36C24719Q0683-005.docx
DOCX document 13 KB Posted
- Solicitation number
- 36C24719Q0683
About this file
36C24719Q0683 36C24719Q0683_4.docx
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24719Q0683-007.docx | DOCX document | |
| 36C24719Q0683-006.docx | DOCX document | |
| 36C24719Q0683-004.docx | DOCX document | |
| 36C24719Q0683-003.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FedBizOpps Amendment to a Previous Combined Solicitation
CLASSIFICATION CODE
SUBJECT
CONTRACTING OFFICE'S
ZIP-CODE
SOLICITATION NUMBER
BASE NOTICE TYPE
RESPONSE DATE (MM-DD-YYYY)
ARCHIVE
DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
SET-ASIDE
NAICS CODE
CONTRACTING OFFICE
ADDRESS
POINT OF CONTACT
(POC Information Automatically Filled from User Profile Unless Entered)
DESCRIPTION
See Attachment
AGENCY'S URL
URL DESCRIPTION
AGENCY CONTACT'S EMAIL
ADDRESS
EMAIL DESCRIPTION
ADDRESS
POSTAL CODE
COUNTRY
ADDITIONAL INFORMATION
GENERAL INFORMATION
PLACE OF PERFORMANCE
* = Required Field FedBizOpps Amendment to a Previous Combined Solicitation Rev. March 2010 J Chiller and Boiler Plant Water Treatment Service SITE VISIT Questions and Answers (Q&A) 29403-5799 36C24719Q0683 07-26-2019 N 325998 Department of Veterans Affairs Ralph H. Johnson VA Medical Center 109 Bee Street Charleston SC 29403-5799 John.Norway@va.gov WJB Dorn VA Medical Center Columbia, South Carolina 29209 Solicitation No. 36C247-19-Q-0683 Chiller & Boiler Water Treatment Service WJB Dorn VA Medical Center Columbia, South Carolina
Amendment No. 02
The purpose of this Amendment is to provide Answers against the Questions raised following the Site Visit held on Wednesday, July 17th 2019 at the WJB Dorn VA Medical Center, Chiller and Boiler Plants.
Question: What is the system volume of the chilled water closed loop?
Answer: 12-15K
Question: What is the approximate volume of the cooling tower (condenser) system?
Answer: 12,000 Gallons, with one tower scheduled to be replaced with a larger one at some point in the future (not certain what size replacement tower will be at this time).
Question: My understanding is that the chemical pumps and chemical tanks are not owned by the Veterans Administration (VA). It is clear in the solicitation that the tanks are to be provided. However, do you expect that we need to include pumps in the quote as well? Also, the controllers were said to belong to the VA, I want to clarify that the controllers are going to stay on site.
Answer: Yes, pumps have to be provided; controllers belong to VA. PUMPS DO NOT.
NOTE from Government Program Office: NO CHLORINE IS TO BE USED IN THE COOLING TOWERS. BROMINE CAN BE USED.