36C24825Q0691_1.docx

DOCX document 17 KB Posted

Attached to
H161--Generator Load Banking Federal contract opportunity
Solicitation number
36C24825Q0691
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

This is a Presolicitation Notice for generator load banking services at the C.W. Bill Young VA Medical Center in Bay Pines, Florida. The Department of Veterans Affairs is seeking a contractor to perform annual load banking on eight generators across different buildings, with a base year from 06/29/2025 to 06/28/2026 and four additional one-year option periods through 06/28/2030. The solicitation (36C24825Q0691) is set aside for SBA and requires a response by 04-22-2025 at 2:00 PM Eastern Time.

The contractor must conduct a four-hour load bank test meeting Joint Commission requirements, including 30% rating for 2 hours, 50% for 1 hour, and 75% for 1 hour, with comprehensive documentation. Qualified contractors must have at least five years of generator operations experience, electrical safety training per OSHA and NFPA standards, and provide detailed reports including generator specifications, 15-minute interval logs, and equipment condition assessments. Work will be performed Monday through Friday between 6:00 AM and 4:00 PM, with a target month of June, and must not interrupt building power operations.

View the file

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Presolicitation Notice Presolicitation Notice

SUBJECT*
Generator Load Banking

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
33744
SOLICITATION NUMBER*
36C24825Q0691
RESPONSE DATE/TIME/ZONE
04-22-2025 2:00pm EASTERN TIME, NEW YORK, USA
ARCHIVE
60 DAYS AFTER THE RESPONSE DATE
SET-ASIDE
SBA
PRODUCT SERVICE CODE*
H161
NAICS CODE*
811310
PLACE OF PERFORMANCE
C.W. Bill Young VA Healthcare System

10000 Bay Pines Blvd.

Bay Pines FL

POSTAL CODE
33744
COUNTRY
USA

CONTACT INFORMATION

CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Network Contracting Office 8 (NCO 8)

10,000 Bay Pines Blvd Bay Pines FL 33744

POINT OF CONTACT*

Contract Specialist William Penhallegon william.penhallegon@va.gov

ADDITIONAL INFORMATION

AGENCY’S URL

URL DESCRIPTION

AGENCY CONTACT’S EMAIL ADDRESS
Contract Specialist
EMAIL DESCRIPTION
William Penhallegon

DESCRIPTION

STATEMENT OF WORK FOR GENERATOR LOAD BANKING

AT CW BILL YOUNG VA MEDICAL CENTER

10000 BAY PINES BLVD., BAY PINES, FL 33744

OVERVIEW

The contractor shall provide all the necessary labor, equipment, cables, transportation and supervision for an annual load banking of eight (8) generator units at CW Bill Young VA Medical Center. This is for a four hour load bank.

Base and 4 option years.

Base year06/29/2025 – 06/28/2026
Option year 106/29/2026 – 06/28/2027
Option year 206/29/2027 – 06/28/2028
Option year 306/29/2028 – 06/28/2029
Option year 406/29/2029 – 06/28/2030

GENERATORS

The generators in this scope of work are:

Bldg. 1, Marathon 600 kW, 750 kVA, 277/480v Bldg. 19, Magnetek 100 kW, 120 kVA, 120/208v Bldg. 24, Allis-Chalmers 100 kW, 113 kVA, 120/208 Bldg. 37, Caterpillar 300 kW, 375 kVA, 120/208v Bldg. 46, Onan 350 kW, 437 kVA, 277/480v Bldg. 101, Caterpillar 210 kW, 263 kVA, 277/480v Bldg. 102, Caterpillar 350 kW, 400 kVA, 277/480v Bldg. 106, Generac 600 kW, 750 kVA, 277/480v

GENERAL REQUIREMENTS

The load banking shall meet the Joint Commission’s requirements and are as follows:

30% of nameplate rating for 2 hours, followed by 50% of nameplate rating for 1 hour, followed by 75% of nameplate ratings for 1 hour, plus warm up and cool down time for a total continuous run of 4 hours.

A written record shall be kept of each generator run. At 15 minute intervals, the following readings will be recorded:

Lube Oil Pressure
Water Temperature
Exhaust Temperature
Amperes
Volts
Frequency

Prior to starting the generators, the contractor shall perform a pre-run inspection to include checking the oil level, coolant level and a visual inspection of the motor/generator.

The contractor will be required to furnish and make the necessary cable connections from the generator to the load bank. This may require parallel runs of cabling. In some locations, this may require barricades, safety cones or both.

A site visit will be required to determine parking, pathways and proper connections to the generator units.

Hours of work will be Monday through Friday, 6:00 AM - 4:00 PM. Government Holidays will not be worked. The target month for this work will be June.

The work performed shall not interrupt any power to the buildings in this Scope of Work.

QUALIFICATIONS OF CONTRACTORS

The contractor shall have technical training and track records of proven experience with generator operations and load banking for a minimum of five (5) continuous years.

The contractor shall have safety training – either on-the-job or class-room type in electrical safety outlined in the OSHA Standard 29 Code of Federal Regulations (CFR) 1910 Subpart S – Electrical and NFPA 70E – Standard of Electrical Safety in the Workplace. Training certifications shall be submitted to the VA Contracting Officer prior to work. If no training certificates are available, the contractor’s employer shall certify that the service technician has met this requirement and submit it to the VA Contracting Officer.

The contractor shall contact the Supervisor of the Electric Shop, Greg Thomas, at (727) 410-4808 to schedule the load banking a minimum of two weeks in advance.

SUMMARY OF WORK

Provide a complete written report of the load banking for each generator. Information in the report shall have the following data:

1. Company’s name, address, telephone number and fax number

2. Name and signature of contractors who performed the load bank.

3. VA purchase order number or Contract Number.

4. Date and time of work.

5. Generator building number.

6. Generator model, Engine model, Nameplate rating

7. The fifteen minute interval log that was that was recorded during the load bank.

8. Description of generator condition and any deficiencies, if any.

*=Required Field
Presolicitation Notice

Presolicitation Notice

File details come from the government source that posted it. Updated .