SERVICES: Boilers Annual Inspection and Semi -Annual Safety
Solicitation number
36C24819Q0304
Issued by

About this file

36C24819Q0304 0002 Questions and Answers Solicitation # 36C24819Q0304 22819.docx

View the file

Other files

File Type Posted
36C24819Q0304-0003000.docx DOCX document
36C24819Q0304-0002000.docx DOCX document
36C24819Q0304-0002002.docx DOCX document
36C24819Q0304-0001001.docx DOCX document
36C24819Q0304-0001000.docx DOCX document
36C24819Q0304-001.docx DOCX document
36C24819Q0304-003.docx DOCX document
36C24819Q0304-000.docx DOCX document
36C24819Q0304-002.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers Posted 2/28/2019 Solicitation # 36C24819Q0304

Boiler Annual Inspection- Semi- Annual Safety Services

Question:

1) Please confirm inspections of the DA and Condensate tanks are only visual. If Non-Destructive Test inspections are required, please provide specifics of the NDT requirements (mag particle, UT with mapping, frequency, etc.)

Answer: Yes, the DA and Condensate Tanks are visual inspections.

Question:

2) Since the DA and Condensate tanks are a part of the inspections, please advise if they can be inspected in the same visit and in conjunction with a trip to inspect one of the boilers or will a separate trip be required for the tanks?

Answer: Yes, the DA or Condensate Tank can be inspected in the same trip with one boiler inspection.

Question:

3) In the past the VA’s Information Security Awareness wasn’t a requirement because we weren’t working the VA’s IT system, therefore it wasn’t applicable. Please advise if this this training is a requirement for this contract.

Answer: Contractor is not required to work with any IT system? Training is not required in this case.