4890 west kennedy boulevard suite 930 tampa, fl 33609 voice 813-383-5500 fax 813-383-5515 schenkelshultz.com SS Lic No - AA-C000937
ARCHITECTURAL
INFORMATION
Permit Set Documents
0920805
VA Clinic Expansion & Community Pharmacy Citrus County Resource Center - C Wing 2804 W. Marc Knighton Court Lecanto, Florida 34461
Citrus County 3600 W. Sovereign Path Lecanto, Florida 34461
NK
KT
SCHENKELSHULTZ
A R C H I T E C T U R E comm. no.:
date:
checked:
drawn:
ALL IDEAS, DESIGNS, ARRANGEMENTS AND PLANS INDICATED OR REPRESENTED BY
THIS DRAWING ARE OWNED BY AND THE PROPERTY OF SCHENKELSHULTZ AND WERE
CREATED, EVOLVED, AND DEVELOPED FOR USE ON AND IN CONNECTION WITH THE
SPECIFIED PROJECT. NONE OF THE IDEAS, DESIGNS, ARRANGEMENTS OR PLANS SHALL
BE USED BY OR DISCLOSED TO ANY PERSON, FIRM, OR CORPORATION FOR ANY
PURPOSE WHATSOEVER WITHOUT THE WRITTEN PERMISSION OF SCHENKELSHULTZ.
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE
DIMENSIONS. CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF
ANY VARIATION FROM THE DIMENSIONS AND CONDITIONS SHOWN BY THESE
DRAWINGS. REVIEW OF SHOP DRAWINGS DOES NOT RELIEVE THE CONTRACTOR FROM
THE REQUIREMENT OF MEETING OR EXCEEDING THE PLANS AND SPECIFICATIONS .
CONFIDENTIAL COPYRIGHT 2006 SCHENKELSHULTZ. WARNING: REPRODUCTION
HEREOF IS A CRIMINAL OFFENSE UNDER 18 U.S.C. SEC. 506. UNAUTHORIZED
DISCLOSURE MAY CONSTITUTE A VIOLATION OF APPLICABLE STATE AND FEDERAL LAW.
THE IDEAS, ARRANGEMENTS AND DESIGNS DISCLOSED HEREIN MAY BE PATENTED OR
BE THE SUBJECT OF PENDING PATENT APPLICATION.
SYMBOLS
ARCHITECTURAL GENERAL NOTES
1. EACH CONTRACTOR SHALL VERIFY ALL DIMENSIONS SHOWN ON THE DRAWINGS AND OBTAIN ALL MEASUREMENTS REQUIRED FOR PROPER EXECUTION OF
WORK. WHEN VERIFICATION OF EXISTING DIMENSIONS IS REQUIRED, THE CONTRACTOR REQUIRING SAID VERIFICATION FOR THE CONSTRUCTION OR FABRICATION OF HIS MATERIAL SHALL BE THE CONTRACTOR RESPONSIBLE FOR THE PROCUREMENT OF THE FIELD INFORMATION.
2. PROVIDE ALL WOOD BLOCKING NECESSARY FOR THE ATTACHMENT OF MISCELLANEOUS EQUIPMENT INCLUDING BUT NOT LIMITED TO TOILET ACCESSORIES, DOOR HARDWARE, ELECTRICAL DEVICES, LABORATORY EQUIPMENT, GRAB BARS, HANDRAILS, CASEWORK AND MILLWORK.
3. THE TRANSITION OF DIFFERENT FLOORING MATERIALS AT A DOORWAY SHALL OCCUR AT THE CENTERLINE OF DOOR UNLESS INDICATED OTHERWISE.
4. ALL WALL SURFACES, DOOR FRAMES, BULKHEADS AND CEILINGS SHALL RECEIVE PAINT WHEN PAINT IS INDICATED ON THE FINISH SCHEDULE OR FINISH PLANS.
PAINT SURFACES BEHIND MOVABLE EQUIPMENT AND FURNITURE TO BE SAME AS SIMILAR EXPOSED SURFACES. PAINT SURFACES BEHIND PERMANENTLY FIXED EQUIPMENT OR FURNITURE WITH PRIME COAT ONLY BEFORE FINAL INSTALLATION OF EQUIPMENT. PAINT ALL MECHANICAL AND ELECTRICAL EQUIPMENT
EXPOSED IN FINISHED SPACES UNLESS INDICATED OTHERWISE.
5. REPAIR ALL SURFACES DAMAGED BY RENOVATION AND NEW CONSTRUCTION TO MATCH EXISTING ADJACENT OR CONTIGUOUS FINISH.
6. ALL CUTTING AND PATCHING AS A RESULT OF NEW CONSTRUCTION OR DEMOLITION SHALL BE PERFORMED IN A WORKMANLIKE MANNER, AND SHALL MATCH IN
COLOR, SHAPE, SIZE AND TEXTURE ADJACENT AND/OR CONTIGUOUS FINISHED SURFACES.
7. FIGURED DIMENSIONS TAKE PRECEDENCE OVER SCALED MEASUREMENTS. DO NOT SCALE DRAWINGS.
8. DETAILED DRAWINGS AND LARGER SCALE DRAWINGS TAKE PRECEDENCE OVER SMALL SCALE DRAWINGS.
9. UNLESS OTHERWISE NOTED, PLAN DIMENSIONS ARE TAKEN FROM FACE OF CMU OR CONCRETE TO FACE OF STUD, OR FACE OF STUD TO FACE OF STUD.
10. DOORS NOT OTHERWISE DIMENSIONED SHALL BE 8" FROM FACE OF ADJACENT CMU OR CONCRETE WALL TO ROUGH DOOR OPENING, AND 2" FROM FACE OF
ADJACENT STUD WALL TO ROUGH DOOR OPENING.
11. FOR CONSTRUCTION DETAILS NOT SHOWN, USE THE PRODUCT MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS AND STANDARD DETAILS, IN STRICT
ACCORDANCE WITH THE PROJECT SPECIFICATION REQUIREMENTS AND DESIGN INTENT.
12. PROVIDE FIRE EXTINGUISHERS FE AND FIRE EXTINGUISHER CABINETS FEC AS INDICATED ON THE PLANS. PROVIDE TYPE AND SIZE AS SPECIFIED. MOUNT AT
42" AFF TO TOP OF FE AND 48" AFF TO TOP OF FEC
WALL TYPE IDENTIFICATION SYSTEM
GENERAL DEMOLITION NOTES
1. CONTRACTOR SHALL REVIEW FINAL CONDITIONS REQUIRED AND PROVIDE ALL DEMOLITION WORK, PATCHING AND REPAIRING AS NECESSARY.
2. ALL ELECTRICAL, MECHANICAL AND PLUMBING SERVICES LOCATED IN WALLS, CEILINGS, OR FLOORS TO BE REMOVED SHALL BE CAPPED AND REROUTED AS
REQUIRED FOR NEW CONDITIONS AND IN ACCORDANCE WITH APPLICABLE CODES.
3. CONTRACTOR SHALL PROVIDE ALL NECESSARY DEMOLITION FOR NEW PLUMBING, MECHANICAL AND ELECTRICAL WORK AS REQUIRED. COORDINATE WITH
CONSTRUCTION DOCUMENTS FOR NEW CONSTRUCTION.
4. REMOVE ALL EXISTING FLOOR FINISHES AND PREPARE SLAB TO RECEIVE NEW FLOOR FINISHES IN ACCORDANCE WITH THE NEW FLOOR FINISH
MANUFACTURERS' WRITTEN RECOMMENDATIONS UNLESS NOTED OTHERWISE.
5. DEMOLITION / RESTORATION ITEMS MAY NOT BE ALL INCLUSIVE. THE DEMOLITION CONTRACTOR SHALL REVIEW THE REQUIREMENTS OF NEW CONSTRUCTION AND COMPLETE ALL DEMOLITION / RESTORATION, CUTTING AND PATCHING NECESSARY TO ACHIEVE INTENDED NEW CONDITION AND QUALITY.
6. REMOVE FROM BUILDING SITE ALL DEBRIS, RUBBISH AND OTHER MATERIALS RESULTING FROM DEMOLITION OPERATIONS. TRANSPORT AND LEGALLY DISPOSE
OF OFF SITE. PROVIDE THE OWNER WITH THE RIGHT OF FIRST REFUSAL.
7. ALL DEMOLITION WORK INDICATED ON THE DEMOLITION PLANS SHALL BE FIELD VERIFIED BY THE CONTRACTOR PRIOR TO COMMENCING WORK.
8. RELOCATION OF ANY ITEMS INVOLVED IN THE WORK IS SUBJECT TO THE CONTRACTOR'S ABILITY TO DO SO WITHOUT PERMANENTLY DAMAGING OR MARRING THE ITEMS TO BE RELOCATED. IF THE CONTRACTOR IS UNABLE TO RELOCATE ANY ITEM AS PRESCRIBED HEREIN, S/HE SHALL CONSULT ARCHITECT FOR
DIRECTION. SAFELY STORE MATERIAL TO BE REUSED UNTIL TIME OF INSTALLATION.
9. CONTRACTOR SHALL PROTECT ALL STRUCTURAL MEMBERS FROM DAMAGE.
ABBREVIATIONS
AB ANCHOR BOLTS
ABBREV ABBREVIATION(S)
AC AIR CONDITIONING
ACOUS ACOUSTICAL
AD ACCESS DOOR
A/E ARCHITECT/ENGINEER
AFF ABOVE FINISHED FLOOR
ALUM ALUMINUM
APPR APPROVED
APPROX APPROXIMATELY
BD BOARD
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BM BENCHMARK
BOB BOTTOM OF BEAM
BOC BOTTOM OF CURB
BOT BOTTOM
BUR BUILT-UP ROOFING
C/C CENTER TO CENTER
CEM CEMENT
CH CEILING HEIGHT
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMP COMPOSITION
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CORR CORRIDOR
CORS COURSE, COURSES
CSK COUNTERSINK
CT CERAMIC TILE
CUST CUSTODIAL
DBL DOUBLE
DEG DEGREE
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIR DIRECTION
DN DOWN
DO DOOR OPENING
DR DOOR
DS DOWNSPOUT
DWG DRAWING
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXT EXTERIOR
EWC ELEC WATER COOLER
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FH FULL HEIGHT
FHC FIRE HOSE CABINET
FIN FINISH
FLR FLOOR
FO FINISHED OPENINIG
FOC FACE OF CONCRETE
FOS FACE OF STUD
FOW FACE OF WALL
FRP FIBER REINFORCED PLASTIC
FS FLOOR SINK
FSD FULL SIZE DETAIL
FT FOOT/FEET
FTG FOOTING
R RISER
R RADIUS
RD ROOF DRAIN
REF REFERENCE
REFL REFLECTED
REINF REINFORCED
REQD REQUIRED
RES RESILIENT
RL RAIN LEADER
RM ROOM
RO ROUGH OPENING
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SHT SHEET
SIM SIMILAR
SIMUL SIMULATED
SJ SAW JOINT
SPECS SPECIFICATIONS
SS STAINLESS STEEL
SQ SQUARE
STA STATION
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SYM SYMMETRICAL
T TREAD
T & G TONGUE & GROOVE
TDC TRAFFIC DECK COVERING
TEL TELEPHONE
TEMP TEMPERED
THK THICK
TJ TOOLED JOINT
TOC TOP OF CONCRETE
TOC TOP OF CURB
TOJ TOP OF JOIST
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOS TOP OF STEEL
TOW TOP OF WALL
TYP TYPICAL
UL UNDERWRITERS
LABORATORY
UNO UNLESS NOTED OTHERWISE
VER VERIFY
VERT VERTICAL
VEST VESTIBULE
W WIDE
W/ WITH
WC WATER CLOSET
WD WOOD
WI WROUGHT IRON
WL WATER LEVEL
W/O WITHOUT
WP WORKING POINT
WP WATERPROOFING
YR YEAR
GA GAUGE
GALV GALVANIZED
GR GRADE
GYP GYPSUM
H HIGH
HC HOLLOW CORE
HDWD HARDWOOD
HDWE HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HIGH POINT
HT HEIGHT
ID INSIDE DIAMETER
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
JAN JANITOR
LAV LAVATORY
LB POUND
LEV LEVEL
LF LINEAR FEET
LTG LIGHTING
LTWT LIGHT WEIGHT
LVR LOUVER
MAINT MAINTENANCE
MAT MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MECH MECHANICAL
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MTL METAL
MULL MULLION
N NEW
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NR NON-RATED
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OWNER FURNISHED
OFF OFFICE
OH OPPOSITE HAND
OPN'G OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
PC PORTLAND CEMENT
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTIC
PLYWD PLYWOOD
PNT PAINT
PR PAIR
PREP PREPARATION
PROJ PROJECTION
QT QUARRY TILE
EXTENT OF WALL TYPE M
EX
TE
NT
O
F W
AL
L T
YP
E
M
EX
TE
NT
O
F W
AL
L
TY
PE
X 2 (
TO
CO
RN
ER
O R
TA
G)
EX
TE
NT
O
F W
AL
L T
YP
E
X1
EXTENT OF WALL TYPE X3
(TO CORNER OR TAG)
EXTENT OF
WALL TYPE X2
EX
TE
NT
O
F W
AL
L T
YP
E
X
X1
X3X2 X3
X2
A-111
A-111
A-111
A-111
1 1/8"=1'-0"
DETAIL
A-111
STORAGE
1-123
100 SF
BUILDING NUMBER
DOOR NUMBER
DOOR NUMBER SUFFIX
S1
PARTITION TYPE
ROOM NAME
ROOM NUMBER
AREA
LETTER FOR WINDOW
NUMBER FOR LOUVER
KEY
CEILING HEIGHT FROM FLOOR
EXTERIOR ELEVATION DETAIL NUMBER
SHEET WHERE ELEVATION IS DRAWN
CONTRACT FURNISHED, CONTRACT INSTALLED
OWNER FURNISHED, CONTRACT INSTALLED
OWNER FURNISHED, OWNER INSTALLED
CONTRACT FURNISHED, OWNER INSTALLED
WALL FINISH ON THIS WALL IF WALL FINISHES VARY
WALL FINISH IF ALL WALLS THE SAME
(DASHES IF WALL FINISHES VARY)
BASE FINISH
FLOOR FINISH
DRAWING IDENTIFICATION NUMBER
DRAWING SCALE
DETAIL TITLE
SECTION NUMBER
SHEET WHERE SECTION IS DRAWN
DETAIL NUMBER
SHEET WHERE DETAIL IS DRAWN
DETAIL NUMBER
SHEET WHERE DETAIL IS DRAWN
AREA TO BE DETAILED OR ENLARGED
REVISION NUMBER
REVISED AREA CLOUDED
ELEVATION LOCATION
SHEET WHERE ELEVATION IS DRAWN
100 SF
ROOM SQUARE FOOTAGE
SQUARE FEET PER OCCUPANT
MAXIMUM NUMBER OF OCCUPANTS
Electrical Julius D. Davis, PE
Mechanical Jorge L. Rivera, PE
Plumbing Jorge L. Rivera, PE
Architectural Khashayar Teimouri, AIA
Architecture Mechanical Engineering
Electrical Engineering Plumbing Engineering
Schenkel Shultz Architecture VoltAir Consulting Engineers sheet index
VoltAir Consulting Engineers VoltAir Consulting Engineers
ARCHITECTURAL
A-01 ARCHITECTURAL INFORMATION
A-011 WALL TYPES
A-02 LIFE SAFETY PLAN
A-10 DEMOLITION PLAN
A-11 NEW FLOOR PLAN
A-20 RFLECTED CEILING PLAN
A-30 FINISH PLAN
A-40 EQUIPMENT AND SIGNAGE PLAN
A-50 ENLARGED PLAN, UNTERIOR ELEVATIONS AND DETAILS
A-60 DOOR WINDOW SCHEDULES AND DETAILS
STRUCTURAL
S-01 GENERAL STRUCTURAL NOTES
S-02 DEMO & NEW CONSTRUCTION
S-03 SECTIONS & DETAILS
S-04 SECTIONS & DETAILS
ELECTRICAL
E-01 ELECTRICAL LEGEND AND SCHEDULES
E-10 DEMOLITION PLAN - POWER
E-11 DEMOLITION PLAN - LIGHTING
E-12 FLOOR PLAN - POWER
E-13 FLOOR PLAN - LIGHTING
MECHANICAL
M-01 HVAC LEGEND SYMBOLS AND NOTES
M-10 DEMOLITION PLAN - HVAC
M-11 FLOOR PLAN - HVAC
M-20 DETAILS - HVAC
PLUMBING
P-01 PLUMBING LEGEND SYMBOLS AND NOTES
P-10 DEMOLITION PLAN - GRAVITY
P-11 DEMOLITIOM PLAN - PRESSURE
P-12 FLOOR PLAN - GRAVITY PIPING
P-13 FLOOR PLAN - PRESSURE PIPING
P-20 DETAILS - PLUMBING
P-21 DETAILS - PLUMBING
FIRE PROTECTION
FP-01 FIRE PROTECTION LEGEND SYMBOLS AND NOTES
FP-11 FLOOR PLAN - FIRE PROTECTION
consultants citrus county board members:
Gary Bartell Dennis Damato
Vicki Phillips John Thrumston Joyce Valentino
Structural Engineering Master Consulting Engineers
July 15, 2009
1/2" = 1'-0"
WALL TYPE S1 / S1A - NON-RATEDS1
6"
CEILING AS
SCHEDULED
PLAN
SILL
HEAD
ONE LAYER OF 5/8" GYPSUM
WALLBOARD ON EACH SIDE OF
3 5/8" METAL STUDS @ 16" O.C.
BASE AS SCHEDULED
SOUND ATTENUATION BATT
INSULATION AT WALLS
DESIGNATED S1A
4 7/8"
ACOUSTICAL SEALANT @
TYPE S1a WALLS
PLAN
DETAIL
PLAN
SYMBOL
3 5/8" STUD BRACING
1/2" = 1'-0"
WALL TYPE S3 / S3A - NON-RATEDS3
CEILING AS
SCHEDULED
PLAN
SILL
BASE AS SCHEDULED
SOUND ATTENUATION BATT
INSULATION AT WALLS
DESIGNATED S7a - FULL HEIGHT
2 1/ 4"
ACOUSTICAL SEALANT @
TYPE S7a WALLS
PLAN
DETAIL
PLAN
SYMBOL
ONE LAYER OF 5/8" GYPSUM
WALLBOARD ON 1 5/8" METAL
STUDS @ 16" O.C.
1/2" = 1'-0"
WALL TYPE S4 / S4A - SMOKE PARTITIONS4
CEILING AS
SCHEDULED
PLAN
SILL
HEAD
BASE AS SCHEDULED
SOUND ATTENUATION BATT
INSULATION AT WALLS
DESIGNATED S6a - FULL HEIGHT
ACOUSTICAL SEALANT @
TYPE S6a WALLS
PLAN
DETAIL
PLAN
SYMBOL
ONE LAYER OF 5/8" GYPSUM
WALLBOARD ON EACH SIDE OF
8" METAL STUDS @ 16" O.C.
8"
1/2" = 1'-0"
WALL TYPE S2 / S2A - NON-RATEDS2
CEILING AS
SCHEDULED
PLAN
SILL
HEAD
BASE AS SCHEDULED
SOUND ATTENUATION BATT
INSULATION AT WALLS
DESIGNATED S9a - FULL HEIGHT
ACOUSTICAL SEALANT @
TYPE S9a WALLS
PLAN
DETAIL
PLAN
SYMBOL
ONE LAYER OF 5/8" GYPSUM
WALLBOARD ON EACH SIDE OF
6" METAL STUDS @ 16" O.C.
6"
3 5/8" STUD BRACING
1/2" = 1'-0"
WALL TYPE S5 / S5A - 1 HR RATED SHAFT WALL UL 499S6
CEILING AS
SCHEDULED
BASE AS SCHEDULED
1" TYPE X GYPSUM BOARD
LINER
FIRE CAULKING CONT.
ACOUSTICAL SEALANT @
TYPE S8a WALLS
PLAN
DETAIL
PLAN
SYMBOL
ONE LAYER OF 5/8" TYPE X
GYPSUM WALLBOARD ON 2 1/2"
C-H METAL STUDS @ 16" O.C.
2 1/2"
PROVIDE 48" SOUND ATUNIATION
GLASSFIBER BLANKET ON BOTH
SIDES AND OVER WALL LENGHTH
PROVIDE 48" SOUND ATUNIATION
GLASSFIBER BLANKET ON BOTH
SIDES AND OVER WALL LENGHTH
1/2" = 1'-0"
WALL TYPE S5 / S5A - ONE HOUR RATED WALL UL # U465S5
CEILING AS
SCHEDULED
PLAN
SILL
BASE AS SCHEDULED
SOUND ATTENUATION BATT
INSULATION AT WALLS
DESIGNATED S6a - FULL HEIGHT
ACOUSTICAL SEALANT @
TYPE S6a WALLS
PLAN
DETAIL
PLAN
SYMBOL
ONE LAYER OF 5/8" GYPSUM
WALLBOARD ON EACH SIDE OF
8" METAL STUDS @ 16" O.C.
8"
FIRE CAULKING CONT. TYP.
STEEL COLUMN WHERE OCCURS
WITH FIREPRROFING SPRAY
UL # Y733
STEEL COLUMN WHERE OCCURS
WITH FIREPRROFING SPRAY
UL # Y733
7 1 /4"
7 1 /4" 9 1/4" 4 1/ 8" 1" + /-
FROM F.O.
GWB
AT EXISTING
WALL
4890 west kennedy boulevard suite 930 tampa, fl 33609 voice 813-383-5500 fax 813-383-5515 schenkelshultz.com SS Lic No - AA-C000937
WALL TYPES
Permit Set Documents
0920805
VA Clinic Expansion & Community Pharmacy Citrus County Resource Center - C Wing 2804 W. Marc Knighton Court Lecanto, Florida 34461
Citrus County 3600 W. Sovereign Path Lecanto, Florida 34461
NK
KT
SCHENKELSHULTZ
A R C H I T E C T U R E comm. no.:
date:
checked:
drawn:
ALL IDEAS, DESIGNS, ARRANGEMENTS AND PLANS INDICATED OR REPRESENTED BY
THIS DRAWING ARE OWNED BY AND THE PROPERTY OF SCHENKELSHULTZ AND WERE
CREATED, EVOLVED, AND DEVELOPED FOR USE ON AND IN CONNECTION WITH THE
SPECIFIED PROJECT. NONE OF THE IDEAS, DESIGNS, ARRANGEMENTS OR PLANS SHALL
BE USED BY OR DISCLOSED TO ANY PERSON, FIRM, OR CORPORATION FOR ANY
PURPOSE WHATSOEVER WITHOUT THE WRITTEN PERMISSION OF SCHENKELSHULTZ.
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE
DIMENSIONS. CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF
ANY VARIATION FROM THE DIMENSIONS AND CONDITIONS SHOWN BY THESE
DRAWINGS. REVIEW OF SHOP DRAWINGS DOES NOT RELIEVE THE CONTRACTOR FROM
THE REQUIREMENT OF MEETING OR EXCEEDING THE PLANS AND SPECIFICATIONS .
CONFIDENTIAL COPYRIGHT 2006 SCHENKELSHULTZ. WARNING: REPRODUCTION
HEREOF IS A CRIMINAL OFFENSE UNDER 18 U.S.C. SEC. 506. UNAUTHORIZED
DISCLOSURE MAY CONSTITUTE A VIOLATION OF APPLICABLE STATE AND FEDERAL LAW.
THE IDEAS, ARRANGEMENTS AND DESIGNS DISCLOSED HEREIN MAY BE PATENTED OR
BE THE SUBJECT OF PENDING PATENT APPLICATION.
WALL TYPE NOTES
1. PROVIDE THROUGH-PENETRATION FIRESTOP SYSTEMS AND THROUGH-PENETRATION FIRESTOP DEVICES, SEALANTS AND RELATED PRODUCTS FOR FIRE-RATED FLOOR AND WALL PENETRATIONS (AND SEALING TOP OF RATED WALLS TO DECK). THIS WORK ALSO INCLUDES FIRESTOPPING AT NEW PENETRATIONS THROUGH EXISTING FIRE-RATED WALLS AND FLOORS. ALL RATED WALL PENETRATIONS SHALL MAINTAIN THE INTEGRITY OF THE WALL
ASSEMBLY.
2. PROVIDE ACOUSTICAL SEALANT AT ALL WALLS WITH SOUND ATTENUATION BLANKETS.
3. ALL STUDS SHALL BE SPACED AT 16" O.C. UNLESS NOTED OTHERWISE. ALL FURRING CHANNELS SHALL BE
SPACED AT 24" O.C. UNLESS NOTED OTHERWISE.
4. WHERE TWO LAYERS OF GYPSUM BOARD OCCUR IN A NON-RATED WALL ASSEMBLY, TAPE AND FINISH SECOND
LAYER ONLY.
5. PROVIDE CONSTRUCTION IN ACCORDANCE WITH THE UL DESIGN NUMBER INDICATED.
6. WHERE CHASE, PILASTER, AND COLUMN ENCLOSURES OCCUR, GYPSUM BOARD MAY BE OMITTED ON CONCEALED
SIDE UNLESS REQUIRED FOR FIRE RATING.
7. WHERE GYPSUM BOARD ABUTS CMU CONSTRUCTION, PROVIDE CONTINUOUS J-MOLD AND SEALANT AT JOINT.
July 15, 2009
Fire Resistance Ratings - ANSI/UL 263 Design No. Y733
July 03, 2008
Ratings — 1, 1-1/2, 2, 3 and 4 Hr
1.Steel Pipe or Steel Tube — Steel circular pipe (SP) or steel square or rectangular tube (ST) of min sizes as shown in the table below.
2. Spray-Applied Fire Resistive Materials* — Applied by mixing with water and spraying in more than one coat to the thickness shown below, to steel surfaces which are clean and free of dirt, loose scale and oil. Min avg and min ind density of 18/16 pcf for Type PMCP2 and 23/21 pcf for Type PMP20. For method of density see Design Information Section, Sprayed Material.
CAFCO INTERNATIONAL L L C — Types PMCP2 or PMP20.
CAFCO INTERNATONAL, DIV OF PROMAT UK
LTD — Types PMCP2 or PMP20.
FLAMTECHNIC CO LTD — Types PMCP2 or PMP20.
MOY YUAN INDUSTRIAL LTD — Types PMCP2 or PMP20.
NEWKEM PRODUCTS CORP — Types PMCP2 or PMP20.
PROSTAR CONTRACT SERVICES PTE LTD — Types PMCP2 or PMP20.
P T HUME CONCRETE INDONESIA — Types PMCP2 or PMP20.
SHIN SUNG TRADING CO LTD — Types PMCP2 or PMP20.
*Bearing the UL Classification Mark
1. Floor and Ceiling Runners — (not shown) — Channel shaped runners, 3-5/8 in. wide (min), 1-1/4 in. legs, formed from min No. 25 MSG galv steel, attached to floor and ceiling with fasteners spaced 24 in. OC max.
1A. Framing Members*— Floor and Ceiling Runners — (Not shown) — As an alternate to Item 1 - Channel shaped, min. 3-5/8 in. wide, attached to floor and ceiling with fasteners 24 in. OC. max.
SCAFCO STEEL STUD MANUFACTURING CO — Type SUPREME Framing System
1B. Framing Members - Floor and Ceiling Runner* — Not shown - In lieu of Item 1 — For use with Item 2B, proprietary channel shaped runners, 1-1/4 in.
deep by 3-5/8 in. wide fabricated from min 0.0200 in. thick galv steel, attached to floor and ceiling with fasteners spaced 24 in. OC max.
MARINO\WARE A DIV OF WARE INDUSTRIES INC — Viper20S™ Track, Viper20D™ Track
2. Steel Studs — Channel shaped, 3-5/8 in. wide (min), 1-1/4 in. legs, 3/8 in. folded back returns, formed from min No. 25 MSG galv steel spaced 24 in.
OC max. Studs to be cut 3/4 in. less than assembly height.
2A. Framing Members*— Steel Studs — As an alternate to Item 2 - Channel shaped studs, min. 3-5/8 in. wide, spaced a max of 24 in. OC. Studs to be cut 3/4 in. less than assembly height.
SCAFCO STEEL STUD MANUFACTURING CO — Type SUPREME Framing System
2B. Framing Members - Metal Studs* — Not shown - In lieu of Item 2 — For use with Item 1B, proprietary channel shaped steel studs, 1-1/4 in. deep by 3-5/8 in. wide fabricated from min 0.0200 in. thick galv steel. Studs 3/4 in. less in lengths than assembly heights.
MARINO\WARE A DIV OF WARE INDUSTRIES INC — Viper20S™, Viper20D™
3. Batts and Blankets* — (Optional) — Mineral wool or glass fiber batts partially or completely filling stud cavity.
See Batts and Blankets (BZJZ) category for names of Classified companies.
3A. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 3) — Spray applied cellulose material. The fiber is applied with water to completely fill the enclosed cavity in accordance with the application instructions supplied with the product. Nominal dry density of 3.0 lb/ft3. Alternate application method: The fiber is applied with U.S. Greenfiber LLC Type AD100 hot melt adhesive at a nominal ratio of one part adhesive to 6.6 parts fiber to completely fill the enclosed cavity in accordance with the application instructions supplied with the product. Nominal dry density of 2.5 lb/ft3.
U S GREENFIBER L L C — Cocoon2 Stabilized or Cocoon-FRM (Fire Rated Material)
3B. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 3) and Item 3A - Spray applied cellulose insulation material. The fiber is applied with water to interior surfaces in accordance with the application instructions supplied with the product. Applied to completely fill the enclosed cavity.
Minimum dry density of 4.3 pounds per cubic ft.
NU-WOOL CO INC — Cellulose Insulation
4. Gypsum Board* — 5/8 in. thick, 4 ft wide, attached to steel studs and floor and ceiling track with 1 in. long, Type S steel screws spaced 8 in. OC.
along edges of board and 12 in. OC in the field of the board. Joints oriented vertically and staggered on opposite sides of the assembly. When attached to item 6 (resilient channels) or 6A (furring channels), wallboard is screw attached to furring channels with 1 in. long, Type S steel screws spaced 12 in.
OC.
AMERICAN GYPSUM CO — Types AG-C, AGX-1
BEIJING NEW BUILDING MATERIALS PUBLIC LTD CO — Type DBX-1.
CANADIAN GYPSUM COMPANY — Types AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, WRC or WRX.
CERTAINTEED GYPSUM INC — Types 1, EGRG, ProRoc Type X, ProRoc Type C.
CERTAINTEED GYPSUM CANADA INC — ProRoc Type C, ProRoc Type X or ProRoc Type Abuse-Resistant.
GEORGIA-PACIFIC GYPSUM L L C — Types 5, 9, C, DAP, DD, DA, DAPC, DGG, DS, GPFS6.
LAFARGE NORTH AMERICA INC — Types LGFC2, LGFC2A, LGFC6, LGFC6A, LGFC-C, LGFC-C/A.
NATIONAL GYPSUM CO — Types FSK, FSK-C, FSK-G, FSW-C, FSW-G, FSW, FSW-3, FSW-5, FSW-6.
PABCO BUILDING PRODUCTS L L C, DBA
PABCO GYPSUM — Type PG-C, PG-11 or PG-9.
PANEL REY S A — Type PRX.
SIAM GYPSUM INDUSTRY (SARABURI) CO LTD — Type EX-1
TEMPLE-INLAND FOREST PRODUCTS CORP — Type X, Veneer Plaster Base - Type X, Water Rated - Type X, Sheathing - Type X, Soffit - Type X, TG-C, GreenGlass Type X.
UNITED STATES GYPSUM CO — Type AR, C, FRX-G, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, WRC, WRX, USGX (Joint tape and compound, Item 5, optional for use with Type USGX).
USG MEXICO S A DE C V — Type AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, WRC or WRX.
4A. Gypsum Board* — (As alternate to Item 4) - Nom 5/8 in. thick gypsum panels with beveled, square or tapered edges, applied vertically or horizontally. Vertical joints centered over studs and staggered one stud cavity on opposite sides of studs. Horizontal edge joints and horizontal butt joints on opposite sides of studs need not be staggered or backed by steel framing. Panels attached to steel studs and floor runner with 1 in. long Type S steel screws spaced 8 in. OC when applied horizontally, or 8 in. OC along vertical and bottom edges and 12 in. OC in the field when panels are applied vertically. When used in widths other than 48 in., gypsum panels to be installed horizontally.
CANADIAN GYPSUM COMPANY — Types AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, WRC or WRX.
CERTAINTEED GYPSUM INC — ProRoc Type X, ProRoc Type C.
CERTAINTEED GYPSUM CANADA INC — ProRoc Type X, ProRoc Type C.
GEORGIA-PACIFIC GYPSUM L L C — Types DAP, DAPC, DGG, DS.
LAFARGE NORTH AMERICA INC — Type LGFC6A, LGFC-C/A
UNITED STATES GYPSUM CO — T ype AR, C, FRX-G, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, WRC, WRX, , USGX (Joint tape and compound, Item 5, optional for use with Type USGX).
USG MEXICO S A DE C V — Type AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, WRC or WRX.
4B. Gypsum Board* — (As an alternate to Items 4 or 4A) — Nom 3/4 in. thick, 4 ft wide, installed as described in Item 4A with screw length increased to 1-1/4 in.
CANADIAN GYPSUM COMPANY — Types AR, IP-AR.
UNITED STATES GYPSUM CO — Types AR, IP-AR.
USG MEXICO S A DE C V — Types AR, IP-AR.
4C. Gypsum Board* — As an alternate to Items 4, 4A, and 4B - Nom. 5/8 in. thick gypsum panels, with square edges, applied horizontally. Gypsum panels fastened to framing with 1 in. long bugle head steel screws spaced a max 8 in. OC, with last 2 screws 3/4 in. and 4 in. from each edge of board.
Horizontal joints need not be backed by steel framing. Horizontal edge joints and horizontal butt joints on opposite sides of studs on interior walls need not be staggered or backed by steel framing.
TEMPLE-INLAND FOREST PRODUCTS CORP — GreenGlass Type X.
4D. Gypsum Board* — As an alternate to Items 4, 4A, 4B, and 4C - Nom. 5/8 in. thick gypsum panels applied horizontally. Horizontal joints need not be backed by steel framing. Horizontal edge joints and horizontal butt joints on opposite sides of studs need not be staggered. Gypsum panels fastened to framing with 1 in. long Type S steel screws 1-1/2 in. from board edges, 3 in. from board edge and every 8 in. OC in the field. Screws spaced a max 12 in.
along the top and bottom edges of the wall.
NATIONAL GYPSUM CO — Types FSK, FSK-C, FSK-G, FSW-C, FSW-G, FSW.
5. Joint Tape and Compound — Vinyl, dry or premixed joint compound, applied in two coats to joints and screw heads; paper tape, 2 in. wide, embedded in first layer of compound over all joints. As an alternate, nominal 3/32 in. thick gypsum veneer plaster may be applied to the entire surface of Classified veneer baseboard. Joints reinforced. Paper tape and joint compound may be omitted when gypsum boards are supplied with square edges.
6. Resilient Channel — (Optional-Not Shown) — 25 MSG galv steel resilient channels spaced vertically max 24 in. OC, flange portion attached to each intersecting stud with 1/2 in. long type S-12 panhead steel screws.
6A. Steel Framing Members (Not Shown)* — As an alternate to Item 3, furring channels and resilient sound isolation clip as described below:
a. Furring Channels — Formed of No. 25 MSG galv steel. 2-3/8 in. wide by 7/8 in. deep, spaced 24 in. OC perpendicular to studs. Channels secured to studs as described in Item b. Ends of adjoining channels are overlapped 6 in. and tied together with double strand of No. 18 SWG galv steel wire near each end of overlap. As an alternate, ends of adjoining channels may be overlapped 6 in. and secured together with two self-tapping #6 framing screws, min. 7/16 in. long at the midpoint of the overlap, with one screw on each flange of the channel.
b. Steel Framing Members* — Used to attach furring channels (Item a) to studs (Item 1). Clips spaced 48 in. OC., and secured to studs with 1-5/8 in. wafer or hex head Type S steel screw through the center grommet. Furring channels are friction fitted into clips.
PAC INTERNATIONAL INC — Type RSIC-1.
6B. Steel Framing Members* — Optional - Not Shown - Used as an alternate method to attach resilient channels (Item 6). Clips attached at each intersection of the resilient channel and the steel studs (Item 2). Resilient channels are friction fitted into clips, and then clips are secured to the stud with min. 1 in. long Type S-12 panhead steel screws through the center hole of the clip and the resilient channel flange.
KEENE BUILDING PRODUCTS CO INC — Type RC Assurance.
7. Wall and Partition Facings and Accessories* — (Optional, Not shown) — Nominal 1/2 in. thick, 4 ft wide panels, for optional use as an additional layer on one or both sides of the assembly. Panels attached in accordance with manufacturer's recommendations. When the QR-510 panel is installed between the steel framing and the UL Classified gypsum board, the required UL Classified gypsum board layer(s) is/are to be installed as indicated as to fastener type and spacing, except that the required fastener length shall be increased by a minimum of 1/2 in. Not evaluated or intended as a substitute for the required layer(s) of UL Classified Gypsum Board.
QUIET SOLUTION INC — Type QuietRock QR-510.
Fire Resistance Ratings - ANSI/UL 263 Design No. U465 March 23, 2009
Nonbearing Wall Rating — 1 HR.
Fire Resistance Ratings - ANSI/UL 263
Design No. U499
May 19, 2009
Nonbearing Wall Rating — 1 Hr.
1.Channel Track — "J" -shaped channel, 2-1/2 in. deep with unequal legs of 1 in. and 2 in., fabricated from No.
25 MSG galv steel. Channels attached to structural supports with steel fasteners located not greater than 2 in. from ends and not greater than 24 in. OC.
2. Steel Studs — "I" shaped studs, min 2-1/2 in. deep by 1-1/2 in. wide, fabricated from min 25 MSG galv steel, spaced 24 in. OC. Vertically restrained walls require studs to be cut 1/2 in. less than floor to ceiling height.
2A. Steel Studs — (Not Shown) — "C-H" -shaped studs, min 2-1/2 in. deep by 1-1/2 in. wide, fabricated from min 25 MSG galv steel, spaced 24 in. OC. Vertically restrained walls require studs to be cut 1/2 in. less than floor to ceiling height.
2B. Steel Studs — (Not Shown) — "C-T" - shaped studs, min 2-1/2 in. deep by 1-1/2 in. wide, fabricated from min 25 MSG galv steel, spaced 24 in. OC. Vertically restrained walls require studs to be cut 1/2 in. less than floor to ceiling height.
2C. Furring Channels — (Optional, not shown) - Resilient furring channels fabricated from min. 25 MSG corrosion protected steel, installed horizontally, and spaced vertically a max. 24 in. OC. Flange portion of channel attached to each intersecting stud on side of stud opposite the 1 in. liner panels with 1/2 in. long Type S or S-12 pan-head steel screws.
When furring channels are used, wallboard to be installed vertically only.
3. Gypsum Board* — 1 in. thick gypsum wallboard liner panels, supplied in nominal 24 in. widths. Vertical edges inserted in "I" studs. Free edge of end panels attached to long leg of "J" runners with 1-5/8 in. long Type S self-drilling, self-tapping bugle head steel screws spaced not greater than 24 in. OC.
NATIONAL GYPSUM CO — Types FSW, FSW-B, FSW-7.
4. Gypsum Board* — 5/8 in. thick, 4 ft wide, applied horizontally or vertically and attached to studs with 1 in.
long Type S steel screws spaced 12 in. OC along the edges and in the field of the boards. When Furring Channels (Item 2C) are used, gypsum board attached vertically to furring channels with 1 in. long Type S steel screws spaced 12 in. OC.
NATIONAL GYPSUM CO — Types FSK-C, FSW, FSW-5, FSW-C, FSW-6.
4A. Gypsum Board* — 5/8 in. thick, 4 ft wide, applied vertically and attached to studs with 1 in. long Type S steel screws spaced 12 in. OC along the edges and in the field of the boards. When Furring Channels (Item 2C) are used, gypsum board attached vertically to furring channels with 1 in. long Type S steel screws spaced 12 in. OC.
NATIONAL GYPSUM CO — Types FSW-3, FSMR-C.
5. Batts and Blankets* — (Optional) — Mineral wool or glass fiber batts partially or completely filling stud cavity. Any mineral wool or glass fiber batt bearing the UL Classification Marking as to Fire Resistance. See Batt and Blankets (BZJZ) Category For Names Of Classified Companies.
5A. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 5) — Spray applied cellulose material. The fiber is applied with water to completely fill the enclosed cavity in accordance with the application instructions supplied with the product. Nominal dry density of 3.0 lb/ft3. Alternate application method: The fiber is applied with U.S. Greenfiber LLC Type AD100 hot melt adhesive at a nominal ratio of one part adhesive to 6.6 parts fiber to completely fill the enclosed cavity in accordance with the application instructions supplied with the product. Nominal dry density of 2.5 lb/ft3.
U S GREENFIBER L L C — Cocoon2 Stabilized or Cocoon-FRM (Fire Rated Material)
5B. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 5) and Item 5A - Spray applied cellulose insulation material. The fiber is applied with water to interior surfaces in accordance with the application instructions supplied with the product. Applied to completely fill the enclosed cavity. Minimum dry density of 4.3 pounds per cubic ft.
NU-WOOL CO INC — Cellulose Insulation
GC NOTE:
EXISTING SPRAY APPLIED FIREPROOFING MUST BE TESTED BY CERTIFIED FIRE PROOFING APPLICATOR TO DETERMINE
CURRENT RATING, THICKNESS AND MATERIAL.
EXISTING FIREPROOFING WITHIN THE SCOPE OF PROJECT THAT DOES NOT MEET THE UL REQUIREMENTS AND EXISTING STEEL MEMBERS WHERE FIREPROOFING IS DISTURBED/AFFECTED DUE TO CONSTRUCTION, MUST BE SPRAY
APPLIED WITH NEW FIRE PROOFING PER UL REQUIREMENTS INDICATED.
ALL NEW STRUCTURAL STEEL MEMBERS SHALL BE APPLIED WITH SPRAY FIREPROOFING AS INDICATED PER UL
REQUIREMENTS.
MA
XI
MU
M
TR
AV
EL
D
IS
TA
NC
E
TO
E
XI
T
F
EE
T
1 LIFE SAFETY PLAN
MA
XI
MU
M
TR
AV
EL
D
IS
TA
NC
E
TO
E
XI
T
F
EE
T
MAXIMUM TRAVEL D
ISTANCE
TO EXIT = 70
FEET
C D E F GBA
E.5
OFFICE
OFFICE
HEALTH TECH
OFFICE
MAS/ RECEPTION
ROOM
INTERVIEW
OFFICE
WOMEN
MEN
PHARMACY
IRM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
133A
JAN.
MEN
WOMEN
VESTIBULE
LOBBY
OFFICE
OFFICE
PHARMACIST
OFFICE
IDP
TOILET
STAFF
TOILET
UNISEX
HALLWAY
HALLWAY
LOBBY
STORAGE
3.5
1.5
BREAK ROOM
4890 west kennedy boulevard suite 930 tampa, fl 33609 voice 813-383-5500 fax 813-383-5515 schenkelshultz.com SS Lic No - AA-C000937
LIFE SAFETY PLAN
Permit Set Documents
0920805 July 15, 2009
VA Clinic Expansion & Community Pharmacy Citrus County Resource Center - C Wing 2804 W. Marc Knighton Court Lecanto, Florida 34461
Citrus County 3600 W. Sovereign Path Lecanto, Florida 34461
NK
KT-
SCHENKELSHULTZ
A R C H I T E C T U R E comm. no.:
date:
checked:
drawn:
ALL IDEAS, DESIGNS, ARRANGEMENTS AND PLANS INDICATED OR REPRESENTED BY
THIS DRAWING ARE OWNED BY AND THE PROPERTY OF SCHENKELSHULTZ AND WERE
CREATED, EVOLVED, AND DEVELOPED FOR USE ON AND IN CONNECTION WITH THE
SPECIFIED PROJECT. NONE OF THE IDEAS, DESIGNS, ARRANGEMENTS OR PLANS SHALL
BE USED BY OR DISCLOSED TO ANY PERSON, FIRM, OR CORPORATION FOR ANY
PURPOSE WHATSOEVER WITHOUT THE WRITTEN PERMISSION OF SCHENKELSHULTZ.
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE
DIMENSIONS. CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF
ANY VARIATION FROM THE DIMENSIONS AND CONDITIONS SHOWN BY THESE
DRAWINGS. REVIEW OF SHOP DRAWINGS DOES NOT RELIEVE THE CONTRACTOR FROM
THE REQUIREMENT OF MEETING OR EXCEEDING THE PLANS AND SPECIFICATIONS .
CONFIDENTIAL COPYRIGHT 2006 SCHENKELSHULTZ. WARNING: REPRODUCTION
HEREOF IS A CRIMINAL OFFENSE UNDER 18 U.S.C. SEC. 506. UNAUTHORIZED
DISCLOSURE MAY CONSTITUTE A VIOLATION OF APPLICABLE STATE AND FEDERAL LAW.
THE IDEAS, ARRANGEMENTS AND DESIGNS DISCLOSED HEREIN MAY BE PATENTED OR
BE THE SUBJECT OF PENDING PATENT APPLICATION.
K E
Y P
L A
N
C
B A
NORTH
APPLICABLE CODES
OCCUPANCY CLASSIFICATION
AGENCY HAVING JURISDICTION
CONSTRUCTION TYPE (EXISTING)
FIRE RATING REQUIREMENTS:
EGRESS REQUIREMENTS
FINISH REQUIREMENTS
2007 Florida Building Code (FBC), with 2009 Supplements: (This code includes the Florida Accessibility Code as Chapter 11 and portions of the 2005 National Electric Code as Chapter 27. This code, with the 2009 Supplements includes the 2007 FBC Building, Mechanical, Plumbing and Fuel Gas Volumes. Further, see the 2007 FBC; Building Chapter 35; Mechanical Chapter 15; Plumbing Chapter 13 and Fuel Gas Chapter 8 as amended by the 2009 Supplements for other referenced codes and standards.) (Effective March 1, 2009)
2007 Florida Fire Prevention Code (FFPC): (This code also includes the Florida versions of NFPA 1 and NFPA 101.) (Effective December 31, 2008)
STATE FIRE MARSHAL
CITRUS COUNTY BUILDING DEPARTMENT
BUSINESS PER FBC SECTION 304
II-A SPRINKLERED, PROTECTED. PER FBC SECTION 602
BUILDING ELEMENTS: (FBC TABLE 601 & 602)
STRUCTURAL FRAME: 1 HR.
INTERIOR BEARING WALLS: 1 HR.
INTERIOR NON-BEARING WALLS: 0 HR.
FLOOR CONSTRUCTION: 1 HR.
ROOF CONSTRUCTION: 1 HR.
EXTERIOR BEARING WALLS:
FIRE RATING: O HR. O HR. 0 HR. 0 HR.
% OPENING: NL NL NL NL
PROTECTIVES: NL NL NL NL
(NL - NO LIMIT)
CORRIDORS NOT REQUIRED TO BE FIRE RATED PER FBC SECTION 1017.1
EGRESS WIDTH FACTORS: STAIRWAYS: OTHER EGRESS COMPONENTS:
FBC TABLE 1005.1 0.3 0.2
ALLOWABLE EXIT ACCESS TRAVEL DISTANCE:
UNSPRINKLERED = 200 FT. SPRINKLERED = 300 FT.
FBC TABLE 1016.1
ALLOWABLE COMMON PATH OF EGRESS TRAVEL:
UNSPRINKLERED = 75 FT. SPRINKLERED = 100 FT.
FBC SECTION 1014.3
MAXIMUM DEAD-END CORRIDOR:
UNSPRINKLERED = 20 FT. SPRINKLERED = 50 FT.
FBC SECTION 1017.3
OCCUPANCYLOAD:BUSINESS AREA 100 GSF PER PERSON
PHARMACY 1380 SF=14 CLINIC 3209 SF=33
FBC TABLE 1004.1.1
MINIMUM NUMBER OF EXITS: 1 PER TENANT PROVIDED 2
FBC TABLE 1015.1
MINIMUM CORRIDOR WIDTH: 44 IN.
FBC SECTION 1017.2
INTERIOR FINISHES:
SPRINKLERED UNSPRINKLERED
EXIT ACCESS CORRIDORS AND OTHER EXITWAYS: CLASS C CLASS B
ROOMS AND ENCLOSED SPACES: CLASS C CLASS C
FBC TABLE 803.5
LIFE SAFETY LEGEND
1. CONTRACTOR TO COORDINATE ALL DEVICE LOCATIONS WITH ELECTRICAL DRAWINGS.
NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO INSTALLATION.
2. REFER TO ELECTRICAL DRAWINGS FOR EMERGENCY LIGHTING LOCATIONS.
3. REFER TO SIGNAGE PLAN FOR SIGNAGE REQUIREMENTS.
PRIMARY EXIT
PRIMARY EGRESS PATH
FIRE ALARM PULL STATION - SEE ELECTRICAL
FIRE ALARM HEAT DETECTOR - SEE ELECTRICAL
FIRE ALARM STROBE - SEE ELECTRICAL
DESCRIPTIONSYMBOL
FIRE EXTINGUISHER IN WALL MOUNTED CABINET - RATED
PER WALL RATING - TOP OF CABINET AT 48
TRAVEL DISTANCE PATH116'-9"
H
"FIRE PULL STATION INSIDE" SIGN - SEE SIGNAGE PLAN
"FIRE EXTINGUISHER INSIDE" SIGN - SEE SIGNAGE PLAN
FIRE ALARM SIGNAL HORN WITH STROBE
'WP' DENOTES WEATHERPROOF TYPE - SEE ELECTRICAL
WALL MOUNTED EXIT SIGN - SEE ELECTRICAL
S SPEAKER
WALL MOUNTED FIRE EXTINGUISHER
FIXTURE COUNT
MALE WC / URINALS: 1 / 25 FOR FIRST 50 + 1 / 50 THEREAFTER
FEMALE WC: 1 / 25 FOR FIRST 50 + 1 / 50 THEREAFTER
MALE LAVATORIES: 1 / 40 FOR FIRST 50 + 1 / 80 THEREAFTER
FEMALE LAVATORIES: 1 / 40 FOR FIRST 50 + 1 / 80 THEREAFTER
BATHTUB / SHOWERS:: NONE
DRINKING FOUNTAINS: 1 PER 100
PHARMACY: (14 OCC)
7M, 7F
CLINIC:(33 OCC)
17M, 17F
REQD PROVIDED REQD PROVIDED
1 1
1 1
1 1
1 1
0 0
1 2
1 2
1 2
1 2
1 3
NOTES
C D E F GBA
E.5
NO WORK
IN SHADED AREA
1 1/8" = 1'-0"
DEMOLITION PLAN
3'- 4"
8"
EXISTING SIDEWALK AT
ENTRY TO REMAIN.
NORTH
TYP. ALL EXISTING
PLUMBING FIXTURES
IN AREA OF WORK
TYP. ALL EXISTING INTERIOR
STUD WALLS
IN AREA OF WORK
UNLESS NOTED OTHERWISE
NO WORK THIS AREA
LIM
IT
O F
W
OR
K
LIN
E
CO
NS
TR
UC
TI
ON
F
EN
CE
LI
NE
CO
OR
DI
NA
TE
T
O
MA
IN
TA
IN
AC
CE
SS
/E
XI
T
AT
E
AS
T W
IN
G
24'-0" 24'-0" 24'-0" 15'-5" 16'-0"24'-0"
'-5
9'-
2"
'-5
4'-0"
'-0
10'-0"
3'- 0"
GC NOTE:
• PRIOR TO COMMENCING THE DEMOLITION AND
CONSTRUCTION ACTIVITY AND PRIOR TO USE OF
HEAVY EQUIPMENT, VERIFY LOCATION OF
UNDERGROUND UTILITIES WITHIN THE SCOPE OF
WORK .
• DESIGNATE CLEAR ACCESS POINT FROM EXISTING
PARKLING TO MINIMIZE SITE DISTURBANCE.
• MAINTAIN CLEAR ACCESS TO EAST WING ENTRANCE
AND COORDINATE FENCING FOR WORK CLOSER TO
THE ENTRANCE
4890 west kennedy boulevard suite 930 tampa, fl 33609 voice 813-383-5500 fax 813-383-5515 schenkelshultz.com SS Lic No - AA-C000937
DEMOLITION PLAN
Permit Set Documents
0920805 July 15, 2009
VA Clinic Expansion & Community Pharmacy Citrus County Resource Center - C Wing 2804 W. Marc Knighton Court Lecanto, Florida 34461
Citrus County 3600 W. Sovereign Path Lecanto, Florida 34461
NK
KT-
SCHENKELSHULTZ
A R C H I T E C T U R E comm. no.:
date:
checked:
drawn:
ALL IDEAS, DESIGNS, ARRANGEMENTS AND PLANS INDICATED OR REPRESENTED BY
THIS DRAWING ARE OWNED BY AND THE PROPERTY OF SCHENKELSHULTZ AND WERE
CREATED, EVOLVED, AND DEVELOPED FOR USE ON AND IN CONNECTION WITH THE
SPECIFIED PROJECT. NONE OF THE IDEAS, DESIGNS, ARRANGEMENTS OR PLANS SHALL
BE USED BY OR DISCLOSED TO ANY PERSON, FIRM, OR CORPORATION FOR ANY
PURPOSE WHATSOEVER WITHOUT THE WRITTEN PERMISSION OF SCHENKELSHULTZ.
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE
DIMENSIONS. CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF
ANY VARIATION FROM THE DIMENSIONS AND CONDITIONS SHOWN BY THESE
DRAWINGS. REVIEW OF SHOP DRAWINGS DOES NOT RELIEVE THE CONTRACTOR FROM
THE REQUIREMENT OF MEETING OR EXCEEDING THE PLANS AND SPECIFICATIONS .
CONFIDENTIAL COPYRIGHT 2006 SCHENKELSHULTZ. WARNING: REPRODUCTION
HEREOF IS A CRIMINAL OFFENSE UNDER 18 U.S.C. SEC. 506. UNAUTHORIZED
DISCLOSURE MAY CONSTITUTE A VIOLATION OF APPLICABLE STATE AND FEDERAL LAW.
THE IDEAS, ARRANGEMENTS AND DESIGNS DISCLOSED HEREIN MAY BE PATENTED OR
BE THE SUBJECT OF PENDING PATENT APPLICATION.
K E
Y P
L A
N
C
B A
NORTHEXISTING STEEL COLUMN TO REMAIN. TYPICAL.
EXISTING LEAN TO ROOF ASSEMBLY TO REMAIN
EXISTING CONCRETE ENCASED STEEL COLUMN TO REMAIN
NOT USED
EXISTING HEATER BOX IN WALL TO REMAIN
REMOVE STUD WALL
REMOVE EXISTING PLUMBING FIXTURE AND ALL CONNECTIONS AND
RELATED ASSEMBLIES. CAP CONNECTION BELOW SLAB. SEE PLUMBING
REMOVE EXISTING WINDOW ASSEMBLY PREP FOR NEW WALL
AND DOOR
REMOVE EXISTING DOOR AND FRAME
REMOVE EXISTING ROOF DOWN LEADER. CUT AS REQUIRED BELOW
ROOF DECK FOR CONNECTING TO THE NEW LOCATION OFFSET PER NEW
PLANS SEE PLUMBING
EXISTING STOREFRONT ENTRANCE SYSTEM TO REMAIN.
COMPLETE WITH MISSING MEMBERS TO MATCH EXISTING
SYSTEM AND PREP FOR NEW PAINT. PAINT TO MATCH EXISTING
DEMOLITION KEY NOTES
EXISTING WALL TO REMAIN
REMOVE EXISTING WALL IN ITS ENTIRETY UNLESS KEY NOTED FROM BELOW,
PATCH AND PREPARE ADJACENT SURFACES TO RECEIVE NEW FINISHES
REMOVE DOOR OR WINDOW IN IT'S ENTIRETY. SEE NEW PLANS FOR
PROPOSED FILL OR NEW DOOR AND WINDOW.
1. DEMO DRAWINGS SHOW ITEMS (DASHED) TO BE REMOVED. CM IS TO COORDINATE DEMO
DRAWINGS WITH RENOVATION DRAWINGS IN THE FIELD AND PROVIDE CUTTING AND PATCHING
NECESSARY TO ACHIEVE INTENDED NEW CONDITION AND QUALITY AND ENSURE WEATHER TIGHT
BUILDING ENVELOPE. SPECIFIC DEMOLITION KEYNOTES ARE ARE FOR CLARIFICATION AND DO NOT
REPRESENT THE ENTIRE SCOPE OF WORK.
2. CM SHALL VERIFY ALL EXISTING CONDITIONS
3. SEE MEP AND STRUCTURAL FOR MORE DEMOLITION INFORMATION PERTAINING TO THE
DISCIPLINES.
4. CONTRACTOR TO INVENTORY EXACT AMOUNT OF EXISTING OWNER MECHANICAL & ELECTRICAL ACCESSORIES & GRILLES PRIOR TO DEMOLITION. STORE SUPPLIES IN SAFE LOCATION DURING DEMOLITION AND INSTALL PER MECHANICAL & ELECTRICAL DOCUMENTATION. RETURN ANY UNUSED SUPPLIES TO
OWNER.
EXISTING STUD WALL UP TO DECK TO REMAIN.
EXISTING ROOF DOWN LEADER (OFFSET AT BOTTOM) TO REMAIN
REMOVE EXISTING CONCRETE SIDEWALK AND EXTERIOR
CONCRETE PAD
RELOCATE EXISTING GAZEBO STRUCTURE. COORDINATE WITH
OWNER FOR NEW LOCATION
REMOVE EXISTING STEEL BRACING TO PROVIDE FOR NEW
COLUMN AND BRACING. SEE STRUCTURAL FOR DEMO AND NEW
WORK
REMOVE EXISTING CONCRETE FLOOR SLAB AS REQUIRED:
• FOR RELOCATING AND RECONNECTING THE DOWN LEADER
UNDER GROUND. REPLACE WITH NEW CONC. SLAB.
• FOR NEW PLUMBING CONNECTIONS TO EXISTING MAINS.
SEE PLUMBING TYPICAL . KEEP EXTENT OF DEMOLITION OF SLAB
TO MINIMUM
REPLACE WITH NEW SLAB. SEE STRUCTURAL FOR CONNECTION
DETAILS.
NOTE: EXTENT SHOWN FOR REMOVAL AND REPLACEMENT
CONCRETE SLAB IS PER INFORMATION AVAILABLE. ACTUAL
EXTENT MAY VARY. CONTRACTOR TO VERIFY EXISTING
CONDITIONS AND DETERMINE AREA OF CONC. REMOVAL FOR
REQUIRED CONNECTION
SEE SPEC FOR ALLOWANCE PROVISION.
REMOVE EXISTING FLOOR SLAB FOR NEW COLUMN
FOUNDATIONS. REPLACE WITH NEW SLAB. SEE STRUCTURAL
REMOVE EXISTING CLEAN OUT COVER. REPLACE WITH NEW. SEE
PLUMBING
REMOVE EXISTING WINDOW ASSEMBLY AND PREPARE FOR NEW
WALL INFILL
PREP FOR NEW SHAFT WALL INSTALLATION
1 1/8"=1'-0"
NEW FLOOR PLAN
NO WORK
IN SHADED AREA
NORTH
NEW INFILL WALL MATCH
EXISTING. ALIGN AND MATCH
TEXTURE AND FINISHES
CL
A
AA
NEW CANOPY ABOVE
SEE REFLECTED CEILING PLAN
NEW CANOPY ABOVE
SEE REFLECTED CEILING PLAN
MIDDLE BAY RAISED.
NEW CONCRETE
WALK
C D E F GBA
E.5
533 SF
PHARMACY
237 SF
LOBBY
84 SF
OFFICE
HEALTH TECH
132 SF
OFFICE
56 SF
WOMEN
56 SF
MEN
117 SF
OFFICE
161 SF
OFFICE
127 SF
OFFICE
122 SF
OFFICE
122 SF
OFFICE
41 SF
133A
JAN.
32 SF
STORAGE132 SF
OFFICE
73 SF
IRM
71 SF
ROOM
INTERVIEW 128 SF
OFFICE
54 SF
MEN
55 SF
WOMEN
169 SF
OFFICE
257 SF
MAS/ RECEPTION
117 SF
OFFICE
IDP
55 SF
TOILET
UNISEX
54 SF
TOILET
STAFF
79 SF
HALLWAY
66 SF
HALLWAY
126 SF
OFFICE
PHARMACIST
399 SF
LOBBY
112 SF
VESTIBULE
133A
163 168
A
145 146
NEW CONC SLAB ON COMPACTED
FILL. SLOPE 1 /8" PER 12" AWAY
FROM BUILDING
NEW 58" GWB FINISH AT INTERIOR FACE
OF PERIMETER WALL. TYPICAL.
SEE NOTE
LINE OF EXISTING ROOF
OPERABLE PARTITION
149148
NEW GUTTER AND DOWNLEADER
TO MATCH EXISTING ON BUILDING
NEW INFILL WALL MATCH
EXISTING. ALIGN AND MATCH
TEXTURE AND FINISHES
NEW GUTTER AND DOWNLEADER
TO MATCH EXISTING ON BUILDING
NEW CONCRETE SLAB ON COMPACTED FILL
SLOPE 1 /8" PER 12" AWAY FROM BUILDING
NEW CONCRETE COLUMN
14" DIA TO ENCASE CANOPY COLUMN
SMOOTH RUBBED FINISH AND PAINT
TYPICAL FOR ALL NEW COLUMNS
NEW LANDSCAPE THIS AREA
TYP.
TYP.
178 SF
BREAK ROOM
397 SF
CORRIDOR
NO WORK THIS AREA
NEW GUTTER AND DOWN LEADER
TO MATCH EXISTING ON BUILDING.
PROVIDE CONC SPLASHBLOCK AT EACH
LINE OF EXISTING ROOF
NEW SOD THIS AREA
ON NEW GRADE
3.5
1.5
NEW COLUMN. SEE
STRUCT.
NEW COLUMN. SEE
STRUCT.
02A-50
A-50
A-50
A -50
3.2
1.7
A-60
EXISTING
CONCRETE WALK
EXISTING
CONCRETE WALK
EL= 0'-0"
EL= -0'-1 /2"
SLO
PE 1 /
8" P
ER 12
NEW GRADE TO SLO
PE AWAY
MATCH TO EXISTING SLO
PE
UNIFORMLY
NEW CONC SPLASHBLOCKS
ONE AT EACH WET COLUMN
A-50
A-50
A -50
A-50
A -50
A -50
NEW INFILL @ EXIST.
WINDOW OPENING WALL
THICKNESS TO MATCH
EXISTING ADJACENT WALL.
ALIGN AND MATCH FINISHES
ON BOTH SIDES.
FULL L ENGTH
A1.11
A-11
12'-3" +/-slope slo pe slope slopeslo pe slo pe
TYP
SIM
A-11
'-2
5'- 4"
10'-6 3/8"
'-4
6'-
2" 6'-
2"
'-0 3/
4"
13'-0 1/4"5'-7"12'-0"
10'-11"
'-9
9'-
3" 5'-
5'-
/2
2'-
5 1 /2"
5' min. clear
5' min. clear
1'-5"
10'-11"
1'1
1'- 1"
6'-0"
2'- 1"
1'-9" 6 1/4"
8"
8"
5'-7"
11'-9 3/8"
1'- 0"
7"
4'- 7"
4'- 7"
1'-2" 8" 5"
9" 5 1
/2"
EQ EQ
5'- 6"
'-9
1'-0"
1'- 0"
1'- 9 1
/4"
1'-0"
1'-0" 5'-6"
1'- 0"
5'- 3"
1'- 0"
5'- 6"
1'-0"5'-3"
7'-0"
4'- 3"
'-7
6'-0" 2'-0"
2'-
7'- 0"
1'- 3"
1'- 3"
'-9
2'-1"
'-0
7'-
2" 6'-
3" 9'-
2" 6'-
3" 7'-
2"
'-0
5'- 4"
5'-4"
2'- 3"
2'- 3"
9'- 0"
7'-6"
A
71 SF
STORAGE
-A 164A
108 SF
164A
PHARMACY HELP
-B 164A
-C 164A
A1.11
A-11 slo pe
B
B
5'- 4"
1'-1" 4'-0"
1'- 9"
5'-0" 4'-0"
4" 3'-
0" 1'-
8" 1'-
8" 3'-
0"
TYP
slope
LIM
IT
O F
W
OR
K
LIN
E
CO
NS
TR
UC
TI
ON
F
EN
CE
LI
NE
CO
OR
DI
NA
TE
T
O
MA
IN
TA
IN
AC
CE
SS
/E
XI
T
AT
E
AS
T W
IN
G
TYP
A-50
NEW INFILL WALL
MATCH EXISTING.
ALIGN AND MATCH
TEXTURE AND
FINISHES
1'-5"
2 1"=1'-0"
DETAIL AT INTERIOR COLUMN 3 1"=1'-0"
DETAIL AT PERIMETER COLUMN 4 1"=1'-0"
DETAIL AT COLUMN 5 1"=1'-0"
DETAIL AT COLUMN
7 1/2"7 1/2"
6"
8"
2'- 7 1
/2" 3"
5"
7 1/2"
6"
4 3 /8"
NEW METAL STUD WALL
SEE WALL TYPES
C L
O F
C O
LU
M
N T
O F.
O . S
TU
D
NEW STEEL COLUMN
SEE STRUCTURAL
FIRE PROTECTION PER
UL REQUIREMENT.
SEE SHEET A011
NEW 8" METAL STUD WALL
SEE WALL TYPES
NEW 8" METAL STUD WALL
SEE WALL TYPES
EXISTING EXTERIOR WALL:
METAL STUDS AND EXTERIOR
FINISH TO REMAIN
NEW INSULATION AND 58" GWB
FINISH AT INTERIOR
EXISTING STEEL COLUMN TO
REMAIN. MAINTAIN OR
PROVIDE FIREPROOFING PER
UL REQUIREMENTS. SEE
SHEET A011
NEW GWB ENCLOSURE WITH
1 5 /8" METAL STUD FRAMING
EXISTING STEEL COLUMN TO
REMAIN. MAINTAIN OR
PROVIDE FIREPROOFING PER
UL REQUIREMENTS. SEE
SHEET A011
EXISTING ROOF DRAIN AND
INSULATION TO REMAIN.
(OFFSET IN HEIGHT)
NEW METAL STUD WALL
SEE WALL TYPES
6 1/4" 1'-2"
NEW GWB ENCLOSURE WITH
1 5 /8" METAL STUD FRAMING
NEW HM FRAME FOR
RESTROOM DOOR. SEE DOOR
SCHEDULE
EXISTING EXTERIOR WALL:
METAL STUDS AND EXTERIOR
FINISH TO REMAIN WITH
NEW INSULATION AND 58" GWB
FINISH AT INTERIOR TYPICAL
9"
D D
E E
4890 west kennedy boulevard suite 930 tampa, fl 33609 voice 813-383-5500 fax 813-383-5515 schenkelshultz.com SS Lic No - AA-C000937
FLOOR PLAN
Permit Set Documents
0920805 July 15, 2009
VA Clinic Expansion & Community Pharmacy Citrus County Resource Center - C Wing 2804 W. Marc Knighton Court Lecanto, Florida 34461
Citrus County 3600 W. Sovereign Path Lecanto, Florida 34461
NK
KT
SCHENKELSHULTZ
A R C H I T E C T U R E comm. no.:
date:
checked:
drawn:
ALL IDEAS, DESIGNS, ARRANGEMENTS AND PLANS INDICATED OR REPRESENTED BY
THIS DRAWING ARE OWNED BY AND THE PROPERTY OF SCHENKELSHULTZ AND WERE
CREATED, EVOLVED, AND DEVELOPED FOR USE ON AND IN CONNECTION WITH THE
SPECIFIED PROJECT. NONE OF THE IDEAS, DESIGNS, ARRANGEMENTS OR PLANS SHALL
BE USED BY OR DISCLOSED TO ANY PERSON, FIRM, OR CORPORATION FOR ANY
PURPOSE WHATSOEVER WITHOUT THE WRITTEN PERMISSION OF SCHENKELSHULTZ.
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE
DIMENSIONS. CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF
ANY VARIATION FROM THE DIMENSIONS AND CONDITIONS SHOWN BY THESE
DRAWINGS. REVIEW OF SHOP DRAWINGS DOES NOT RELIEVE THE CONTRACTOR FROM
THE REQUIREMENT OF MEETING OR EXCEEDING THE PLANS AND SPECIFICATIONS .
CONFIDENTIAL COPYRIGHT 2006 SCHENKELSHULTZ. WARNING: REPRODUCTION
HEREOF IS A CRIMINAL OFFENSE UNDER 18 U.S.C. SEC. 506. UNAUTHORIZED
DISCLOSURE MAY CONSTITUTE A VIOLATION OF APPLICABLE STATE AND FEDERAL LAW.
THE IDEAS, ARRANGEMENTS AND DESIGNS DISCLOSED HEREIN MAY BE PATENTED OR
BE THE SUBJECT OF PENDING PATENT APPLICATION.
K E
Y P
L A
N
C
B A
NORTH
NEW PLAN NOTES
NEW STUD WALL. SEE WALL TYPE LEGEND ON A-01
2. FIRE RPOOFING SPRAY PROTECTION:
• PROVIDE NEW FIREPROOFING SPRAY AT NEW COLUMNS AND BRACES TYPICAL.
• PROVIDE NEW FIREPROOFING SPRAY TO EXISTING COLUMNS AND STRUCTURE WHERE
ABSENT. PROVIDE PER UL DESIGN Y 733
3. MAINTAIN AND PROTECT GWB WRAP FIRE PROOFING TO EXISTING COLUMNS WHERE
POSSIBLE. iF REMOVED OR DAMAGED PROVIDE NEW FIREPROOFING SPRAY PER ABOVE.
NEW CONCRETE SLAB TO REPLACE EXISTING SLAB REMOVED FOR
STRUCTURAL OR SYSTEMS SEE MEP, STRUCTURAL.
NOTE: EXTENT SHOWN FOR REMOVAL AND REPLACEMENT CONCRETE
SLAB IS PER INFORMATION AVAILABLE. ACTUAL EXTENT MAY VARY.
CONTRACTOR TO VERIFY EXISTING CONDITIONS AND DETERMINE AREA OF
CONC. REMOVAL FOR REQUIRED CONNECTION
1. PROVIDE BATT INSULATION AT ALL NEW INTERIOR WALLS TYPICAL UNO.
REMOVE EXTSTING GWB FINISH WHERE EXISTS AT INTERIOR
OF PERIMETER WALL. EXISTING METAL STUDS TO REMAIN.
INSTALL NEW BATT INSULATION MIN. R20. INSTALL NEW 58" GWB
FINISH PER SPEC.
REMOVE AND RELOCATE ROOF DOWNLEADER. PROVIDE NEW
CONNECTIONS. NEW CHASE WALL ENCLOSURE.
REMOVE EXISTING PLAM WINDOW SILL. PROVIDE
NEW WINDOW MARBLE WINDO SILLS TYPICAL AT ALL
EXISTING WINDOWS. SEE DETAIL7/A-60
NEW STEEL TUBE COLUMNS FOR OPERABLE WALL TRACK
SUPPORT. SEE 6/A-60
SEE STRUCTURAL
NEW EXTERIOR CONCRETE SLAB ON GRADE / COMPACTED FILL
SLOPE AWAY FROM STRUCTURE TYPICAL. SLOPE AS SHOWN.
PROVIDE FIRE CAULKING AT ALL PENETRATIONS AT ONE HOUR
RATED WALL PER UL REQUIREMENTS. PROVIDE FIRE DAMPERS
AT PENETRATING MECHANICAL DUCTS. SEE MECHANICAL
H.C. PUSH BUTTON FOR DOOR OPERATION. SEE ELECTRICAL06
PAINT ALL EXTERIOR COLUMNS WITHIN SCOPE OF WORK.
COLOR TO MATCH EXISTING COLUMNS
1 1/8" = 1'-0"
REFLECTED CEILING PLAN
NO WORK
IN SHADED AREA
NORTH
NEW CANOPY
C D E F GBA
E.5
OFFICE
OFFICE
HEALTH TECH
OFFICE
WOMEN
MEN
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
133A
JAN.
STORAGE
OFFICE
IRM
ROOM
INTERVIEW
OFFICE
MEN
WOMEN
MAS/ RECEPTION
OFFICE
IDP
TOILET
UNISEX
TOILET
STAFF
PHARMACY
LOBBY
HALLWAY
HALLWAY
OFFICE
PHARMACIST
LOBBY
VESTIBULE
EXISTING CANOPY
EXISTING CANOPY
EXISTING CANOPY
EXISTING
CANOPY
EXISTING CANOPY
WET COLUMN
LINE OF EXISTING COPPER
ROOF AT ENTRY.
NEW CANOPY ABOVE
EXISTING ROOF SHOWN FOR
CLARITY. SEE CANOPY
SECTIONS
NO WORK THIS AREA
6'-0" 2'-0" 1'- 3"
7'- 0"
1'- 3"
3.5
1.5
1'-0"
5'-6"
1'- 0"
5'- 3"
1'- 0"
5'- 6"
1'-0"
5'-3"
4'- 0"
4'-0"
A-60
A-60
PROJECTOR SCREEN
SEE EQUIPMENT PLAN
7'-6"
5'-6
2'-3
2'-3
10"
A-609A
7'- 2"
GUTTER BEAM
WET COLUMN
NEW ALUM CANOPY
WITH TALLER MIDDEL
BAY. SEE SECTIONS
GUTTER BEAM
GUTTER BEAM
TY
P
AT
E
ND
B
AY
S
2"
A-20
5/8" GYPSUM BOARD
PAINTED
3-5/8" METAL STUDS @ 16" O.C.
BRACE TO STRUCTURE ABOVE @
16" O.C.
2"
5/8" GYP. BD., PAINT.
TYPE AND HEIGHT A.F.F.,
SEE R.C.P. FOR CEILING
U.N.O.
2 1 1/2" = 1'-0"
SOFFIT DETAIL
2A 1 1/2" = 1'-0"
BULKHEAD
CEILING PLAN
SEE REFLECTED
CEILING PLAN
SEE REFLECTED
TYP.
4 7/8"
CEILING PLAN
SEE REFLECTED
6" MTL. STUDS @ 24"
O.C., BRACE @ 48" O.C.
TO STRUCTURE ABOVE
4" 4"
CONT. 3 5/8"
CHANNEL FRAMING
TOP OF FLOOR FINISH
TOP OF FLOOR SLAB
5/8" GYPSUM BOARD
BULKHEAD
TRACK SYSTEM
OPERABLE WALL
WRAP…