VA Medical Center - KitchenHoods- OCT2025.pdf
PDF 1012 KB Posted
- Solicitation number
- 36C24726Q0305
About this file
This is a Joint Commission inspection report documenting a semi-annual inspection of automatic kitchen hood fire extinguishing systems at VA Medical Center, located at 1826 Veterans Blvd, Dublin, GA 31021. The inspection was conducted on October 8, 2025, by inspector David Mills (License 4205XHP) from Johnson Controls North America, the service provider. The inspection is identified as Work Order #59851798 and covers Element of Performance EP-13 under Joint Commission Standard EC.02.03.05, which requires testing of all automatic fire extinguishing systems for kitchen hoods every six months in accordance with NFPA 96-2011: 11.2.
The inspection covered six kitchen hood systems and ten kitchen hood appliances across multiple kitchen locations: Building 85, Cafe back, Cafe front, Main kitchen back hood, Main kitchen front hood, and Main kitchen serving line. All 16 devices inspected (100%) passed with no deficiencies identified and no retired devices. All systems achieved full compliance with maintenance requirements including fusible link replacement, detection system testing, remote manual pull station testing, electric switch operation, nozzle cleaning, vacuum testing, and air or nitrogen purging. System manufacturers include Ansul (multiple models ranging from 1.5 to 6 gallons), with electric shunt trip fuel shut-off mechanisms. The systems protect various cooking appliances including ranges, fryers, griddles, tilt skillets, and ovens. Notable items marked "No" or "Not Answered" include personnel instruction in manual system operation and Class K extinguisher presence at certain locations. The report includes detailed maintenance item results for each system and concludes with inspector signature certification on 10/08/2025.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| QA - 36C24726Q0305 - Fire Protection PM final.docx | DOCX document | |
| QA - 36C24726Q0305 - Fire Protection PM final.docx | DOCX document | |
| Carl Vinson VAMC - Rolling Fire Door Inspection Report 2025.pdf | ||
| QA - 36C24726Q0305 - Fire Protection PM.docx | DOCX document | |
| S02 - 36C24726Q0305 - Fire Protection PM final.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Johnson Controls is committed to serving our customers with the best-in-class services and technologies. Xaap is an advanced inspection reporting application that has been used by Johnson Controls on your inspections.
Xaap is a software-as-a-service (SaaS) solution that provides a streamlined and digitized approach for performing fire and life safety inspections and managing compliance reports in a single, centralized platform.
The application allows inspectors to capture data for fire and life safety systems and devices while generating the required compliance reports directly from their phones. It also provides facility managers, building managers and key stakeholders with a centralized view of all building systems and deficiency data. Users can easily access, download and share historical inspection reports through Xaap.
See how your organization can leverage this smart technology for your internal inspections Visit info.jci.com/xaap-tjc To Learn More
This report is powered by Xaap, the Building Compliance Reporting Platform used by Johnson Controls.
This page is informational only and not part of The Joint Commission Report
This report is powered by https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc
[This Page Intentionally Left Blank]
Inspection Summary
Customer Information
Name VA Medical Center
Building Information
Name VA Medical Center
Address 1826 Veterans Blvd, Dublin, GA 31021
Contact Information
Name Daniel DiMartino
Role Monitoring Organization
E-Mail Daniel.dimartino2@va.gov
Phone 4783044664
Account Information
Service Provider Johnson Controls North America
Office Address 50 Technology Drive, Westminster, MA, US, Office Phone 470-214-7160
Office License
Inspector Name David Mills
Inspector License
4205XHP
Inspection Information
Start Date 10/08/2025
Date 10/08/2025
Inspection Type Joint Commission
Work Order# 59851798
Timezone GMT-04:00
Inspection Summary
The following Tests and Inspections have been covered in this inspection
EP 13 - Kitchen auto extinguishing systems
DEVICE DEFICIENCIES
No device deficiencies in this inspection.
www.xaapbuildings.com
INSPECTION RESULTS SUMMARY
CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS
TEST PERFORMED DEVICE TYPE TOTAL PASSED FAILED CANNOT INSPECT % INSPECTED TOTAL
EP13 Kitchen Hood Appliance 10 10 0 0 100 10
EP13 Kitchen Hood System 6 6 0 0 100 6
TOTAL 16 16 0 0 100 16
www.xaapbuildings.com
KITCHEN AUTO EXTINGUISHING SYSTEMS
CUSTOMER NAME: VA Medical Center
BUILDING NAME: VA Medical Center
BUILDING ADDRESS: 1826 Veterans Blvd, Dublin, GA 31021
CONTACT NAME: Daniel DiMartino
CONTACT E-MAIL: Daniel.dimartino2@va.gov
CONTACT ROLE: Monitoring Organization
CONTACT PHONE: 4783044664
SERVICE PROVIDER: Johnson Controls North America
OFFICE PHONE: 470-214-7160
INSPECTOR: David Mills
INSPECTOR LICENSE: 4205XHP
INSPECTION START DATE: 10/08/2025
INSPECTION END DATE: 10/08/2025
WORK ORDER: 59851798
TIMEZONE: GMT-04:00
INSPECTION RESULTS SUMMARY
CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT % INSPECTED INVENTORY COUNT
Kitchen Hood System 6 6 0 0 100 6
Kitchen Hood Appliance 10 10 0 0 100 10
DEVICE DEFICIENCIES
No device deficiencies in this inspection.
RETIRED DEVICES
No retired devices in this inspection.
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Customer: VA Medical Center | Building: VA Medical Center
Elements of Performance #13
Every 6 months the facility tests all automatic fire extinguishing systems for the Kitchen Hoods. The completion date of the tests is documented.
Note: Discharge of the fire-extinguishing system is not required.
Automatic Kitchen Hood Systems
For additional guidance on performing the tests, see NFPA 96-2011: 11.2
Test Method
An inspection and servicing of the fire-extinguishing system and listed exhaust hoods containing a constant or fire-actuated water system shall be made at least every 6 months by properly trained and qualified persons.
All actuation components, including remote manual pull stations, mechanical or electrical devices, detectors, actuators, and fire-actuated dampers, shall be checked for proper operation during the inspection in accordance with the manufacturer's listed procedures.
Fusible links (including fusible links on fire damper assemblies) and automatic sprinkler heads shall be replaced at least annually or more frequently if necessary where required by the manufacturer.
Other detection devices not including fusible links and automatic sprinklers shall be serviced or replaced in accordance with the manufacturer's recommendations.
Where automatic bulb-type sprinklers or spray nozzles are used and annual examination shows no buildup of grease or other material on the sprinkler or spray nozzles, annual replacement shall not be required.
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
System Information
LOCATION DESCRIPTION BARCODE MANUFACTURER MODEL SERIAL NUMBER SERVICE TYPE SIZE
Building 85 — Ansul 1.5 gallon — 288140 Electric N/A
FUEL SHUT OFF TYPE
FUEL SHUT OFF
'ON'
360 FUSIBLE LINK 450 FUSIBLE LINK 500 FUSIBLE LINK
OTHER FUSIBLE
LINK
# LINKS CHANGED
THIS SERVICE
Electric Shunt Trip Yes 1 N/A N/A N/A 1
Ventilation Equipment Information
HOOD SIZE PLENUM SIZE FILTER TYPE FILTER SIZE
48x48 12x10 Baffle 19.5 x19.5
SIZE OF DUCT #1 SIZE OF DUCT #2 SIZE OF DUCT #3 SIZE OF DUCT #4
12x20 N/A N/A N/A
Cooking Appliance Locations
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
— Building 85 Range 36x36 Electric Pass 230 2
Maintenance Items Results
How many 360 degree Thermal Detectors? N/A
How many 600 degree Thermal Detectors? N/A
Thermal Detectors Tested N/A
All appliances properly protected with correct nozzles? Yes
Duct and plenum protected with correct nozzles? Yes
All nozzles properly aimed at hazard/unobstructed? Yes
Proper separation between fryer(s) and open flame? Yes
Nozzle blow-off caps installed (replace if needed) Yes
Hood & duct penetrations sealed with weld or UL device? Yes
Check cartridge weight (replace if needed)? Yes
Test detection system from terminal detector? Pass
Replace fusible links (every 6 months)? Yes
Date of links 2025
Test remote manual pull station? Pass
Test mechanical gas shut-off valve? N/A
Test electric solenoid gas shut-off valve with reset relay? N/A
Test electric switch for proper operation? Pass
Clean nozzles? Yes
System installed in accordance with mfg. UL listing? Yes
System meets UL 300 standards? Yes
Piping and conduit secured to rigid surface? Yes
Tamper seal(s) installed? Yes
Building fire alarm connected/activated? Pass
Actuation line vacuum test performed (every 6 months)? Yes
Distribution piping network last purged with dry air or nitrogen (every 12 months)? Yes
Exhaust fan(s) operating? Yes
Make-up/return air fan(s) shut down? N/A
Air filters/spacers reinstalled? Yes
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Maintenance Items Results
Personnel instructed in manual operation of system? No
Class K extinguisher with placard present? No
Last regulator test date (every 12 years)? 10/08/2025
System returned to normal operation? Yes
Service and certification tag on system? Yes
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Cafe back — Ansul 6 gallon — 4210015 Electric N/A
FUEL SHUT OFF TYPE
FUEL SHUT OFF
'ON'
360 FUSIBLE LINK 450 FUSIBLE LINK 500 FUSIBLE LINK
OTHER FUSIBLE
LINK
# LINKS CHANGED
THIS SERVICE
Electric Shunt Trip Yes 4 N/A N/A N/A 4
Ventilation Equipment Information
HOOD SIZE PLENUM SIZE FILTER TYPE FILTER SIZE
2-9ftx6ft 16x12 Baffle 12x20
SIZE OF DUCT #1 SIZE OF DUCT #2 SIZE OF DUCT #3 SIZE OF DUCT #4
20x20 20x20 N/A N/A
Cooking Appliance Locations
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
— Cafe back fryer Fryer 12x12 Electric Pass 3n 1
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
— Cafe back fryer Fryer 12x12 Electric Pass 3n 1
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
— Cafe back range Range 36x24 Electric Pass 290 2
Maintenance Items Results
How many 360 degree Thermal Detectors? N/A
How many 600 degree Thermal Detectors? N/A
Thermal Detectors Tested N/A
All appliances properly protected with correct nozzles? Yes
Duct and plenum protected with correct nozzles? Yes
All nozzles properly aimed at hazard/unobstructed? Yes
Proper separation between fryer(s) and open flame? Yes
Nozzle blow-off caps installed (replace if needed) Yes
Hood & duct penetrations sealed with weld or UL device? Yes
Check cartridge weight (replace if needed)? Yes
Test detection system from terminal detector? Pass
Replace fusible links (every 6 months)? Yes
Date of links 2025
Test remote manual pull station? Pass
Test mechanical gas shut-off valve? N/A
Test electric solenoid gas shut-off valve with reset relay? N/A
Test electric switch for proper operation? Pass
Clean nozzles? Yes
System installed in accordance with mfg. UL listing? Yes
System meets UL 300 standards? Yes
Piping and conduit secured to rigid surface? Yes
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Tamper seal(s) installed? Yes
Building fire alarm connected/activated? Pass
Actuation line vacuum test performed (every 6 months)? Yes
Distribution piping network last purged with dry air or nitrogen (every 12 months)? Yes
Exhaust fan(s) operating? Yes
Make-up/return air fan(s) shut down? N/A
Air filters/spacers reinstalled? Yes
Personnel instructed in manual operation of system? No
Class K extinguisher with placard present? Yes
Last regulator test date (every 12 years)? 10/08/2023
System returned to normal operation? Yes
Service and certification tag on system? Yes
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Cafe front — Ansul — 354544 Electric N/A
FUEL SHUT OFF TYPE
FUEL SHUT OFF
'ON'
360 FUSIBLE LINK 450 FUSIBLE LINK 500 FUSIBLE LINK
OTHER FUSIBLE
LINK
# LINKS CHANGED
THIS SERVICE
Electric Shunt Trip Yes 5 N/A N/A N/A 5
Ventilation Equipment Information
HOOD SIZE PLENUM SIZE FILTER TYPE FILTER SIZE
10x5 16x12 Baffle 12x20
SIZE OF DUCT #1 SIZE OF DUCT #2 SIZE OF DUCT #3 SIZE OF DUCT #4
20x20 N/A N/A N/A
Cooking Appliance Locations
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
— Cafe front fryer Fryer 21x13 Electric Fail 3n 1
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
— Cafe front fryer Fryer 21x13 Electric Pass 3n 1
Maintenance Items Results
How many 360 degree Thermal Detectors? N/A
How many 600 degree Thermal Detectors? N/A
Thermal Detectors Tested N/A
All appliances properly protected with correct nozzles? Yes
Duct and plenum protected with correct nozzles? Yes
All nozzles properly aimed at hazard/unobstructed? Yes
Proper separation between fryer(s) and open flame? Yes
Nozzle blow-off caps installed (replace if needed) Yes
Hood & duct penetrations sealed with weld or UL device? Yes
Check cartridge weight (replace if needed)? Yes
Test detection system from terminal detector? Pass
Replace fusible links (every 6 months)? Yes
Date of links 2025
Test remote manual pull station? Pass
Test mechanical gas shut-off valve? N/A
Test electric solenoid gas shut-off valve with reset relay? N/A
Test electric switch for proper operation? Pass
Clean nozzles? Yes
System installed in accordance with mfg. UL listing? Yes
System meets UL 300 standards? Yes
Piping and conduit secured to rigid surface? Yes
Tamper seal(s) installed? Yes
Building fire alarm connected/activated? Pass
Actuation line vacuum test performed (every 6 months)? Yes
Distribution piping network last purged with dry air or nitrogen (every 12 months)? Yes
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Exhaust fan(s) operating? Yes
Make-up/return air fan(s) shut down? N/A
Air filters/spacers reinstalled? Yes
Personnel instructed in manual operation of system? Yes
Class K extinguisher with placard present? Yes
Last regulator test date (every 12 years)? 10/08/2023
System returned to normal operation? Yes
Service and certification tag on system? Yes
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Main kitchen back hood
— Ansul 6 gallon — 132508 Electric N/A
FUEL SHUT OFF TYPE
FUEL SHUT OFF
'ON'
360 FUSIBLE LINK 450 FUSIBLE LINK 500 FUSIBLE LINK
OTHER FUSIBLE
LINK
# LINKS CHANGED
THIS SERVICE
Electric Shunt Trip Yes 4 N/A N/A N/A 4
Ventilation Equipment Information
HOOD SIZE PLENUM SIZE FILTER TYPE FILTER SIZE
2- 16 ft x4 ft 24x12 Baffle 19.5 x19.5
SIZE OF DUCT #1 SIZE OF DUCT #2 SIZE OF DUCT #3 SIZE OF DUCT #4
20x20 20x20 N/A N/A
Cooking Appliance Locations
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
Main back hood skillet Tilt Skillet 21x13 Electric Pass 3n 3
Maintenance Items Results
How many 360 degree Thermal Detectors? N/A
How many 600 degree Thermal Detectors? N/A
Thermal Detectors Tested N/A
All appliances properly protected with correct nozzles? Yes
Duct and plenum protected with correct nozzles? Yes
All nozzles properly aimed at hazard/unobstructed? Yes
Proper separation between fryer(s) and open flame? Yes
Nozzle blow-off caps installed (replace if needed) Yes
Hood & duct penetrations sealed with weld or UL device? Yes
Check cartridge weight (replace if needed)? Yes
Test detection system from terminal detector? Pass
Replace fusible links (every 6 months)? Yes
Date of links 2025
Test remote manual pull station? Pass
Test mechanical gas shut-off valve? N/A
Test electric solenoid gas shut-off valve with reset relay? N/A
Test electric switch for proper operation? Pass
Clean nozzles? Yes
System installed in accordance with mfg. UL listing? Yes
System meets UL 300 standards? Yes
Piping and conduit secured to rigid surface? Yes
Tamper seal(s) installed? Yes
Building fire alarm connected/activated? Pass
Actuation line vacuum test performed (every 6 months)? Yes
Distribution piping network last purged with dry air or nitrogen (every 12 months)? Yes
Exhaust fan(s) operating? Yes
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Make-up/return air fan(s) shut down? N/A
Air filters/spacers reinstalled? Yes
Personnel instructed in manual operation of system? No
Class K extinguisher with placard present? Yes
Last regulator test date (every 12 years)? 10/08/2023
System returned to normal operation? Yes
Service and certification tag on system? Yes
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Main kitchen front hood
— Ansul 6 gallon — 188162 Electric N/A
FUEL SHUT OFF TYPE
FUEL SHUT OFF
'ON'
360 FUSIBLE LINK 450 FUSIBLE LINK 500 FUSIBLE LINK
OTHER FUSIBLE
LINK
# LINKS CHANGED
THIS SERVICE
Electric Shunt Trip Yes 4 N/A N/A N/A 4
Ventilation Equipment Information
HOOD SIZE PLENUM SIZE FILTER TYPE FILTER SIZE
13ftx9.5 16.24 v bank Baffle 19.6x19.6
SIZE OF DUCT #1 SIZE OF DUCT #2 SIZE OF DUCT #3 SIZE OF DUCT #4
20x20 20x20 N/A N/A
Cooking Appliance Locations
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
Front main hood fryer Fryer 12 round Electric Pass 3n 1
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
Front main hood griddle Griddle 36x24 Electric Pass 1n 1
Maintenance Items Results
How many 360 degree Thermal Detectors? N/A
How many 600 degree Thermal Detectors? N/A
Thermal Detectors Tested N/A
All appliances properly protected with correct nozzles? Yes
Duct and plenum protected with correct nozzles? Yes
All nozzles properly aimed at hazard/unobstructed? Yes
Proper separation between fryer(s) and open flame? Yes
Nozzle blow-off caps installed (replace if needed) Yes
Hood & duct penetrations sealed with weld or UL device? Yes
Check cartridge weight (replace if needed)? Yes
Test detection system from terminal detector? Pass
Replace fusible links (every 6 months)? Yes
Date of links 2025
Test remote manual pull station? Pass
Test mechanical gas shut-off valve? N/A
Test electric solenoid gas shut-off valve with reset relay? N/A
Test electric switch for proper operation? Pass
Clean nozzles? Yes
System installed in accordance with mfg. UL listing? Yes
System meets UL 300 standards? Yes
Piping and conduit secured to rigid surface? Yes
Tamper seal(s) installed? Yes
Building fire alarm connected/activated? Pass
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Actuation line vacuum test performed (every 6 months)? Yes
Distribution piping network last purged with dry air or nitrogen (every 12 months)? Yes
Exhaust fan(s) operating? Yes
Make-up/return air fan(s) shut down? N/A
Air filters/spacers reinstalled? Yes
Personnel instructed in manual operation of system? No
Class K extinguisher with placard present? Yes
Last regulator test date (every 12 years)? 10/08/2023
System returned to normal operation? Yes
Service and certification tag on system? Yes
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Main kitchen serving line
— Ansul 3 gallon — 51117 Electric N/A
FUEL SHUT OFF TYPE
FUEL SHUT OFF
'ON'
360 FUSIBLE LINK 450 FUSIBLE LINK 500 FUSIBLE LINK
OTHER FUSIBLE
LINK
# LINKS CHANGED
THIS SERVICE
Electric Shunt Trip Yes 3 N/A N/A N/A 3
Ventilation Equipment Information
HOOD SIZE PLENUM SIZE FILTER TYPE FILTER SIZE
7x4.6ft 13x10 Water wash N/A
SIZE OF DUCT #1 SIZE OF DUCT #2 SIZE OF DUCT #3 SIZE OF DUCT #4
12x12 N/A N/A N/A
Cooking Appliance Locations
LOCATION DESCRIPTION Appliance Type APPLIANCE SIZE FUEL SOURCE
APPLIANCE
COVERAGE
NOZZLE TYPE NOZZLE QUANTITY
— Serving line oven Oven 42x36 Electric Pass 290 2
Maintenance Items Results
How many 360 degree Thermal Detectors? N/A
How many 600 degree Thermal Detectors? N/A
Thermal Detectors Tested N/A
All appliances properly protected with correct nozzles? Yes
Duct and plenum protected with correct nozzles? Yes
All nozzles properly aimed at hazard/unobstructed? Yes
Proper separation between fryer(s) and open flame? Yes
Nozzle blow-off caps installed (replace if needed) Yes
Hood & duct penetrations sealed with weld or UL device? Not Answered
Check cartridge weight (replace if needed)? Yes
Test detection system from terminal detector? Pass
Replace fusible links (every 6 months)? Yes
Date of links 2025
Test remote manual pull station? Pass
Test mechanical gas shut-off valve? N/A
Test electric solenoid gas shut-off valve with reset relay? N/A
Test electric switch for proper operation? Pass
Clean nozzles? Yes
System installed in accordance with mfg. UL listing? Yes
System meets UL 300 standards? Yes
Piping and conduit secured to rigid surface? Yes
Tamper seal(s) installed? Yes
Building fire alarm connected/activated? Pass
Actuation line vacuum test performed (every 6 months)? Yes
Distribution piping network last purged with dry air or nitrogen (every 12 months)? Yes
Exhaust fan(s) operating? Yes
Make-up/return air fan(s) shut down? N/A
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Air filters/spacers reinstalled? Yes
Personnel instructed in manual operation of system? Yes
Class K extinguisher with placard present? Yes
Last regulator test date (every 12 years)? 10/08/2025
System returned to normal operation? Yes
Service and certification tag on system? Yes
Inspector Signature
Inspector Name David Mills Date 10/08/2025
Element of Performance - EP-13 Automatic Kitchen Hood Extinguishing Systems – Semi-Annual
NFPA 96-2011: 11.2
Joint Commission Standard EC.02.03.05 Element of Performance 13 EP
-1
07e3cbad-bcf3-415c-86a9-7f3d9c592983 | Kitchen auto extinguishing systems | 10/08/2025
Terms And Conditions
1. Limitation of Liability; Limitations Of Remedy. It is understood and agreed by the Customer that Company is not an insurer and that insurance coverage, if any, shall be obtained by the Customer and that amounts payable to Company hereunder are based upon the value of the services and the scope of liability set forth in this agreement and are unrelated to the value of the Customer's property and the property of others located on the premises. Customer agrees to look exclusively to the Customer's insurer to recover for injuries or damage in the event of any loss or injury and that Customer releases and waives all right of recovery against Company arising by way of subrogation. Company makes no guaranty or Warranty, including any implied warranty of merchantability or fitness for a particular purpose that equipment or services supplied by Company will detect or avert occurrences or the consequences there from that the equipment or service was designed to detect or avert.<br />It is impractical and extremely difficult to fix the actual damages, if any, which may proximately result from failure on the part of Company to perform any of its obligations under this agreement. Accordingly, Customer agrees that, Company shall be exempt from liability for any loss, damage or injury arising directly or indirectly from occurrences, or the consequences therefrom, which the equipment or service was designed to detect or avert. Should Company be found liable for any loss, damage or injury arising from a failure of the equipment or service in any respect, Company's liability shall be limited to an amount equal to the agreement price (as increased by the price for any additional work) or where the time and material payment term is selected, Customer's time and material payments to Company. Where this agreement covers multiple sites, liability shall be limited to the amount of the payments allocable to the site where the incident occurred. Such sum shall be complete and exclusive. If Customer desires Company to assume greater liability, the parties shall amend this agreement by attaching a rider setting forth the amount of additional liability and the additional amount payable by the Customer for the assumption by Company of such greater liability, provided however that such rider shall in no way be interpreted to hold Company as an insurer. IN NO EVENT SHALL COMPANY BE LIABLE FOR ANY DAMAGE, LOSS, INJURY, OR ANY OTHER CLAIM ARISING FROM ANY SERVICING, ALTERATIONS, MODIFICATIONS, CHANGES, OR MOVEMENTS OF THE COVERED SYSTEM(S) OR ANY OF ITS COMPONENT PARTS BY THE CUSTOMER OR ANY THIRD PARTY. COMPANY SHALL NOT BE LIABLE FOR INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED TO DAMAGES ARISING FROM THE USE, LOSS OF THE USE, PERFORMANCE, OR FAILURE OF THE COVERED SYSTEM(S) TO PERFORM. The limitations of liability set forth in this agreement shall inure to the benefit of all parents, subsidiaries and affiliates of Company, whether direct or indirect, Company's employees, agents, officers and directors.
2. Limited Warranty. COMPANY WARRANTS THAT ITS WORKMANSHIP AND MATERIAL FURNISHED UNDER THIS AGREEMENT WILL BE FREE FROM DEFECTS FOR A PERIOD OF NINETY
(90) DAYS FROM THE DATE OF FURNISHING. Where Company provides product or equipment of others, Company will warrant the product or equipment only to the extent warranted by such third party. EXCEPT AS EXPRESSLY SET FORTH HEREIN, COMPANY DISCLAIMS ALL WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE SERVICES PERFORMED OR THE PRODUCTS, SYSTEMS OR EQUIPMENT, IF ANY, SUPPORTED HEREUNDER. COMPANY MAKES NO WARRANTY OR REPRESENTATION, AND UNDERTAKES NO OBLIGATION TO ENSURE BY THE SERVICES PERFORMED UNDER THIS AGREEMENT, THAT COMPANY'S PRODUCTS OR THE SYSTEMS OR EQUIPMENT OF THE CUSTOMER WILL CORRECTLY HANDLE THE PROCESSING OF CALENDAR DATES BEFORE OR
AFTER DECEMBER 31, 1999.
3. Indemnity. Customer agrees to indemnify, hold harmless and defend Company against any and all losses, damages, costs, including expert fees and costs, and expenses including reasonable defense costs, arising from any and all third party claims for personal injury, death, property damage or economic loss, including specifically any damages resulting from the exposure of workers to Hazardous Conditions whether or not Customer pre-notifies Company of the existence of said hazardous conditions, arising in any way from any act or omission of Customer or Company relating in any way to this agreement, including but not limited to the Services under this agreement, whether such claims are based upon contract, warranty, tort (including but not limited to active or passive negligence), strict liability or otherwise. Company reserves the right to select counsel to represent it in any such action.
4. Hazardous Materials. Customer represents that, except to the extent that Company has been given written notice of the following hazards prior to the execution of this agreement, to the best of Customer's knowledge there is no:
a. "permit confined space," as defined by OSHA, or space in which work must be performed that, because of its construction, location, contents or work activity therein, accumulation of a hazardous gas, vapour, dust or fume or the creation of a risk of infectious disease
b. need for air monitoring, respiratory protection, or other medical risk
c. asbestos, asbestos-containing material, formaldehyde or other potentially toxic or otherwise hazardous material contained in or on the surface of the floors, walls, ceilings, insulation or other structural components of the area of any building
d. All of the above are hereinafter referred to as "Hazardous Conditions". Company shall have the right to rely on the representations listed above. If hazardous conditions are encountered by Company during the course of Company's work, the discovery of such conditions shall constitute an event beyond Company's control and Company shall have no obligation to further perform in the area where the hazardous conditions exist until the area has been made safe by Customer as certified in writing by an independent testing agency, and Customer shall pay disruption expenses and re-mobilization expenses as determined by Company. This agreement does not provide for the cost of capture, containment or disposal of any hazardous waste materials, or hazardous materials, encountered in any of the Covered System(s) and/or during performance of the Services. Said materials shall at all times remain the responsibility and property of Customer. Company shall not be responsible for the testing, removal or disposal of such hazardous materials.
5. Equipment Disconnections. This represents Company's notice to you that the system(s)/device(s) listed on the face of this agreement as temporarily or permanently disconnected are no longer in service and, thus, cannot detect, perform and/or report
6. General. Unless otherwise specified, work shall be performed during company's regular business hours,, exclusive of Saturdays, Sundays and Company holidays. All work is subject to review and rebilling in accordance with the terms and conditions of Customer's agreement/contract with Company, if one is in effect. Company shall not be responsible for failure to render services due to causes beyond its control, including but not limited to material shortages, work stoppages, fires, civil disobedience or unrest, severe weather, fire or any other cause beyond the control of Company. Customer is aware that the Limitation of Liability and other provisions set forth in any existing agreement/contract, if one is in effect, or set forth above, apply to services performed and materials supplied. The terms of this agreement shall govern notwithstanding any inconsistent or additional terms and conditions in any purchase order or other document submitted by Customer.
Joint Commission Report | Date: 10/08/2025 Page 15 of 16
DEVICE NOTE IMAGE APPENDICES
Joint Commission Report | Date: 10/08/2025 Page 16 of 16