596-16-101
A/E Renovate Building 28 for Specialty Care Volume 2 of 4 Divisions 08 through 22 October 5, 2018
Department of Veterans Affairs Lexington VA Medical Center- Lexington, KY
Bid Documents
A/E Renovate Bldg. 28 for Specialty Care VA #596-16-101
Lexington VA Medical Center
Lexington, KY HDG #15018
00 01 10-1
DEPARTMENT OF VETERANS AFFAIRS
VHA MASTER SPECIFICATIONS
TABLE OF CONTENTS
Section 00 01 10
DIVISION 00 - SPECIAL SECTIONS DATE
00 01 13 Project Seals Page 00 01 15 List of Drawing Sheets 07-15
DIVISION 01 - GENERAL REQUIREMENTS
01 00 00 General Requirements 11-15 01 32 16.15 Project Schedules 01 33 23 Shop Drawings, Product Data, and Samples 07-15 01 35 26 Safety Requirements 10-14 01 42 19 Reference Standards 07-15 01 45 29 Testing Laboratory Services 06-15 01 57 19 Temporary Environmental Controls 01-11 01 58 16 Temporary Interior Signage 07-15 01 74 19 Construction Waste Management 09-13 01 81 13 Sustainable Construction Requirements 09-13 01 81 13.02 Sustainability Certification Requirements- LEED NC V4 09-15 01 91 00 General Commissioning Requirements 10-15
DIVISION 02 – EXISTING CONDITIONS
02 21 00 Site Surveys 05-13 02 41 00 Demolition 02-15 02 82 11 Traditional Asbestos Abatement 09-15 EFI Global Report dated 9/09 and Associated Plans
DIVISION 03 – CONCRETE
03 30 00 Cast-in-Place Concrete
DIVISION 04 – MASONRY
04 05 13 Masonry Mortaring 02-16 04 05 16 Masonry Grouting 02-16 04 20 00 Unit Masonry 02-16
DIVISION 05 – METALS
05 12 00 Structural Steel Framing 02-16 05 31 00 Steel Decking 02-16
00 01 10-2
05 40 00 Cold-Formed Metal Framing 07-11 05 50 00 Metal Fabrications 07-14
DIVISION 06 – WOOD,PLASTICS AND COMPOSITES
06 10 00 Rough Carpentry 10-15 06 20 00 Finish Carpentry 06-13
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 11 13 Bituminous Dampproofing 02-16 07 21 00 Spray Polyurethane Thermal Insulation 02-16 07 21 13 Thermal Insulation 02-16 07 31 13 Asphalt Shingles 02-16 07 60 00 Flashing and Sheet Metal 07-14 07 84 00 Firestopping 02-16 07 92 00 Joint Sealants 10-15
DIVISION 08 - OPENINGS
08 11 13 Hollow Metal Doors and Frames 01-13 08 14 00 Interior Wood Doors 02-16 08 17 10 Integrated Door Assemblies 02-16 08 31 13 Access Doors and Frames 02-16 08 41 13 Aluminum-Framed Entrances and Storefronts 10-15 08 51 13 Aluminum Windows 02-16 08 71 00 Door Hardware 01-16 08 71 13 Automatic Door Operators 02-16 08 80 00 Glazing 10-15 08 90 00 Louvers and Vents 05-15
DIVISION 09 – FINISHES
09 05 16 Subsurface Preparation for Floor Finishes 02-15 09 06 00 Schedule for Finishes 04-15 09 22 16 Non-Structural Metal Framing 10-14 09 24 00 Portland Cement Plastering 10-15 09 29 00 Gypsum Board 11-14 09 30 13 Ceramic/Porcelain Tiling 09-15 09 51 00 Acoustical Ceilings 12-15 09 65 13 Resilient Base and Accessories 02-16 09 65 16 Resilient Sheet Flooring 02-16 09 67 23.20 Reinous (Epoxy Base) with Vinyl Chip Broadcast (RES-01 and RES-02)
09 67 23.60 Resinous Urethane and Epoxy Mortar FlooRing Res-6A 07-14 09 91 00 Painting 01-16
DIVISION 10 – SPECIALTIES
10 13 00 Directories 05-15
00 01 10-3
10 14 00 Signage 10-15 10 21 13 Toilet Compartments 12-15 10 26 00 Wall and Door Protection 10-15 10 44 13 Fire Extinguisher Cabinets 08-14
DIVISION 11 – EQUIPMENT
11 05 12 General Motor Requirements for Equipment 11-11
DIVISION 12 – FURNISHINGS
12 24 00 Window Shades 09-15 12 31 00 Manufactured Metal Casework 05-15 12 34 00 Manufactured Plastic Casework 09-15 12 36 00 Countertops 12-15
DIVISION 13 - SPECIAL CONSTRUCTION
13 05 41 Seismic Restraint Requirements for Non-Structural
Components 01-14
13 49 00 Radiation Protection 02-16
DIVISION 14– CONVEYING EQUIPEMENT
14 24 00 Electric Hydraulic Elevator 2-21
DIVISION 21- FIRE SUPPRESSION
21 08 00 Commissioning of Fire Suppression System 05-15 21 13 13 Wet-Pipe Sprinkler Systems 06-15
DIVISION 22 – PLUMBING
22 05 11 Common Work Results for Plumbing 09-15 22 05 12 General Motor Requirements for Plumbing Equipment 09-15 22 05 19 Meters and Gages for Plumbing Piping 09-15 22 05 23 General-Duty Valves for Plumbing Piping 09-15 22 07 11 Plumbing Insulation 09-15 22 08 00 Commissioning of Plumbing Systems 09-15 22 11 00 Facility Water Distribution 09-15 22 11 23 Domestic Water Pumps 09-15 22 13 00 Facility Sanitary and Vent Piping 09-15 22 14 29 Sump Pumps 09-15 22 34 00 Fuel-Fired Domestic Water Heaters 09-15 22 40 00 Plumbing Fixtures 09-15 22 61 13.74 Dental Compressed-Air Piping 09-15 22 61 19.74 Dental Compressed-Air Equipment 09-15 22 62 19.74 Dental Vacuum and Evacuation Equipment 09-15 22 63 00 Gas Systems for Laboratory and Healthcare Facilities 09-15
00 01 10-4
DIVISION 23 – HEATING, VENTILATING, AND AIR
CONDITIONING (HVAC)
23 05 11 Common Work Results for HVAC 02-15 23 05 12 General Motor Requirements for HVAC and Steam
Generation Equipment 11-10
23 05 41 Noise and Vibration Control for HVAC Piping and Equipment
02-15
23 05 93 Testing, Adjusting, and Balancing for HVAC 02-15 23 07 11 HVAC and Boiler Plant Insulation 02-15 23 08 00 Commissioning of HVAC Systems 06-13 23 09 23 Direct-Digital Control System for HVAC 09-11 23 11 23 Facility Natural-Gas Piping 02-15 23 21 13 Hydronic Piping 09-12 23 21 23 Hydronic Pumps 02-15 23 23 00 Refrigerant Piping 02-15 23 25 00 HVAC Water Treatment 02-15 23 31 00 HVAC Ducts and Casings 03-13 23 34 00 HVAC Fans 02-15 23 36 00 Air Terminal Units 02-15 23 37 00 Air Outlets and Inlets 02-15 23 40 00 HVAC Air Cleaning Devices 02-12 23 73 00 Indoor Central-Station Air-Handling Units 04-11 23 81 00 Decentralized Unitary HVAC Equipment 02-11 23 82 00 Convection Heating and Cooling Units 04-11 23 82 16 Air Coils 04-11
DIVISION 25 – INTEGRATED AUTOMATION
25 10 10 Advanced Utility Metering System
DIVISION 26 – ELECTRICAL
26 05 11 Requirements for Electrical Installations 01-16 26 05 19 Low-Voltage Electrical Power Conductors and Cables 07-13 26 05 26 Grounding and Bonding for Electrical Systems 12-12 26 05 33 Raceway and Boxes for Electrical Systems 05-14 26 05 41 Underground Electrical Construction 12-12 26 05 73 Overcurrent Protective Device Coordination Study 12-15 26 08 00 Commissioning of Electrical Systems 06-13 26 09 23 Lighting Controls 05-14 26 12 19 Pad-Mounted, Liquid-Filled, Medium-Voltage
Transformers
26 24 13 Distribution Switchboards 08-14 26 24 16 Panelboards 05-14 26 27 26 Wiring Devices 01-16 26 29 11 Motor Controllers 08-14 26 29 21 Enclosed Switches and Circuit Breakers 12-12 26 41 00 Facility Lightning Protection 12-12 26 43 13 Surge Protective Device 12-12
00 01 10-5
26 51 00 Interior Lighting 08-14
DIVISION 27 – COMMUNICATIONS
27 05 11 Requirements for Communications Installations 06-15 27 05 26 Grounding and Bonding for Communications Systems 06-15 27 05 33 Raceways and Boxes for Communications Systems 06-15 27 08 00 Commissioning of Communications Systems 06-15 27 10 00 Control, Communication and Signal Wires 06-15 27 11 00 Communications Equipment Room Fittings 06-15 27 15 00 Communications Horizontal Cabling 01-16
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY
28 05 00 Common Work Results for Electronic Safety and Security 09-11 28 05 13 Conductors and Cables for Electronic Safety and
Security 09-11
28 05 26 Grounding and Bonding for Electronic Safety and Security
09-11
28 05 28.33 Conduits and Backboxes for Electronic Safety and Security
09-11
28 08 00 Commissioning of Electronic Safety and Security Systems
06-13
28 13 00 Physical Access Control System 10-11 28 23 00 Video Surveillance 09-11 28 31 00 Fire Detection and Alarm 10-11
DIVISION 31 – EARTHWORK
31 20 11 Earthwork (Short Form) 10-12 31 23 19 Dewatering 10-12
DIVISION 32 – EXTERIOR IMPROVEMENTS
32 05 23 Cement and Concrete for Exterior Improvements 05-13 32 12 16 Asphalt Paving 09-15 32 17 23 Pavement Markings 04-10 32 90 00 Planting 10-11
DIVISION 33 – UTILITIES
33 08 00 Commissioning of Site Utility Systems 06-13 33 10 00 Water Utilities 01-14 33 30 00 Sanitary Sewer Utilities 06-13 33 40 00 Storm Sewer Utilities 10-11
Lexington, KY HDG #15018
08 11 13-1
SECTION 08 11 13
HOLLOW METAL DOORS AND FRAMES
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies steel doors, steel frames and related components.
B. Terms relating to steel doors and frames as defined in ANSI A123.1 and as specified.
1.2 RELATED WORK
A. Frames fabricated of structural steel: Section 05 50 00, METAL
FABRICATIONS.
B. Aluminum frames entrance work: Section 08 41 13, ALUMINUM-FRAMED
ENTRANCES AND STOREFRONTS.
C. Door Hardware: Section 08 71 00, DOOR HARDWARE.
D. Glazing: Section 08 80 00, GLAZING.
E. Card readers and biometric devices: Section 28 13 00, ACCESS CONTROL.
F. Sustainable Design Requirements: Section 01 81 13, SUSTAINABLE
CONSTRUCTION REQUIREMENTS.
1.3 TESTING
A. An independent testing laboratory shall perform testing.
1.4 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Manufacturers Literature and Data:
1. Fire rated doors and frames, showing conformance with NFPA 80 and
Underwriters Laboratory, Inc., or Intertek Testing Services or
Factory Mutual fire rating requirements and temperature rise rating for stairwell doors. Submit proof of temperature rating.
2. Sound rated doors, including test report from Testing Laboratory.
1.5 SHIPMENT
A. Prior to shipment label each door and frame to show location, size, door swing and other pertinent information.
B. Fasten temporary steel spreaders across the bottom of each door frame.
1.6 STORAGE AND HANDLING
A. Store doors and frames at the site under cover.
Lexington, KY HDG #15018
08 11 13-2
B. Protect from rust and damage during storage and erection until completion.
1.7 APPLICABLE PUBLICATIONS
A. Publications listed below form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only.
B. Federal Specifications (Fed. Spec.):
L-S-125B................Screening, Insect, Nonmetallic
C. Door and Hardware Institute (DHI):
A115 Series.............Steel Door and Frame Preparation for Hardware, Series A115.1 through A115.17 (Dates Vary)
D. Steel Door Institute (SDI):
113-01 (R2006)..........Thermal Transmittance of Steel Door and Frame
Assemblies
128-09..................Acoustical Performance for Steel Door and Frame
Assemblies
E. American National Standard Institute:
A250.8-2003 (R2008).....Specifications for Standard Steel Doors and
Frames
F. American Society for Testing and Materials (ASTM):
A167-99(R2009)..........Stainless and Heat-Resisting Chromium-Nickel
Steel Plate, Sheet, and Strip
A568/568-M-11...........Steel, Sheet, Carbon, and High-Strength, Low-alloy, Hot-Rolled and Cold-Rolled
A1008-10................Steel, sheet, Cold-Rolled, Carbon, Structural, High Strength Low Alloy and High Strength Low
Alloy with Improved Formability
B209/209M-10............Aluminum and Aluminum-Alloy Sheet and Plate
B221/221M-12............Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles and Tubes
D1621-10................Compressive Properties of Rigid Cellular
Plastics
D3656-07................Insect Screening and Louver Cloth Woven from
Vinyl Coated Glass Yarns
E90-09..................Laboratory Measurement of Airborne Sound
Transmission Loss of Building Partitions
G. The National Association Architectural Metal Manufactures (NAAMM):
Lexington, KY HDG #15018
08 11 13-3
Metal Finishes Manual (AMP 500-06)
H. National Fire Protection Association (NFPA):
80-13...................Fire Doors and Fire Windows
I. Underwriters Laboratories, Inc. (UL):
Fire Resistance Directory
J. Intertek Testing Services (ITS):
Certifications Listings…Latest Edition
K. Factory Mutual System (FM):
Approval Guide
PART 2 - PRODUCTS
2.1 MATERIALS
A. Stainless Steel: ASTM A167, Type 302 or 304; finish, NAAMM Number 4.
B. Sheet Steel: ASTM A1008, cold-rolled for panels (face sheets) of doors.
C. Anchors, Fastenings and Accessories: Fastenings anchors, clips connecting members and sleeves from zinc coated steel.
D. Insect Screening: ASTM D3656, 18 by 18 regular mesh.
E. Aluminum Sheet: ASTM B209/209M.
F. Aluminum, Extruded: ASTM B221/221M.
G. Prime Paint: Paint that meets or exceeds the requirements of A250.8.
2.2 FABRICATION GENERAL
A. GENERAL:
1. Follow ANSI A250.8 for fabrication of standard steel doors, except as specified otherwise. Doors to receive hardware specified in
Section 08 71 00, DOOR HARDWARE. Tolerances as per ANSI A250.8.
Thickness, 44 mm (1-3/4 inches), unless otherwise shown.
2. Close top edge of exterior doors flush and seal to prevent water intrusion.
3. When vertical steel stiffeners are used for core construction, fill spaces between stiffeners with mineral fiber insulation.
B. Standard Duty Doors: ANSI A250.8, Level 1, Full flush seamless design of size and design shown. Use for interior locations only. Do not use for stairwell doors, security doors and detention doors.
C. Heavy Duty Doors: ANSI A250.8, Level 2, Full flush seamless design of size and design shown. Core construction types a, d, or f, for interior doors, and, types b, c, e, or f, for exterior doors.
D. Extra Heavy Duty Doors: ANSI A250.8, Level 3, Full flush seamless design of size and design shown. Core construction Types d or f, for
Lexington, KY HDG #15018
08 11 13-4 interior doors, and Types b, c, e, or f, for exterior doors. Use for detention doors, stairwell doors and security doors. See additional requirements for detention doors, under paragraph “Custom Hollow Metal
Doors.
Core Construction
Type
Door Core Description a Kraft honeycomb b Polyurethane c Polystyrene d Unitized steel grid e Mineral fiberboard f Vertical steel stiffeners
E. Smoke Doors:
1. Close top and vertical edges flush.
2. Provide seamless vertical edges.
3. Apply Steel astragal to the meeting style at the active leaf of pair of doors or double egress doors.
4. Provide clearance at head, jamb and sill as specified in NFPA 80.
F. Fire Rated Doors (Labeled):
1. Conform to NFPA 80 when tested by Underwriters Laboratories, Inc., Inchcape Testing Services, or Factory Mutual for the class of door or door opening shown.
2. Fire rated labels of metal, with raised or incised markings of approving laboratory shall be permanently attached to doors.
3. Close top and vertical edges of doors flush. Vertical edges shall be seamless. Apply steel astragal to the meeting stile of the active leaf of pairs of fire rated doors, except where vertical rod exit devices are specified for both leaves swinging in the same direction.
4. Construct fire rated doors in stairwell enclosures for maximum transmitted temperature rise of 230 °C (450 °F) above ambient temperature at end of 30 minutes of fire exposure when tested in accordance with ASTM E152.
G. Custom Metal Hollow Doors:
Lexington, KY HDG #15018
08 11 13-5
1. Provide custom hollow metal doors where nonstandard steel doors are indicated. At the Contractor’s option, custom hollow metal doors may be provided in lieu of standard steel doors. Door size(s), design, materials, construction, gages and finish shall be as specified for of standard steel doors.
H. Sound Rated Doors:
1. SDI 114, except as specified otherwise.
2. Sound Transmission Class minimum of 45 when tested in accordance with ASTM E90.
3. Doors complete with integral spring type automatic door bottom seal and with integral continuous gaskets on the frames. Applied spring type automatic door bottom seal and applied continuous gaskets for the frames for doors that are not sound rated but sealed for flanking noises are specified in Section 08 71 00, DOOR HARDWARE.
4. Fabricate vision panels to receive double glazing where shown.
2.3 METAL FRAMES
A. General:
1. ANSI A250.8, 1.3 mm (0.053 inch) thick sheet steel, types and styles as shown or scheduled.
2. Frames for exterior doors: Fabricate from 1.7 mm (0.067 inch) thick galvanized steel conforming to ASTM A525.
3. Frames for labeled fire rated doors.
a. Comply with NFPA 80. Test by Underwriters Laboratories, Inc., Inchcape Testing Services, or Factory Mutual.
b. Fire rated labels of approving laboratory permanently attached to frames as evidence of conformance with these requirements.
Provide labels of metal or engraved stamp, with raised or incised markings.
4. Frames for lead-lined doors:
a. Frames for doors 900 mm (3 feet) or less in width and having lead lining of 1 mm or less in thickness, and not shown to have structural steel supports: Minimum 1.7 mm (0.067 inch) thick.
b. Frames for doors over 900 mm (3 feet) in width or having lead-lining more than 1 mm in thickness shown to be supported by and attached to structural steel subframes: Minimum 1.3 mm (0.053 inch) thick.
Lexington, KY HDG #15018
08 11 13-6
c. Lead-lining and its application are specified in Section 13 49
00, RADIATION PROTECTION.
5. Frames for detention door (Type 22): Minimum 2 mm (0.093 inch) thick.
6. Frames for doors specified to have automatic door operators;
Security doors (Type 36); service window: minimum 1.7 mm (0.067 inch) thick.
7. Knocked-down frames are not acceptable.
B. Reinforcement and Covers:
1. ANSI A250.8 for, minimum thickness of steel reinforcement welded to back of frames.
2. Provide mortar guards securely fastened to back of hardware reinforcements except on lead-lined frames.
3. Where concealed door closers are installed within the head of the door frames, prepare frames for closers and provide 1 mm (0.042 inch) thick steel removable stop sections for access to concealed face plates and control valves, except when cover plates are furnished with closer.
C. Terminated Stops: ANSI A250.8.
D. Glazed Openings and Panel Opening:
a. Integral stop on exterior, corridor, or secure side of door.
b. Design rabbet width and depth to receive glazing material or panel shown or specified.
E. Frame Anchors:
1. Floor anchors:
a. Where floor fills occur, provide extension type floor anchors to compensate for depth of fill.
b. At bottom of jamb use 1.3 mm (0.053 inch) thick steel clip angles welded to jamb and drilled to receive two 6 mm (1/4 inch) floor bolts. Use 50 mm x 50 mm (2 inch by 2 inch) 9 mm by (3/8 inch) clip angle for lead lined frames, drilled for 9 mm (3/8 inch) floor bolts.
c. Where mullions occur, provide 2.3 mm (0.093 inch) thick steel channel anchors, drilled for two 6 mm (1/4 inch) floor bolts and frame anchor screws.
d. Where sill sections occur, provide continuous 1 mm (0.042 inch) thick steel rough bucks drilled for 6 mm (1/4 inch) floor bolts
Lexington, KY HDG #15018
08 11 13-7 and frame anchor screws. Space floor bolts at 50 mm (24 inches) on center.
2. Jamb anchors:
a. Locate anchors on jambs near top and bottom of each frame, and at intermediate points not over 600 mm (24 inches) apart, except for fire rated frames space anchors as required by labeling authority.
b. Form jamb anchors of not less than 1 mm (0.042 inch) thick steel unless otherwise specified.
c. Anchors set in masonry: Use adjustable anchors designed for friction fit against the frame and for extension into the masonry not less than 250 mm (10 inches). Use one of following type:
1) Wire loop type of 5 mm (3/16 inch) diameter wire.
2) T-shape or strap and stirrup type of corrugated or perforated sheet steel.
d. Anchors for stud partitions: Either weld to frame or use lock-in snap-in type. Provide tabs for securing anchor to the sides of the studs.
e. Anchors for frames set in prepared openings:
1) Steel pipe spacers with 6 mm (1/4 inch) inside diameter welded to plate reinforcing at jamb stops or hat shaped formed strap spacers, 50 mm (2 inches) wide, welded to jamb near stop.
2) Drill jamb stop and strap spacers for 6 mm (1/4 inch) flat head bolts to pass thru frame and spacers.
3) Two piece frames: Subframe or rough buck drilled for 6 mm (1/4 inch) bolts.
f. Anchors for observation windows and other continuous frames set in stud partitions.
1) In addition to jamb anchors, weld clip anchors to sills and heads of continuous frames over 1200 mm (4 feet) long.
2) Anchors spaced 600 mm (24 inches) on centers maximum.
g. Modify frame anchors to fit special frame and wall construction and provide special anchors where shown or required.
2.4 TRANSOM PANELS- NOT USED
2.5 LOUVERS
A. General:
Lexington, KY HDG #15018
08 11 13-8
1. Sight proof type with stationary blades the full thickness of the door.
2. Design lightproof louvers to exclude passage of light but permit free ventilation.
3. Provide insect screen and wire guards at exterior doors, except where doors are located below completely enclosed areaways, the wire guard is not required.
B. Fabrication:
1. Steel louvers 0.8 mm (0.032 inch) thick for interior doors, and 1.3 mm (0.053 inch) inch thick for exterior doors.
2. Fabricate louvers as complete units. Install in prepared cutouts in doors.
3. Weld stationary blades to frames. Weld louvers into door openings.
C. Screen frames:
1. Frame of either extruded aluminum or tubular aluminum.
2. Fabricate frame to hold wire fabric in a channel with a retaining bar anchor and to mount on surface of door with screws.
3. Do not lap frame over louver opening.
4. Miter corners of frame members and join by concealed mechanical fastenings extending about 57 mm (2-1/4 inches) into ends of each member.
5. Drill frame and doors for screw attachment. Space screws 50 mm (2 inches) from end of each leg of frame and not over 300 mm (12 inches) on center between end screws.
6. Finish: Clear anodized finish, 0.4 mils thick.
7. Insect Screens: Fasten insect screens to interior side of doors with retaining bar against door and not exposed to view.
8. Wire Guards:
a. Wire fabric shall be wire guard screen as specified.
b. Fasten wire guard to exterior side of door with retaining bar against door and not exposed to view.
2.6 SHOP PAINTING
A. ANSI A250.8.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Plumb, align and brace frames securely until permanent anchors are set.
Lexington, KY HDG #15018
08 11 13-9
1. Use triangular bracing near each corner on both sides of frames with temporary wood spreaders at midpoint.
2. Use wood spreaders at bottom of frame if the shipping spreader is removed.
3. Protect frame from accidental abuse.
4. Where construction will permit concealment, leave the shipping spreaders in place after installation, otherwise remove the spreaders after the frames are set and anchored.
5. Remove wood spreaders and braces only after the walls are built and jamb anchors are secured.
B. Floor Anchors:
1. Anchor the bottom of door frames to floor with two 6 mm (1/4 inch) diameter expansion bolts. Use 9 mm (3/8 inch) bolts on lead lined frames.
2. Power actuated drive pins may be used to secure frame anchors to concrete floors.
C. Jamb Anchors:
1. Anchors in masonry walls: Embed anchors in mortar. Fill space between frame and masonry wall with grout or mortar as walls are built.
2. Coat frame back with a bituminous coating prior to lining of grout filling in masonry walls.
3. Secure anchors to sides of studs with two fasteners through anchor tabs. Use steel drill screws to steel studs.
4. Frames set in prepared openings of masonry or concrete: Expansion bolt to wall with 6 mm (1/4 inch) expansion bolts through spacers.
Where subframes or rough bucks are used, 6 mm (1/4 inch) expansion bolts on 600 mm (24 inch) centers or power activated drive pins 600 mm (24 inches) on centers. Secure two piece frames to subframe or rough buck with machine screws on both faces.
D. Install anchors for labeled fire rated doors to provide rating as required.
E. Frames for Sound Rated Doors: Coordinate to line frames for sound rated doors with insulation.
F. Overhead Bracing (Lead Lined Frames): Where jamb extensions extend to structure above, anchor clip angles with not less than two, 9 mm (3/8
Lexington, KY HDG #15018
08 11 13-10 inch) expansion bolts or power actuated drive pins to concrete slab.
Weld to steel overhead members.
3.2 INSTALLATION OF DOORS AND APPLICATION OF HARDWARE
A. Install doors and hardware as specified in Sections Section 08 11 13, HOLLOW METAL DOORS AND FRAMES Section 08 14 00, WOOD DOORS Section 08
71 00, DOOR HARDWARE.
- - - E N D - - -
Lexington, KY HDG #15018
08 14 00 - 1
SECTION 08 14 00
INTERIOR WOOD DOORS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Interior flush wood doors transparent finish.
a. Fire rated doors.
b. Acoustical doors.
1.2 RELATED REQUIREMENTS
A. Door Hardware including hardware location (height): Section 08 71 00, DOOR HARDWARE.
B. Installation of Doors and Hardware: Section 08 11 13, HOLLOW METAL
DOORS AND FRAMES Section 08 71 00, DOOR HARDWARE.
C. Door Finish: Section 09 06 00, SCHEDULE FOR FINISHES.
D. Sustainable Design Requirements: Section 01 81 13, SUSTAINABLE
CONSTRUCTION REQUIREMENTS.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. American National Standards Institute/Window and Door Manufacturers
Association (ANSI/WDMA):
1. I.S. 1A-13 - Architectural Wood Flush Doors.
C. ASTM International (ASTM):
1. E90-09 - Laboratory Measurements of Airborne Sound Transmission Loss of Building Partitions and Elements.
D. National Fire Protection Association (NFPA):
1. 80-16 - Fire Doors and Other Opening Protectives.
2. 252-12 - Fire Tests of Door Assemblies.
E. UL LLC (UL):
1. 10C-09 - Positive Pressure Fire Tests of Door Assemblies.
F. Window and Door Manufacturers Association (WDMA):
1. TM 7-14 - Cycle-Slam Test.
2. TM 8-14 - Hinge Loading Test.
3. TM 10-14 - Screw Holding Capacity.
Lexington, KY HDG #15018
08 14 00 - 2
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and fabrication and installation details.
2. Include details of glazing and louvers.
3. Indicate project specific requirements not included in
Manufacturer's Literature and Data submittal.
C. Manufacturer's Literature and Data:
1. Description of each product.
2. Fire rated doors showing conformance with NFPA 80.
D. Samples:
1. Corner section of flush veneered door 300 mm (12 inches) square, showing details of construction, labeled to show grade and type number and conformance to specified standard.
2. Veneer sample 200 mm by 275 mm (8 inch by 11 inch) showing specified wood species sanded to receive a transparent finish. Factory finish veneer sample where the prefinished option is accepted.
E. Sustainable Construction Submittals:
1. Low Pollutant-Emitting Materials:
a. Show volatile organic compound types and quantities.
F. Test Reports: Indicate each product complies with specifications.
1. Screw Holding Capacity Test.
2. Cycle-Slam Test.
3. Hinge-Loading Test.
G. Operation and Maintenance Data:
1. Care instructions for each exposed finish product.
1.5 QUALITY ASSURANCE
A. Manufacturer Qualifications:
1. Regularly and presently manufactures specified products.
2. Manufactures specified products with satisfactory service on five similar installations for minimum five years.
1.6 DELIVERY
A. Deliver products in manufacturer's original sealed packaging.
1. Minimum 0.15 mm (6 mil) polyethylene bags or cardboard packaging to remain unbroken during delivery and storage.
Lexington, KY HDG #15018
08 14 00 - 3
B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, and manufacture date.
1. Identify door opening corresponding to Door Schedule.
C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.7 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight, conditioned facility.
1. Store doors according to ANSI/WDMA I.S. 1A.
B. Protect products from damage during handling and construction operations.
1.8 FIELD CONDITIONS
A. Environment:
1. Product Temperature: Minimum 21 degrees C (70 degrees F) for minimum
48 hours before installation.
2. Work Area Ambient Temperature Range: 21 to 27 degrees C (70 to
80 degrees F) continuously, beginning 48 hours before installation.
3. Install products when building is permanently enclosed and when wet construction is completed, dried, and cured.
a. Comply with door manufacturer's instructions for relative humidity.
1.9 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction."
B. Manufacturer's Warranty: Warrant interior factory finished flush wood doors against material and manufacturing defects.
1. Warranty Period: Lifetime of original installation.
PART 2 - PRODUCTS
2.1 PRODUCTS - GENERAL
A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.
B. Provide each product from one manufacturer.
C. Sustainable Construction Requirements:
1. Low Pollutant-Emitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:
Lexington, KY HDG #15018
08 14 00 - 4
a. Paints and coatings.
b. Composite wood and agrifiber.
2.2 FLUSH WOOD DOORS
A. General:
1. ANSI/WDMA I.S. 1A, Extra Heavy Duty.
2. Adhesive: Type II.
3. Core: Structural composite lumber, except when mineral core is required for fire rating.
4. Thickness: 44 mm (1-3/4 inches) unless otherwise shown or specified.
B. Faces:
1. ANSI/WDMA I.S. 1A.
2. One species throughout project unless scheduled or otherwise shown.
3. Transparent Finished Faces: Premium Grade, rotary cut, natural cherry.
a. A Grade face veneer.
b. Match face veneers for doors for uniform effect of color and grain at joints.
c. Door Edges: Same species as door face veneer.
4. Factory sand doors for finishing.
C. Wood For Stops, Louvers, Muntins and Moldings For Flush Doors Required to Have Transparent Finish:
1. Solid wood of same species as face veneer.
2. Glazing:
a. On non-fire-rated doors, use applied wood stops nailed tightly on room side and attached on opposite side with flathead, countersunk wood screws, spaced approximately 125 mm (5 inches) on center.
3. Wood Louvers:
a. Door manufacturer's standard product, fabricated of solid wood sections.
b. Wood Slats: minimum 5 mm (3/16 inch) thick.
c. Stiles routed out to receive slats.
d. Secure louvers in prepared cutouts with wood stops.
D. Fire-Rated Wood Doors:
1. Fire Resistance Rating:
a. B Label: 1-1/2 hours.
Lexington, KY HDG #15018
08 14 00 - 5
b. C Label: 3/4 hour.
2. Labels:
a. Comply with NFPA 252, UL 10C, and labeled by qualified testing and inspection agency showing fire resistance rating.
b. Metal labels with raised or incised markings.
3. Performance Criteria for Stiles of Doors Utilizing Standard Mortise
Leaf Hinges:
a. Hinge Loading: WDMA TM 8. Average of 10 test samples for Extra
Heavy Duty doors.
b. Direct Screw Withdrawal: WDMA TM 10 for Extra Heavy Duty doors.
Average of 10 test samples using a steel, fully threaded #12 wood screw.
c. Cycle-Slam: 1,000,000 cycles with no loose hinge screws or other visible signs of failure when tested according to WDMA TM 7.
4. Hardware Reinforcement:
a. Provide fire smoke rated doors with hardware reinforcement blocking.
b. Size of lock blocks as required to secure hardware specified.
c. Top, Bottom and Intermediate Rail Blocks: Minimum 125 mm
(5 inches) by full core width.
d. Reinforcement blocking in compliance with labeling requirements.
e. Mineral material similar to core is not acceptable.
5. Other Core Components: Manufacturer's standard as allowed by labeling requirements.
6. Glazed Vision Panel Frame: Steel approved for use in labeled doors.
E. Smoke Barrier Doors:
1. Glazed Vision Panel Frame: Steel approved for use in labeled doors.
2. Astragal: Steel type for pairs of doors, including double egress doors.
F. Sound Rated Doors:
1. Fabricated as specified for flush wood doors with additional construction requirements to comply with specified sound transmission class (STC).
2. STC Rating of door assembly in place when tested according to
ASTM E90 by independent acoustical testing laboratory minimum 35.
3. Accessories:
Lexington, KY HDG #15018
08 14 00 - 6
a. Frame Gaskets and Automatic Door Bottom Seal: As specified in
Section 08 71 00, DOOR HARDWARE.
2.3 STILE AND RAIL WOOD DOORS- NOT USED
2.4 FABRICATION
A. Factory machine interior wood doors to receive hardware, bevels, undercuts, cutouts, accessories and fitting for frame.
1. Factory fit fire rated doors according to NFPA 80.
B. Rout doors for hardware using templates and location heights specified in Section 08 71 00, DOOR HARDWARE.
C. Factory fit doors to frame, bevel lock edge of doors 3 mm (1/8 inch) for each 50 mm (2 inches) of door thickness undercut where shown.
D. Clearances between Doors and Frames and Floors:
1. Fire Rated Doors: Comply with NFPA 80.
a. Doors with Automatic Bottom Seal: Maximum clearance 10 mm
(3/8 inch) at threshold.
b. Other Door Bottoms: Maximum 3 mm (1/8 inch) clearance at the jambs, heads, and meeting stiles, and a 19 mm (3/4 inch) clearance at bottom, except as otherwise specified.
2. Door Jambs, Heads, and Meeting Stiles: Maximum 3 mm (1/8 inch).
E. Provide cutouts for glazed and louver openings.
F. Finish surfaces, including both faces, top and bottom and edges of the doors smooth to touch.
G. Identify each door on top edge.
1. Mark with stamp, brand or other indelible mark, giving manufacturer’s name, door’s trade name, construction of door, date of manufacture and quality.
2. Mark door or provide separate certification including name of inspection organization.
3. Identify door manufacturing standard, including glue type.
4. Identify veneer and quality certification.
5. Identification of preservative treatment for stile and rail doors.
2.5 FINISHES
A. Field Finished Doors: Seal top and bottom edges of doors with two coats of catalyzed polyurethane or water resistant sealer.
B. Factory Transparent Finish:
1. Factory finish flush wood doors.
Lexington, KY HDG #15018
08 14 00 - 7
a. ANSI/WDMA I.S. 1A Section F-3 Finish System Descriptions for
System 5, Conversion Varnish or System 7, Catalyzed Vinyl.
b. Use stain when required to produce finish specified in Section
09 06 00, SCHEDULE FOR FINISHES.
PART 3 - EXECUTION
3.1 PREPARATION
A. Examine and verify substrate suitability for product installation.
1. Verify door frames are properly anchored.
2. Verify door frames are plumb, square, in plane, and within tolerances for door installation.
B. Protect existing construction and completed work from damage.
C. Install astragal on active leaf of pair of smoke doors and one leaf of double egress smoke doors.
3.2 INSTALLATION
A. Install products according to manufacturer's instructions and approved submittal drawings.
1. Install fire rated doors according to NFPA 80.
2. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.
3.3 PROTECTION
A. After installation, place shipping container over door and tape in place.
1. Do not apply tape to door faces and edges.
B. Provide protective covering over exposed hardware in addition to covering door.
C. Maintain covering in good condition until removal is directed by
Contracting Officer's Representative.
- - E N D - -
Lexington, KY HDG #15018
08 17 10 - 1
SECTION 08 17 10
INTEGRATED DOOR ASSEMBLIES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Integrated door assemblies including metal door frame, door, and hardware, unless specified in another Section, installed at cross-corridor locations.
B. Smoke and draft control seals, unless specified in another Section.
1.2 RELATED REQUIREMENTS
A. Lock Cylinders: Section 08 71 00, DOOR HARDWARE.
B. Automatic Door Operators: Section 08 71 13, AUTOMATIC DOOR OPERATORS.
C. Door and Frame Color: Section 09 06 00, SCHEDULE FOR FINISHES.
D. Electrical Power: DIVISION 26, ELECTRICAL.
E. Sustainable Design Requirements: Section 01 81 13, SUSTAINABLE
CONSTRUCTION REQUIREMENTS.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. Builders Hardware Manufacturers Association (BHMA):
1. A156.3-14 - Exit Devices.
2. A156.26-06 - Continuous Hinges.
3. A156.32-14 - Integrated Door Opening Assemblies.
C. ASTM International (ASTM):
1. A1011/A1011M-14 - Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with
Improved Formability, and Ultra-High Strength.
2. E2180-07 (2012) - Determining the Activity of Incorporated
Antimicrobial Agents in Polymeric or Hydrophobic Materials.
D. Door and Hardware Institute (DHI):
1. Recommended Locations for Architectural Hardware for Standard Doors
& Frames (2004).
2. Recommended Locations for Builders' Hardware Custom Steel Doors &
Frames (1996).
E. National Fire Protection Association (NFPA):
1. 105-16 - Smoke Door Assemblies and Other Opening Protectives.
Lexington, KY HDG #15018
08 17 10 - 2
2. 252-12 - Fire Tests of Door Assemblies.
F. Steel Door Institute (SDI):
1. A250.3-11 - Test Procedure and Acceptance Criteria for Factory
Applied Finish Coatings for Steel Doors and Frames.
2. A250.8-14 - Specifications for Standard Steel Doors and Frames.
3. A250.10-11 - Test Procedure and Acceptance Criteria for Prime
Painted Steel Surfaces for Steel Doors and Frames.
G. UL LLC (UL):
1. 10C-09 - Positive Pressure Fire Tests of Door Assemblies.
2. 1784-15 - Air Leakage Tests of Door Assemblies and Other Opening
Protectives.
1.4 PREINSTALLATION MEETINGS
A. Conduct pre-installation meeting at project site minimum 30 days before beginning Work of this section.
1. Required Participants:
a. Contracting Officer's Representative.
b. Architect/Engineer.
c. Contractor.
d. Installer.
e. Other installers responsible for adjacent and intersecting work, including electrical.
2. Meeting Agenda: Distribute agenda to participants minimum 3 days before meeting.
a. Installation schedule.
b. Installation sequence.
c. Preparatory work.
d. Protection before, during, and after installation.
e. Installation.
f. Transitions and connections to other work.
g. Other items affecting successful completion.
3. Document and distribute meeting minutes to participants to record decisions affecting installation.
1.5 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
Lexington, KY HDG #15018
08 17 10 - 3
1. Show size, configuration, and fabrication and installation details.
2. For each opening, list finish hardware items included in assembly, finish, degree of opening, and electrical rough-in requirements according to Door Schedule.
3. Submit templates to door and frame manufacturers to ensure proper size and location of hardware.
C. Manufacturer's Literature and Data:
1. Description of each product.
2. Installation instructions.
D. Sustainable Construction Submittals:
1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.
2. Low Pollutant-Emitting Materials:
a. Show volatile organic compound types and quantities.
E. Certificates: Indicate integrated door assemblies comply with specifications.
1. Show fire rated integrated door assembly is UL Listed for specified application.
F. Qualifications: Substantiate qualifications comply with specifications.
1. Installer.
G. Operation and Maintenance Data:
1. Care instructions for each exposed finish product.
2. Maintenance and adjustment instructions for integrated door assemblies.
1.6 QUALITY ASSURANCE
A. Installer Qualifications:
1. Regularly installs specified products.
2. Installed specified products with satisfactory service on five similar installations for minimum five years.
a. Provide contact names and addresses for completed projects when requested by Contracting Officer's Representative.
1.7 DELIVERY
A. Deliver products in manufacturer's original sealed packaging.
B. Mark packaging, legibly. Indicate manufacturer's name.
C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
Lexington, KY HDG #15018
08 17 10 - 4
1.8 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight facility.
B. Protect products from damage during handling and construction operations.
1.9 FIELD CONDITIONS
A. Field Measurements: Verify field conditions affecting integrated door assembly fabrication and installation. Show field measurements on
Submittal Drawings.
1. Coordinate field measurement and fabrication schedule to avoid delay.
2. Coordinate electrical work for electrified hardware installation.
1.10 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction."
B. Manufacturer's Warranty: Warrant door closers and hinges against material and manufacturing defects.
1. Warranty Periods:
a. Door Closers: 10 years.
b. Steel Pinned Continuous Hinges: 10 years.
PART 2 - PRODUCTS
2.1 SYSTEM PERFORMANCE
A. Design integrated door assemblies complying with specified performance:
1. BHMA A156.32: Grade 1: 1,000,000 cycles.
B. Fire Rated Doors:
1. Fire Resistance Rating: As shown in Door Schedule.
2. Label: Comply with NFPA 252, UL 10C, and labeled by qualified testing and inspection agency showing fire resistance rating.
C. Smoke Rated Doors:
1. Smoke Resistance Rating: As shown in Door Schedule.
2. Label: Comply with NFPA 105, UL 1784, and labeled by qualified testing and inspection agency showing smoke resistance rating.
2.2 PRODUCTS - GENERAL
A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.
B. Provide each integrated door assembly from one manufacturer.
Lexington, KY HDG #15018
08 17 10 - 5
C. Sustainable Construction Requirements:
1. Steel Recycled Content: 30 percent total recycled content, minimum.
2. Low Pollutant-Emitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:
a. Non-flooring adhesives and sealants.
b. Paints and coatings.
2.3 INTEGRATED DOOR ASSEMBLY
A. Metal Frames: SDI A250.8 Level 2.
1. Metal: ASTM A1011/A1011M; cold rolled steel, 1.3 mm (0.05 inches) thick, minimum.
2. Construction: Continuously welded.
3. Reinforce frame for hardware.
a. Continuous Hinges: 2.3 mm (0.09 inches) thick.
b. Other Hardware: Comply with SDI A250.8.
4. Frame Anchors: Provide adjustable type anchors coordinated with wall construction, minimum 4 per jamb.
B. Integrated Hardware:
1. Exit Device: BHMA A156.3; Grade 1, passage function, inset in door face, clean and unobtrusive in design.
a. Push Bar End Caps: Metal, plated satin nickel (BHMA 619) finish.
b. Exit Device Trim: Lever matching door hardware specified in
Section 08 71 00, DOOR HARDWARE.
2.4 FINISHES
A. Hardware Finish Symbols:
Table 1 Hardware Finish Symbols
US BHMA 156.18 Description
USP 600 Primed for field painting
US15 619 Dull Nickel Plated
US26D 626/652 Satin Chrome Plated
US28 628 Satin Aluminum
US32 629 Bright Stainless
US32D 630 Satin Stainless
N/A 689 Aluminum Painted
Lexington, KY HDG #15018
08 17 10 - 6
B. Finish Requirements:
1. Door Faces: Prime painted, SDI A250.10.
2. Frames: Prime painted, SDI A250.10.
3. Door Hardware:
a. Continuous Hinges: BHMA 630.
b. Push Bar: BHMA 630 clad with BHMA 619 end caps.
c. Exit Device Trim: BHMA 630.
d. Push/Pull Trim: BHMA 626.
e. Door Closers: BHMA 689.
f. Miscellaneous: To match other finishes.
4. Anti-Microbial Coating: ASTM E2180; ionic silver coating.
5. Apply coating to hand-operated hardware including levers, pulls, push bars, push plates, and paddles.
PART 3 - EXECUTION
3.1 PREPARATION
A. Examine and verify substrate suitability for product installation.
B. Protect existing construction and completed work from damage.
3.2 INSTALLATION - INTEGRATED DOOR ASSEMBLIES
A. Install products according to manufacturer's instructions and approved submittal drawings.
B. Install door hardware at locations indicated in DHI Recommended
Locations for Architectural Hardware for Standard Steel Doors & Frames and DHI Recommended Locations for Builders' Hardware Custom Steel Doors
& Frames, unless otherwise indicated, or to comply with requirements of governing regulations, or if otherwise directed by Contracting
Officer's Representative.
C. Install door hardware in compliance with manufacturers' instructions, and templates. Comply with specified degree of opening for doors with automatic operators and overhead door closers. Securely fasten hardware. Confirm operating parts move freely and smoothly without binding, sticking, and excessive clearance.
D. Coordinate installation and interface wiring with fire alarm and smoke detection systems. Provide auxiliary contacts, relays, and interface for fire alarm and security systems.
Lexington, KY HDG #15018
08 17 10 - 7
E. Remove or protect door hardware, before painting and finishing performed after integrated door assembly installation.
F. Adjust and check door assembly and each operating hardware item to ensure correct operation and function. Replace products which cannot be adjusted to operate as intended.
G. Final Adjustment: Perform final hardware check and adjustment maximum one month before building acceptance or partial building occupancy.
3.3 CLEANING
A. Clean exposed surfaces, including hardware. Do not use cleaners that will harm finishes.
3.4 PROTECTION
A. Protect integrated door assemblies from construction operations.
3.5 SCHEDULES
A. The following is a general listing of the Integrated Door Assembly requirements and is not intended for use as a final door submittal.
Provide hardware items required by established standards and practices, and to meet IBC and NFPA 101 whether specified or not in the following listed groups.
120VAC POWER, CONDUIT, AND WIRING BY DIVISION 26.
CARD READER BY DIVISION 28.
LOCK CYLINDER BY SECTION 08 71 00, DOOR HARDWARE.
HW-SH-4A
Each [ADO, AC, ELR, REX, DPS]
Integrated Door to Have:
RATED
1 Steel Frame
1 Integrated Door w/Elec Exit
Device
Q2131 x TYPE 8 ELECTRIC DEVICE (E01, E04)x F13 LEVER
1 Continuous Transfer Hinge A51031B x 12-THRUWIRE TRANSFER x
IN-HINGE ACCESS PANEL
1 Power Supply BY EXIT DEVICE MFR. FOR E04 FUNCTION
1 Armor Plate J101 x 1.275 mm (0.050 inch)
THICKNESS
1 Floor Stop L02121 x 3 FASTENERS
Lexington, KY HDG #15018
08 17 10 - 8
1 Set Self-Adhesive Seals R0E154
1 Alarm Contact
120VAC POWER, CONDUIT, AND WIRING BY DIVISION 26.
AUTO DOOR OPERATOR AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR
OPERATORS.
CARD READER BY DIVISION 28.
HW-3
Each Door to Have: RATED
Hinges QUANTITY & TYPE AS REQUIRED
1 Office Lock F04
1 Closer C02011/C02021
1 Kick Plate J102
1 Floor Stop L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0Y154
HW-SH-12
Each [AC, ADO, EL, REX, DPS] Integrated Door to Have:
NON-RATED
1 Steel Frame 1 Integrated Door w/Elec. Exit Device
Q2131 x TYPE 8 ELECTRIC DEVICE (E01, E04) x F03 OUTSIDE CYLINDER ONLY
1 Continuous Transfer Hinge A51031B x 12-THRUWIRE TRANSFER x
IN-HINGE ACCESS PANEL
1 Power Supply BY EXIT DEVICE MFR. FOR E04 FUNCTION
1 Offset Pull J402 x 1” (25mm) DIAMETER x 12” (305mm)CTC
1 Closer C02021 (PT4D, PT4F, PT4H) 1 Kick Plate J102 1 Floor Stop L02121 x 3 FASTENERS 1 Threshold J35130 x SILICONE GASKET 1 Door Sweep 90100CNB (PEMKO), OR EQUAL
1 Set Frame Seals
2891AS X CSK SCREWS (PEMKO), OR
EQUAL
1 Drip R0Y976 1 Alarm Contact
120VAC POWER, CONDUIT, AND WIRING BY DIVISION 26.
CARD READER BY DIVISION 28.
LOCK CYLINDER BY SECTION 08 71 00, DOOR HARDWARE.
08 17 10 - 9
HW-SH-12
Each [AC, ELR, REX, DPS] Integrated Door to Have: NON-RATED
1 Key Cylinder TYPE AS REQUIRED
BALANCE OF HARDWARE BY SECTION 08 17 10, INTEGRATED DOOR ASSEMBLIES
HW-8A
Each Aluminum Storefront Pair to Have: NON-RATED
2 Floor Closers C06041
2 Intermediate Pivots C07321
2 Push/Pull Bar Sets J505 – 305 MM (12 INCH) CENTER-TO-CENTER
PULL
2 Overhead Stops C01541-ADJUSTABLE
Lexington, KY HDG #15018
08 31 13 - 1
SECTION 08 31 13
ACCESS DOORS AND FRAMES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Access doors and panels installed in walls and ceilings.
1.2 RELATED REQUIREMENTS
A. Wire Mesh and Screen Access Doors: Section 05 50 00, METAL
FABRICATIONS.
B. Lock Cylinders: Section 08 71 00, DOOR HARDWARE.
C. Field Painting: Section 09 91 00, PAINTING.
D. Finish Color: Section 09 06 00, SCHEDULE FOR FINISHES.
E. Access Doors for Control or Drain Valves: Section 21 13 13, WET-PIPE
SPRINKLER SYSTEMS.
F. Access Doors for Plumbing Valves: Section 22 40 00, PLUMBING FIXTURES.
G. Locations of Access Doors for Ductwork Cleanouts: Section 23 31 00, HVAC DUCTS AND CASINGS.
H. Sustainable Design Requirements: Section 01 81 13, SUSTAINABLE
CONSTRUCTION REQUIREMENTS.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. American Welding Society (AWS):
1. D1.3/D1.3M-08 - Structural Welding Code - Sheet Steel.
C. ASTM International (ASTM):
1. A653/A653M-15 - Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron
Alloy-Coated (Galvannealed) by the Hot-Sip Process.
2. A1008/A1008M-15 - Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved
Formability, Solution Hardened, and Baked Hardenable.
3. A666-15 - Annealed or Cold-Worked Austenitic Stainless Steel sheet, Strip, Plate, and Flat Bar.
4. E119-15 - Fire Test of Building Construction and Materials.
D. National Fire Protection Association (NFPA):
1. 80-16 - Fire Doors and Other Opening Protectives.
2. 251-12 - Fire Tests of Door Assemblies.
Lexington, KY HDG #15018
08 31 13 - 2
E. National Association of Architectural Metal Manufacturers (NAAMM):
1. AMP 500-06 - Metal Finishes Manual.
F. UL LLC (UL):
1. Listed - Online Certifications Directory.
2. 10B-08 - Standard for Fire Tests of Door Assemblies.
3. 263-11 - Fire Tests of Building Construction and Materials.
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and fabrication and installation details.
C. Manufacturer's Literature and Data:
1. Description of each product.
2. Installation instructions.
D. Sustainable Construction Submittals:
1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.
1.5 DELIVERY
A. Deliver products in manufacturer's original sealed packaging.
B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, production run number, and manufacture date.
C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.6 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight facility.
B. Protect products from damage during handling and construction operations.
1.7 FIELD CONDITIONS
A. Field Measurements: Verify field conditions affecting access door fabrication and installation. Show field measurements on Submittal
Drawings.
1. Coordinate field measurement and fabrication schedule to avoid delay.
Lexington, KY HDG #15018
08 31 13 - 3
1.8 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction."
PART 2 - PRODUCTS
2.1 MATERIALS
A. Steel Sheet: ASTM A1008/A1008M.
B. Galvanized Steel: ASTM A 653/A 653M.
C. Stainless Steel: ASTM A666; Type 302 or Type 304.
2.2 PRODUCTS - GENERAL
A. Basis of Design: Section 09 06 00, SCHEDULE FOR…