Troy Bowling Campus
1. Deficiency note “F simply says UNSEALED. Are these areas to be resealed?
Response: Deficiency Legend Note “L” has been revised to require sealing existing conduit/pipe penetrations of brick.
2. Deficiency note “D” says reset brick. Does this mean that all the brink in this area is to be removed and reinstalled?
Response: Quantity of unit of measure as indicated at Deficiency Legend symbol. Remove existing brick, clean and re-install.
3. Deficiency Legend. Note E repoint. Unit of measure identified is a count or each. Tuck-pointing is usually quantified in SF or LF. Please clarify.
Response: In this instance the unit of measure is “per brick”.
4. Drawing AS102A. Mech-A Elevation 2. Note reads “Rebuild Brick Full Width”. The limits of the note are vague . Is this 1 row tall across the face or a larger area?
Response: Demo and rebuild all brick below louver, full width of the elevation. Rework/replace roof to wall flashing.
5. Drawing AS102A. Mech-B Elevation 3. Notes call for rebuild above and below and rebuild below louver. How far above and below needs to be reconstructed at this louver?
Response: quantities/scope of Work this area indicated by units of measure at Deficiency Symbol.
Rework/replace roof to wall flashing.
6. The unit price requirements for brick are identified on the plans as each brick to be replaced.
Would it be better to provide unit prices per brick to be replaced rather than
Response: Question is confusing. Provide unit prices as specified.
7. Spec 01 35 26 1.9.B says a Certified Safety Professional is required for safety inspections. Is this person required or can the Super/SSHO handle all safety inspections?
Response: Super/SSHO can handle safety inspections