SCHEDULES DETAILS AND SINGLE LINE DIAGRAM.pdf

PDF 679 KB Posted

Attached to
J061--Tri-annual switch gear maintenance Federal contract opportunity
Solicitation number
36C24922Q0662
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9

View the file

Other files for this federal contract opportunity

Other files attached to J061--Tri-annual switch gear maintenance, newest first.
File Type Posted
Electrical One Line.pdf PDF
PARTIAL MEDIUM VOLTAGE SINGLE LINE DIAGRAM.pdf PDF
36C24922Q0662 0001.docx DOCX document
36C24922Q0662.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LINK SEAL

CONDUIT PIPE

WALL SLEEVE

WALL

EXISTING PANEL

EMS-480V

480/277V

EXISTING

SWITCHGEAR

SB-1 480V

E N

200A

200A

260A ATS-9

4P 4W

EF-43 AH-43 S

4#3/0 AWG, #6 GROUND, 2"C.

4#3/0 AWG, #6 GROUND, 2"C.

200A MLO 480V

3PH 4W

PANELBOARD

NEMA 1

FEED THRU LUGS

60A NF DISC.

NEW

BREAKERS

CONNECT GENERATOR START

CONTACTS TO WIRES IN ATS-B

2#12 AWG, 12 GROUND, 3/4" C.

EEQC

60A NF DISC.

200A MLO 480V

3PH 4W

PANELBOARD

NEMA 3R

EEQD4#3/0 AWG, #6 GROUND, 2"C.

SPD

400A 225A 225A

G

800A (EXISTING AND REUSED)

PANEL EDP-480V

480/277V

600A

N E

600A ATS-10

4P 4W

600A

EEQE

600KW

480/277V

1200A

ATS-A ATS-CATS-B

(2 SETS) 4#350 KCMIL, #1 GROUND, 3"C.

(2 SETS) 4#350 KCMIL,

#1 GROUND, 3"C.

SUB-BASEMENT

SUB-BASEMENT

SUB-BASEMENT

SUB-BASEMENT

SPS EXTERIOR

GENERATOR ROOM

NEW

CONNECT GENERATOR START

CONTACTS TO WIRES IN ATS-B

2#12 AWG, 12 GROUND, 3/4" C.

600A MLO 480V

3PH 4W

PANELBOARD

NEMA 1

SPD

(3 SETS) 4#600 KCMIL, #3/0 GROUND, 4"C.NEW PANEL

ATL #4

ATL #2

ATL #1

17,605 A

25,258 A

LENGTH AS REQUIRED

CONDUIT CLAMP.

SIZE AS REQUIRED

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

REFER TO PLANS FOR

QUANTITY & SIZE OF

CONDUITS

GENERAL NOTES:

1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL

LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A

CENTER SUPPORT ROD.

2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED

METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES

FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.

LOCKING SQUARE

WASHER & LOCKNUT

9.52mm (3/8") MIN

GALVANIZED THREADED

ROD, TYP.

WASHER &

LOCKNUT

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

4-WAY DUCT LINE2-WAY DUCT LINE

GENERAL NOTES:

1.

2.

3.

4.

5.

CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.

PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS

WHEN CROSSING OR PLACED IN

ROADWAYS.

MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR

AS OTHERWISE SPECIFIED IN SECTION 26 05 41.

PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND

TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.

INNERDUCT QUANTITY AND SIZE AS INDICATED ON

PLANS.

(3")

(3") 76mm

(3 m m (3 m m

76mm

(3") 76mm

(3 m m

(3 m m (3 m m

(3")

(3") 76mm

(3") 76mm76mm

(T

YP

1 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956

STAMPCONSULTANT

321 4 5 6 7 8 9 10

603-20-505

Louisville, KY

UPGRADE 480V

ELECTRICAL SYSTEM

C :\U se rs

\J ac k\ D oc um en ts

\L ou is vi lle

U pg ra de

V El ec S ys te m (2

8)

_j ac k.

bo nb rig ht T4

3D B.

rv t

3/

/2

2:

:1

PM

E500

SCHEDULES, DETAILS AND

SINGLE-LINE DIAGRAM

03/01/21 JB HT

LIGHTING FIXTURE SCHEDULE

IMAGE MARK Description

MOUNTING

LOAD

(VA)

LUMINOUS

FLUX

COLOR

TEMPERATURE CRI

S-SURFACE

R-RECESSED

SM-STEM MTD

WM-WALL MTD

C-CHAIN MTD

UC-UNDER CAB

CS-CEIL SURFACE

W1 SURFACE MOUNTED LED WALL LUMINAIRE WITH SWITCH. WEATHERPROOF HOUSING. 120V.

DARK BRONZE.

S 12 3000 lm 4000 K 70

4 LINK SEAL DETAIL

3 EMERGENCY SINGLE-LINE DIAGRAM

5 CONDUIT TRAPEZE MOUNTING DETAIL

1 DUCT BANK DETAILS2 EXISTING PANEL EDP-480V

Revisions: Date:

SCHEMATIC DESIGN 25% 11/06/20

BID DOCUMENTS 100% 03/12/21

G E N E R A L N O T E S

BASE BID:

PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS

DEDUCT ALTERNATES

ALT #1:

DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL RISER FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED WATER PUMP (PANELBOARD HB).

DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY

FAN & EXHAUST FAN.

ALT #2:

DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR AHU - 17, 23, 43.

ALT #3:

DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).

PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.

ALT #4:

DEDUCT ALL ELECTRICAL WORK FOR AHU - 42 AND DX - 42 (PANELBOARD DP)

K E Y N O T E S

1 TRANSFER SWITCHES SHALL BE ASCO 4000 SERIES 4-POLE 4-WIRE.

NON-OVERLAPPING NEUTRALS. NO BYPASS ISOLATION. WITHSTAND

AND CLOSE RATING 42KA AT 480V. RATING FOR ANY BREAKER. SEE

SPECS FOR FURTHER DETAILS.

2 PROVIDE FEED-THRU LUGS IN PANEL EEQC. FEED WIRE FOR PANEL

EEQD TO BE EXTENDED FROM THESE LUGS.

03/12/2021

Sheets
AE101 - SCREEN WALL DETAILS
E001 - LEGEND
E500 - SCHEDULES, DETAILS AND SINGLE-LINE DIAGRAM
E501 - PARTIAL MEDIUM VOLTAGE SINGLE-LINE DIAGRAM
E600 - PANEL SCHEDULES
EP000 - OVERALL BASEMENT ELECTRICAL PLAN
EP0000 - OVERALL SUB-BASEMENT PLAN
EP0001 - SUB-BASEMENT ELECTRICAL PLAN
EP001A - BASEMENT ELECTRICAL PLAN-A
EP001B - BASEMENT ELECTRICAL PLAN-B
EP100 - OVERALL FIRST FLOOR PLAN
EP101 - FIRST FLOOR ELECTRICAL PLAN
EP200 - OVERALL SECOND FLOOR PLAN
EP201 - SECOND FLOOR ELECTRICAL PLAN
EP300 - OVERALL THIRD FLOOR PLAN
EP400 - OVERALL FOURTH FLOOR PLAN
EP500 - OVERALL FIFTH FLOOR PLAN
EP600 - OVERALL SIXTH FLOOR PLAN
EP700 - OVERALL SEVENTH FLOOR PLAN
EP800 - OVERALL EIGHT FLOOR PLAN
EP900 - OVERALL NINTH FLOOR PLAN
ES100 - ELECTRICAL SITE PLAN
GI000 - COVER SHEET AND SHEET INDEX