36C24819Q0304-0002001.docx
DOCX document 15 KB Posted
- Solicitation number
- 36C24819Q0304
About this file
36C24819Q0304 0002 Questions and Answers Solicitation # 36C24819Q0304 22819.docx
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24819Q0304-0003000.docx | DOCX document | |
| 36C24819Q0304-0002000.docx | DOCX document | |
| 36C24819Q0304-0002002.docx | DOCX document | |
| 36C24819Q0304-0001001.docx | DOCX document | |
| 36C24819Q0304-0001000.docx | DOCX document | |
| 36C24819Q0304-001.docx | DOCX document | |
| 36C24819Q0304-003.docx | DOCX document | |
| 36C24819Q0304-000.docx | DOCX document | |
| 36C24819Q0304-002.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions and Answers Posted 2/28/2019 Solicitation # 36C24819Q0304
Boiler Annual Inspection- Semi- Annual Safety Services
Question:
1) Please confirm inspections of the DA and Condensate tanks are only visual. If Non-Destructive Test inspections are required, please provide specifics of the NDT requirements (mag particle, UT with mapping, frequency, etc.)
Answer: Yes, the DA and Condensate Tanks are visual inspections.
Question:
2) Since the DA and Condensate tanks are a part of the inspections, please advise if they can be inspected in the same visit and in conjunction with a trip to inspect one of the boilers or will a separate trip be required for the tanks?
Answer: Yes, the DA or Condensate Tank can be inspected in the same trip with one boiler inspection.
Question:
3) In the past the VA’s Information Security Awareness wasn’t a requirement because we weren’t working the VA’s IT system, therefore it wasn’t applicable. Please advise if this this training is a requirement for this contract.
Answer: Contractor is not required to work with any IT system? Training is not required in this case.