BID SET
CSA Architects & Engineers, LLP
MERCANTIL PLAZA, MEZZANINE SUITE
SAN JUAN PUERTO RICO 00918
tel. (787) 641-6800 fax (787) 641-6850
CONTRACTING OFFICER
CHRIS LASHURE
PROJECT MANAGER
JOSE PUNCHIN, PE
VETERANS ADMINISTRATION CARIBBEAN HEALTHCARE SYSTEM
REPAIR MAIN BUILDING
BASEMENT METAL DECK
SAN JUAN, PUERTO RICO
PROJECT NO. 672-14-607
CONTRACT NO. VA248-P-0886
TASK ORDER NO.VA248-14-J-4625
CONSTRUCTION DOCUMENTS PHASE SUBMISSION
DATE SUBMITTED: SEPTEMBER 30, 2015
APPROVED: CHEIF FACILITIES MANAGEMENT SERVICES
NAME
SIGNATURE
DATE
APPROVED: CHEIF PROJECTS SECTION
NAME
SIGNATURE
DATE
Sheet List Table
Sheet Num. Sheet Title
Sheet Description
GENERAL
01 GI001 COVER SHEET AND DRAWING INDEX
02 GI002 GENERAL SYMBOLS AND ABBREVIATIONS
AREA 1 : MAIN BUILDING BASEMENT METAL DECK
AREA 2 : CANTEEN
GENERAL
Sheet List Table
Sheet Num. Sheet Title
Sheet Description
PHASE - 1: ARCHITECTURE
03 AE101 ARCHITECTURAL ROOF PLAN
04 AE102 ROOF DETAILS
PHASE - 1: STRUCTURE
05 SB001 STRUCTURAL NOTES
06 SB101 SUB-BASEMENT CANTEEN AREA - EXISTING FRAMING PLAN
07 SB102 METAL DECK AREA - EXISTING FLOOR STRUCTURAL DEMOLITION
08 SB103
METAL DECK AREA - FOUNDATION AND COLUMNS LAYOUT PLAN, DETAILS AND SECTIONS (1 OF 2)
09 SB104
METAL DECK AREA - FOUNDATION AND COLUMNS LAYOUT PLAN, DETAILS AND SECTIONS (2 OF 2)
10 SF101 METAL ROOF AREA - EXISTING ROOF DEMOLITION PLAN
11 SF102 METAL DECK AREA - ROOF FRAMING PLAN
12 SF301 METAL DECK AREA - ROOF SECTIONS
PHASE - 1: PLUMBING
13 PD101 PARTIAL ROOF PLAN - PLUMBING DEMOLITION
14 PD102 PARTIAL ROOF PLAN - PLUMBING DEMOLITION
15 PL101 PARTIAL ROOF PLAN - PROPOSED PLUMBING
16 PL102 PARTIAL ROOF PLAN - PROPOSED PLUMBING
PHASE - 1: MECHANICAL
17 MPD101 PARTIAL ROOF PLAN - PIPING DEMOLITION
18 MPD102 PARTIAL ROOF PLAN - PIPING DEMOLITION
19 MP101 PARTIAL ROOF PLAN - PROPOSED PIPING
20 MP102 PARTIAL ROOF PLAN - PROPOSED PIPING
PHASE - 1: ELECTRICAL
21 EP101 PARTIAL ROOF PLAN - EXISTING AND DEMOLITION ELECTRICAL PLAN
22 EP102 PARTIAL ROOF PLAN - EXISTING AND DEMOLITION ELECTRICAL PLAN
23 EL101 PARTIAL ROOF PLAN-PROPOSED LIGHTING PLAN
24 EL102 PARTIAL ROOF PLAN-PROPOSED LIGHTING PLAN
Sheet List Table
Sheet Num. Sheet Title
Sheet Description
PHASE - 2: ARCHITECTURE
25 AD101 DEMOLITION PLANS
26 AE103
PROPOSED FLOOR PLAN, REFLECTED CEILING PLAN AND DOOR SCHEDULE
27 AE104 BASIS OF DESIGN PERFORMANCE FOR CEILING RESTRAINTS
PHASE - 2: STRUCTURE
28 SB111 SUB-BASEMENT CANTEEN AREA - FRAMING PLAN AND SECTIONS
PHASE - 2: FIRE PROTECTION
29 FD103 BASEMENT CANTEEN AREA - FIRE PROTECTION DEMOLITION
PHASE - 2: PLUMBING
30 PD103 BASEMENT CANTEEN AREA - PLUMBING DEMOLITION
31 PD104 SUB-BASEMENT CANTEEN AREA - SANITARY DEMOLITION
32 PD105 SUB-BASEMENT CANTEEN AREA - COLD AND HOT WATER PIPING DEMOLITION
33 PL104 SUB-BASEMENT CANTEEN AREA - PROPOSED SANITARY
34 PL105 SUB-BASEMENT CANTEEN AREA - COLD AND HOT WATER PROPOSED PIPING
PHASE - 2: MECHANICAL
35 MD103 BASEMENT CANTEEN AREA - HVAC DEMOLITION
36 MD104 SUB-BASEMENT CANTEEN AREA - HVAC DEMOLITION
37 MH103 BASEMENT CANTEEN AREA CEILING - PROPOSED HVAC PLAN
38 MPD104 SUB-BASEMENT CANTEEN AREA - PIPING - DEMOLITION
39 MP104 SUB-BASEMENT CANTEEN AREA - PROPOSED PIPING
PHASE - 2: ELECTRICAL
40 EP103 BASEMENT CANTEEN AREA-EXISTING AND DEMOLITION ELECTRICAL PLAN
41 EP104 SUB-BASEMENT CANTEEN AREA-EXISTING AND DEMOLITION ELECTRICAL PLAN
42 EL103 BASEMENT CANTEEEN AREA - PROPOSED LIGHTING PLAN
AutoCAD SHX Text
COVER SHEET AND DRAWING INDEX
AutoCAD SHX Text
GI001
AutoCAD SHX Text
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of 43
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text 672-14-607
AutoCAD SHX Text
AutoCAD SHX Text
VAMC SAN JUAN
AutoCAD SHX Text P.R.
AutoCAD SHX Text
REPAIR MAIN BUILDING
AutoCAD SHX Text
BASEMENT METAL DECK
AutoCAD SHX Text
JUNE-20-2017
vfiguer Sello_Firma
BID SET
CSA Architects & Engineers, LLP
MERCANTIL PLAZA, MEZZANINE SUITE
SAN JUAN PUERTO RICO 00918
tel. (787) 641-6800 fax (787) 641-6850
CONTRACTING OFFICER
CHRIS LASHURE
PROJECT MANAGER
JOSE PUNCHIN, PE
DISCIPLINE DESIGNATORS
GI GENERAL INFORMATION SF STRUCTURAL FRAMING
AD ARCHITECTURAL DEMOLITION PD PLUMBING DEMOLITION
ARD ARCHITECTURAL REFLECTED CEILING DEMOLITION PL PLUMBING
AS ARCHITECTURAL SITE MD MECHANICAL DEMOLITION
AE ARCHITECTURAL ELEMENTS MH MECHANICAL HVAC
AF ARCHITECTURAL FINISHES EP ELECTRICAL INTERIOR POWER
AG ARCHITECTURAL GRAPHICS ED ELECTRICAL DEMOLITION
AR ARCHITECTURAL REFLECTED CEILING EL ELECTRICAL INTERIOR LIGHTING
IG INTERIOR GRAPHICS
IF INTERIOR FINISHES
SB STRUCTURAL SUBSTRUCTURE
SHEET TYPE DESIGNATOR
GENERAL
PLANS
ELEVATIONS
SECTIONS
LARGE SCALE VIEWS
DETAILS
SCHEDULES AND DIAGRAMS
E.CALZADILLA L.RIVERA
ROOM IDENTIFICATION
NORTH ARROW
DETAIL REFERENCE NUMBER
SHEET WHERE DETAIL IS DRAWN
ROOM NUMBER
DETAIL REFERENCE SYMBOL
ELEVATION
ELEVATION REFERENCE NUMBER
SHEET WHERE ELEVATION IS DRAWN
GENERAL BUILDING SECTION
SECTION REFERENCE NUMBER
SHEET WHERE SECTION IS DRAWN
X
XXXXX
XXXXX
X
A
ROOM
NAME
00-00
X
X-X
MATCH LINE
7"
MATCH LINE
SHEET TO MATCH
CURRENT SHEET
I 0 0
SHEET TYPE DESIGNATOR
SHEET SEQUENCE DESIGNATOR
DISCIPLINE DESIGNATOR
G 2
NOTE:
VERIFY WITH EACH DISCIPLINE FOR SPECIFIC
DRAWING SYMBOLS AND ABBREVIATIONS
DRAWING NUMBER LEGEND
GENERAL ABBREVIATIONS
A.F.F.
ABOVE FINISHED FLOOR
AL.
ALUMINUM
A.T.
ACOUSTICAL CEILING TILE
BOT.
BOTTOM
EQ.
EQUAL
CLG.
CEILING
F.F.E.
FINISH FLOOR ELEVATION
F.F.L.
FINISH FLOOR LEVEL
FRL
FIBER REINFORCED LAMINATE
HP
HIGH POINT
HGT.
HEIGHT
GA
GAUGE
GAL.
GALVANIZED
GDS.
GYPSUM DIMENSIONAL SURFACE
GWB.
GYPSUM WALL BOARD
LP
LOW POINT
MECH.
MECHANICAL
MAX
MAXIMUM
MIN.
MINIMUM
MTD.
MOUNTED
N.I.C.
NOT IN CONTRACT
O.C.
ON CENTER
OPNG.
OPENING
PETG
POLYETHYLENE TEREPHTHALATE GLYCOL
R.D.
ROOF DRAIN
RM
ROOM
REQ.
REQUIRED
REV.
REVISION
STRUCT.
STRUCTURAL
S.S.
STAINLESS STEEL
ST
STEEL
TYP.
TYPICAL
T.O.
TOP OF
GENERAL DRAWING SYMBOLS
EXISTING WALL
NEW GWB REFACING
HIDDEN OUTLINE (SHOWING CONDITION BELOW, ABOVE OR
BEHIND AS INDICATED)
EXISTING BUILDING AXIS SYMBOL
NEW COLUMN AXIS SYMBOL
KEY NOTE
LEVEL SYMBOL
RISER SYMBOL
REVISION SYMBOL
CEILING HEIGHT
FURNISHINGS
WALL TYPE DESIGNATION
X X
X
X
X
SHEET WHERE SECTION IS DRAWN
INTERIOR ELEVATION
ELEVATION REFERENCE NUMBER
A
0'-0"
X
X
GENERAL DEMOLITION NOTES:
1. DEMOLITION PLANS AND ELEVATIONS INCLUDED FOR THE SOLE PURPOSE OF REFERENCE AND ARE NOT MEANT TO BE CONSIDERED AS CERTIFIED “AS BUILT” DOCUMENTATION. HAZARDOUS MATERIAL SHALL BE REMOVED PRIOR TO
COMMENCING DEMOLITION WORK.
2. VISIT THE SITE AND FAMILIARIZE WITH THE EXISTING CONDITIONS UNDER WHICH THE DEMOLITION WORK IS TO BE PERFOMED; CORRELATE OBSERVATIONS WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.. ANY DEVIATION OF ACTUAL CONDITIONS FROM THOSE SHOWN ON DRAWINGS SHALL BE REFERED TO THE PROJECT MANAGER IN WRITING. PERFORM DEMOLITION WORK IN ACCORDANCE WITH CONTRACT DOCUMENTS, APPLICABLE CODES, STANDARDS AND SPECIFICATIONS.
3. RECYCLE STEEL, ALUMINUM, COPPER AND ANY OTHER RECYCLABLE MATERIAL RESULTING FROM THE DEMOLITION WORK. PROMPTLY DISPOSE OF THE DIMOLISHED AND RECYCLED MATERIAL, EXEPT THOSE INDICATED TO REMAIN IN OWNERS PROPERTY. PAY ALL THE DISPOSAL FEES REQUIRED BY MUNICIPALITY AND BY ENVIRONMENTAL QUALITY BOARD. OBTAIN ALL APPLICABLE PERMITS FOR OFF SITE DISPOSAL AND FILE COPIES OF PERMITS WITH
OWNER.
4. VERIFY LOCATION OF EXISTING UTILITIES TO AVOID DAMAGE DURING THE DEMOLITION WORK. ALL UTILITIES CONNECTIONS TO BE REMOVED SHALL BE CUT AND CAPPED. PROTECT CONCEALED LINES OF UTILITIES SUCH AS WATER, POWER, TELEPHONE, CABLE,SANITARY; STORM SEWER AND GAS THAT MAY BE UNCOVER DURING THE PROCESS OF DEMOLITION AND THAT ARE ESSENTIAL FOR SERVICE AND OPERATION. REPAIR OR REPLACE ANY
UTILITY SERVICE LINE BROKEN OR DAMAGED DURING THE DEMOLITION WORK
5. PERFORM DEMOLITION WORK IN SUCH A WAY THAT THE FREE FLOW OF STORM SEWER SYSTEM IS NOT
INTERRUPTED OR AFFECTED.
6. CONTRACTOR SHALL PROVIDE SECURITY OF THE PREMISES AT ALL TIMES
7. PERFORM SELECTIVE DEMOLITION WITH THE PROPER EQUIPMENT AS NOT TO IMPAIR THE STRUCTURAL INTEGRITY
OF THE STRUCTURES TO REMAIN.
AutoCAD SHX Text
GENERAL SYMBOLS AND ABBREVIATIONS
AutoCAD SHX Text
GI002
AutoCAD SHX Text
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of 43
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text 672-14-607
AutoCAD SHX Text
AutoCAD SHX Text
VAMC SAN JUAN
AutoCAD SHX Text P.R.
AutoCAD SHX Text
REPAIR MAIN BUILDING
AutoCAD SHX Text
BASEMENT METAL DECK
AutoCAD SHX Text
JUNE-20-2017
AutoCAD SHX Text
NORTH
B
AE102
A
AE102
C
AE102
B
AE102
D
E
F
G
H
I
J
K
A
B
C
2 3 4 5
A
AE102
A
AE
BID SET
CSA Architects & Engineers, LLP
MERCANTIL PLAZA, MEZZANINE SUITE
SAN JUAN PUERTO RICO 00918
tel. (787) 641-6800 fax (787) 641-6850
CONTRACTING OFFICER
CHRIS LASHURE
CANTEEN
KEY PLAN
MAIN BUILDING
BASEMENT
METAL DECK
PROJECT MANAGER
JOSE PUNCHIN, PE
ARCHITECTURAL ROOF PLAN
J.Q.V.F.
ALUMINUM EXPANSION
CAP FLASHING
BASE MEMBRANE
INTERMEDIATE MEMBRANE
TOP MEMBRANE W/
MINERAL GRANULES
SILICONE SEALANT
EXISTING WALL
GASKETED FASTENER
TO 12" MAX.
ALUMINUM CLAD TOP
PROTECTION FLASHING
MEMBRANE (AT VERTICAL
SURFACES)
MODIFIED BITUMINOUS
MEMBRANE
SILICONE
SEALANT
POLYISO TAPERED
INSULATION
WOOD OR
METAL CANT STRIP
ROOF METAL DECK
" DENSE DECK
ROOFING BOARD
2 PLY MODIFIED BITUMINOUS
(SBS) ROOFING MEMBRANE
CERAMIC GRANULES
FINISH
" INSULATION
COVER
5/8" INSULATION
COVER
POLYISO TAPPERED
INSULATION
METAL DECKING
GUTTER
4" DRIP EDGE
TREATED WOOD NAILER
SECURED TO METAL DECK
WITH TEK TRUEGRIP GT
#9 SCREW (1-1/2"
EMBEDEMENT) AT 12" O.C.
ANCHORING
(#11x1-1/4" ELECTRO
GALVANIZED STEEL)
L 2
" X 2
" X
AT 4'-0" SPACING
WELDED TO CHANNEL
" TREATED
PLYWOOD
FASCIA
1'-0"
FOR DOWNSPOUT
AND FRAIN REFER
TO PL-102
8" MIN.
2 PLY MODIFIED BITUMINOUS
(SBS) MEMBRANE
" DENSE DECK
ROOFING BOARD
SILICONE SEALANT
ALUMINUM CLAD FINISH
MEMBRANE
ROOF DRAIN REFER TO PL-102
2 PLY COVER STRIP
POLYISO TAPERED INSULATION
" INSULATION COVER
METAL DECKING
2 PLY MODIFIED
BITUMINOUS (SBS)
ROOFING MEMBRANE
CERAMIC GRANULES FINISH
" DENSE DECK ROOFING BOARD
POLYISO TAPERED INSULATION-
WIDTH TO BE DETERMINED BY ROOF
CONTRACTOR
" INSULATION COVER
METAL DECKING
2 PLY MODIFIED
BITUMINOUS (SBS)
ROOFING MEMBRANE
CERAMIC GRANULES FINISH
" DENSE DECK
ROOFING BOARD
BID SET
CSA Architects & Engineers, LLP
MERCANTIL PLAZA, MEZZANINE SUITE
SAN JUAN PUERTO RICO 00918
tel. (787) 641-6800 fax (787) 641-6850
CONTRACTING OFFICER
CHRIS LASHURE
CANTEEN
KEY PLAN
MAIN BUILDING
BASEMENT
METAL DECK
PROJECT MANAGER
JOSE PUNCHIN, PE
ROOF DETAILS
SCALE:AE102
SECTION
FLASHING
3"=1'-0"
A SCALE:AE102
SECTION
GUTTER
1 1/2"=1'-0" B
SCALE:AE102
SECTION
ROOF DRAIN
1"=1'-0" C
L.M.E.L.
SCALE:AE102
SECTION
TYP. ROOF SECTION
1"=1'-0" D
HEIGHT
INFORMATION
HORIZONTAL
INFO
HT
HORIZ
WWR
W/S
W/
W/O
UNO
VERT
T & B
T.O.W.
U
WITH
AND
TOP AND BOTTOM
UNLESS NOTED OTHERWISE
WATERSTOP
WELDED WIRE REINFORCEMENT
WITHOUT
TOP OF WALL
VERTICAL
UNITS
STANDARD DRAWING ABBREVIATIONS
No. or #
REQ'D
DETAILDTL
DOWEL
EACH
DRAWING
EMBEDMENT
EQUAL
EXISTING
EXTERIOR
ETCETERA
ELEVATION, ELEVATOR
EXPANSION JOINT
EACH WAY
ELEVATION
EACH FACE
FINISH
FOOTING
FOOT, FEET
FOUNDATION
GRADE
FAR FACE, FINISHED FLOOR
GR
FT
FTG
FND
FIN
EW
ETC
EXT
FF
EXIST
EQ
EJ
EL
ELEV
EF
EMB
EA
DWL
DWG
T.O.P.
T.O.S.
T.O.C.
T.O.F.
TYP
STD
SOG
SPEC
SHT
SPCS
SECT
SCHD
BEARING
COLUMN
CENTERLINE
CONCRETE
CONCRETE MASONRY UNIT
CLEAR, CLEARANCE
CAST-IN-PLACE CONCRETE
DEGREES
CONTINUOS
CONSTRUCTION
CENTER TO CENTER
CONTROL OR CONSTRUCTION JOINT
DOWN
DIMENSIONDIM
DN
DEG
CTR
C.C.
CONT
CONST
CENTER
CL
COL
CONC
CMU
CLR
CJ
CIP
BRG
REV
REINF
QTY
PROJ
OC
OPNG
NTS
NF
NIC
ALTERNATE
ARCHITECT, ARCHITECTUAL
ADDITIONAL
BUILDING
BOTTOM
BEAMS (S)
BOUNDARY ELEMENT
BY OTHERS, BLOCKOUT, BOTTOM OF OPENING
ADD'L
BE
BO
B
BLDG
BM (s)
ARCH
ALT
LEV
MECH
MIN
MTL
MK
MISC
MID
MEZZ
MAX
LOCT
REQUIRED
TOP OF SLAB OR STEEL
TOP OF PARAPET
TOP OF FOOTING
TOP OF CONCRETE
TYPICAL
SLAB ON GRAPE
SPECIFICATION
STANDARD
SHEET
SPACES
SCHEDULE
SECTION
REINFORCEMENT/ REINFORCE
QUANTITY
REVISION
PROJECTION
NOT IN CONTRACT
ON CENTER
OPENING
NOT TO SCALE
NEAR FACE
NUMBER
LEVEL
MATERIAL, METAL
MECHANICAL
MIDDLE
MISCELLANEOUS
MEZZANINE
MINIMUM
MARK
MAXIMUM
LOCATION
TSL TENSILE SPLICE LENGTH
180° 90°
2'-4 1/2"3'-0" 3'-5"24"#18
FINISHED BEND
DIAMETER
19 1/4"
10 3/4"
#3 2 1/2"
#8
#9
#11
#14
#10
#4
#7
#6
#5
6"
9 1/2"
12"
3"
3 3/4"
4 1/2"
5 1/4"
SIZE
BAR
"D", IN.
10"
8"
6"
1'-7"
1'-4"
1'-2"
1'-0"
2'-7"
2'-0"
1'-10"
5"
1'-3"
1'-5"
1'-7"
2'-3"
11"
6"
7"
8"
10"
A OR G
180° HOOKS
J
3"
5"
1'-1 1/4"
11 3/4"
8"
7"
6"
1'-9 3/4"
1'-2 3/4"
4"
90° HOOKS
A OR G
FOR DOWELS
INTO FOUNDATION
3,000 f'c (psi)
ALL OTHER
CASES
4,000
15.5 db
13.5 db
22 db
19 db
DEVELOPMENT OF STANDARD HOOKS
IN TENSION (ldh)
END HOOKS FOR ALL GRADES
No. 6 AND
SMALLER
3,000 f'c (psi)
No. 7 AND
LARGER
4,000
44 db
38 db
55 db
48 db
DEVELOPMENT LENGTH (ld)
5,000 34 db 42 db
ACI 318-08 TENSILE
No. 6 AND
SMALLER
3,000 f'c (psi)
No. 7 AND
LARGER
4,000
58 db
50 db
72 db
63 db
CLASS B LAP SPLICE
5,000 45 db 56 db
ACI 318-08 TENSILE
3,500 41 db 51 db
3,500 54 db 67 db
HOOK
A OR G
4db
OR 2
" MIN.
d b d b
J
A
O
R
G d b
D D
GENERAL STRUCTURAL NOTES :
1. THE REQUIREMENTS AND RECOMMENDATIONS OF THE FOLLOWING CODES AND
STANDARDS SHALL APPLY TO DESIGN AND CONSTRUCTION OF THIS PROJECT:
- PUERTO RICO BUILDING CODE (PRBC) 2011 (REV. JUN 20,2012)
- LATEST IBC CODE
- AISC MANUAL OF STEEL CONSTRUCTION
- BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE ACI 318
- AWS-D1.1 STRUCTURAL WELDING CODE
- SPECIFICATIONS FOR STRUCTURAL CONCRETE BUILDINGS ACI 301
- BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES ACI530
- AMERICAN SOCIETY OF TESTING AND MATERIALS (ASTM)
- ANSI / ASCE 7 MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES
- AISC 341 SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS
- AISC 360 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
- AISC 358 PREQUALIFIED CONNECTIONS FOR SPECIAL AND INTERMEDIATE STEEL
MOMENT FRAMES FOR SEISMIC APPLICATIONS
- ACI 304 CONCRETE PLACEMENT STANDARD
- CONCRETE REINFORCING STEEL INSTITUTE (CRSI), LATEST EDITION
2. UNLESS OTHERWISE INDICATED, THESE NOTES APPLY TO ALL STRUCTURAL
DRAWINGS OF THIS SET OF PLANS.
3. IN CASE OF DISCREPANCY BETWEEN THESE NOTES AND THE CONSTRUCTION
DRAWINGS, SPECIFICATIONS OR ANY REFERRED STANDARD, THE MORE
RESTRICTIVE PROVISION SHALL APPLY.
4. STRUCTURAL DRAWINGS SHALL BE COORDINATED AND SUPPLEMENTED BY
ARCHITECTURAL, ELECTRICAL, MECHANICAL AND ANY OTHER BUILDING DRAWINGS.
5. CONTRACTOR MUST VERIFY ALL DIMENSIONS AND EXISTING FIELD CONDITIONS
PRIOR TO STARTING CONSTRUCTION. IF ANY DISCREPANCY ARISES IN THE
STRUCTURAL AND ARCHITECTURAL PLANS THE ARCHITECTS AND ENGINEERS SHALL
BE NOTIFIED IMMEDIATELY.
6. CONTRACTOR SHALL BRING TO THE ATTENTION OF THE ENGINEER ANY DETAIL OR
DIMENSION THAT IS OMITTED OR NOT SPECIFICALLY SHOWN ON PLANS WITHOUT
TAKING ANY FURTHER ACTION.
7. CONTRACTOR SHALL PROTECT ALL PROPERTY FROM DAMAGE. ANY DAMAGED
PROPERTY SHALL BE PROMPTLY REPLACED, AT CONTRACTORS EXPENSE.
8. ALL CONSTRUCTION, DEMOLITION AND / OR EXCAVATION WORK SHALL BE
PERFORMED IN SUCH A WAY AS NOT TO IMPAIR THE SAFETY OF ADJOINING
EXISTING STRUCTURES.
9. NO OPENINGS, OTHER THAN THOSE SHOWN ON THE STRUCTURAL DRAWINGS, SHALL
BE MADE IN ANY STRUCTURAL MEMBER WITHOUT THE WRITTEN APPROVAL OF THE
STRUCTURAL ENGINEER.
10. NO CHANGE IN SIZE OR DIMENSION OF STRUCTURAL MEMBER SHALL BE MADE
WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.
11. ALL STRUCTURES HAVE BEEN DESIGNED ACCORDING TO FINAL BEHAVIOR AND
CONDITIONS. HOWEVER, DURING ERECTION OF SAME, CERTAIN CONDITIONS CAN
ARISE FOR WHICH THE BEHAVIOR OR THE STRUCTURE HAS NOT BEEN
CONTEMPLATED. THEREFORE, THE CONTRACTOR SHOULD PROVIDE AT ALL TIMES
ADEQUATE SHORING AND RESTORING UNTIL THE DESIGN CONDITIONS HAVE BEEN
MET. IF THERE IS ANY DOUBT DURING ANY PHASE OF THE CONSTRUCTION, THE
STRUCTURAL ENGINEER SHALL BE CONSULTED AND/OR NOTIFIED.
12. THE CONTRACTOR IS RESPONSIBLE FOR LIMITING THE AMOUNT OF CONSTRUCTION
LOAD IMPOSED UPON STRUCTURAL FRAMING. CONSTRUCTION LOADS SHALL NOT
EXCEED THE DESIGN CAPACITY OF THE FRAMING AT THE TIME THE LOADS ARE
IMPOSED.
13. HORIZONTAL MOVEMENT OF ANY HEAVY EQUIPMENT OVER STRUCTURAL FLOORS
OR ROOF AND ITS TEMPORARY AND/OR DEFINITE LOCATIONS MUST BE PREVIOUSLY
APPROVED BY THE ENGINEER SO AS NOT TO OVERLOAD THE STRUCTURE OR IN ANY
OTHER WAY IMPAIR THE STRUCTURE. SAME PRECAUTION SHALL BE TAKEN FOR THE
PILING OF CONSTRUCTIONS MATERIALS.
14. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. THE
CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL TEMPORARY BRACING
AND/OR SUPPORT THAT MAY BE REQUIRED AS THE RESULT OF THE CONTRACTOR'S
CONSTRUCTION METHODS AND/OR SEQUENCES. OBSERVATION VISITS TO THE SITE
BY THE STRUCTURAL ENGINEER SHALL NOT INCLUDE INSPECTION OF THE ABOVE
ITEMS.
15. ALL STRUCTURES HAVE BEEN DESIGNED ACCORDING TO FINAL BEHAVIOR AND
CONDITIONS. HOWEVER, DURING ERECTION OF SAME, CERTAIN CONDITIONS CAN
ARISE FOR WHICH THE BEHAVIOR OR THE STRUCTURE HAS NOT BEEN
CONTEMPLATED. THEREFORE, THE CONTRACTOR SHOULD PROVIDE AT ALL TIMES
ADEQUATE SHORING AND RESTORING UNTIL THE DESIGN CONDITIONS HAVE BEEN
MET. IF THERE IS ANY DOUBT DURING ANY PHASE OF THE CONSTRUCTION, THE
STRUCTURAL ENGINEER SHALL BE CONSULTED AND/OR NOTIFIED.
16. DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON DRAWINGS.
REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS NOT SHOWN ON
STRUCTURAL DRAWINGS.
17. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL
NOTES AND TYPICAL DETAILS.
18. THE USE OF PRODUCTS, EQUIPMENT OR MATERIALS OF A BRAND NAME IS
REGARDED AS TO ESTABLISHING A STANDARD OF QUALITY AND SHALL NOT BE
CONSTRUED AS LIMITING COMPETITION. THE CONTRACTOR MAY, AT HIS OPTION,
USE ANY EQUIPMENT, MATERIAL, ARTICLE OR PROCESS THAT IN THE JUDGMENT OF
THE ARCHITECT/ENGINEER IS EQUAL TO THAT NAMED IN THE CONTRACT
DOCUMENTS OR PLANS, UNLESS SPECIFICALLY PROVIDED OTHERWISE IN THE
CONTRACT.
19. THE CONTRACTOR SHALL INFORM THE ARCHITECT/ENGINEER IN WRITING OF ANY OF
THE RESPONSIBILITY OF SUCH DEVIATION BY THE PROFESSIONAL OF RECORD IN
THE REVIEW OF SHOP DRAWINGS, PRODUCT DATA, ETC., UNLESS THE CONTRACTOR
HAS SPECIFICALLY INFORMED THE PROFESSIONAL OF RECORD OF SUCH DEVIATION
AT THE TIME OF SUBMISSION, AND THE PROFESSIONAL OF RECORD HAS GIVEN
WRITTEN APPROVAL TO THE SPECIFIC DEVIATION.
20. CONTRACTOR SHALL SUBMIT FOR OWNER'S APPROVAL THE LOCATION AND DETAILS
OF CONSTRUCTION JOINTS IN SLABS AND BEAMS, AND IN ANY OTHER STRUCTURAL
MEMBERS.
DESIGN LOADS :
WIND ............................... ASCE 7-05 (145 MPH), EXPOSURE C
OCCUPANCY CATEGORY: II
IMPORTANCE FACTOR: 1.00
EARTHQUAKE ................. AS PER INTERNATIONAL BUILDING CODE, 2009
SEISMIC DESIGN CATEGORY: D
SEISMIC IMPORTANCE FACTOR: 1.00
SITE CLASS: D (ASSUMED)
SPECTRAL RESPONSE PARAMETERS: Ss = 0.90, S
= 0.31
S D s = 0.702, S D1
= 0.371
SEISMIC PARAMETERS ARE ASSUMED AND SHALL BE
VERIFIED WITH FINAL GEOTECHNICAL RECOMMENDATIONS
LIVE LOADS :
METAL ROOF.......................... 40 PSF
SUPERIMPOSED DEAD LOAD:
SDL .......................................... 5 PSF
FOUNDATIONS :
1. ALL FOOTINGS SHALL BEAR ON UNDISTURBED STRATUM HAVING A MINIMUM
ASSUMED ALLOWABLE BEARING PRESSURE OF 2,000 P.S.F. THAT SHALL BE FIELD
VERIFIED BY A GEOTECHNICAL ENGINEER HIRED BY THE OWNER.
2. FOOTINGS MAY BE POURED INTO AN EARTH-FORMED TRENCH IF SOIL CONDITIONS
PERMIT.
3. ALL BEARING MATERIAL SHALL BE INSPECTED BY THE ENGINEERING IN INSPECTION
PRIOR TO CONCRETE PLACEMENT. THE INDEPENDENT INSPECTOR SHALL BE THE
SOLE JUDGE AS TO THE SUITABILITY OF THE BEARING MATERIAL FOOTING
ELEVATIONS SHALL BE ADJUSTED AS REQUIRED. THE INSPECTOR SHALL BE THE
OWNER'S REPRESENTATIVE AT THE PROJECT SITE, AND AS SUCH WILL BE
RESPONSIBLE TO HIM.
4. FOUNDATION WALLS THAT RETAIN EARTH SHALL BE BRACED AGAINST BACKFILLING
PRESSURES UNTIL FLOOR SLABS AT TOP AND BOTTOM ARE IN PLACE.
5. WHERE FOUNDATION WALLS ARE TO HAVE EARTH PLACED ON EACH SIDE, PLACE
FILL SIMULTANEOUSLY SO AS TO MAINTAIN A COMMON ELEVATION ON EACH SIDE OF
THE WALL.
6. FOUNDATION WORK SHALL BE SUBJECT TO QUALITY ASSURANCE TESTING AND
INSPECTION, AS PER TECHNICAL SPECIFICATIONS FOR THE PROJECT.
7. ALL BACKFILL SHALL BE COMPACTED TO 95% OF MODIFIED PROCTOR DENSITY.
8. ALL EXCAVATIONS AND BACKFILLS SHALL BE INSPECTED FOR COMPLIANCE WITH
THE SUBSOIL REPORT RECOMMENDATIONS.
9. FOOTINGS SHALL BE PLACED ACCORDING TO THE DEPTH SHOWN IN THE
STRUCTURAL DRAWINGS. ALL FOUNDATION BASES SHALL BE INSPECTED WHEN THE
DEPTH INDICATED HAS BEEN ACHIEVED. THE GEOTECHNICAL ENGINEER SHALL
GIVE THE FINAL APPROVAL FOR ANY CHANGES IN FOOTING DEPTH, AND SHALL GIVE
WRITTEN NOTIFICATION TO THE ARCHITECT AND ENGINEER. NO FOOTING SHALL BE
CAST WITHOUT THE GEOTECHNICAL ENGINEER APPROVAL.
REINFORCED CONCRETE :
1. ALL AGGREGATES SHALL COMPLY WITH ASTM SPECIFICATION C-33 . CEMENT SHALL
COMPLY WITH ASTM SPECIFICATION C-150. MAXIMUM SIZE OF COARSE AGGREGATES
SHALL BE 3/4" INCH. MANUFACTURED AGGREGATES FROM WATER SOLUBLE
MATERIALS WILL NOT BE PERMITTED.
2. MINIMUM CONCRETE COMPRESSIVE STRENGTH SHALL BE AS FOLLOWS: (U.N.O.)
FOOTING & FOUNDATION; WALLS & PEDESTALS.................. 3,000 PSI
3. FORM WORKS SHALL BE CONSTRUCTED SO THAT THE CONCRETE SURFACES WILL
CONFORM TO THE TOLERANCE LIMITS SET FORTH IN CHAPTER 4 OF THE
"SPECIFICATIONS FOR STRUCTURAL MEMBERS FOR BUILDINGS" (ACI 301).
4. ALL DIMENSIONS SHOWN ARE STRUCTURAL AND DO NOT INCLUDE THICKNESS OF
PLASTER OR ANY OTHER CONCRETE FINISH.
5. MINIMUM CONCRETE COVER FOR REBARS SHALL BE AS FOLLOWS UNLESS
OTHERWISE NOTED: EXPOSED TO WEATHER:
SLABS .................................... 1 1/2 INCH
BEAMS AND COLUMNS ....... 1 1/2 INCH
WALLS ................................... 1 1/2 INCH
FOOTINGS.............................. 3 INCHES (AT BOTTOM)
2 INCHES (AT SIDES)
NOT EXPOSED TO WEATHER:
SLABS.................................... 3/4 INCHES
SUSPENDED SLABS.............. 1 1/2 INCHES
BEAMS AND COLUMNS....... 1 1/2 INCHES
WALLS................................... 3/4 INCHES
FOOTINGS.............................. 3 INCHES (AT BOTTOM)
2 INCHES (AT SIDES)
6. CONSTRUCTION LOADS SHALL NOT BE SUPPORTED ON, OR ANY SHORING REMOVED
FROM, ANY PART OF THE STRUCTURE UNDER CONSTRUCTION EXCEPT THAT
PORTION OF THE STRUCTURE IN COMBINATION WITH THE REMAINING FORMING AND
SHORING SYSTEM HAS SUFFICIENT STRENGTH TO SUPPORT SAFELY ITS WEIGHT
AND LOADS PLACED THEREON. TIME FOR REMOVING CONCRETE FORMS AND
SHORING IN BEAMS, SLABS AND STAIRWAYS SHALL BE ONE WEEK.
7. ALL SLEEVES, CONDUITS, INSERTS AND BOLTS SHALL BE HELD ACCURATELY IN
PLACE BEFORE CONCRETE IS POURED. FOR ANCHOR BOLTS TO BE FIXED TO
EXISTING STRUCTURES, AN EPOXY SYSTEM SUCH AS SIKADUR 32 HI-MOD OR
APPROVED EQUAL SHALL BE USED.
8. CONTRACTOR SHALL NOT PROCEED TO POUR ANY CONCRETE UNTIL THE
REINFORCEMENT PLACEMENT HAS BEEN APPROVED BY ENGINEER.
9. ALL FOUNDATION CONCRETE IN EACH AREA SHALL BE POURED MONOLITHICALLY,
UNLESS OTHERWISE INDICATED ON PLANS.
10. PROVIDE A POLYETHYLENE VAPOR RETARDER MEMBRANE UNDER ALL CONCRETE
POURED AGAINST THE SOIL. UNLESS OTHERWISE INDICATED ON PLANS, VAPOR
RETARDER SHALL BE EQUAL OR SIMILAR TO GRIFFOLYN TYPE-65.
11. REINFORCING BARS SHALL BE GRADE 60 HIGH STRENGTH DEFORMED NEW BILLET
STEEL MEETING ASTM SPECIFICATION A-615 .
12. REINFORCING BARS INTENDED FOR WELDING SHALL CONFORM TO ASTM A706.
13. ALL BENDING LAPPING AND PLACING OF REINFORCEMENT SHALL BE DONE IN
STRICT ACCORDANCE WITH CHAPTER 12 OF ACI BUILDING CODE.
14. REINFORCEMENT SHALL BE PLACED TO THE TOLERANCE LIMITS SET FORTH IN
CHAPTER 5 OF THE "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS"
(ACI 301).
15. WIRE MESH SHALL COMFORM WITH "SPECIFICATIONS FOR WELDED DEFORMED
STEEL WIRE FABRIC FOR CONCRETE". WIRE MESH SHALL ALSO COMPLY WITH ASTM
SPECIFICATION A-497 AND SHALL HAVE A YIELD STRENGTH RANGING FROM 60,000
PSI TO 75,000 PSI.
16. NO REBAR SPLICE SHALL BE MADE AT OR NEAR REGIONS OF MAXIMUM STRESS AND
NO MORE THAN 50% OF REBARS SHALL BE SPLICED AT ANY LOCATION.
17. ALL REINFORCING SHALL BE SUPPORTED IN FORMS USING STEEL CHAIRS, SPACED
WITH NECESSARY ACCESSORIES AND SHALL BE SECURELY WIRED TOGETHER, IN
ACCORDANCE WITH CRSI "MANUAL OF STANDARD PRACTICE".
18. ALL SLABS AND CORRESPONDING BEAMS, CURBS, OR APRONS SHALL BE POURED
MONOLITHICALLY.
19. PROVIDE 2#5 LONGITUDINAL BARS ALONG SLAB PERIMETER.
20. CONTRACTION JOINTS SHALL BE PROVIDED AT ALL SLAB-ON-GRADE AT A MAXIMUM
SPACING OF 15 FEET IN EACH DIRECTION.
21. FOR WATER-CEMENT RATIO AND PERMEABILITY LIMITS REFER TO SPECIFICATIONS.
22. CONCRETE MIX DESIGN SHALL INCLUDE A CORROSION INHIBITOR ADMIXTURE.
23. CONCRETE WORK SHALL BE SUBJECT TO QUALITY ASSURANCE TESTING AND
INSPECTIONS. SEE QUALITY ASSURANCE GENERAL NOTES AND PROJECT
SPECIFICATIONS.
24. FOR CONSTRUCTION JOINTS IN STRUCTURAL MEMBERS A KEY JOINT MUST BE
PROVIDED.
25. ALL OPENINGS IN CONCRETE WALLS SHALL BE REINFORCED AROUND WITH 2 #5
BARS PLACED AT 2 INCHES FROM THE FACE AND EXTENDING 24 INCHES BEYOND
CORNERS, UNLESS OTHERWISE SPECIFIED IN PLANS.
26. ALL ONE WAY SLAB TEMPERATURE REINFORCEMENT SHALL BE AS FOLLOWS;
(UNLESS NOTED OTHERWISE) 0.18% OF SECTIONAL AREA (INCLUDING INTEGRAL
TOPPING).
27. MINIMUM LAP OF WELDED WIRE FABRIC SHALL BE 6 INCHES OR ONE FULL MESH,
WHICHEVER IS GREATER.
28. FOR CONCRETE FORMWORK, SURFACE FINISHING, BEVELED CORNERS AND DRIPS,
SEE ARCHITECTURAL PLANS.
29. PLACEMENT OF CONCRETE SHALL CONFORM TO ACI STANDARD 304 AND PROJECT
SPECIFICATIONS.
30. PROVIDE DOWELS IN PEDESTAL AND/OR WALL FOOTINGS EQUAL IN GRADE,
SPACING, SIZE AND NUMBER TO VERTICAL REINFORCEMENT, EXTENDING A TENSION
SPLICE LENGTH INTO THE PEDESTAL AND/OR WALL AND 40 BAR DIAMETER INTO
FOOTING. THE LATERAL EMBEDMENT SHALL BE EXTENDED AS NECESSARY TO
PROVIDE A MINIMUM HORIZONTAL LEG RESTING ON FOOTING REINFORCEMENT
EQUAL TO THE CORRESPONDING "G" LENGTH FOR THE BAR SIZE.
31. CONCRETE SHALL NOT BE DROPPED THROUGH REINFORCING STEEL SO AS TO
CAUSE SEGREGATION OF AGGREGATES IN SUCH CASES, HOOPERS OR VERTICAL
CHUTES OR TRUNKS SHALL BE USED. THE FREE UNCONFINED FALL OF CONCRETE
SHALL NOT EXCEED THE ABOVE REQUIREMENTS.
32. THE SIZE OF NAILS AND SIMILAR FASTENERS DRIVEN INTO CONCRETE SHALL BE
SUCH, AS NOT TO CRACK OR IMPAIR IT. NEVERTHELESS, IF THE CONCRETE IS
DAMAGED, IT SHALL BE PROPERLY REPAIRED AFTER REMOVING THE DAMAGED
PORTION AND SUITABLE JOINT SURFACE ARE PROVIDED.
33. ALL CAST IN PLACE REINFORCED CONCRETE STRUCTURAL MEMBERS SHALL BE
PROPERLY CURED IN ACCORDANCE WITH THE ACI CODE, CHAPTER V AND ACI 308.
34. ALL REINFORCING BAR BENDS SHALL BE MADE COLD.
35. NO JOINT, OPENING, SLOT OR GROOVE OTHER THAN THAT SHOWN ON DRAWINGS
SHALL BE PERMITTED WITHOUT PREVIOUS APPROVAL BY THE ENGINEER. ALL
CONSTRUCTION JOINT SURFACES SHALL BE CLEANED AND ROUGHENED
IMMEDIATELY BEFORE CONCRETING AND TREATED AS INSTRUCTED IN THE "ACI
MANUAL OF CONCRETE PRACTICE".
36. CONDUIT OF PIPE SIZE (O.D.) SHALL NOT EXCEED 30 PERCENT OF TOTAL SLAB
THICKNESS AND SHALL BE PLACED BETWEEN THE TOP & BOTTOM REINFORCEMENT,
UNLESS SPECIFICALLY DETAILED OTHERWISE. CONCENTRATIONS OF CONDUITS OR
PIPES SHALL BE AVOIDED EXCEPT WHERE DETAILED OPENINGS ARE PROVIDED.
37. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL OPENINGS IN CONCRETE
BEFORE PLACING. DO NOT CUT ANY REINFORCEMENT BAR WHICH MAY CONFLICT.
CORING IN CONCRETE IS NOT PERMITTED U.N.O.
38. ALL WALL ENDS AND CORNERS SHALL BE REINFORCED WITH 2 #5 VERTICAL BARS
U.N.O.
STRUCTURAL STEEL :
1. STRUCTURAL STEEL SHALL COMPLY WITH THE FOLLOWING SPECIFICATIONS:
W-SECTIONS ..................................... ASTM A992, FY = 50 KSI
HSS SQUARE/RECT. ........................ ASTM A500, GRADE B, FY = 46 KSI
ANGLES, CHANNELS AND ANY OTHER MISCELLANEOUS
STRUCTURAL STEEL ........................ ASTM A36, FY = 36 KSI
ANCHOR RODS .................................. ASTM F1554, GRADE 36 (FY = 36 KSI)
2. WELDED SPLICES OF STRUCTURAL SECTIONS WILL NOT BE PERMITTED.
CONTRACTOR SHALL OBTAIN THE SECTIONS IN LENGTHS THAT ARE PROVIDED
3. CONNECTIONS, WHEN NOT SHOWN ON PLANS, SHALL BE DESIGNED TO TRANSMIT
THE MAXIMUM STRESS ALLOWED FOR THE CONNECTED MEMBERS.
4. THE ERECTION OF STRUCTURAL STEEL ELEMENTS SHALL STRICTLY FOLLOW
SECTION 7 OF THE AISC "CODE OF STANDARD PRACTICE".
5. DIMENSIONS OF STRUCTURAL STEEL ELEMENTS SHALL BE WITHIN THE DIMENSIONAL
TOLERANCES SET FORTH IN SECTION 6 OF THE CODE OF STANDARD PRACTICE OF
THE AISC MANUAL OF STEEL CONSTRUCTION.
6. NO LOADS SHALL BE PLACED OVER ANY STEEL STRUCTURE UNTIL ALL ANCHORS,
PURLINS AND BEAMS, ARE PROPERLY BRACED.
7. FIELD WELDS SHALL BE DONE BY AN AWS CERTIFIED WELDER. WELDS SHALL BE
PERFORMED USING E70XX ELECTRODES U.N.O.
8. SLIP CRITICAL BOLTED CONNECTIONS WILL REQUIRE AN INITIAL PRETENSION FORCE
TO BE COORDINATED WITH THE DESIGNER.
9. SHOP DRAWINGS FOR ALL STRUCTURAL STEEL FABRICATION AND ERECTION SHALL
BE SUBMITTED TO THE DESIGNER FOR APPROVAL WELL IN ADVANCE OF
CONSTRUCTION.
10. INCORRECTLY FABRICATED, DAMAGED OR OTHERWISE MISFITTING OR
NON-CONFORMING MATERIALS OR CONDITIONS SHALL BE REPORTED TO THE
ENGINEER FOR REVIEW AND APPROVAL OR REJECTION, PRIOR TO REMEDIAL OR
CORRECTIVE ACTION TO BE IMPLEMENTED.
11. ALL FIELD WELDS SHALL BE VISUALLY INSPECTED BY AN AWS CERTIFIED WELD
INSPECTOR.
12. MINIMUM WELD SIZE
" U.N.O.
METAL DECK :
1. METAL DECK SHALL COMPLY WITH THE REQUIREMENT OF THE STEEL DECK
INSTITUTE SPECIFICATIONS AND COMMENTARY FOR STEEL DECK.
2. METAL DECK SHALL BE CONFIGURATION, DEPTH AND MINIMUM GAGE AS SHOWN ON
THE DRAWINGS. ATTACHMENT TO THE SUPPORTING STRUCTURE SHALL BE AS
SHOWN ON THE DETAIL ON THIS SHEET AS A MINIMUM. DO NOT HANG OR SUPPORT
ANY LOADS FROM METAL ROOF DECK.
3. METAL DECK WORK SHALL BE SUBJECT TO QUALITY ASSURANCE TESTING AND
SPECIFICATIONS.
4. UPLIFT CONNECTION SHALL BE CHECKED PER DESIGN LOADS AS APPLICABLE WHEN
INDICATED ON DESIGN DRAWINGS.
5. BEFORE THE INSTALLATION OF STEEL DECK, CONTRACTOR SHALL VERIFY THE
HEIGHT OF ADJACENT STEEL JOIST TO PROVIDE ADEQUATE HSS SECTIONS OR
SHIMS FOR STEEL DECK SUPPORT.
6. SPLICE EXISTING STEEL DECK WITH PROPOSED NEW DECK A MINIMUM OF 12". IF
DECK SECTIONS DOES NOT MATCH.
SPECIAL INSPECTIONS :
1. PERFORM SPECIAL INSPECTIONS AS REQUIRED IN IBC 2009 FOR:
STEEL CONSTRUCTION PER SECTION 1704.3
CONCRETE CONSTRUCTION PER SECTION 1704.4
STRUCTURAL DEMOLITION :
1. PERFORM SELECTIVE DEMOLITION AND REMOVAL WITH THE PROPER EQUIPMENT
AND PRECAUTIONS TO PREVENT EXCESSIVE VIBRATIONS SO AS NOT TO IMPAIR THE
STRUCTURAL INTEGRITY OF THE BUILDING OR BUILDING PORTIONS TO REMAIN AND
TO PREVENT DISRUPTIONS IN THE FACILITIES OPERATIONS.
2. WELL IN ADVANCE OF ANY DEMOLITION PROCEDURE, CONTRACTOR SHALL
PERFORM SURVEY OF STRUCTURAL ELEMENTS (BEAMS, COLUMNS, BRACINGS,
SLABS) IN THE AREAS REQUIRING SELECTIVE DEMOLITION. CONTRACTOR SHALL
NOTIFY STRUCTURAL ENGINEER OF EXISTING CONDITIONS DIFFERING FROM
CONSTRUCTION PLANS. NO WORK SHALL PROCEED UNLESS WRITTEN APPROVAL BY
STRUCTURAL ENGINEER IS PROVIDED.
3. UNLESS DETAILED SPECIFICALLY IN STRUCTURAL PLANS, PERFORATIONS AND/OR
PENETRATIONS IN SLABS, AND/OR THE REMOVAL OF STRUCTURAL ELEMENTS SHALL
NOT BE PERFORMED WITHOUT THE EXPRESS AUTHORIZATION OF THE STRUCTURAL
ENGINEER.
4. PRIOR TO INSTALLING MECHANICAL/ELECTRICAL EQUIPMENT OR CREATING
OPENINGS IN EXISTING SLABS, THE CONTRACTOR SHALL PERFORM A SURVEY OF
STRUCTURAL ELEMENTS (BEAM SIZES, SPACING, ETC.) . THIS SURVEY SHALL
INCLUDE AS A MINIMUM TESTING TO DETERMINE SLAB THICKNESS, (EITHER BY
CONCRETE CORE OR ALTERNATE NON-DESTRUCTIVE TESTING METHOD), AND
REINFORCEMENT MAPPING INDICATING SIZE AND DISTRIBUTION OF
REINFORCEMENT. ONCE THIS INFORMATION HAS BEEN GATHERED, IT SHALL BE
SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVISION OF THE FLOOR SYSTEM
CAPACITY. THE CONTRACTOR SHALL NOT PROCEED WITH THE INSTLLATION OF
EQUIPMENT OR SLAB PERFORATION UNTIL AUTHORIZATION IS PROVIDED BY
STRUCTURAL ENGINEER.
5. PRIOR TO DEMOLISHING ANY GRADE LEVEL STRUCTURE, CONTRACTOR SHALL
CONSULT CIVIL, MECHANICAL AND ELECTRICAL PLANS TO VERIFY THE PRESENCE OF
UTILITIES. SIDEWALK, CURB SLAB, OR STRUCTURE, CUT IT WITH A POWER SAW AND
PROVIDE A "V" TYPE CONSTRUCTION JOINT.
6. PRIOR TO DEMOLISHING ANY SIDEWALK, CURB SLAB, OR GRADE LEVEL STRUCTURE,
PROVIDE A "V" TYPE CONSTRUCTION JOINT CUT WITH A POWER SAW.
7. SELECTIVE DEMOLITION TYPICALLY ENTAILS REMOVAL OF MATERIAL NOT INCLUDING
REINFORCEMENT OR STEEL DECKING. REFER TO DRAWINGS FOR EACH PARTICULAR
CONDITION.
STRUCTURAL NOTES
BID SET
CSA Architects & Engineers, LLP
MERCANTIL PLAZA, MEZZANINE SUITE
SAN JUAN PUERTO RICO 00918
tel. (787) 641-6800 fax (787) 641-6850
CONTRACTING OFFICER
CHRIS LASHURE
PROJECT MANAGER
JOSE PUNCHIN, PE
J.Q.V.F.
AutoCAD SHX Text
SB001
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of 43
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text 672-14-607
AutoCAD SHX Text
AutoCAD SHX Text
VAMC SAN JUAN
AutoCAD SHX Text P.R.
AutoCAD SHX Text
REPAIR MAIN BUILDING
AutoCAD SHX Text
BASEMENT METAL DECK
AutoCAD SHX Text
JUNE-20-2017
3.4
2.3
1.3
R S T
W6 x 12
(EXIST.)
TYP.
TYP.
SCALE:
BASE PLATE RETROFIT DETAIL
1½" = 1'-0"
SCALE:
BEAM TO COLUMN
CONNECTION RETROFIT DETAIL
1½" = 1'-0"
SCALE:
BEAM TO GIRDER
CONNECTION RETROFIT DETAIL
1½" = 1'-0"
BID SET
CSA Architects & Engineers, LLP
MERCANTIL PLAZA, MEZZANINE SUITE
SAN JUAN PUERTO RICO 00918
tel. (787) 641-6800 fax (787) 641-6850
CONTRACTING OFFICER
CHRIS LASHURE
CANTEEN
KEY PLAN
MAIN BUILDING
BASEMENT
METAL DECK
PROJECT MANAGER
JOSE PUNCHIN, PE
SUB-BASEMENT CANTEEN EXISTING FRAMING PLAN
1/4"= 1'-0"
SUB-BASEMENT CANTEEN AREA -
EXISTING FRAMING PLAN
J.Q.V.F.
AutoCAD SHX Text 16W40
AutoCAD SHX Text 16W26
AutoCAD SHX Text 16B31
AutoCAD SHX Text 16B26
AutoCAD SHX Text 16W36
AutoCAD SHX Text 21W68
AutoCAD SHX Text 16B26
AutoCAD SHX Text
18WF45
AutoCAD SHX Text 16B26
AutoCAD SHX Text 16B26
AutoCAD SHX Text
18WF45
AutoCAD SHX Text 21W68
AutoCAD SHX Text 16B26
AutoCAD SHX Text 18W45
AutoCAD SHX Text
21WF55
AutoCAD SHX Text
21WF55
AutoCAD SHX Text
21WF55
AutoCAD SHX Text
21WF55
AutoCAD SHX Text
21WF55
AutoCAD SHX Text 16W40
AutoCAD SHX Text 16W40
AutoCAD SHX Text
21WF55
AutoCAD SHX Text
12" STEEL JOIST
AutoCAD SHX Text
12" STEEL JOIST
AutoCAD SHX Text
12" STEEL JOIST
AutoCAD SHX Text
12" STEEL JOIST
AutoCAD SHX Text
12" STEEL JOIST
AutoCAD SHX Text
12" STEEL JOIST
AutoCAD SHX Text 10B12
AutoCAD SHX Text 16W36
AutoCAD SHX Text 16B26
AutoCAD SHX Text 16B26
AutoCAD SHX Text 16W36
AutoCAD SHX Text 16B26
AutoCAD SHX Text 16B26
AutoCAD SHX Text 16B26
AutoCAD SHX Text W6x12
AutoCAD SHX Text W6x12
AutoCAD SHX Text W6x12
AutoCAD SHX Text W6x12
AutoCAD SHX Text W6x12
AutoCAD SHX Text W6x12
AutoCAD SHX Text W6x12
AutoCAD SHX Text W6x12
AutoCAD SHX Text
12" STEEL JOIST
AutoCAD SHX Text
12" STEEL JOIST
AutoCAD SHX Text
12" STEEL JOIST
AutoCAD SHX Text
12" STEEL JOIST
AutoCAD SHX Text
12" STEEL JOIST
AutoCAD SHX Text
12" STEEL JOIST
AutoCAD SHX Text W8x24
AutoCAD SHX Text W8x24
AutoCAD SHX Text W8x24
AutoCAD SHX Text 14B22
AutoCAD SHX Text 12B14
AutoCAD SHX Text 12B14
AutoCAD SHX Text
8WF24
AutoCAD SHX Text
8WF24
AutoCAD SHX Text
SEE "BEAM TO COLUMN CONNECTION RETROFIT DETAIL" ON THIS DWG. (TYP.)
AutoCAD SHX Text
SEE "BEAM TO COLUMN CONNECTION RETROFIT DETAIL" ON THIS DWG. (TYP.)
AutoCAD SHX Text
NOTE: SCOPE OF WORK INCLUDES RETROFIT OF TEMPORARY SHORING ELEMENTS ONLY
AutoCAD SHX Text W6 x 12 (EXIST.)
AutoCAD SHX Text HSS 3"x 3" (EXIST.)
AutoCAD SHX Text
EXIST. FLOOR DECK
AutoCAD SHX Text PL 6"x 4"x " EACH FACE14" EACH FACE
AutoCAD SHX Text L 3"x 3"x "x 5" LG. 14"x 5" LG. EACH FACE
AutoCAD SHX Text HSS 3"x 3" (EXIST.)
AutoCAD SHX Text
(4) " DIA. KWIK BOLT TZ 34" DIA. KWIK BOLT TZ EXPANSION ANCHOR (EMB. = 4 ") BY HILTI OR 14") BY HILTI OR APPROVED EQUAL
AutoCAD SHX Text PL 12"x 12" (EXIST.)
AutoCAD SHX Text
PLAN VIEW
AutoCAD SHX Text
SECTION VIEW
AutoCAD SHX Text
EXIST. SLAB
AutoCAD SHX Text W6 x 12 (EXIST.)
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
W BEAM EXIST.
AutoCAD SHX Text L 3"x 3"x " x 5" LG. 14" x 5" LG.
AutoCAD SHX Text
EXIST. FLOOR DECK
AutoCAD SHX Text 316"
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of 43
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text 672-14-607
AutoCAD SHX Text
AutoCAD SHX Text
VAMC SAN JUAN
AutoCAD SHX Text P.R.
AutoCAD SHX Text
REPAIR MAIN BUILDING
AutoCAD SHX Text
BASEMENT METAL DECK
AutoCAD SHX Text
JUNE-20-2017
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
EXISTING STRUCTURE
AutoCAD SHX Text
%%ULEGEND:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
SB101
E
F
G
H
I
J
K
A
B
C
1 2 3 4 5
BID SET
CSA Architects & Engineers, LLP
MERCANTIL PLAZA, MEZZANINE SUITE
SAN JUAN PUERTO RICO 00918
tel. (787) 641-6800 fax (787) 641-6850
CONTRACTING OFFICER
CHRIS LASHURE
CANTEEN
KEY PLAN
MAIN BUILDING
BASEMENT
METAL DECK
PROJECT MANAGER
JOSE PUNCHIN, PE
LEGEND:
EXISTING FLOOR STRUCTURAL DEMOLITION PLAN
3/16"= 1'-0"
METAL DECK AREA - EXISTING
FLOOR STRUCTURAL DEMOLITION
J.Q.V.F.
AutoCAD SHX Text
EXIST. HSS & STL. PLATE TO BE DEMOLISHED (TYP.)
AutoCAD SHX Text
EXISTING SLAB AT FOOTING AREA TO BE PARTIALLY DEMOLISHED.
AutoCAD SHX Text
EXIST. HSS, STL. PLATE, CONC. & FOUNDATIONS PEDESTAL TO BE DEMOLISHED (TYP.)
AutoCAD SHX Text HSS 8"x8" (EXIST.)
AutoCAD SHX Text
EXIST. HSS & STL. PLATE TO BE DEMOLISHED (TYP.)
AutoCAD SHX Text
EXIST. STD. PIPE & STL. PLATE TO BE DEMOLISHED (TYP.)
AutoCAD SHX Text
PIV (POST INDICATOR VALVE) TO BE DEMOLISHED UP TO 12" BELOW EXISTING SLAB.
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of 43
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text 672-14-607
AutoCAD SHX Text
AutoCAD SHX Text
VAMC SAN JUAN
AutoCAD SHX Text P.R.
AutoCAD SHX Text
REPAIR MAIN BUILDING
AutoCAD SHX Text
BASEMENT METAL DECK
AutoCAD SHX Text
JUNE-20-2017
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
EXISTING STRUCTURE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
MATCH LINE
AutoCAD SHX Text
MATCH LINE
AutoCAD SHX Text
SB102
AutoCAD SHX Text DEMOLITION NOTES: 1. CONTRACTOR SHALL PARTIALLY DEMOLISH EXISTING CONCRETE SLAB AND CONTRACTOR SHALL PARTIALLY DEMOLISH EXISTING CONCRETE SLAB AND STAIRS AS REQUIRED TO DEMOLISH AND RE-BUILD PROPOSED FOUNDATIONS. 2. EXISTING METAL GRATING SHALL BE TEMPORARY REMOVED AS REQUIRED TO EXISTING METAL GRATING SHALL BE TEMPORARY REMOVED AS REQUIRED TO COMPLETE PROPOSED DEMOLITION AND RE-BUILD OF NEW FOUNDATIONS IN THE AREA. 3. RE-CAST CONCRETE SLAB, STAIRS, AND RAMPS TO MATCH EXISTING RE-CAST CONCRETE SLAB, STAIRS, AND RAMPS TO MATCH EXISTING CONDITION INCLUDING FINISH AND ELEVATIONS. 4. RE-INSTALL REMOVED METAL GRATING TO MATCH EXISTING CONDITION. RE-INSTALL REMOVED METAL GRATING TO MATCH EXISTING CONDITION. 5. EXISTING METAL ROOF AREA TO BE REPLACED SHALL BE ALSO CONSIDERED EXISTING METAL ROOF AREA TO BE REPLACED SHALL BE ALSO CONSIDERED FOR THE DEMOLITION PROCESS. 6. SELECTIVE DEMOLITION AT SLAB AREA SHALL BE PERFORMED IN ORDER TO SELECTIVE DEMOLITION AT SLAB AREA SHALL BE PERFORMED IN ORDER TO KEEP IN PLACE EXISTING SLAB REINFORCEMENT. BARS CAN BE CUT AT CENTER OF PARTIAL DEMOLITION TO BE RE-USE AFTER FOOTING INSPECTION.
AutoCAD SHX Text
SLAB AREA TO BE PARTIALLY DEMOLISHED AS SELECTIVE DEMOLITION.
AutoCAD SHX Text
PEDESTAL, PIPE COLUMN AND BOLT TO BE DEMOLISHED.
AutoCAD SHX Text
PEDESTAL, SQUARE COLUMN AND BOLT TO BE DEMOLISHED.
A
B
C
D
E
F
G
H
I
J
K
SCALE:
FOOTING TYPE F-1 DETAIL
1/2"=1'-0" SCALE:
FOOTING TYPE F-2 DETAIL
1/2"=1'-0" SCALE:
FOOTING TYPE F-3 DETAIL
1/2"=1'-0"
A
SB103
B
SB103
A
SB103
A
SB103
B
SB103
B
SB103
SCALE:SB103
SECTION
TYP. PEDESTAL
1"=1'-0" A
SCALE:SB103
SECTION
TYPICAL BP-2
1"=1'-0" B
BID SET
CSA Architects & Engineers, LLP
MERCANTIL PLAZA, MEZZANINE SUITE
SAN JUAN PUERTO RICO 00918
tel. (787) 641-6800 fax (787) 641-6850
CONTRACTING OFFICER
CHRIS LASHURE
CANTEEN
KEY PLAN
MAIN BUILDING
BASEMENT
METAL DECK
PROJECT MANAGER
JOSE PUNCHIN, PE
LEGEND:
FOUNDATION AND NEW COLUMNS LAYOUT PLAN
3/16"= 1'-0"
METAL DECK AREA - FOUNDATION
AND COLUMNS LAYOUT PLAN,
DETAILS AND SECTIONS (1 OF 2)
J.Q.V.F.
AutoCAD SHX Text W8 x 35 (TYPICAL)
AutoCAD SHX Text W8 x 35 (TYPICAL)
AutoCAD SHX Text W8 x 35 (TYPICAL)
AutoCAD SHX Text F-2
AutoCAD SHX Text F-2
AutoCAD SHX Text F-2
AutoCAD SHX Text F-2
AutoCAD SHX Text F-2
AutoCAD SHX Text F-2
AutoCAD SHX Text F-1
AutoCAD SHX Text F-1
AutoCAD SHX Text F-1
AutoCAD SHX Text F-1
AutoCAD SHX Text F-2
AutoCAD SHX Text F-2
AutoCAD SHX Text F-2
AutoCAD SHX Text F-3
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text
BP-2
AutoCAD SHX Text 4'-9"
AutoCAD SHX Text 4'-9"
AutoCAD SHX Text 4'-9"
AutoCAD SHX Text 4'-9"
AutoCAD SHX Text 6'-0"
AutoCAD SHX Text 6'-0"
AutoCAD SHX Text 6'-0"
AutoCAD SHX Text 6'-0"
AutoCAD SHX Text
BP-2
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text #5 @ 6" (T & B)
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text #5 @ 6" (T & B)
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text #5 @ 6" (T & B)
AutoCAD SHX Text
VAPOR BARRIER
AutoCAD SHX Text W8
AutoCAD SHX Text
4- 3/4" X 1'-6"ANCHOR ROD ASTM F-1554 GR. 36
AutoCAD SHX Text
1 " NON-SHRINK GROUT12" NON-SHRINK GROUT
AutoCAD SHX Text W8
AutoCAD SHX Text
4- 3/4" X 1'-6"ANCHORROD ASTM F-1554 GR. 36
AutoCAD SHX Text
1 " NON-SHRINK GROUT12" NON-SHRINK GROUT
AutoCAD SHX Text
W8 (TYP.)
AutoCAD SHX Text
4- " ANCHOR X 1'-6" ROD 34" ANCHOR X 1'-6" RODASTM F-1554 GR. 36 (TYP.)
AutoCAD SHX Text
1 " NON-SHRINK 12" NON-SHRINK GROUT (TYP.)
AutoCAD SHX Text
PREMOLDED JT. FILLER
AutoCAD SHX Text
PREMOLDED JT. FILLER
AutoCAD SHX Text
PREMOLDED JT. FILLER (TYP.)
AutoCAD SHX Text PL 14"x14"x1" W/ HSS 4"x4"x " SHEAR LUG38" SHEAR LUG
AutoCAD SHX Text PL 14"x14"x1" W/ HSS 4"x4"x " SHEAR LUG38" SHEAR LUG
AutoCAD SHX Text PL 14"x14"x1" W/ HSS 4"x4"x " 38" SHEAR LUG (TYP.)
AutoCAD SHX Text 14"
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
(2) #4 ANCHOR REINF. (ADDITIONAL)
AutoCAD SHX Text 14"
AutoCAD SHX Text
TYP.
AutoCAD SHX Text 14"
AutoCAD SHX Text
(2) #4 ANCHOR REINF.
AutoCAD SHX Text
(2) #4 ANCHOR REINF. (ADDITIONAL)
AutoCAD SHX Text 14"
AutoCAD SHX Text 14"
AutoCAD SHX Text
#3 @ 4" TIES
AutoCAD SHX Text
4- " X 1'-6" 34" X 1'-6"ANCHOR RODS ASTM F-1554 GR. 36
AutoCAD SHX Text
PLATE 1" THK.
AutoCAD SHX Text W8
AutoCAD SHX Text 14"
AutoCAD SHX Text HSS 4"x4"x " 38" SHEAR LUG WELDED TO PLATE
AutoCAD SHX Text 14"
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of 43
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text 672-14-607
AutoCAD SHX Text
AutoCAD SHX Text
VAMC SAN JUAN
AutoCAD SHX Text P.R.
AutoCAD SHX Text
REPAIR MAIN BUILDING
AutoCAD SHX Text
BASEMENT METAL DECK
AutoCAD SHX Text
JUNE-20-2017
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
EXISTING STRUCTURE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
SB103
AutoCAD SHX Text NOTES: 1. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO AVOID DAMAGES CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO AVOID DAMAGES TO EXISTING SHALLOW PULL BOX NEAR PROPOSED FOUNDATIONS IN CASE ANY CONFLICTS ARISES, CONTACT DESIGNER PRIOR TO TAKE ANY FURTHER ACTION.
F
G
H
I
J
K
1 2 3 4 5
A
B
C
SCALE:
FOOTING TYPE F-4 DETAIL
1/2"=1'-0"
B
SB104
A
SB104
SCALE:SB104
SECTION
TYP. PEDESTAL
1"=1'-0"…