S05 - A0004 - Questions and Answers.pdf

PDF 189 KB Posted

Attached to
Project: 603-20-202 - Restore AHU-10 System OR's 5-7 - VA Louisville, Kentucky
Solicitation number
36C24922B0001
Issued by

About this file

This document contains questions and answers regarding project number 603-20-202 to restore AHU-10 systems in operating rooms 5-7 at the Robley Rex Veterans Affairs Medical Center in Louisville, Kentucky. The project involves completely preparing the site for building operations, including demolishing and removing existing structures, and furnishing all labor, materials, and work to restore the AHU-10 system as required by the drawings and specifications. One question clarified that the fan array has three fans, with two stacked vertically and therefore only visible on one drawing. No other substantive details are provided in the questions and answers document.

The related federal contract opportunity notice involves solicitation number 36C24922B0001 for the project to restore the AHU-10 system at the Louisville VAMC. The opportunity type is listed as pre-solicitation. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9 is the contracting agency.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Restore AHU-10 Systems (OR’s 5-7)

Project Number 603-20-202 Requests for Information (RFI’s)

RESTORE AHU-10 SYSTEMS (OR’s 5-7)

ROBLEY REX VETERANS AFFAIRS MEDICAL CENTER (VAMC)

LOUISVILLE, KY

PROJECT NUMBER: 603-20-202

REQUEST FOR INFORMATION (RFI’s)

December 7, 2021

QUESTIONS AND ANSWERS (RFIs)

1. RFI 1 Question: Drawing M601 Fan Schedule, shows quantity of (3) Fans and Drawing M105 AHU Drawing shows quantity of (2) Fans. We don’t believe (3) Fans are available for this configuration. Please confirm.

a. RFI 1 Answer. The fan array has 3 fans. Two of the fans are stacked vertically, so only two are visible from the plan view, which is why only two are showing on sheet M105.

GENERAL

The following changes, additions, or deletions shall be made to the following documents as indicated, and all other conditions shall remain the same:

Restore AHU-10 Systems (OR’s 5-7)

Project Number 603-20-202 Requests for Information (RFI’s)

1. SPECIFICATIONS

a. N/A

2. DRAWINGS

a. GENERAL:

i. NA

b. ARCHITECTURAL

i. N/A

c. MECHANICAL

d. ELECTRICAL:

File details come from the government source that posted it. Updated .