- J063--Boiler Remote Alarm Panel Install Federal contract opportunity
- Solicitation number
- 36C24824Q1263
About this file
This document is an amendment to a previous combined solicitation for boiler remote alarms issued by the Department of Veterans Affairs Veterans Integrated Service Network 8. The amendment updates the Statement of Work, changes the Cost and Price Schedule, extends the closing date to July 26, 2024 at 4:30 PM Eastern Time, and extends the due date for questions to July 18, 2024 at 4:30 PM Eastern Time.
The key requirements include replacing the DA steam relief valve, installing a remote alarm panel for the DA and surge tank alarms, furnishing and installing 2 new CO monitoring system alarms in the boiler plant, connecting alarms for the natural gas and propane gas high pressure switches, and installing secondary low atomizing media pressure switches on the boilers. The contractor must have 5 years' experience working on hospital boiler plants and all personnel must have the OSHA 10-hour construction safety certification. The work must be performed between 8 AM and 4:30 PM Monday through Friday, excluding federal holidays. Pricing is provided in the Cost and Price Schedule.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Question and Answer Document.pdf | ||
| 36C24824Q1263_3.pdf | ||
| 36C24824Q1263_1.docx | DOCX document | |
| S02 36C24824Q1263.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Amendment to a Previous Combined Solicitation
Amendment to a Previous Combined Solicitation
| SUBJECT* |
| Boiler Remote Alarms |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 32601-3460 |
| SOLICITATION NUMBER* |
| 36C24824Q1263 |
| RESPONSE DATE/TIME/ZONE |
| 07-26-2024 16:30 EASTERN TIME, NEW YORK, USA |
| ARCHIVE |
| 30 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
| SET-ASIDE |
| SBA |
| PRODUCT SERVICE CODE* |
| J063 |
| NAICS CODE* |
| 238210 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
Network Contracting Office 8 (NCO 8)
1601 SW Archer RD Gainesville FL 32608
POINT OF CONTACT*
Contracting Officer John H. Shultzaberger John.Shultzaberger@va.gov 352-214-5135
PLACE OF PERFORMANCE
| ADDRESS |
| Department of Veterans Affairs |
North Florida/South Georgia VHS
Malcom Randall VA Medical Center
1601 SW Archer RD
Gainesville FL
| POSTAL CODE |
| 32608 |
| COUNTRY |
| USA |
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
DESCRIPTION
The Purpose of this Amendment is to Update the Statement of Work, change the Cost and Price Schedule, extend the closing date and the question due date of the solicitation.
1. Closing date of this solicitation is changed from 07-18-2024 at 16:30 Eastern Time to 07-26-2024 at 16:30 Eastern Time.
2. Due date for questions regarding this solicitation is changed from 07-12-2024 at 16:30 Eastern Time to 07-18-2024 at 16:30 Eastern Time.
STATEMENT OF WORK
Background: The Malcom Randall VA Medical Center in Gainesville, The DA and Condensate Alarms only sound off locally. The DA Supply Steam Relief Valve needs to be changed to Cast Steel. The CO Monitors need to alarm out in the Plant.
Objective: Replace the DA Relief Valve and various alarms in the boiler plant as stated below.
Scope of Work:
DA Steam Relief Valve Remove existing Cast Iron Relief Valve on DA Steam Supply Furnish and install new Cast Steel Relief Valve on DA Steam Supply
KUNKLE MODEL 300
Suitable for use on Pressure Vessels 4 Inch 300# Inlet Flange 6 Inch 150# Outlet Flange 9427 Lb/Hr Cast Steel Set Pressure 15 psi
DA and Surge Tank Remote Alarm Panel in Boiler Office:
Contractor will provide and install a remote alarm panel in the Boiler Plant Office.
This panel is for the DA and surge Tank alarms.
Contractor will run conduit and wiring to remote alarm panel from DA and Surge Tank.
DA High Water Alarm will be connected to remote panel and alarm audibly and visually.
DA Low Water Alarm will be connected to remote panel and alarm audibly and visually.
DA Overflow Alarm will be connected to remote panel and alarm audibly and visually.
Surge Tank High Water Alarm will be connected to remote panel and alarm audibly and visually.
Surge Tank Low Water Alarm will be connected to remote panel and alarm audibly and visually.
CO Alarms in the Plant Contractor will furnish and install 2 new MSA CO Monitoring system alarms (audible and visual) in the new Boiler Plant. One on each end of the Boiler Plant.
Contactor will furnish and install conduit and wiring to new CO alarms in the Plant.
Contractor will connect new CO Monitor Alarms to the existing MSA CP Monitoring system. The COR will observe the testing of the Remote Alarms.
Natural Gas Incoming High Gas Pressure alarm The Contractor will connect an audio and visual alarm to the existing High Gas Pressure switch coming into the Plant.
Propane Gas Incoming High Gas Pressure alarm The Contractor will install a High Gas Pressure Switch on the Propane Gas System. The Contractor will install an audio and visual alarm in the Plant, for the Propane High Gas Pressure switch coming in to the Plant.
Low Atomizing Media Pressure Switches The Contractor will install a secondary Low Atomizing Media Pressure Switch on each of the three Boilers. The switch will have to be wired in to the existing Boiler Control System and work when tested.
Provide all documentation to the COR
Preferred Qualifications:
· Technician shall possess 5 years’ experience working on Hospital Boiler Plants to perform the services listed in the SOW.
Required Certifications:
· The contractor and all individuals working on the project site must have taken the OSHA Certified 10-hour construction safety course.
Safety Regulations:
All OSHA safety regulations shall be observed during the project. The VA Safety Officer shall have full authority to see that the contractor obeys all safety rules and regulations relative to the fulfillment of this project. Contractors will wear Safety Harnesses when working over ten feet above the ground. Contractor will ensure all Lockout Tagout procedures in the Plant are followed while doing Electrical Work. Provide the necessary barricades/signage where required.
Scheduling and Hours of Work: All work in areas involved shall be scheduled with the POC. Work will be performed between 0800 and 1630 Monday through Friday except on Federal Holidays. The 11 holidays observed by the Federal Government, are New Years’ Day, Labor Day, Columbus Day, Veterans Day, Thanksgiving Day, Juneteenth, MLK day, Presidents Day, Independence Day and Christmas or any other day specifically declared by the President of the United States to be a national holiday.
Price and Cost Schedule
| Item Number |
| Description of Supplies/Services |
| Quantity |
| Unit |
| Unite Price |
| Amount |
| 0001 |
| Cast Steel DA Steam Relief Valve |
| 1 |
| EA |
| 0002 |
| DA and Surge Tank Remote Alarm Panel |
| 1 |
| EA |
| 0003 |
| CO Alarms |
| 2 |
| EA |
| 0004 |
| Natural Gas Incoming High Gas Pressure Alarm / Audio and Visual |
| 1 |
| EA |
| 0005 |
| Propane Gas Incoming High Gas Pressure Alarm / Audio and Visual |
| 1 |
| EA |
| 0006 |
| Low Atomizing Media Pressure Switches / Secondary Switch |
| 1 |
| EA |
| 0007 |
| Installation |
| 1 |
| SV |