36C24726Q0680 0001.docx
DOCX document 46 MB Posted
- Attached to
- J059--EMERGENCY LOW VOLTAGE (480) SOURCE SWITCHGEAR and AUTOMATIC TRANSFER SWITCH (ATS) AND THE UTILITY LOW VOLTAGE (480) SOURCE SWITCHGEAR AND ATS Federal contract opportunity
- Solicitation number
- 36C24726Q0680
About this file
This is a Standard Form 30 Amendment to Solicitation extending the closing date and providing supplemental information for a low-voltage electrical switchgear maintenance and testing project at the Department of Veterans Affairs Central Alabama Veterans Health Care System.
The solicitation 36C24726Q0680 is for Emergency Low Voltage (480V) Source Switchgear and Automatic Transfer Switch (ATS) maintenance, as well as Utility Low Voltage (480V) Source Switchgear and ATS services. The amendment extends the receipt of offers deadline to August 4, 2026, at 1:00 PM EDT and specifies that site visits may be conducted between July 27 and August 3, 2026, with Raymond Herndon serving as the point of contact (843-543-3820). The work involves testing and maintenance of low-voltage automatic transfer switches (480V) only and specifically excludes the VHA Directive 1028 tri-annual maintenance contract. Key findings from the questions and answers clarify that PIV credentialing (approximately 6 weeks processing) will not delay mobilization, contractor personnel may access the site under escort during credentialing, and existing active VA-issued PIV credentials are acceptable. Only foremen and supervisors require initial PIV credential issuance. The equipment includes three GE 489 protective relays on CAT-ISO parallelling switchgear and four Eaton FP-5000 protective relays on main distribution switchgear. ASCO brand automatic transfer switches are specified. Any work requiring outages must be scheduled at least two weeks in advance, likely occurring after hours or weekends. The amendment includes comprehensive manufacturer drawings and technical documentation for Cutler-Hammer medium-voltage switchgear assemblies and Eaton medium-voltage switches with detailed bills of material, certified production test reports, and seismic application guidelines.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24726Q0680.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) 07-24-2026 Department of Veterans Affairs Central Alabama Veterans Health Care 215 Perry Hill Road Montgomery
AL
36109-3798 Department of Veterans Affairs Central Alabama Health Care System East Campus 2400 Hospital Road Tuskegee
AL
36083-5001 To all Offerors/Bidders
36C24726Q0680
X X X ** HOUR & DATE for Receipt of Offers is EXTENDED to: 08-04-2026 1:00 EDT X The purpose of this amendment is to extend the closing date, provide Question and Answers and to provide Site Visit POC and times. Any site visit should be accomplished between 27 July through 3 August 2026.
POC: Raymond Herndon raymond.herndod@va.gov Mobile # 843-543-3820 Charleston VAMC
SEE ATTACHED QUESTIONS AND ANSWERS
Marcus Watts Contracting Officer
1. What is the expected processing time for background investigations and PIV credential issuance?
A: Approximately 6 weeks. (Contractor will be escorted during P/M and temporary badges are available).
1. May contractor personnel access the site under escort while PIV credentialing is pending?
A: Yes.
1. Will existing active VA-issued PIV credentials be accepted for this contract?
A: Yes
1. Which contractor personnel are required to obtain PIV credentials under this contract?
A: Initially, foreman and supervisors.
1. Has the project schedule accounted for the personnel vetting and PIV credentialing process before mobilization?
A: PIV process will not affect mobilization. (See item 1)
1. Can you confirm the quantity of all low-voltage circuit breakers that are 1600A and higher?
A; This P/M is for the low voltage Automatic Transfer switches (480v) only.
7. Please confirm whether all testing and services are to be performed in accordance with ANSI/NETA MTS and VHA Directive 1028.
A: This contract is not for the 1028 Directive tri-annual maintenance and inspection
8. Please provide the shutdown and test schedule for this solicitation A: Any work that requires an outage will need to be scheduled at least 2 weeks in advance, and most likely will need to happen after hours or on a weekend 9 . I don't see the protective relays on the switchgear listed, can you confirm they are excluded?
A: There are three (3) GE 489 protective relays on the CAT-ISO parallelling switchgear, and, four (4) Eaton FP-5000 protective relays on the main distribution switchgear. These should be included
10. What brand(s) are the ATS's?
A: ASCO
See below one line (comprehensive)
CAT-1SO Gear Manufacturers Drawings Switchgear Manufacturer
Generator (Big 3) and Main Switchgear Project drawings
N/a image1.png image2.emf
CAT-ISO Gear Manufacturers Drawings.pdf
Xerox Scan_07212026100528
Xerox Scan_07212026100424
Xerox Scan_07212026100313
Xerox Scan_07212026100002 image3.emf
Main Switchgear Manufacturer Drawing (Birdhouse & H200 Switchgear).pdf
Master Document Index
Cutler-Hammer Medium Voltage Assemblies
MVA 15 kV Lineup
GO-ITEM: MCS03114-002 File/Rev: MM001J47.HTM/2 SO Number: PO Number:
Designation: Customer:
EMS0625 - Ralph Johnson VA Medical
User: hillpp Date: 5/21/2009 9:49:52
AM
Approval: Construction: As-Built: X
Drawing Description Document Name Rev
1 Master Drawing List MM001J47.DOC 2 2 Certified Production Test Report M90006K3.DOC 2
3 NAMEPLATES MK876I2Y0101.DOC 2
4 KEY LOCK SCHEDULE MK876I2K0101.DOC 2
5 BILL OF MATERIAL MK876I2P0101.DOC 3
6 INDOOR BASE PLAN WITH FLOOR CHANNELS
(36W X 96.25D) 6533C07.DWG 8
7 LEGEND LEGEND-GWD.DWG 5
8 PANEL BOARD MK876I2D0101.DOC 2
9 END VIEW MK876I2O0101.DWG 2
10 ROOF PLAN & FLOOR PLAN MK876I2Q0101.DWG 2
11 GENERAL DESCRIPTION MK876I2Z9001.DOC 2
12 FRONT VIEW MK876I2F0101.DWG 2
13 ONE LINE MK876I2L0101.DWG 2
14 SECTIONAL SIDE VIEW MK876I2V0101.DWG 2
15 SECTIONAL SIDE VIEW MK876I2V0201.DWG 2
16 SECTIONAL SIDE VIEW MK876I2V0301.DWG 2
17 SECTIONAL SIDE VIEW MK876I2V0401.DWG 2
18 ELECTRICAL MASTER DRAWING MK876I2E0101.DWG 2
19 SCHEMATIC DIAGRAM MK876I2S0101.DWG 3
20 THREE LINE DIAGRAM MK876I2T0101.DWG 2
21 WIRING DIAGRAM MK876I2W0101.DWG 1
22 WIRING DIAGRAM MK876I2W0102.DWG 1
23 WIRING DIAGRAM MK876I2W0201.DWG 1
24 WIRING DIAGRAM MK876I2W0202.DWG 1
25 WIRING DIAGRAM MK876I2W0203.DWG 1
26 WIRING DIAGRAM MK876I2W0301.DWG 1
27 WIRING DIAGRAM MK876I2W0302.DWG 1
28 WIRING DIAGRAM MK876I2W0303.DWG 1
29 WIRING DIAGRAM MK876I2W0401.DWG 1
30 WIRING DIAGRAM MK876I2W0402.DWG 1
Certified Production Test Report - MVA
Cutler-Hammer, 2210 Highway 72/221 East, Greenwood, SC 29648
GO-ITEM: MCS03114-002
EQUIPMENT DESIGNATION:
CERTIFICATION
The test below reflect the requirements in ANSI/IEEE C37.20.2 CSA C22.2 No. 31-04 and EEMAC G11-1 for inspections and production testing.
TESTING PASSED NA
Actual operation performed wherever possible, inspection or continuity checks made. X Component devices operated as shown on diagrams. X Control bus energized as 80% rated D-C or 85% A-C control voltage. X Control devices operated as shown on diagrams. X Verification of all remote circuits and spare contacts which were not included in operational test. X
Unless otherwise reported, protective relays, and other associated equipment functionally tested by energizing current and potential circuits to rated values. X
Instruments operated, expected readings verified. X Electro-mech watt hour meters checked for proper direction of disc rotation and current circuits for phasing. X
Protective relays operated for functional check in accordance with rating and application. Instantaneous trips manually operated to verify correct functioning of operation indicator and associated circuits.
Relays set and checked for operation within range of test equipment X Control circuits and associated wiring received insulation test of 1500 volts, 60 cycles for one minute, except where equipment manufacturer specifications do not permit. X
Primary insulation tested at (19K VAC, 60Hz RMS). X Primary insulation tested at (36K VAC, 60Hz RMS). X Primary insulation tested at (60K VAC, 60Hz RMS). X Primary insulation tested at (80K VAC, 60Hz RMS). X The corona pulse magnitude was less than 100pC when tested at a corona-extinction voltage of 3.5 KV. X voltage of 5.5 KV. X voltage of 10.5 KV. X voltage of 19.5 KV. X voltage of 26.5 KV. X
This certifies that the above is based upon recorded factory tests made at this location.
Silas Childs
Tester
Certified Production Test Report - MVA
02/25/2009 Date
M90006K3.DOC
NAMEPLATES
JIANG
GREENWOOD
RALPH H. JOHNSON VA MEDICAL CENTER
CHARLESTON, SC MP00031
FILENAME : MK876I2Y0101
GO. : MCS03114-002 ITEM: 002 SHEET 1
THE INFORMATION ON THIS
DOCUMENT WAS CREATED
BY CUTLER-HAMMER. IT
WAS DISCLOSED IN
CONFIDENCE AND IS ONLY
TO BE USED FOR THE
PURPOSE IN WHICH IT WAS
SUPPLIED. REV: 2 DESIGNATION: NAMEPLATES
CIRCUIT NAMEPLATES
4.32 x 1.00 [109.7 x 25.4] SCREW MOUNTED NAMEPLATES WHITE WITH BLACK LETTERS 0.20 [5.1]
Maximum number of characters per line – 18
ID LINE ONE LINE TWO LINE THREE TOTAL
QTY
C01A CPT FUSE DRAWER 1
C01D BUS 1 VT 1
C02A LINE 1 VTS 1
C02D MAIN BKR 1 1
C03A LINE 2 VTS 1
C03D MAIN BKR 2 1
C04A CPT FUSE DRAWER 1
C04D BUS 2 VT 1
EXTERIOR DEVICE NAMEPLATES
2.50 x 0.75 [63.5 x 19.05] SCREW MOUNTED NAMEPLATES WHITE WITH BLACK LETTERS 0.20 [5.08]
Maximum number of characters per line – 14
ID LINE ONE LINE TWO TOTAL
D137 86-1 1 D138 86-2 1
D480A FP5200 2
D612 CPT 2
D642 TRIP 86 2
D750A POWER XPERT METER 2
INTERIOR DEVICE NAMEPLATES
2.50 x 0.75 [63.5 x 19.05] SCREW MOUNTED NAMEPLATES WHITE WITH BLACK LETTERS 0.20 [5.08]
Maximum number of characters per line – 14
ID LINE ONE LINE TWO TOTAL
D007 BUS V.T.S 2
D017 LINE V.T.S 2
D199 BKR CONTROL 30 AMP 2
D624 FUSE DRAWER 2
NAMEPLATES
FILENAME : MK876I2Y0101
GO. : MCS03114-002 ITEM: 002 SHEET 2
BY CUTLER-HAMMER. IT
WAS DISCLOSED IN
CONFIDENCE AND IS ONLY
TO BE USED FOR THE
SUPPLIED. REV: 2 DESIGNATION: NAMEPLATES
ID NP ENGRAVING
G.O: MCS03114 Manufactured in: GREENWOOD,SC, USA Date of Mfr.: 01/22/2009 Item: 002 Rated Freq: 60 Phases: 3
Shop Order: 72YK876 Rated Max Voltage: 15kV Type: VC-W Power Frequency Withstand: 36 kV BIL: 95 kV
MAIN BUS CURRENT RATINGS
Continuous: 1200A Momentary, RMS Asymmetrical:
36.8 KA RMS 2 Second Short Time: 23kA
Enclosure Type: 1 Enclosure Category: C Instructions: IB 32-255-1 8063A76H05
KEY LOCK SCHEDULE
FILENAME : MK876I2K0101
BY CUTLER-HAMMER. IT
WAS DISCLOSED IN
CONFIDENCE AND IS ONLY
TO BE USED FOR THE
SUPPLIED. REV: 2 DESIGNATION: KEYLOCK
ITEM
NO.
CATALOG
TYPE PROJ. EXTENDED /
WITHDRAWN
INT LOCK
NOTE WHERE USED VS
H01 KFL000010S E 0 E K1 BREAKER PAN ASSEMBLY 02
H02 KFL000010S E 0 E K1 BREAKER PAN ASSEMBLY 03
H03 KFL003710S E 3/8 E K2 F-FRAME LV BKR 01
H04 KFL000010S E 0 E K2 FUSE DRAWER 01
H05 KFL003710S E 3/8 E K3 F-FRAME LV BKR 04
H06 KFL000010S E 0 E K3 FUSE DRAWER 04
NOTES:
1. SECTION 2 AND SECTION 3
2. SECTION 1 AND SECTION 4
PURCHASE FROM ----- KIRK KEY COMPANY
ULTIMATE USER ----- RALPH H. JOHNSON VA MEDICAL CENTER
LOCATION ----- CHARLESTON, SC
BILL OF MATERIAL
FILENAME : MK876I2P0101
BY CUTLER-HAMMER. IT
WAS DISCLOSED IN
CONFIDENCE AND IS ONLY
TO BE USED FOR THE
SUPPLIED. REV: 3 DESIGNATION: BILL OF MATERIAL
DEVICE
NAMEPLATE QTY PART
NUMBER DESCRIPTION * DEVICE ID’s
VERTICAL SECTION 01
D624 3 677C453G03 PRI-FUSE, CH, CLE, 15.5 KV 5.0E CLE-
PT
1AF
1 K876LKH04 KEY INTERLOCK PER DWG
MK876I2K0101
1AK
1 K876LKH03 KEY INTERLOCK PER DWG
1BA
1 EHD3100 PROT/CTRL, CH, BREAKER, EHD, 3
POLE 100 AMP
1BB
D017 1 1C17629G06 VT, ITI, 1PT L-L ASSY, 110KV BIL,
14400:120 SYS V
1DA
2 5981C07G05 PRI-FUSE, CH, CLE, 15.5 KV 1.0E CLE-
1DF
1 KYK1 PROT/CTRL, CH, INTLK KIT, FOR
SERIES C F-FRAME BKR
1BC
1 YS2036 PROT/CTRL, CH, PANEL BOARD BOX,
20W X 36H X 5.75D
1PA
1 LT2036S PROT/CTRL, CH, PANEL BOARD TRIM,
20 X 36 SURF
1PB
1 MK876I2D0101 PROT/CTRL, CH, PANEL BOARD
INTERNALS FOR K876
1PC
D612 1 3CPT595301382A CPT, ITI, 30 KVA, 95KV BIL, 3-PH
13800/120-208V, 2 TAPS 7.5%
1WA
VERTICAL SECTION 02
1 68C5010G01 CH, BREAKER WHEEL CONVERSION
KIT
B 2BW
D007 1 1C17639G06 VT, ITI, 2PTS L-L ASSY 14400:120 SYS
V
2BA
4 5981C07G05 PRI-FUSE, CH, CLE, 15.5 KV 1.0E CLE-
2BF
D199 1 3A40335G20 PROT/CTRL, CH, PULL FUSE 2P W/2 30
AMP FUSES
2CA
1 3A40369G02 BREAKER, 150 VCPW 750, 1200A 60HZ,
UL, 125VDC C/M/T
2DB
1 K876LKH01 KEY INTERLOCK PER DWG
2DK
1 6510C50G03 SWITCH, GWD, MOC, 9 POLE 5A-4B
CONN ONLY
2DM
3 6350C24H01 CT, ABB, SCV 1200/5MR STD ACC C200 2DP
1 6510C49G03 SWITCH, GWD, TOC, 9-POLE 4A-5B
WIRED
2DT
1 PX4051A1BB METER, CH, POWER-XPERT 4000
METER W/ COMM EXPANSION AND I/O
CARDS
2HA
D750A 1 PXD-MMG METER, CH, POWER-XPERT GRAPHIC
DISPLAY MODULE
2HB
D642 1 3A40273G06 LIGHT, CH, E22, IND LT ASSY AMBER
125V
2PA
GO. : MCS03114-002 ITEM: 002 SHEET 2
BY CUTLER-HAMMER. IT
WAS DISCLOSED IN
CONFIDENCE AND IS ONLY
TO BE USED FOR THE
1 3A40273G36 LIGHT, CH, E22, IND LT ASSY GREEN
2PB
1 3A40273G46 LIGHT, CH, E22, IND LT ASSY RED
2PC
D137 1 7802D RELAY, ELS, LOR-24, 125VDC/120VAC
2 DECK 30-140VDC
2PD
1 2452D SWITCH, ELS, SER 24, BKR CTRL,
PULL-TO-LOCK HNDL 5-ST
2PE
D480A 1 66D2041G11 RELAY, CH, FP5200-00, 5A, 48-125VDC
120VAC, INCOM,DRAWOUT CASE
2PF
3 UHS12060B0D0A1A ARRESTER, CPS, 12KV DISTRIBUTION
CLASS
2WA
6 8264A16H06 COMPONENT, WES, TERMINAL 1/0
AWG COMPRESSION
2WL,2ZL
2 8264A16H01 COMPONENT, WES, TERMINAL 6 AWG
COMPRESSION
2WY,2ZY
1 6353C97H01 ZERO SEQ CT, ABB, 50:5A C10 2ZZ
VERTICAL SECTION 03
1 68C5010G01 CH, BREAKER WHEEL CONVERSION
B 3BW
D007 1 1C17639G06 VT, ITI, 2PTS L-L ASSY 14400:120 SYS
3BA
4 5981C07G05 PRI-FUSE, CH, CLE, 15.5 KV 1.0E CLE-
3BF
D199 1 3A40335G20 PROT/CTRL, CH, PULL FUSE 2P W/2 30
3CA
1 3A40369G02 BREAKER, 150 VCPW 750, 1200A 60HZ,
3DB
1 K876LKH02 KEY INTERLOCK PER DWG
3DK
1 6510C50G03 SWITCH, GWD, MOC, 9 POLE 5A-4B
3DM
3 6350C24H01 CT, ABB, SCV 1200/5MR STD ACC C200 3DP
1 6510C49G03 SWITCH, GWD, TOC, 9-POLE 4A-5B
3DT
3HA
D750A 1 PXD-MMG METER, CH, POWER-XPERT GRAPHIC
3HB
D642 1 3A40273G06 LIGHT, CH, E22, IND LT ASSY AMBER
3PA
1 3A40273G36 LIGHT, CH, E22, IND LT ASSY GREEN
3PB
1 3A40273G46 LIGHT, CH, E22, IND LT ASSY RED
3PC
D138 1 7802D RELAY, ELS, LOR-24, 125VDC/120VAC
3PD
GO. : MCS03114-002 ITEM: 002 SHEET 3
BY CUTLER-HAMMER. IT
WAS DISCLOSED IN
CONFIDENCE AND IS ONLY
TO BE USED FOR THE
1 2452D SWITCH, ELS, SER 24, BKR CTRL,
3PE
D480A 1 66D2041G11 RELAY, CH, FP5200-00, 5A, 48-125VDC
3PF
3 UHS12060B0D0A1A ARRESTER, CPS, 12KV DISTRIBUTION
3WA
6 8264A16H06 COMPONENT, WES, TERMINAL 1/0
3WL,3ZL
2 8264A16H01 COMPONENT, WES, TERMINAL 6 AWG
3WY,3ZY
1 6353C97H01 ZERO SEQ CT, ABB, 50:5A C10 3ZZ
VERTICAL SECTION 04
D624 3 677C453G03 PRI-FUSE, CH, CLE, 15.5 KV 5.0E CLE-
4AF
1 K876LKH05 KEY INTERLOCK PER DWG
4BA
1 K876LKH06 KEY INTERLOCK PER DWG
4AK
1 EHD3100 PROT/CTRL, CH, BREAKER, EHD, 3
4BB
D017 1 1C17629G06 VT, ITI, 1PT L-L ASSY, 110KV BIL,
4DA
2 5981C07G05 PRI-FUSE, CH, CLE, 15.5 KV 1.0E CLE-
4DF
1 KYK1 PROT/CTRL, CH, INTLK KIT, FOR
4BC
D612 1 3CPT595301382A CPT, ITI, 30 KVA, 95KV BIL, 3-PH
4WA
MISCELLANEOUS
1 32220WA00K MISC, PAINT, ANSI 61, 9OZ AEROSOL COMP
1 REF700B214 SWITCHGEAR STORAGE INSTRUCT
DWG
COMP
1 8064A02G01 HANDLE ASSY COMP
1 7813C41G03 RAIL EXTENSION LH/RH COMP
1 701B601G03 BREAKER, CH, LEV-IN CRANK W/
CLUTCH – CLOSED DOOR
2 69B1003H01 NAMEPLATE, GWD, ARC FLASH LABEL COMP
1 691C607G01 BREAKER LIFTING YOKE, CH, VCPW
5/15/27KV 36IN-WIDE
1 6526C23G11 TEST JUMPER, CH, VCPW, 5/15/27KV COMP
1 5676B22H01 SEISMIC CERTIFICATE COMP
1 1C19086H01 LIFT DEVICE, CH, BREAKER COMP
1 1A30257G01 ELEC LEVERING-IN DEVICE W/CLUTCH
120VAC
GO. : MCS03114-002 ITEM: 002 SHEET 4
BY CUTLER-HAMMER. IT
WAS DISCLOSED IN
CONFIDENCE AND IS ONLY
TO BE USED FOR THE
1 6511C83G01 RAIL CLAMP, CH, FOR 5/15/27KV VCPW
SWITCHGEAR
2 RP02201001E INSTRUCT , CH , RENEWAL-PARTS
LEAFLET, 5/15KV
SP
VERTICAL SECTION SUMMARY
2 3A40369G02 BREAKER, 150 VCPW 750, 1200A 60HZ,
2DB,3DB
6 6350C24H01 CT, ABB, SCV 1200/5MR STD ACC C200 2DP,3DP
D017 2 1C17629G06 VT, ITI, 1PT L-L ASSY, 110KV BIL,
1DA,4DA
D007 2 1C17639G06 VT, ITI, 2PTS L-L ASSY 14400:120 SYS
2BA,3BA
12 5981C07G05 PRI-FUSE, CH, CLE, 15.5 KV 1.0E CLE-
1DF,2BF,3BF,4DF
D624 6 677C453G03 PRI-FUSE, CH, CLE, 15.5 KV 5.0E CLE-
1AF,4AF
2 2452D SWITCH, ELS, SER 24, BKR CTRL,
2PE,3PE
D642 2 3A40273G06 LIGHT, CH, E22, IND LT ASSY AMBER
2PA,3PA
2 3A40273G36 LIGHT, CH, E22, IND LT ASSY GREEN
2PB,3PB
2 3A40273G46 LIGHT, CH, E22, IND LT ASSY RED
2PC,3PC
D480A 2 66D2041G11 RELAY, CH, FP5200-00, 5A, 48-125VDC
2PF,3PF
D137 1 7802D RELAY, ELS, LOR-24, 125VDC/120VAC
2PD
D138 1 7802D RELAY, ELS, LOR-24, 125VDC/120VAC
3PD
1 LT2036S PROT/CTRL, CH, PANEL BOARD TRIM,
20 X 36 SURF
1PB
1 MK876I2D0101 PROT/CTRL, CH, PANEL BOARD
INTERNALS FOR K876
1PC
3 PX4051A1BB METER, CH, POWER-XPERT 4000
2HA,3HA
D750A 2 PXD-MMG METER, CH, POWER-XPERT GRAPHIC
2HB,3HB
1 YS2036 PROT/CTRL, CH, PANEL BOARD BOX,
20W X 36H X 5.75D
1PA
D199 2 3A40335G20 PROT/CTRL, CH, PULL FUSE 2P W/2 30
2CA,3CA
2 EHD3100 PROT/CTRL, CH, BREAKER, EHD, 3
1BB,4BB
2 KYK1 PROT/CTRL, CH, INTLK KIT, FOR
1BC,4BC
1 1A30257G01 ELEC LEVERING-IN DEVICE W/CLUTCH
120VAC
GO. : MCS03114-002 ITEM: 002 SHEET 5
BY CUTLER-HAMMER. IT
WAS DISCLOSED IN
CONFIDENCE AND IS ONLY
TO BE USED FOR THE
1 1C19086H01 LIFT DEVICE, CH, BREAKER COMP
1 32220WA00K MISC, PAINT, ANSI 61, 9OZ AEROSOL COMP
1 5676B22H01 SEISMIC CERTIFICATE COMP
1 6511C83G01 RAIL CLAMP, CH, FOR 5/15/27KV VCPW
SWITCHGEAR
1 6526C23G11 TEST JUMPER, CH, VCPW, 5/15/27KV COMP
2 68C5010G01 CH, BREAKER WHEEL CONVERSION
B
1 691C607G01 BREAKER LIFTING YOKE, CH, VCPW
5/15/27KV 36IN-WIDE
2 69B1003H01 NAMEPLATE, GWD, ARC FLASH LABEL COMP
1 701B601G01 BREAKER, CH, LEV-IN CRANK W/
CLUTCH
1 7813C41G03 RAIL EXTENSION LH/RH COMP
1 8064A02G01 HANDLE ASSY COMP
1 K876LKH01 KEY INTERLOCK PER DWG
2DK
1 K876LKH02 KEY INTERLOCK PER DWG
3DK
1 K876LKH03 KEY INTERLOCK PER DWG
1BA
1 K876LKH04 KEY INTERLOCK PER DWG
1AK
1 K876LKH05 KEY INTERLOCK PER DWG
4BA
1 K876LKH06 KEY INTERLOCK PER DWG
4AK
1 REF700B214 SWITCHGEAR STORAGE INSTRUCT
DWG
2 RP02201001E INSTRUCT , CH , RENEWAL-PARTS
LEAFLET, 5/15KV
SP
2 6510C49G03 SWITCH, GWD, TOC, 9-POLE 4A-5B
2DT,3DT
2 6510C50G03 SWITCH, GWD, MOC, 9 POLE 5A-4B
2DM,3DM
D612 2 3CPT595301382A CPT, ITI, 30 KVA, 95KV BIL, 3-PH
1WA,4WA
2 6353C97H01 ZERO SEQ CT, ABB, 50:5A C10 2ZZ,3ZZ
4 8264A16H01 COMPONENT, WES, TERMINAL 6 AWG
2WY,2ZY,3WY,3ZY
12 8264A16H06 COMPONENT, WES, TERMINAL 1/0
2WL,2ZL,3WL,3ZL
6 UHS12060B0D0A1A ARRESTER, CPS, 12KV DISTRIBUTION
2WA,3WA
GO. : MCS03114-002 ITEM: 002 SHEET 6
BY CUTLER-HAMMER. IT
WAS DISCLOSED IN
CONFIDENCE AND IS ONLY
TO BE USED FOR THE
* NOTES
B SHOP TO INSTALL ON VCP-W BREAKERS FOR THIS JOB
DISTRIBUTION PANEL BOARD
TITLE DISTRIBUTION PANELBOARD CUTLER-HAMMER
GREENWOOD, SC
G.O. # - ITEM
MC03114-002
DATE
08/25/2008
REV 2 SHEET 1OF 1 MK876I2D0101
CUTLER-HAMMER
TYPE POW-R-LINE 2A DC 100A MAIN BREAKER
CIRCUIT DESCRIPTION LEFT SIDE POLES AMPS
BKR CTRL 2B 1 2 30
PWR XPERT DEV 5 2 15
SPARE 9 2 20
SPARE 13 2 20
CIRCUIT DESCRIPTION RIGHT SIDE POLES AMPS
BKR CTRL 3B 2 2 30
SPARE 6 2 20
SPARE 10 2 20
SPARE 14 2 20
ALL BREAKERS ARE TYPE GHB.
NOTE: THE SUM OF THE BRANCH BREAKER AMPERE RATINGS MOUNTED OPPOSITE
ONE ANOTHER CANNOT EXCEED 140A.
1) PROVIDE COVERPLATE OVER UNIDENTIFIED SPACES.
2) PROVIDE UL LABEL.
3) SHIP INTERIOR ONLY. BOX AND TRIM ORDERED SEPERATELY.
BOX: YS2036 36”H X 20”W X 5.75”D
TRIM: LT2036S SURFACE
SERVICE: 2-WIRE 125 VDC
BUS: COPPER
INCOMING: MAIN BREAKER TOP FEED
DEVICE ID: PB1
PURCHASE FROM SUMTER PLANT
GENERAL DESCRIPTION
DAVIS
CHARLESTON, SC
FILENAME: MK876I2Z9001
BY CUTLER-HAMMER. IT
WAS DISCLOSED IN
CONFIDENCE AND IS ONLY
TO BE USED FOR THE
SUPPLIED. REV: 2 DESIGNATION:
CUSTOMER NAME RALPH H. JOHNSON VA MEDICAL CENTER
INSTALLATION CHARLESTON, SC
P.O. # MP00031
S.O. # 72YK876
SYSTEM LINE TO LINE VOLTAGE 13800 V
BASIC IMPULSE LEVEL 95 KV CREST
GROUND SOLID GROUNDING
NUMBER OF PHASES 3 PH
FREQUENCY 60 HZ
PHASE SEQUENCE 1 - 2 - 3 OR A - B - C
ENCLOSURE TYPE GEAR INDOOR
REAR ACCESS COVERS
REAR LATCHING BOLTED
FRONT LATCHING QUARTER TURN KNOB
FINISH ENCLOSURE EXTERIOR ANSI 61
VERTICAL SECTION INTERIOR ANSI 61
BUS BUS RATING 1200A COPPER SILVER PLATED
JOINT HARDWARE HT STL (YELLOW ZINC CR)
SUPPORT INSULATION GLASS POLYESTER
GROUND BUS .25 X 2 COPPER NO PLATING
CIRCUIT BREAKER TYPE BREAKER 150 VCP-W 500 DIRECT ROLL IN
SHORT CKT CURRENT @ MAX KV 18 KA RMS SYM
VOLTAGE RANGE FACTOR, K= 1.3
CLOSING AND LATCHING CURRENT 62 KA PEAK
INTERRUPTING TIME 5 CYCLE
MOTOR VOLTAGE 125VDC
CLOSE VOLTAGE 125VDC
TRIP VOLTAGE 125VDC
SECONDARY & CONTROL BREAKER CONTROL POWER REMOTE
WIRE TYPE SIS
WIRE SIZE NON CURRENT CKT’S # 14 MIN
WIRE SIZE CURRENT CKT’S # 14 MIN
TERMINALS INSULATED LOCK IN FORK (ALL)
WIRE MARKERS ADHESIVE WRAP ON
TERMINAL BLOCKS (GENERAL) STANDARD 50A, 600V
TERMINAL BLOCKS (CTS) SHORT CKT TYPE 50A, 600V
WIRING DIAGRAM STANDARD
STANDARDS ANSI, IEEE, NEMA , UBC-SEISMIC ZONE 4
MISC REQUIREMENTS MIMIC BUS REQUIRED - 3/8" RED PLASTIC ADHESIVE
OPTIONAL EQUIPMENT 1 BREAKER LIFT DEV., ELECTRIC LEVERING DEVICE
Medium Voltage Switches
MVS 5/15 kV Trnsfmr Primary Switch
GO-ITEM: MCS03114-003 File/Rev: WM002Z44.HTM/2
Designation: Sub 1A Customer:
User: erontm Date: 1/12/2009 6:43:14
1 Master Drawing List WM002Z44.DOC 2 2 Certified Production Test Report - Greenwood W9000UA2.DOC 1
3 SEISMIC APPLICATION 7278A58.DOC 9
4 GWD-EMS0625-RALPH JOHNSON G081G62P.PDF 1
5 FRONT VIEW G081G62F.DWG 1
6 SCHEDULE G081G62N.DWG 1
7 FLOOR PLAN G081G62Q.DWG 1
8 SECTION VIEW G081G62V.DWG 1
9 BASE BOLT DOWN GUIDLINES MVS 5-15KV
SEISMIC 260C258.DWG 4
10 BASE WELDING GUIDLINES MVS 5-15KV
SEISMIC 260C258A.DWG 4
11 MVS 5/15KV SEISMIC ANCHOR PLAN 91C2504.DWG 1
W9000UA2.DOC
Certified Test Report
GO NO.: MCS03114 ITEM (S): 003
CUSTOMER ORDER NO.: 192528
EQUIPMENT DESIGNATION: Sub 1A
REFERENCE DRAWINGS:
CERTIFICATION: CERTIFICATION: The test below reflect the requirements in ANSI/IEEE C.37.20.3, CSA C22.2 No. 31-M89, and EEMAC G11-1 for inspections and production testing.
TESTING:
PASSED
DOES NOT
APPLY
v Mechanical Inspection Check X v Mechanical Function Check X v Electrical Joint Tightness Check X v Grounding of Instrument Transformer Case Test X v Electrical Operation Check / Sequence Test X v Power Circuitry Di-electric Test (19kVAC, 60Hz RMS for one
(1) minute) v Power Circuitry Di-electric Test (36kVAC, 60Hz RMS for one v Power Circuitry Di-electric Test (60kVAC, 60Hz RMS for one v Power Circuitry Di-electric Test (80kVAC, 60Hz RMS for one v Control Circuitry Di-electric Test (1.8 kVAC 60Hz RMS for one (1) second) v Polarity Test Transformer to Meters / Relays X v Cleanliness and Completeness Check X
Jason Brooks Tester
1/7/2009
Seismic Application Guidelines for Users of Cutler-Hammer Type MVS/MEB/MSB Medium Voltage Switchgear Assemblies and Unitized
Power Centers.
Greenwood, South Carolina USA
See the last page for Revisions Drawing No.: 7278A58
Based upon testing performed on generic MVS Medium Voltage Switchgear Assemblies and a generic Unitized Power Center (UPC) fastened to a tri-axial seismic test table and shaken to simulate the effects of an earthquake, the following requirements must be accommodated during design the of the foundation and the installation of the switchgear:
1. Foundation Design:
The foundation must be continuously true and level within 0.32mm (0.0125") in 36” in any direction beneath the switchgear assembly. The foundation must be designed to withstand loads imposed on it by the earthquake motion. The maximum equipment reaction loads are to be based upon the maximum tensile strength of a 13mm (.5") diameter SAE J429 Grade 5 bolt (or ASTM 449, type 1) at each point of fastening to the foundation, tightened a minimum torque of 10.4 kg-m (75 ft-lb.). Use of equal strength weldments may be utilized. The documents 260C258 (5/15kV MVS switchgear), 6977C74 (27/38kV MVS switchgear), and 6977C76 (UPC) shows supplemental floor plan details indicating where the foundation's load-supporting surfaces must be.
2. Movement at the Top of a MVS/MEB/MSB Switchgear Assembly or a
Unitized Power Center (UPC) During an Earthquake:
MVS/MEB/MSB switchgear or a UPC will move up to 150mm (6") in the directions of up and down, side to side, or front to rear. The maximum motion from the "at rest" position would be 75mm (3") up or down, left or right, front or rear. Top entry of conduits, bus duct, power cables, etc., must accommodate the maximum expected motion excursions. Bottom entry of such apparatus will obviously eliminate the need to accommodate the top of switchgear movement.
3. Field assembly of a MVS/MEB/MSB Switchgear Assembly or a Unitized
Power Center (UPC) shipped in multiple shipping groups:
The inter-unit tie fasteners to join the shipping groups together must be installed and properly tightened when the MVS/MEB/MSB Switchgear or UPC is installed on the foundation. Failure to join the shipping groups together could result in damage to the equipment during an earthquake.
4. Securing of Entering/Exiting power cables.
Power cables must be lashed together from the point of entry to the point of termination as shown in the instruction leaflet IB02102001E.
5. Storage of "loose" pieces of equipment:
The user must provide storage areas to secure "loose" pieces of equipment (such as spare fuses and miscellaneous accessories) away from the switchgear so that the switchgear, unitized power center, and/or the loose pieces are not damaged during an earthquake.
6. Locking of enclosure doors during an earthquake:
Enclosure door handles must be either locked or fastened closed with fasteners to prevent their attempting to unlatch during an earthquake.
7. Internal cross bracing behind any optional rear door:
The internal cross braces located behind any rear door must be in place and securely fastened at all times to properly brace the rear of the enclosure. These cross braces may be removed for access during installation procedures or maintenance procedures, but they must be replaced and securely fastened when these procedures are either completed or suspended.
Revisions
Revision 1. Prepared by GLF 7/14/93. Approved by TGR 7/14/93.
Revision 2. Completely redrawn. GLF 11/17/93. TGR 11/24/93.
Revision 3. 75 FP’s was 65 FP’s. GLF 1/14/94. TGR 14AP94.
Revision 4. Sections 1, 2, and 6 changed based upon input from Seismic Council.
TGR. 19AP95
Revision 5. Grammatical correction in section 1. TGR 07AU95.
Revision 6. WLI/WVB changed to MVS/MEB throughout the document. TGR
02OC00.
Revision 7. GMVS-0611: “Greenwood” was “Sumter” in title block. TGR 09/28/05.
Revision 8. GMVS-0702. Extensive revisions to clause 1. TGR 08/24/06.
Revision 9. GMVS0807. Several changes throughout document. Compare revisions
8 and 9 to see changes. T.G. Robirds 09/06/2007.
| Power Distribution Assemblies Division | | Eaton Cutler−Hammer | | Greenwood, S.C. 29649 | | Order MCS03114 | Revision 01 DATE 11/19/08 | Parts List G081G62P | | Customer: EMS0625−RALPH JOHNSON | | Product Code: 3324 |
| VA MEDICAL |
| SUB 1A |
| G.O. Item | Assembly / Section | Description |
| 003 | G081G62PA01 | MVS SWITCHGEAR 15KV |
| | | INDOOR |
| | | FRONT VIEW − G081G62F SHEET 1 |
| | G081G62PG01 | FUSED SWITCH |
| Technician _________ Engineer ___________ | | Sheet 1 of 4 |
| Power Distribution Assemblies Division | | Eaton Cutler−Hammer | | Greenwood, S.C. 29649 | | Order MCS03114 | Revision 01 DATE 11/19/08 | Parts List G081G62P | | Notes: |
| NT01− EXTERIOR COLOR: ANSI 61 LIGHT GRAY |
| NT02− INTERIOR COLOR: ANSI 61 LIGHT GRAY |
| NT03− LINE SWITCH BUS: 800 AMPERE SILVER PLATED COPPER. |
| GROUND BUS: SILVER PLATED COPPER. |
| NT04− ASSEMBLY DESIGN MOMENTARY RATING: 64KA ASYMMETRICAL |
| NT05− ANCHOR CLIP FOR ANCHORING OF MVS SWITCHGEAR |
| TO CUSTOMER PAD SUPPLIED UNMOUNTED. |
| NT06− THIS JOB IS UL LISTED. |
| NT07− SEISMIC QUALIFIED DESIGN, ZONES 3−4. |
| NT08− SEISMIC QUALIFIED, SPARE FUSES (IF SUPPLIED) STORED ELSEWHERE. |
| NT09− CUSTOMER TO REFER TO DRAWING 7278A58: |
| ITEM 1−WHEN DESIGNING FOUNDATION |
| ITEM 2−FOR SPECIFIC DETAILS CONCERNING MOTION OF THE SWGR |
| ITEM 3−FOR PROPER INSTALLATION OF HARDWARE AT SHIPPING SPLITS |
| ITEM 4−FOR PROPER SECURING OF CABLES ENTERING |
| ________ AND EXITING THE SWITCHGEAR |
| ITEM 5−CONCERNING STORAGE OF ITEMS THAT ARE SHIPPED LOOSE. |
| NT10− NAMEPLATES WILL BE SUPPLIED BLANK AND REMOVABLE |
| UNLESS OTHERWISE SPECIFIED. |
| NT11− MIMIC BUS SUPPLIED |
| Revisions: |
| RV01− DATE 11/19/08 DRAFTER DLM |
| FOR CONSTRUCTION |
| Sheet 2 of 4 |
| Power Distribution Assemblies Division | | Eaton Cutler−Hammer | | Greenwood, S.C. 29649 | | Order MCS03114 | Revision 01 DATE 11/19/08 | Parts List G081G62P | | Customer: EMS0625−RALPH JOHNSON | | Item |Style Number | Description |G01|G02|G03|G04|G05 |
| 0001 |1D78050G36 | SWITCH, MVS2 15KV 95KV BIL | 1| | | | |
| | | 600A CONTINUOUS & LOAD BREAK | | | | | |
| | | 61KA MOM. & FAULT CLOSE | | | | | |
| | | CU EPOXY 33W | | | | | |
| 0002 |LL02000001E | SF6 FREE LABEL | 1| | | | |
| 0003 |260C146G07 | SELECTOR SWITCH, TOP ENTRY | 1| | | | |
| | | 36 WIDE, 5/15KV, 60/95KV BIL | | | | | |
| | | EPOXY FINN SUPPORTS | | | | | |
| 0004 |ULNOTE | THIS STRUCTURE IS UL LISTED |REF| | | | |
| 0005 |54A9955H01 | NAMPL, E|C−H SWGR RATING UL | 1| | | | |
| | | EATON|CUTLER−HAMMER LOGO | | | | | |
| | | MVS, MVS2, MVS−C, MVS2−C | | | | | |
| 0006 |54A9955H02 | NAMPL, E|C−H SWITCH RATING UL | 1| | | | |
| | | EATON|CUTLER−HAMMER LOGO | | | | | |
| | | MVS, MVS2, MVS−C, MVS2−C | | | | | |
| 0007 |54A9955H03 | NAMPL, E|C−H SEL SW RATING UL | 1| | | | |
| | | EATON|CUTLER−HAMMER LOGO | | | | | |
| | | MVS, MVS2, MVS−C, MVS2−C | | | | | |
| 0008 |5676B40H03 | SEISMIC LABEL | 1| | | | |
| | | BOS 2.75 X 2.875 | | | | | |
| 0009 |7278A58 | SEISMIC APPLICATION GUIDELINES |REF| | | | |
| | | FOR USERS OF CUTLER−HAMMER | | | | | |
| | | TYPE MVS MEDIUM VOLT SWGR ASSY | | | | | |
| 0010 |91C2504 | STANDARD 5/15KV SEISMIC |REF| | | | |
| | | DRAWING | | | | | |
| 0011 |260C258 | TYPICAL LOAD BEARING SURFACES |REF| | | | |
| | | FOR SEISMIC APPLICATIONS | | | | | |
| | | BASE BOLT DOWN OR WELDING | | | | | |
| | | 5−15KV MVS | | | | | |
| Sheet 3 of 4 |
| Power Distribution Assemblies Division | | Eaton Cutler−Hammer | | Greenwood, S.C. 29649 | | Order MCS03114 | Revision 01 DATE 11/19/08 | Parts List G081G62P | | Customer: EMS0625−RALPH JOHNSON | | Item |Style Number | Description |G01|G02|G03|G04|G05 |
| 0012 |5981C19G09 | FUSE, 15.5KV CLE 125A 31 | 3| | | | |
| 0013 |UHS12060B0D0A1A| ARRESTER, CPS, 12KV DISTRIBUTI | 3| | | | |
| | | BOS COOPER VARISTAR HEAVY | | | | | |
| | | DUTY | | | | | |
| 0014 |KFL005010S | KEY INTERLOCK TYPE F KIRK | 1| | | | |
| | | .50" BOLT PROJECTION | | | | | |
| 0015 |ISA029 | SCHEME FOR ABOVE KEY |REF| | | | |
| | | INTERLOCK | | | | | |
| 0016 |7274A78 FIG 1 | NEMA 2 HOLE DRILLING PLAN |REF| | | | |
| 0017 |SA00646H08 | MIMIC BUS, RED PLASTIC STRIP | 3| | | | |
| | | SHEET, ADHESIVE BACKED | | | | | |
| | | BOS .375 X .02 X 36, NO. 117 | | | | | |
| 0018 |G081G62ZG01 | FUSED SWITCH | 1| | | | |
| | | MANUFACTURING INFORMATION | | | | | |
| 0019 |1A33762G31 | SUPPORT, CABLE 36W CHANNEL KIT | 1| | | | |
| | | 14 GAUGE CHLI | | | | | |
| | | FLANGE MTD | | | | | |
| Sheet 4 of 4 |
C
GO-ITEM: MCS03114-004 File/Rev: WM002Z46.HTM/2
Designation: Sub 1B Customer:
User: erontm Date: 1/12/2009 6:47:59
1 Master Drawing List WM002Z46.DOC 2 2 Certified Production Test Report W9000UB0.DOC 1
3 SEISMIC APPLICATION 7278A58.DOC 9
4 GWD-EMS0625-RALPH JOHNSON G081G63P.PDF 1
5 FRONT VIEW G081G63F.DWG 1
6 SCHEDULE G081G63N.DWG 1
7 FLOOR PLAN G081G63Q.DWG 1
8 SECTION VIEW G081G63V.DWG 2
Certified Production Test Report - Greenwood
GO-ITEM: MCS03114-004
EQUIPMENT DESIGNATION: Sub 1B
The test below reflect the requirements in ANSI/IEEE C.37.20.3, CSA C22.2 No. 31-M89, and EEMAC G11-1 for
Mechanical Inspection Check X Mechanical Function Check X Electrical Joint Tightness Check X Grounding of Instrument Transformer Case Test X Electrical Operation Check / Sequence Test X Power Circuitry Di-electric Test (19kVAC, 60Hz RMS for one (1) minute) X Power Circuitry Di-electric Test (36kVAC, 60Hz RMS for one (1) minute) X Power Circuitry Di-electric Test (60kVAC, 60Hz RMS for one (1) minute) X Power Circuitry Di-electric Test (80kVAC, 60Hz RMS for one (1) minute) X Control Circuitry Di-electric Test (1.8 kVAC 60Hz RMS for one (1) second) X Polarity Test Transformer to Meters / Relays X Cleanliness and Completeness Check X
Ansel Fambrough
01/09/2009
W9000UB0.DOC
test table and shaken to simulate the effects of an earthquake, the following requirements must be accommodated during design the of the foundation and the designed to withstand loads imposed on it by the earthquake motion. The maximum equipment reaction loads are to be based upon the maximum tensile strength of a 13mm (.5") diameter SAE J429 Grade 5 bolt (or ASTM 449, type 1) at each point of fastening to the foundation, tightened a minimum torque of 10.4 kg-m (75 ft-lb.). Use of equal strength weldments may be utilized. The documents 260C258 (5/15kV MVS switchgear), 6977C74 (27/38kV MVS from the "at rest" position would be 75mm (3") up or down, left or right, front or rear. Top entry of conduits, bus duct, power cables, etc., must accommodate cross braces may be removed for access during installation procedures or
Revision 2. Completely redrawn. GLF 11/17/93. TGR 11/24/93.
| Power Distribution Assemblies Division | | Eaton Cutler−Hammer | | Greenwood, S.C. 29649 | | Order MCS03114 | Revision 01 DATE 11/19/08 | Parts List G081G63P | | Customer: EMS0625−RALPH JOHNSON | | Product Code: 3324 |
| VA MEDICAL |
| SUB 1B |
| G.O. Item | Assembly / Section | Description |
| 004 | G081G63PA01 | MVS SWITCHGEAR 15KV |
| | | INDOOR |
| | | FRONT VIEW − G081G63F SHEET 1 |
| | G081G63PG01 | FUSED SWITCH |
| Technician _________ Engineer ___________ | | Sheet 1 of 4 |
| Power Distribution Assemblies Division | | Eaton Cutler−Hammer | | Greenwood, S.C. 29649 | | Order MCS03114 | Revision 01 DATE 11/19/08 | Parts List G081G63P | | Notes: |
| NT01− EXTERIOR COLOR: ANSI 61 LIGHT GRAY |
| NT02− INTERIOR COLOR: ANSI 61 LIGHT GRAY |
| NT03− LINE SWITCH BUS: 800 AMPERE SILVER PLATED COPPER. |
| GROUND BUS: SILVER PLATED COPPER. |
| NT04− ASSEMBLY DESIGN MOMENTARY RATING: 64KA ASYMMETRICAL |
| NT05− ANCHOR CLIP FOR ANCHORING OF MVS SWITCHGEAR |
| TO CUSTOMER PAD SUPPLIED UNMOUNTED. |
| NT06− THIS JOB IS UL LISTED. |
| NT07− SEISMIC QUALIFIED DESIGN, ZONES 3−4. |
| NT08− SEISMIC QUALIFIED, SPARE FUSES (IF SUPPLIED) STORED ELSEWHERE. |
| NT09− CUSTOMER TO REFER TO DRAWING 7278A58: |
| ITEM 1−WHEN DESIGNING FOUNDATION |
| ITEM 2−FOR SPECIFIC DETAILS CONCERNING MOTION OF THE SWGR |
| ITEM 3−FOR PROPER INSTALLATION OF HARDWARE AT SHIPPING SPLITS |
| ITEM 4−FOR PROPER SECURING OF CABLES ENTERING |
| ________ AND EXITING THE SWITCHGEAR |
| ITEM 5−CONCERNING STORAGE OF ITEMS THAT ARE SHIPPED LOOSE. |
| NT10− NAMEPLATES WILL BE SUPPLIED BLANK AND REMOVABLE |
| UNLESS OTHERWISE SPECIFIED. |
| NT11− MIMIC BUS SUPPLIED |
| Revisions: |
| RV01− DATE 11/19/08 DRAFTER DLM |
| FOR CONSTRUCTION |
| Sheet 2 of 4 |
| Power Distribution Assemblies Division | | Eaton Cutler−Hammer | | Greenwood, S.C. 29649 | | Order MCS03114 | Revision 01 DATE 11/19/08 | Parts List G081G63P | | Customer: EMS0625−RALPH JOHNSON | | Item |Style Number | Description |G01|G02|G03|G04|G05 |
| 0001 |1D78050G36 | SWITCH, MVS2 15KV 95KV BIL | 1| | | | |
| | | 600A CONTINUOUS & LOAD BREAK | | | | | |
| | | 61KA MOM. & FAULT CLOSE | | | | | |
| | | CU EPOXY 33W | | | | | |
| 0002 |LL02000001E | SF6 FREE LABEL | 1| | | | |
| 0003 |260C146G07 | SELECTOR SWITCH, TOP ENTRY | 1| | | | |
| | | 36 WIDE, 5/15KV, 60/95KV BIL | | | | | |
| | | EPOXY FINN SUPPORTS | | | | | |
| 0004 |ULNOTE | THIS STRUCTURE IS UL LISTED |REF| | | | |
| 0005 |54A9955H01 | NAMPL, E|C−H SWGR RATING UL | 1| | | | |
| | | EATON|CUTLER−HAMMER LOGO | | | | | |
| | | MVS, MVS2, MVS−C, MVS2−C | | | | | |
| 0006 |54A9955H02 | NAMPL, E|C−H SWITCH RATING UL | 1| | | | |
| | | EATON|CUTLER−HAMMER LOGO | | | | | |
| | | MVS, MVS2, MVS−C, MVS2−C | | | | | |
| 0007 |54A9955H03 | NAMPL, E|C−H SEL SW RATING UL | 1| | | | |
| | | EATON|CUTLER−HAMMER LOGO | | | | | |
| | | MVS, MVS2, MVS−C, MVS2−C | | | | | |
| 0008 |5676B40H03 | SEISMIC LABEL | 1| | | | |
| | | BOS 2.75 X 2.875 | | | | | |
| 0009 |7278A58 | SEISMIC APPLICATION GUIDELINES |REF| | | | |
| | | FOR USERS OF CUTLER−HAMMER | | | | | |
| | | TYPE MVS MEDIUM VOLT SWGR ASSY | | | | | |
| 0010 |91C2504 | STANDARD 5/15KV SEISMIC |REF| | | | |
| | | DRAWING | | | | | |
| 0011 |260C258 | TYPICAL LOAD BEARING SURFACES |REF| | | | |
| | | FOR SEISMIC APPLICATIONS | | | | | |
| | | BASE BOLT DOWN OR WELDING | | | | | |
| | | 5−15KV MVS | | | | | |
| Sheet 3 of 4 |
| Power Distribution Assemblies Division | | Eaton Cutler−Hammer | | Greenwood, S.C. 29649 | | Order MCS03114 | Revision 01 DATE 11/19/08 | Parts List G081G63P | | Customer: EMS0625−RALPH JOHNSON | | Item |Style Number | Description |G01|G02|G03|G04|G05 |
| 0012 |5981C19G09 | FUSE, 15.5KV CLE 125A 31 | 3| | | | |
| 0013 |UHS12060B0D0A1A| ARRESTER, CPS, 12KV DISTRIBUTI | 3| | | | |
| | | BOS COOPER VARISTAR HEAVY | | | | | |
| | | DUTY | | | | | |
| 0014 |KFL005010S | KEY INTERLOCK TYPE F KIRK | 1| | | | |
| | | .50" BOLT PROJECTION | | | | | |
| 0015 |ISA029 | SCHEME FOR ABOVE KEY |REF| | | | |
| | | INTERLOCK | | | | | |
| 0016 |7274A78 FIG 1 | NEMA 2 HOLE DRILLING PLAN |REF| | | | |
| 0017 |SA00646H08 | MIMIC BUS, RED PLASTIC STRIP | 3| | | | |
| | | SHEET, ADHESIVE BACKED | | | | | |
| | | BOS .375 X .02 X 36, NO. 117 | | | | | |
| 0018 |G081G63ZG01 | FUSED SWITCH | 1| | | | |
| | | MANUFACTURING INFORMATION | | | | | |
| 0019 |1A33762G31 | SUPPORT, CABLE 36W CHANNEL KIT | 1| | | | |
| | | 14 GAUGE CHLI | | | | | |
| | | FLANGE MTD | | | | | |
| Sheet 4 of 4 |
C
GO-ITEM: MCS03114-005 File/Rev: WM002Z45.HTM/2
Designation: Sub 2A Customer:
User: erontm Date: 1/12/2009 6:45:50
1 Master Drawing List WM002Z45.DOC 2 2 Certified Production Test Report W9000UB1.DOC 1
3 SEISMIC APPLICATION 7278A58.DOC 9
4 GWD-EMS0625-RALPH JOHNSON G081G64P.PDF 1
5 FRONT VIEW G081G64F.DWG 1
6 SCHEDULE G081G64N.DWG 1
7 FLOOR PLAN G081G64Q.DWG 1
8 SECTION VIEW G081G64V.DWG 2
Certified Production Test Report - Greenwood
GO-ITEM: MCS03114-005
EQUIPMENT DESIGNATION: Sub 2A
The test below reflect the requirements in ANSI/IEEE C.37.20.3, CSA C22.2 No. 31-M89, and EEMAC G11-1 for
Mechanical Inspection Check X Mechanical Function Check X Electrical Joint Tightness Check X Grounding of Instrument Transformer Case Test X Electrical Operation Check / Sequence Test X Power Circuitry Di-electric Test (19kVAC, 60Hz RMS for one (1) minute) X Power Circuitry Di-electric Test (36kVAC, 60Hz RMS for one (1) minute) X Power Circuitry Di-electric Test (60kVAC, 60Hz RMS for one (1) minute) X Power Circuitry Di-electric Test (80kVAC, 60Hz RMS for one (1) minute) X Control Circuitry Di-electric Test (1.8 kVAC 60Hz RMS for one (1) second) X Polarity Test Transformer to Meters / Relays X Cleanliness and Completeness Check X
Ansel Fambrough
01/09/2009
W9000UB1.DOC
test table and shaken to simulate the effects of an earthquake, the following requirements must be accommodated during design the of the foundation and the designed to withstand loads imposed on it by the earthquake motion. The maximum equipment reaction loads are to be based upon the maximum tensile strength of a 13mm (.5") diameter SAE J429 Grade 5 bolt (or ASTM 449, type 1) at each point of fastening to the foundation, tightened a minimum torque of 10.4 kg-m (75 ft-lb.). Use of equal strength weldments may be utilized. The documents 260C258 (5/15kV MVS switchgear), 6977C74 (27/38kV MVS from the "at rest" position would be 75mm (3") up or down, left or right, front or rear. Top entry of conduits, bus duct, power cables, etc., must accommodate cross braces may be removed for access during installation procedures or
Revision 2. Completely redrawn. GLF 11/17/93. TGR 11/24/93.
| Power Distribution Assemblies Division | | Eaton Cutler−Hammer | | Greenwood, S.C. 29649 | | Order MCS03114 | Revision 01 DATE 11/19/08 | Parts List G081G64P | | Customer: EMS0625−RALPH JOHNSON | | Product Code: 3324 |
| VA MEDICAL |
| SUB 2A |
| G.O. Item | Assembly / Section | Description |
| 005 | G081G64PA01 | MVS SWITCHGEAR 15KV |
| | | INDOOR |
| | | FRONT VIEW − G081G64F SHEET 1 |
| | G081G64PG01 | FUSED SWITCH |