36C24824Q0861.docx

DOCX document 17 KB Posted

Attached to
J044--FY24: HAYS-CLEVELAND BOILER CONTROL SYSTEM REPAIR
Solicitation number
36C24824Q0861
Issued by

About this file

This document is a Presolicitation Notice for a sole source contract to provide repair services for the Hays Cleveland Control System at the Orlando VA Medical Center in Orlando, FL. The Department of Veterans Affairs, Network Contracting Office 8 (NCO 8) intends to negotiate a sole source contract with Venergy Group, LLC of Fort Pierce, FL to repair three boilers operated by the Hays Cleveland Control System, which were installed in 2011 and 2012.

The Hays Universal Programmable Automation Controller (UPAC) provides an operator interface for the boiler control, steam header pressure control, tank level controls, pump sequencers, and plant-wide monitoring. A site survey determined the Plant Master control panel is a single point of failure that will shut down the entire plant upon loss of power. NCO 8 seeks to separate the subsystems to create a more secure and reliable system. This is a one-time service repair effort with a Firm-Fixed Price purchase order. The applicable NAICS code is 238220 - Plumbing, Heating, and Air-Conditioning Contractors, with a small business size standard of $19.0 Million. Interested firms must provide information about their services and customer references by April 30, 2024. The Government will evaluate responses, but retains sole discretion on whether to compete the procurement.

View the file

Other files

File Type Posted
36C24824Q0861 0001.docx DOCX document
ATTACHMENT A HAYS CLEVELAND CONTROL PANELS.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Presolicitation Notice Presolicitation Notice

SUBJECT*
FY24: HAYS-CLEVELAND BOILER CONTROL SYSTEM REPAIR

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
32827
SOLICITATION NUMBER*
36C24824Q0861
RESPONSE DATE/TIME/ZONE
04-30-2024 2:00PM EASTERN TIME, NEW YORK, USA
ARCHIVE
60 DAYS AFTER THE RESPONSE DATE
SET-ASIDE
SDVOSBC
PRODUCT SERVICE CODE*
J044
NAICS CODE*
238220
PLACE OF PERFORMANCE
Department of Veteran Affairs

Orlando VA Healthcare System

13800 Veterans Way

Orlando FL

POSTAL CODE
32827
COUNTRY
USA

CONTACT INFORMATION

CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Network Contracting Office 8 (NCO 8) Orlando VA Healthcare System 13800 Veterans Way Orlando FL 32827

POINT OF CONTACT*

Contract Specialist Jesus Carrillo jesus.carrillo@va.gov

ADDITIONAL INFORMATION

AGENCY’S URL

URL DESCRIPTION

AGENCY CONTACT’S EMAIL ADDRESS

EMAIL DESCRIPTION

DESCRIPTION

The Department of Veterans Affairs, Network Contracting Office 8 (NCO 8) intends to negotiate a sole source contract with Venergy Group, LLC of Fort Pierce, FL to provide repair services to three boilers that are operated by the Hays Cleveland Control Systems (Refer to ATTACHMENTS A). These systems were installed in years 2011 and 2012 at the Orlando VA Medical Center at Lake Nona located at 13800 Veterans Way, Orlando, FL 32827. This Notice of Intent is not a request for competitive quotes. No solicitation documents are available and telephone requests will not be honored. However, if a firm believes it can meet the requirements, it must furnish information as well as references from other customers providing repairs of the same Hays Cleveland Control System.

The Hays Universal Programmable Automation Controller (UPAC) provides an operator interface for each boiler control, steam header pressure control loop, deaerator tank and condensate tank level controls, feedwater pump sequencer, condensate transfer pump sequencer, and various plant-wide flow and pressure monitoring. The boiler plant workstation is supported by a Supervisory Control and Data Acquisition (SCADA) General Electric (GE) Cimplicity based graphical SCADA software package.

After a site survey, it is determined that the Plant Master control panel containing the six control functions listed above is considered a single-point failure that will shut the plant down upon loss of power to the control panel, ceasing all steam generation. Separating the various subsystems such as the tank level controls, and pump controls, and returning the operator interface to the individual boilers, will result in a sensible and secure system that cannot be shut down by a single failure. The feedwater pump sequencer in the plant master is not being utilized, and pumps are turned on manually by the operator with the Manual / Off / Auto selector switches on the plant master panel.

NCO 8 anticipates awarding a Firm Fixed Priced purchase order for a one-time service repair. This procurement is being conducted in accordance with FAR 13.106-1(b)(1)(i), Soliciting from a single source. The applicable North American Industry Classification System (NAICS) Code is 238220– Plumbing, Heating, and Air-Conditioning Contractors, with a small business size standard of $19.0 Million.

This Notice of Intent is not a request for competitive quotes. No solicitation documents are available; however, Contractors are encouraged to join us on Microsoft Team on April 22, 2024, from 09:30 AM to 10:00 AM for discussions by dialing +1 872-701-0185, phone conference ID: 491854034 or emailing Contract Specialist Jesus M. Carrillo no later than 2:00PM April 19, 2024, to added to the meeting invite for April 22, 2024. If a firm believes it can meet the requirements it must furnish information about its services, as well as references from other customers. Supporting evidence must be furnished in sufficient detail to demonstrate the ability to comply with the above requirement. Submit responses to Contract Specialist, Jesus M. Carrillo, jesus.carrillo@va.gov, and Contracting Officer rohan.mckenzie@va.gov no later than 2:00 PM, EST April 30, 2024.

Responses received will be evaluated; however, a determination by the Government not to compete the proposed procurement based upon responses to this notice is solely within the discretion of the Government. If no responses are received, NCO 8 will proceed with the sole source negotiation with Venergy Group LLC.

See attached document: ATTACHMENT A HAYS CLEVELAND CONTROL PANELS.

*=Required Field
Presolicitation Notice

Presolicitation Notice

File details come from the government source that posted it. Updated .