBALTOILET

OFFICE

N024

OFFICE

N022

TOILET

OFFICE

N020

OFFICE

N018

PRTP

CLERK ELEC

STAIR

N0-4

TOILET

UTIL

LAUNDRY

N012

CLOTHING RM

N010

RECREATION STORAGE /

SEWING RM

N008

N016

W

W

W

W

W

W

W

W

W

W

W

W

W

W

D

D

D

D

D

D

LAUNDRY

N012

D D D D D D D 1-1/4"

1-1/2"

1-1/2" 1-1/2" 1-1/2"

1-1/2"

CW

HW

CW

HW HW

CW

HW

HW

CW

CW

HW

CW

CW HW

HW

CW

CW

HW

CW

HW

HW

CW

1/2"

1-1/2"

1/2"

P-415

3"

1/2"

1-1/4"

P-415

P-103

1-1/2"

3"

P-103 P-103P-415 P-415

1-1/2" 1/2" 1-1/2"

1 1/4"

1"

3"

P-103P-415

P-103 P-103P-415 P-415

1-1/2"

3"

1"

P-302

P-415

P-103

1-1/4" HW

P-801 P-801

1-1/2"

P-502

P-103

P-414

P-801

P-604

CW

HW

CW

HW HW

CW

HW

HW

CW

CW

HW

CW

CW HW

HW

CW

CW

HW

CW

HW

2"

HW

CW

1/2"

1-1/4"

1"

3"

1/2"

P-521

3"

1/2"

P-418

P-103

1/2"

1-1/4" HW

1 1/4"

3"

P-103 P-103P-418 P-418

1/2" 1/2"

1-1/4" HW

3"

3"

1-1/4" HW

3"

1-1/4" HW

P-103P-418

1/2" 1-1/4" CW

P-103 P-103P-418 P-418

1/2"1-1/4" CW 1/2"

1-1/4"

3"

1-1/4"

3"

1-1/4 HW"

1-1/4"

3" P-302

P-418

P-103

3" CW

3/4"

P-801 P-801

3/4"

1-1/2" CW

P-502

P-103

P-418

P-801

3/4"

1-1/4" CW

P-802

3/4" HW

1"

1"

P-604

2"

1/2"

P-801 P-810

P-604

P-604

1/2"

P-604

3" C

W 1"

H W

3" C

W

2" 140 HW

2" HWC

4" HW

1" 140 HW

2" 140 HW

2" HWC

4" HW

1" 140 HW

2" 140 HW

3" C

W 1"

H W

3" C

W

2" HWC

4" HW

6" CW

1" 140 HW

2" 140 HW

2" 140 HW

4" HW

(E) 6" CW

1" 140 HWC

2" 140 HW

2" HWC

4" HW

1" 140 HWC

2" 140 HW

2" HWC

4" HW

1" 140 HWC

2" 140 HW

3" C

W 1"

H W

3" C

W

2" HWC

4" HW

(E) 6" CW

1" 140 HWC

2" 140 HW

2" HWC

4" HW

(E) 6" CW

1" 140 HWC

2" 140 HW

4"

HW

6"

CW2"

HW

2"

HWC

1"

HWC

1" CW

WATER PIPES IN BOX AREA ARE

ABOVE LARGE DUCTWORK.

EXISTING DUCTWORK SHALL BE

REMOVED AND REINSTALLED.

1" EXISTING

TO REMAIN

1-1/2" CW

P-804

3/4" CW

EXISTING TO

REMAIN

3/4" WATER SYSTEM

DRAINAGE LINES WITH

3/4" HOSE CONNECTION

1-1/4" CW 1/2" HW

3/4" HW &

1/2" HW

CONNECT TO

EXISTING 1" CW

CONNECT TO

EXISTING 1" CW

EXISTING VALVE

AND PIPE TO

REMAIN.

3/4" CW

3" CW

1-1/4" HW

EXISTING 2" 140 HW TO REMAIN

EXISTING 6" CW PIPE TO REMAIN

P-502

3/4" HW & CW

1-1/4" HW & CW

1-1/4" HW & CW

P-808

TYPICAL

OF 14

ALL COLD WATER PIPES TO

BE REPLACED IN

MECHANICAL ROOM AND

CONNECT BACK INTO

EXISTING.

1" H

W 3"

C W

CWCW

(E) 6" CW

(E) 6" CW

o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

Raymond-Pond 8A II JV, LLC 1035 Green Street Suite A | Conyers, Georgia 30012

Office: (919) 872-7866

CONSULTANTS:

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

SDVOSB

CVE

FINAL CONSTRUCTION DRAWINGS FOR BID

Department of Veterans Affairs

Office of Construction and Facilities Management

AE REPLACE BLDG 160

DOMESTIC WATER PIPING

CONTR. No. #36C24919D0021

MOUNTAIN HOME, TN

621-22-113

2023-05-04

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

KEY PLAN

N

SCALE:

SUB-BASEMENT EAST DOMESTIC FLOOR PLAN-DEMO

1/8" = 1'-0" PD101B

F1

F1

PD401

GENERAL NOTES:

1. REPLACE FROM VALVE IN CORRIDOR UP IN CHASE. THE 6"

COLD-WATER AQUATHERM TO REMAIN.

2. THE EXTENT OF PLUMBING FIXTURE DEMO WORK SHALL BE

COORDINATED WITH THE PLUMBING FIXTURE SCHEDULE AND

DEDUCT ALTERNATES TAKEN.

3. ALL WATER PIPING IS GENERALLY SHOWN ABOVE CEILING AND/OR

WITHIN WALLS, UNLESS OTHERWISE NOTED.

4. REFER TO PLUMBING FIXTURE SCHEDULE FOR FIXTURE

CONNECTION SIZES.

5. COORDINATE ALL WORK WITH OTHER TRADES.

6. ALL CHAIR CARRIERS TO REMAIN AND INSTALL NEW FASTENERS TO

ANCHOR NEW PLUMBING FIXTURES.

1. UNDER BASE BID FIXTURE P-801 IS TO BE REPLACED.

2. UNDER BASE BID THE TUB P-302 IS TO REMAIN AND ONLY FAUCET

AND SHOWER HEAD TO BE REPLACED.

3. UNDER BASE BID FIXTURE P-502 AND P-701 ARE TO REMAIN AND ONLY

THE FAUCET IS TO BE REPLACED.

4. LOCKER ROOM WAS RECENTLY RENOVATED WITH HARD CEILINGS.

PIPE IN CHASE WALLS AND ALL FIXTURES TO REMAIN. REMOVE PIPE

TO CHASE OR TO WALL DROPS.

5. UNDER BASE BID THE FIXTURE P-802 AND P-810 ARE TO BE

REPLACED.

6. REMOVE BOTTLE FILLER, TRIM AND PIPING. SEE PHOTO #2624

7. REMOVE P-604, TRIM, AND ASSOCIATED PIPING. SEE PHOTO #2627.

8. REMOVE P-604, TRIM, AND ASSOCIATED PIPING. SEE PHOTO #2628.

9. REMOVE LAUNDRY TUB P-521, TRIM, AND ASSOCIATED PIPING. SEE

PHOTO #2638.

10. EXISTING BFP FOR FAST FILL OF CHILLED WATER PIPES TO BE

REMOVED. SEE PHOTO #2657 AND #2665.

11. EXISTING BFP AND PRV TO BE REMOVED FOR HOT WATER SYSTEM

MAKE UP WATER. SEE PHOTO #2659.

12. DISCONNECT AND RELOCATE WASHERS BEFORE BEGINNING WORK.

REINSTALL EXISTING WASHER ONCE PIPING WORK IS COMPLETE.

REMOVE P-808 AT EACH WASHING MACHINE AND PIPE IN HORIZONTAL

CHASE BETWEEN WASHING MACHINES. SEE PHOTO #2871 FOR

ADDITIONAL INFORMATION.

13. SHAMPOO SINK AND FAUCET TO REMAIN. SEE PHOTO #2873 .

14. EXISTING 2" 140 HW PIPE RECENTLY REPLACED TO VALVE IN

CORRIDOR TO REMAIN.

# KEYED NOTE

FO

R

CO

NT

IN

UA

TI

ON

S

EE

P D1

A

#2624

#2627

#2628

#2638

#2657

#2665

#2659

1. REFER TO PLAN: REMOVE EXISTING GYPSUM WALL BOARD /

WALLCOVERING AND ASSOCIATE CONSTRUCTION AS NECESSARY

TO ACCESS AND COMPLETE INDICATED WORK. INFILL OPENING

TO MATCH EXISTING ADJACENT CONSTRUCTION AND FINISHES.

DO NOT DISTURB EXISTING FINISHES ON UNDISTURBED SIDE OF

PARTITION. DO NOT TOUCH WALL TILE, ACCESS WORK ON

GYPSUM SIDE ONLY.

2. REFER TO PLAN: REMOVE AND SALVAGE FOR REUSE EXISTING

CEILING GRID AND TILE AS NECESSARY TO ACCESS WORK.

REINSTALL GRID AND TILE TO MATCH EXISTING ADJACENT

CONSTRUCTION. PROVIDE NEW MATERIALS TO REPLACE

DAMAGED MATERIALS; DO NOT REUSE DAMAGED MATERIALS.

3. REFER TO PLAN: REPLACE EXISTING WALL TILE AND ASSOCIATED

CONSTRUCTION TO MATCH EXISTING ADJACENT CONSTRUCTION.

4. REFER TO PLAN: REMOVE AND SALVAGE FOR REUSE EXISTING

CEILING GRID AND WATER RESISTANT TILE AS NECESSARY TO

ACCESS WORK. REINSTALL GRID AND TILE TO MATCH EXISTING

ADJACENT CONSTRUCTION. PROVIDE NEW MATERIALS TO

REPLACE DAMAGED MATERIALS; DO NOT REUSE DAMAGED

MATERIALS.

5. REFER TO PLAN: REMOVE EXISTING GYPSUM WALL BOARD AND

ASSOCIATE CONSTRUCTION AS NECESSARY TO ACCESS AND

COMPLETE INDICATED WORK. INFILL OPENING TO MATCH

EXISTING ADJACENT CONSTRUCTION AND FINISHES.

6. IN ALL INSTANCES OF DEMOLITION, PREPARE EXISTING

CONSTRUCTION TO REMAIN TO RECEIVE NEW WORK AS

INDICATED.

7. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE

EXTENT OF DEMOLITION NECESSARY TO ACCESS CONCEALED

WORK. IN ALL INSTANCES, DEMOLITION MUST BE HELD TO THE

MINIMUM EXTENT NECESSARY.

8. IN ALL INSTANCES OF REPAIR/RESTORATION NEW WORK/INFILL

MUST MATCH EXISTING ADJACENT CONSTRUCTION.

9. IN ALL INSTANCES OF REPAIR/RESTORATION PROVIDE NEW

MATERIALS TO REPLACE DAMAGED MATERIALS; DO NOT REUSE

DAMAGED MATERIALS.

10. ARCHITECTURAL KEYNOTES ON PLAN REPRESENT WHICH SIDES

OF THE WALL WILL NEED TO BE OPENED FOR THE INSTALLATION

OF NEW PIPE WORK. REFER TO ARCHITECTURAL NOTE # ON

WHAT FINISH WILL NEED TO BE REPLACED. VERIFY WITH

EXISTING ADJACENT CONDITIONS TO MATCH ACCORDINGLY.

WALL IS COMPOSED OF METAL STUDS.

11. DO NOT DEMOLISH / REMOVE ANY EXISTING WALL TILE UNLESS

STATED BY THE ARCHITECTURAL KEYNOTE ON PLAN.

ARCHITECTURAL NOTE#

#2871

#2873

DN

DN

OFFICE

P072

CORRIDOR

CORRIDOR

CORRIDOR

TOILET

CORRIDORCORRIDOR

WAITING AREA

WAITING AREA

CORRIDOR

SIG

P071

CORRIDOR

CORRIDOR

TV

LOUNGE

P007

ARTS AND

CRAFT

STORAGE

P009

SLEEP RM

P011

TOILET

SLEEP RM

P013

SLEEP RM

P015

SLEEP RM

P017

TOILET

ELEC

P014

STAIR

NO-5

CUBICLE

P002Y

P002Z

TOILET

P080

HAC

P082

CONSOLIDATED

LIBRARY

P026

CONG

BATH

P010

TOILET

TV

LOUNGE

P078

STOR

P026A

TUB

P076

MED LIBRARIAN

OFFICE

P074

MULTI-

PURPOSE

RM/KIT

P070

P068

TUB

TOILET

TUB

CONG

BATH

P064

PSYCHOLOGY SVC

P073

GROUP RM

P069

CLEAN

LINEN

P062

ELEC

P056

STORAGE

P067

HAC

P063

GROUP RM

P065

SLEEP RM

P019

SLEEP RM

P021

TOILET

TOILET

SLEEP RM

P023

BAL

SLEEP RM

P025

TOILET

SLEEP RM

P027SLEEP RM

P029

SLEEP RM

P031

TOILET

SLEEP RM

P033

SLEEP RM

P035

BAL

SLEEP RM

P037SLEEP RM

P039

TOILET

SLEEP RM

P041

TOILET

SLEEP RM

P043ASLEEP RM

P043

STAIR

NO-6

TOILET

MECH

P075

SLEEP RM

P061

SLEEP RM

P059

SLEEP RM

P057

SLEEP RM

P055

TOILET

SLEEP RM

P053

BAL

TOILET

SLEEP RM

P051

TOILET

SLEEP RM

P049

SLEEP RM

P047

DOM ASST

P045

BATH

1-1/4" HW

P-418

1-1/2"

1-1/2"1-1/2"

CW

CW

HWHW

CW

HW

CW

HW

CW

CWHW

HW

CW

CW

HW

1-1/2"

1"

3"

1"3"

1/2"

P-415

P-103

1"

3" P-418

P-103

1/2"

P-418

P-103

1/2"

3"

1"

1"

1"

P-103P-103 P-418P-418

1/2"1/2"

1"

3"

1"

3"

1"

3"

1"

P-415

1/2"1-1/4" CW

P-103P-103 P-418P-418

1/2" 1-1/4" CW1/2"

1-1/4"

3"

1"

1-1/4"

3"P-302 P-418

P-103 1-1/4"

3"

1 1/4"P-302 P-801

3/4"

1/2"

P-103

P-502

P-418

P-103

P-701

1-1/2" CW

1/2"

P-604

1-1/4" CW

P-302 P-701

P-502

P-103

P-103P-103

P-418

1-1/2"

CW

CW

HW

HW

CW

CW

CW

CW

CW

CW

CW

HW

HW

HW

HW

HW

HW

3"

1-1/4" CW

3/4" 3"

1 1/4"

1-1/4" CW

1/2"

1-1/4" CW

1/2" 3"

1 1/4"

1-1/2"

1/2"

1 1/4"

3"

1 1/4"

3"

1-1/4" CW

1/2"

1 1/4"

3"

3"

1 1/2"

1-1/2" CW

3/4" HW

1" CW

P-418

P-418

P-302

CW

HW

P-801

3/4"

P-103

P-103

P-418

P-418

P-103

P-801 3/4"

1 P-418

CW

HW

CW

HW

CW

HW

P-103

P-418

P-302

P-418

P-302

3/4" WATER SYSTEM

DRAINAGE SYSTEM W/

HOSE END CONNECTIONS

2 2

44 2

P-804

3" CW

1" HWC

1-1/2" HW

3" CW

1" H

W 3"

C W

1" H

W 3"

C W

1" H

W 3"

C W

1"

HWC

1 1 /2"

HW3"

CW

1" H

W 3"

C W

1" H

W 3"

C W

1" H

W 3"

C W

2" HW

HW

1-1/4" CW

WATER PIPES IN BOX AREA ARE

ABOVE LARGE DUCTWORK.

EXISTING DUCTWORK SHALL BE

REMOVED AND REINSTALLED.

CONNECT TO

EXISTING PIPE UP

THIS IS A

SECURED

LOCATION.

COORDINATE

WITH COR

ACCESS TO

ROOM

1/2"HW

1-1/4" CW

1/2" HW

CONNECT TO

EXISTING

1/2" HW & CW

3/4" DN

TO P-804 1" CW

1" CW

1/2" HW

1-1/4" CW

1/2" HW

3/4" HW & CW

1-1/4" CW

1-1/4" CW

P-418

P-103

3/4" CW

3/4" HW

P-103

P-103 o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

Raymond-Pond 8A II JV, LLC 1035 Green Street Suite A | Conyers, Georgia 30012

Office: (919) 872-7866

CONSULTANTS:

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

SDVOSB

CVE

FINAL CONSTRUCTION DRAWINGS FOR BID

Department of Veterans Affairs

Office of Construction and Facilities Management

AE REPLACE BLDG 160

DOMESTIC WATER PIPING

CONTR. No. #36C24919D0021

MOUNTAIN HOME, TN

621-22-113

2023-05-04

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

KEY PLAN

N

SCALE:

SUB-BASEMENT WEST DOMESTIC FLOOR PLAN-DEMO

1/8" = 1'-0" PD101C

F1

GENERAL NOTES:

1. REPLACE FROM VALVE IN CORRIDOR UP IN CHASE. THE 6"

COLD-WATER AQUATHERM TO REMAIN.

2. THE EXTENT OF PLUMBING FIXTURE DEMO WORK SHALL BE

COORDINATED WITH THE PLUMBING FIXTURE SCHEDULE AND

DEDUCT ALTERNATES TAKEN.

3. ALL WATER PIPING IS GENERALLY SHOWN ABOVE CEILING AND/OR

WITHIN WALLS, UNLESS OTHERWISE NOTED.

4. REFER TO PLUMBING FIXTURE SCHEDULE FOR FIXTURE

CONNECTION SIZES.

5. COORDINATE ALL WORK WITH OTHER TRADES.

6. ALL CHAIR CARRIERS TO REMAIN AND INSTALL NEW FASTENERS TO

ANCHOR NEW PLUMBING FIXTURES.

1. UNDER BASE BID FIXTURE P-801 IS TO BE REPLACED.

2. UNDER BASE BID THE TUB P-302 OR P-310 IS TO REMAIN AND

ONLY FAUCET AND SHOWER HEAD TO BE REPLACED.

3. UNDER BASE BID FIXTURE P-502 IS TO REMAIN AND ONLY THE

FAUCET IS TO BE REPLACED.

4. UNDER BASE BID FIXTURE P-701 IS TO REMAIN AND ONLY THE

SHOWER VALVE AND SHOWER HEAD TO BE REPLACED.

5. BREAK ROOM DROP IN SS SINK TO BE REMOVED AND REPLACED.

SEE PHOTO #93614 FOR ADDITIONAL INFORMATION.

6. LAB SINK TO REMAIN. REPLACE FAUCET, SUPPLIES, STOP

VALVES, AND ALL WATER PIPE TO SINK. SEE PHOTO # 2869.

7. REMOVE LAVATORY P-403 WITH FOOT CONTROLS. SEE PHOTO #

2861 FOR ADDITIONAL INFORMATION.

8. REMOVE SHOWER VALVE, HEAD, HAND HELD SHOWER, AND ALL

TRIM. SEE PHOTO # 2859 FOR EXISTING CONDITIONS.

9. REMOVE FIXTURES AND TRIM AS NOTED. SEE PHOTO #2862 FOR

EXISTING CONDITIONS.

10. REMOVE EXISTING CW INTO ROOM WITH P-804 AT FLOOR. SEE

PHOTO #2868 FOR EXISTING CONDITIONS.

11. REMOVE EXISTING BFP, AND PRV WITH BY-PASS AND PIPING. SEE

PHOTO #2863 FOR EXISTING CONDITIONS.

# KEYED NOTE

FO

R

CO

NT

IN

UA

TI

ON

S

EE

P D1

A

1. REFER TO PLAN: REMOVE EXISTING GYPSUM WALL BOARD /

WALLCOVERING AND ASSOCIATE CONSTRUCTION AS NECESSARY

TO ACCESS AND COMPLETE INDICATED WORK. INFILL OPENING TO

MATCH EXISTING ADJACENT CONSTRUCTION AND FINISHES. DO NOT

DISTURB EXISTING FINISHES ON UNDISTURBED SIDE OF PARTITION.

2. REFER TO PLAN: REMOVE AND SALVAGE FOR REUSE EXISTING

CEILING GRID AND TILE AS NECESSARY TO ACCESS WORK.

REINSTALL GRID AND TILE TO MATCH EXISTING ADJACENT

CONSTRUCTION. PROVIDE NEW MATERIALS TO REPLACE DAMAGED

MATERIALS; DO NOT REUSE DAMAGED MATERIALS.

3. REFER TO PLAN: REPLACE EXISTING WALL TILE AND ASSOCIATED

CONSTRUCTION TO MATCH EXISTING ADJACENT CONSTRUCTION.

4. REFER TO PLAN: REMOVE AND SALVAGE FOR REUSE EXISTING

CEILING GRID AND WATER RESISTANT TILE AS NECESSARY TO

ACCESS WORK. REINSTALL GRID AND TILE TO MATCH EXISTING

ADJACENT CONSTRUCTION. PROVIDE NEW MATERIALS TO REPLACE

DAMAGED MATERIALS; DO NOT REUSE DAMAGED MATERIALS.

5. IN ALL INSTANCES OF DEMOLITION, PREPARE EXISTING

CONSTRUCTION TO REMAIN TO RECEIVE NEW WORK AS INDICATED.

6. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE EXTENT

OF DEMOLITION NECESSARY TO ACCESS CONCEALED WORK. IN ALL

INSTANCES, DEMOLITION MUST BE HELD TO THE MINIMUM EXTENT

NECESSARY.

7. IN ALL INSTANCES OF REPAIR/RESTORATION NEW WORK/INFILL

MUST MATCH EXISTING ADJACENT CONSTRUCTION.

8. IN ALL INSTANCES OF REPAIR/RESTORATION PROVIDE NEW

MATERIALS TO REPLACE DAMAGED MATERIALS; DO NOT REUSE

DAMAGED MATERIALS.

9. ARCHITECTURAL KEYNOTES ON PLAN REPRESENT WHICH SIDES OF

THE WALL WILL NEED TO BE OPENED FOR THE INSTALLATION OF

NEW PIPE WORK. REFER TO ARCHITECTURAL NOTE # ON WHAT

FINISH WILL NEED TO BE REPLACED. VERIFY WITH EXISTING

ADJACENT CONDITIONS TO MATCH ACCORDINGLY. WALL IS

COMPOSED OF METAL STUDS.

10. DO NOT DEMOLISH / REMOVE ANY EXISTING WALL TILE UNLESS

STATED BY THE ARCHITECTURAL KEYNOTE ON PLAN.

ARCHITECTURAL NOTE#

#93614

#2869

#2861

#2859

#2862

#2868

#2863

UP

DN

CHASE

CORRIDOR

HAC/

SAN

SUPPLY

N100C

NFS

STORAGE

N178

TOILET

N176STO

P177

STAFF

ELEVATOR

LOBBY

EL101

NFS SECERATARY

OFFICE

N182

MALE

TOILET

N180

STAIR

NO-2

DIET

OFFICE

P181FEMALE

TOILET

P179

STAIR

NO-1

PRODUCTION MGR

OFFICE

N100G

REFR

N100D

REFRIG

N100F

PGM SUPPORT

CLERK OFFICE

N100E

ELEVATOR

P2

ELEVATOR

P1

ELEC

N102

ELEVATOR

P4

ELEVATOR

P3

FOOD SVC

SUPV

N100L

FOOD SVC

SUPV

N100K

DIET CHANCE

OFFICE

N100B

OFFICE

N100A

N100L

INGREDIENT CONTROL

OFFICE

N100U

MENTAL HEALTH CLINIC

PSYCHIATRIST OFFICE

TOILET

P175

1-1/2"

2"

3/4"

2" P-103

P-103

P-103

P-604

P-417 P-417 P-103

P-604

P-103 P-201 P-202

1/2"

1"

2"

1"

1/2"

1"

1" HWC 1" HWC

1-1/2" HW

3" CW

2" HWC DN & 1-1/2" HWC UP

3" HW DN & 3" HW UP

6" CW DN & 6" CW UP TO REMAIN

1" 140 HWC DN

2" 140 HW DN

1-1/2" HW

3" CW

1-1/2" HW

3" CW

1" HWC

1-1/2" HW

3" CW

1" HWC

3 3

2" HWC DN & 1-1/2" HWC UP REMOVE

3" HW DN & 3" HW UP REMOVE

6" CW DN & 6" CW UP TO REMAIN

1" 140 HWC UP REMOVE

2" 140 HW UP REMOVE

P-414P-414 o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

Raymond-Pond 8A II JV, LLC 1035 Green Street Suite A | Conyers, Georgia 30012

Office: (919) 872-7866

CONSULTANTS:

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

SDVOSB

CVE

FINAL CONSTRUCTION DRAWINGS FOR BID

Department of Veterans Affairs

Office of Construction and Facilities Management

AE REPLACE BLDG 160

DOMESTIC WATER PIPING

CONTR. No. #36C24919D0021

MOUNTAIN HOME, TN

621-22-113

2023-05-04

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

KEY PLAN

N

SCALE:

DOMESTIC FLOOR PLAN-DEMO

1/8" = 1'-0" PD111A

F1

GENERAL NOTES:

1. THE EXTENT OF PLUMBING FIXTURE DEMO WORK SHALL BE

COORDINATED WITH THE PLUMBING FIXTURE SCHEDULE AND

DEDUCT ALTERNATES TAKEN.

2. ALL WATER PIPING IS GENERALLY SHOWN ABOVE CEILING AND/OR

WITHIN WALLS, UNLESS OTHERWISE NOTED.

3. REFER TO PLUMBING FIXTURE SCHEDULE FOR FIXTURE

CONNECTION SIZES.

4. COORDINATE ALL WORK WITH OTHER TRADES.

5. ALL CHAIR CARRIERS TO REMAIN AND INSTALL NEW FASTENERS TO

ANCHOR NEW PLUMBING FIXTURES.

1. UNDER BASE BID FIXTURE P-417 IS TO BE REPLACED. FIXTURE IS

A ROUND CHINA DROP IN BOWL. COUNTER TOP IS TO BE

CLEANED. SEE PHOTO #2581 FOR A TYPICAL ARRANGEMENT

# KEYED NOTE

#2581

1. REFER TO PLAN: REMOVE EXISTING GYPSUM WALL BOARD /

WALLCOVERING AND ASSOCIATE CONSTRUCTION AS NECESSARY

TO ACCESS AND COMPLETE INDICATED WORK. INFILL OPENING

TO MATCH EXISTING ADJACENT CONSTRUCTION AND FINISHES.

DO NOT DISTURB EXISTING FINISHES ON UNDISTURBED SIDE OF

PARTITION.

2. REFER TO PLAN: REMOVE AND SALVAGE FOR REUSE EXISTING

CEILING GRID AND TILE AS NECESSARY TO ACCESS WORK.

REINSTALL GRID AND TILE TO MATCH EXISTING ADJACENT

CONSTRUCTION. PROVIDE NEW MATERIALS TO REPLACE

DAMAGED MATERIALS; DO NOT REUSE DAMAGED MATERIALS.

3. REFER TO PLAN: REMOVE AND SALVAGE FOR REUSE EXISTING

CEILING GRID AND WATER RESISTANT TILE AS NECESSARY TO

ACCESS WORK. REINSTALL GRID AND TILE TO MATCH EXISTING

ADJACENT CONSTRUCTION. PROVIDE NEW MATERIALS TO

REPLACE DAMAGED MATERIALS; DO NOT REUSE DAMAGED

MATERIALS.

4. IN ALL INSTANCES OF DEMOLITION, PREPARE EXISTING

CONSTRUCTION TO REMAIN TO RECEIVE NEW WORK AS

INDICATED.

5. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE

EXTENT OF DEMOLITION NECESSARY TO ACCESS CONCEALED

WORK. IN ALL INSTANCES, DEMOLITION MUST BE HELD TO THE

MINIMUM EXTENT NECESSARY.

6. IN ALL INSTANCES OF REPAIR/RESTORATION NEW WORK/INFILL

MUST MATCH EXISTING ADJACENT CONSTRUCTION.

7. IN ALL INSTANCES OF REPAIR/RESTORATION PROVIDE NEW

MATERIALS TO REPLACE DAMAGED MATERIALS; DO NOT REUSE

DAMAGED MATERIALS.

8. ARCHITECTURAL KEYNOTES ON PLAN REPRESENT WHICH SIDES

OF THE WALL WILL NEED TO BE OPENED FOR THE INSTALLATION

OF NEW PIPE WORK. REFER TO ARCHITECTURAL NOTE # ON

WHAT FINISH WILL NEED TO BE REPLACED. VERIFY WITH

EXISTING ADJACENT CONDITIONS TO MATCH ACCORDINGLY.

WALL IS COMPOSED OF METAL STUDS.

9. DO NOT DEMOLISH / REMOVE ANY EXISTING WALL TILE UNLESS

STATED BY THE ARCHITECTURAL KEYNOTE ON PLAN.

ARCHITECTURAL NOTE#

UP

DN

UNDER CONSTRUCTION

EXAM

N207

CORRIDOR

VEST

L201

CORRIDORCORRIDOR

MED

PREP

N200

STAIR

NO-1

TOILET

P202

FEMALE

TOILET

P200

CHECK-IN

AREA

L202

ELEVATOR

LOBBY

ELEVATOR

P4

ELEVATOR

P3

OUTPATIENT

LAB

PROCESSING

N202

OFFICE

N200A

VENDING

N204

VEND

N204

LAB

TOILET

BUSINESS OFFICE

DOM ADMISSIONS

N202

P204A

MALE

TOILET

N201

STAIR

NO-3

WHEEL CHAIR STORAGE

N205

TOILET

N203

LPN

P244K

OFFICE

P244J

STAFF

LOUNGE

P265

CONFERENCE

P263

OFFICE

P201

ELEVATOR

P1

ELEVATOR

P2

P204

1-1/2" CW

2"

3/4"

2" P-103

P-414

P-103

P-103

P-604

P-417 P-417

P-103

P-604

P-103

P-414

P-201 P-202

P-801P-801

P-415 2"

2"

3/4"

1/2"

3/4"

1" 1/2"

3/4"

1"

1" HWC 1" HWC

1-1/2" HW

3" CW

1-1/2" HWC DN & 1-1/2" HWC UP REMOVE

3" HW DN & 2-1/2" HW UP REMOVE

6" CW DN TO REMAIN & 4" CW UP TO BE REMOVED

3/4" 140 HWC DN REMOVE

1-1/4" 140 HW REMOVED

1-1/2" HW

3" CW

1" HWC

1-1/2" HW

3" CW

1" HWC

1-1/2" HW

3" CW

HW

C

HW

C

CW

CW

HW

HW

3/4" 140 HW

1-1/4" 140 HWC

o n e e ig h th in ch o n e f o o t

B

A

C

D

E

F th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

Raymond-Pond 8A II JV, LLC 1035 Green Street Suite A | Conyers, Georgia 30012

Office: (919) 872-7866

CONSULTANTS:

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

SDVOSB

CVE

FINAL CONSTRUCTION DRAWINGS FOR BID

Department of Veterans Affairs

Office of Construction and Facilities Management

AE REPLACE BLDG 160

DOMESTIC WATER PIPING

CONTR. No. #36C24919D0021

MOUNTAIN HOME, TN

621-22-113

2023-05-04

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

KEY PLAN

N

SCALE:

DOMESTIC FLOOR PLAN-DEMO

1/8" = 1'-0" PD121A

F1

GENERAL NOTES:

1. THE EXTENT OF PLUMBING FIXTURE DEMO WORK SHALL BE

COORDINATED WITH THE PLUMBING FIXTURE SCHEDULE AND

DEDUCT ALTERNATES TAKEN.

2. ALL WATER PIPING IS GENERALLY SHOWN ABOVE CEILING AND/OR

WITHIN WALLS, UNLESS OTHERWISE NOTED.

3. REFER TO PLUMBING FIXTURE SCHEDULE FOR FIXTURE

CONNECTION SIZES.

4. COORDINATE ALL WORK WITH OTHER TRADES.

5. ALL CHAIR CARRIERS TO REMAIN AND INSTALL NEW FASTENERS TO

ANCHOR NEW PLUMBING FIXTURES.

1. UNDER BASE BID FIXTURE P-801 IS TO BE…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .