About this file

36C24719Q0683 36C24719Q0683_4.docx

View the file

Other files

File Type Posted
36C24719Q0683-007.docx DOCX document
36C24719Q0683-006.docx DOCX document
36C24719Q0683-004.docx DOCX document
36C24719Q0683-003.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FedBizOpps Amendment to a Previous Combined Solicitation

CLASSIFICATION CODE

SUBJECT

CONTRACTING OFFICE'S

ZIP-CODE

SOLICITATION NUMBER

BASE NOTICE TYPE

RESPONSE DATE (MM-DD-YYYY)

ARCHIVE

DAYS AFTER THE RESPONSE DATE

RECOVERY ACT FUNDS

SET-ASIDE

NAICS CODE

CONTRACTING OFFICE

ADDRESS

POINT OF CONTACT

(POC Information Automatically Filled from User Profile Unless Entered)

DESCRIPTION

See Attachment

AGENCY'S URL

URL DESCRIPTION

AGENCY CONTACT'S EMAIL

ADDRESS

EMAIL DESCRIPTION

ADDRESS

POSTAL CODE

COUNTRY

ADDITIONAL INFORMATION

GENERAL INFORMATION

PLACE OF PERFORMANCE

* = Required Field FedBizOpps Amendment to a Previous Combined Solicitation Rev. March 2010 J Chiller and Boiler Plant Water Treatment Service SITE VISIT Questions and Answers (Q&A) 29403-5799 36C24719Q0683 07-26-2019 N 325998 Department of Veterans Affairs Ralph H. Johnson VA Medical Center 109 Bee Street Charleston SC 29403-5799 John.Norway@va.gov WJB Dorn VA Medical Center Columbia, South Carolina 29209 Solicitation No. 36C247-19-Q-0683 Chiller & Boiler Water Treatment Service WJB Dorn VA Medical Center Columbia, South Carolina

Amendment No. 02

The purpose of this Amendment is to provide Answers against the Questions raised following the Site Visit held on Wednesday, July 17th 2019 at the WJB Dorn VA Medical Center, Chiller and Boiler Plants.

Question: What is the system volume of the chilled water closed loop?

Answer: 12-15K

Question: What is the approximate volume of the cooling tower (condenser) system?

Answer: 12,000 Gallons, with one tower scheduled to be replaced with a larger one at some point in the future (not certain what size replacement tower will be at this time).

Question: My understanding is that the chemical pumps and chemical tanks are not owned by the Veterans Administration (VA). It is clear in the solicitation that the tanks are to be provided. However, do you expect that we need to include pumps in the quote as well? Also, the controllers were said to belong to the VA, I want to clarify that the controllers are going to stay on site.

Answer: Yes, pumps have to be provided; controllers belong to VA. PUMPS DO NOT.

NOTE from Government Program Office: NO CHLORINE IS TO BE USED IN THE COOLING TOWERS. BROMINE CAN BE USED.