Storage Tank Data.pdf

PDF 4 MB Posted

Attached to
J044--Robotic U/T Testing of Above Ground Fuel Storage Tank
Solicitation number
36C24626Q0052
Issued by

About this file

This document is an out-of-service tank inspection report for Tank #3 located at the VA Hospital in Hampton, VA. The tank is a fixed-roof storage tank built in 1976, with a diameter of 28.50 feet, height of 31.75 feet, and a design capacity of 151,500 gallons. The tank stores #2 Fuel Oil and has a white painted external finish with an internal lining. The inspection report includes comprehensive technical details such as shell and bottom thickness measurements, nozzle layouts, settlement surveys, and out-of-plane calculations.

Key technical findings include minimal corrosion rates, with the remaining service life of the tank bottom exceeding the 20-year inspection interval requirement. The tank's shell courses and nozzles were measured for thickness, with readings indicating stable structural integrity. The out-of-plane edge deflection analysis showed acceptable results per API-653 standards. The report also includes detailed photographic documentation of the tank's nozzles, roof, center support column, and chime, providing visual evidence of the tank's condition at the time of inspection.

View the file

Other files

File Type Posted
36C24626Q0052 0001.docx DOCX document
P07 Wage Determination 15-4341.txt TXT text file
36C24626Q0052.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Report Order

SECTION I Summary/Recommendation

Calculation Pages

SECTION II Shell Layouts and Thicknesses

SECTION ID Bottom Layouts and Thicknesses (If applicable)

SECTION IV Roof Layouts and Thicknesses (If applicable)

SECTIONV Nozzle Layouts Nozzle Reinforcement Calculations and Layout

SECTION VI Settlement Surveys Out-of-Plane Calculations Elevation Surveys

SECTION VII Checklists

SECTIONVID Photo Pages

SECTION IX Certifications

Tank Data Summary

Customer: VA HOSPITAL

Tank#: 3

Manufacturer : UNKNOWN

Tank Description : BUTT WELDED

Product: #2 FUEL OIL Code.: UNKNOWN Product Specific Grav.: 0.850

Maximum Filling Height Used by Facility :

Calculated Filling Height Using S.G.:

Is vessel on original location? :

Vessel drawings? :

Is vessel modified? :

Any previous inspection records? :

Any maintenance records?

Any weld examination records? :

Any leak test records? :

Any mill test records? :

Pressure, operating/design (psig) :

Temperature, operating/design (°F) :

Shell Material Spec : UNKNOWN

Roof type:

Floating roof? :

If so, description :

Type of seals :

Primary:

Secondary:

Floating Roof access? :

STEEL CONE

N

NONE

If so, description : NONE

Bottom construction :

Second bottom? :

If so, year installed :

External finish :

Internal lining :

Insulation type :

FLAT

N

WHITE PAINT

y

NA

NONE

NONE

Location: HAMPTON, VA

Serial#: UNAVAILABLE Year Built: 1976

Diameter: 28.50 feet Height: 31.75 feet Design Capacity : 151,500 gal

3600 bbl

29.50 feet

31.75 feet y y N y y N N N

ATMOS./UNKNOWN

AMBIENT/UNKNOWN

Normal Venting Evaluation:

Venting, Sq in :

Fill openings, Sq in Outlets, Sq in :

Flow Rates:

Max Flow Rate:

Current Flow Rate:

50.27

12.57 12.57

200 GAL/MIN.

UNAVAILABLE

Safe Fill Height Calculation

See APl-653 Sections 2.3.3 and 2.3.4

Tank No. 3

Client VA HOSPITAL

Location : HAMPTON, VA

TANK DIAMETER, D

SHELL HEIGHT

FACILITY FILL HT

G, PRODUCT SP. GRAV.:

Y, YIELD STRENGTH :

T, TENSILE STRNGTH:

JOINT TYPE

E, JOINT EFFICIENCY:

28.50 FT

31.75 FT

29.50 FT

0.850 (water= 1.0)

30,000 PSI

55,000 PSI

BUTT

PER CODE OR USE DESIGN VALUE

1.0 FOR CORRODED PLATE CALC.

t, MINIMUM MEASURED SHELL THICKNESS, INCHES

S, MAXIMUM ALLOWABLE STRESS, PSI

COURSE 1-2: 23,595 PSI (SMALLER OF 0.80Y OR 0.429T)

COURSE 3-11: 25,960 PSI (SMALLER OF 0.88Y OR 0.472T)

RCA, REMAINING CORROSION ALLOWANCE, INCHES

REQUIRED THICKNESS FORMULA FROM APl-653 t = {2.6D(H)G}/{SE}

OR, REARRANGING TERMS:

H = {t(SE)/(2.6DG)}

SHELL READINGS, CONSTRUCTION, AND RESULTS

SHELL MIN. AVG. RCA, JOINT JOINT

COURSE THK, IN THK, IN in. EFF. IE TYPE

1 0.340 0.365 0.228 70% BUTT

2 0.360 0.381 0.260 70% BUTT

3 0.370 0.374 0.270 70% BUTT

4 0.370 0.373 0.270 70% BUTT

Data taken: 07/30/2002

Course Ht, FT

1 7.95

2 7.90

3 8.00

4 7.90

FILL HEIGHTS, FT

(BASED ON S.G. = 0.850)

ALLOWD CAL'D

31.75 89.16

31.75 102.35

31.75 122.60

31.75 130.60

Controlling fill height based on product S. G. is 31. 75 ft for Shell Course 1 (Fill ht based on S.G.=1.0 is 31. 75 ft).

RCA based on Facility Fill Ht and Product S.G.

Fill Ht- Pg 1

Remaining Service Life of Tank Bottom based on APl-653 Section 2.4.7 and allowable minimum bottom thicknesses.

Tank#: 3

Client: VA HOSPITAL Location: HAMPTON, VA

Formula: OR�= RTip-MRT StPr+UPr

OR2 = RTbc - MRT StPr+UPr

Bottom lined (Y/N):

Liner> 50 mils thickness(YIN):

Leak detection (YIN):

Secondary containment (YIN): .

Cathodic protection (YIN):

Age of bottom Original thickness

26.0 years iTh�:&�o}s'.<io¥ inches

Measured min avg thickness 0.509 inches

StPm, max internal pit depth it¥BiAtW}q7.� inches

Are these values corrected to original tank bottom (YIN): Y

UPm, max underside pit depth

Overall corrosion rate =

• No repair is needed. *

Calculated remaining service life :

After Repair:

SiPr= UPr =

Orl : Exceeds 20 year inspection interval requirement

Or2 : Exceeds 20 year inspection interval requirement

RTbc = minimum remaining thickness from bottom side corrosion after repairs RTip = minimum remaining thickness from intemal corrosion after repairs

0.05 inches

0.0000 inches/year

0.0023 inches/year

0.0023 inches/year

StPr = maximum rate of corrosion not repaired on the top side. SiPr = 0 for coated areas of the bottom.

The expected life of the coating must equal or exceed the next inspection interval to use StPr = 0.

UPr = maximum rate of corrosion on the bottom side.

MRTCalc Pg 1

Date of Inspection

Tank#: 3 Client: VA HOSPITAL Location: HAMPTON, VA

Item Thickness Date Roof Q,:'>U 01/U"J//O

Shell Course 1 0.375 01/01/76 Shell Course 2 0.375 01/01/76 Shell Course 3 0.375 01/01/76 Shell Course 4 0.375 01/01/76

!Bottom

NozzleA-4" 0.250 01/01/76 Nozzle 8-2" 0.218 01/01/76 Nozzle c -24 " 0.375 01/01/76

Date of Inspection Pg 1

Minimum Thickness

U.5□

0.34 0.36

0.37 0.37

0.240 0.200 0.380

Date Taken: 07/30/2002

Original thicknesses of Shell and Nozzles are assumed for calculations.

In-Service Out-of-Service In-Service Out-of-Service Remaining Remaining Inspection Inspection Inspection Inspection

Inspection Corrosion Corrosion Corrosion Date Based Date Based Date Based Date Based Date Rate Allowance Life in Davs on ¼Life on ½Life on 5 Years on 20 Years

01/30/02 1 E-1 rn, 0.410 4.1E+1n.4 '"

29.JUl•-'UU/ 25.JUl•l!U:ll!

07/30/02 3.6056E-06 0.228 63096.3186035 6-0ct-2045 13-Dec-2088 29.Jul-2007 25.Jul-2022 07/30/02 1.5453E-06 0.260 168254,666667 28-Seo-2117 28-Nov-2232 29.Jul-2007 25.Jul-2022 07/30/02 5.1509E-07 0.270 524178 13-May-2361 25-Feb-2720 29.Jul-2007 25.Jul-2022 07/30/02 5.1509E-07 0.270 524178 13-Mav-2361 25-Feb-2720 29.Jul-2007 25.Jul-2022

07/30/021 25.Jul-20221

07/30/02 1.0302E-06 0.140 135898 5-Aua-2095 11-Aua-2188 29.Jul-2007 25.Jul-2022 07/30/02 1.8543E-06 0.100 53927. 7777778 27.Jun-2039 25-Mav-2076 29-Jul-2007 25.Jul-2022 07/30/02 1E-105 0.280 2.8E+104 ***•************** **,,.****'-********** 29.Jul-2007 25.Jul-2022

SECTION II

Shell Layouts and Thicknesses

1 2

VA HOSPITAL

HAMPTON. VA

TANK #3

TANK LAYOUT

LADDER

X

3 4 1

SEAM 1 IS THE FIRST SEAM LEFT OF THE FIRST MANWAY

LEFT OF THE STAIRWAY AS VIEWED FROM OUTSIDE OF

THE TANK.

SCfZl4fZll

HAMPTON. VA

TANK 1t3

SHEET IDENTIFICATION

LADDER

[X

SCfZl4fZl2 SCfZl 4k 3

SCfZl301 SC fZl 3 fZl 2 s:0303

SC0201 5[0202 SC 0, D 0 3

SC0101 SC0102 SC0103 SCfZl 104

2 3 4

SC04fZl4

5[0304

SC0204

SC1t1titit - SIGNIFIES THE SHELL COURSE ANO THE SHEET. THE FIRST

TWO DIGIT NUMBER IS THE SHELL COURSE NUMBER ANO THE

FOLLOWING TWO DIGIT NUMBER IS THE SHEET NUMBER.

TYPICAL SHELL SHEET

HORIZONTAL THICKNESS READINGS

SC#### - SIGN IFIES THE COU RSE ANO THE SHEET.

SC####0l - READING TAKEN WITHIN ON E INCH OF THE VERTICAL SEAM AN D APPROXIMATELY

TWO INCHES FROM THE HORIZON TAL SEAM.

SC####0X - FOR READINGS THROUGH [####MAX-! IS THREE FOOT SPACING.

SC####MAX - READING TAKEN WITHIN ON E INCH OF THE VERTICAL SEAM ANO APPROXIMATELY

TWO INCHES FROM THE HORIZON TAL SEAM.

Shell Horizontal Thickness Readings

Client: VA HOSPITAL Location: HAMPTON, VA -- -

J

Shell Sht Point No.•••> Readinas In hundredths of an Inch Course No. 01 02 03 I 04 05 06 07 08 09 10 11

SC:f MM • 39 MIN■ �AVG• :�1'1.9 1 38 36 38 38 38 38 37 38 38 2 35 39 39 38 38 3 36 37 37 36 36 36 36 36 36 4 36 36 39 36 36 36 36 36 36

Shell Course 1 Horiz - Pg 1

J J ]

I - - • - ... -.. --· --Data taken: 07/30/2002

12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

SC[2 201

SC0101

VA HOSPITAL

HAMPTON. VA

TANK #3

VERTICAL THICKNESS READINGS

LADDER

[X

SC0 � 3

�D=0303

SC020 2 SC 0r b 13 SCi

SC0103 SC0104

3 4

)204

- INDICATES THE LOCATION OF THE VERTICAL THICKNESS

READINGS ON THE TANK SHELL LAYOUT.

SC#### - SIGNIFIES THE SHELL COURSE AND THE SHEET. THE FIRST

TWO DIGIT NUMBER IS THE SHELL COURSE NUMBER AND THE

FOLLOWING TWO DIGIT NUMBER IS THE SHEET NUMBER.

TYPICAL SHELL SHEET

VERTICAL THICKNESS READINGS

SC####VMAX

SC####V03

SC####V02

SC####V01

SC#### -. SIGNIFIES THE COURSE AND THE SHEET.

SC####V01 - READING TAKEN APPROXIMATELY TWO INCHES UP FROM HORIZONTAL SEAM.

SC####V0X - FOR READINGS TAKEN THROUGH SC####VMAX - IS ONE FOOT SPACING.

SC####VMAX - LAST READING TAKEN ON SHEET.

Shell Vertical Thickness Readings

Tank#: 3

Client: VA HOSPITAL

Location- HAMPTON, VA Shell Sheet Point No. V - ===>

Course No. 01 02 03

SC-1 MAX: 38 MIN:

1 • 37 37 37

3 35 37 37

4 36 36 37

4 36 37 35

SC-2 MAX: 40 MIN:

1 38 40 38

2 39 38 37

3 37 38 37

4 38 39 37

�v-3 MAX: 38 MIN:

3 37 37 38

SC-4 MAX: 31:l MIN:

3 37 37 38

Vert Shell Data - Pg 1

04 05

34 AVG:

35 38

37 36 37 37 37 37

36 AVG:

38 40 38 36 38 38 39 40 37 AV(.j:

37 37

3/ AVG:

37 38

Data taken: 07/30/2002 Readings in 1 OO's of an inch

06 07 08 09 10 11

36.5 34 37 37 37 37 35 36 37 37 37 37 37

31:l.1

39 39 38 38

38 38 38 38 38 38 38 38 36 39 37 39

3/.4

38 38 38 . 37

-.:S/.3

37 37 38 37

SECTION ill

Bottom Layouts and Thicknesses

MANWAY

VA HOSPITA.L

HAMPTON. VA

TANK #3

BOTTOM LAYOUT

17 1/2" X 17 1/2"

SUMP

CD

TYPICAL BOTTOM PLATES

POINTS

TYPE A

Q

TYPED

5 2

TYPE G

TYPE I

FOR THICKNESS READINGS

I :

TYP.E BI

TYPE B

TYPE E

6 2

TYPE H

5 2

�I

�I

4 1

TYPE _J

G

TYPE C

�I ..

LY

TYPE F

6 2

TYPE Hl

TYPE K

Bottom Plate Thickness Readings

Client: VA HOSPITAL Location: HAMPTON VA

Btm Point••=>

Plate No 01 02 03 04

8-1 53 "" :,q "" 8-2 52 51 52 51

B-3 49 51 49 50

B-4 53 53 54 52

B-5 49 49 49 47

B-8 49 49 49 49

B-7

B-8

8-9

B-10

B-11

B-12

B-13

B-14

B-1!5

B-18

B-17

8-18

B-19

8-20

B-21

B-22

B-23

B-24

8-25

B-28

8-27

8-28

8-29

8-30

Btm Plate Data Pg 1

Plate

05 06 Tvoe

,,,, IJ

51 E 50 E 52 E 50 E 46 J

Btm Point-••>

Plate No 01 02

B-31

B-32

8-33

B-34

B-35 8-36

B-37

B-38 8-39

B-40

B-41

B-42

B-43

B-44

8-4!5

B-46

8-47

B-46

B-49

8-60

B-51

B-52

B-53

B-54

8--66

8-!56

B-57

8-M

8-59 e-eo

J

03 04 overall Min:

overall Max:

overall Av 1:

Plate

05 06 Tu""

J

50.9

Btm

Plate No B-81

B-82

8-63 8-84

8-65 8-68

B-87

8-68 8-89

B-70

B-71

B-72

B-73

B-74

B-7!5

B-78

B-77

8-78

B-79

B-80

B-81

B-82

B-83

8-84

B-8!5

8-88

B-87

8-88

8-89

8-90

Polnt-a11>

01 02 03 04

Plate

05 06 Tvoe

Readings In hundredths of an Inch Data taken: 07/30/2002

Btm Point-=•>

Plate No 01 02 03 04 05 8-91

8-92

8-93

8-94

8-95

8-96

B-97

8-98

8-99

B-100

B-101

8-102

B-103

B-104

B-10!5

B-108

B-107

B-108

B-109

8-110

B-111

8-112

B-113

B-114

8-115

B-118

8-117

B-118

8-119

B-120

Plate

06 Tvoe

BOTTOM THICKNESS READINGS

THICKNESS TAKEN AT THE EDGE

BOTTOM

MAX

SC####

SC##�t - SIGNIFIES THE SHELL COURSE AND THE SHEET. THE

FIRST TWO DIGIT NUMBER IS THE SHELL COURSE NUMBER

�ND THE FOLLOWING TWO DIGIT NUMBER IS THE SHEET

NUMBER.

E-1 - CORRESPONDS WITH SC0101

E-2 - CORRESPONDS WITH SC0102

E-MAX - CORRESPONDS WITH SC01MAX

01 - REAOIDNG TAKEN TWO INCHES FROM THE SHELL AT VERTICAL SEAM.

02-MAX - READINGS TAKEN ONE FOOT APART.

Bottom Edge Thickness Readings

Client: VA HOSPITAL Location: HAMPTON_,_ VA

J J

Btm Point No. E- Readlnas In hundredths of an Inch Plate No. 01 02 03 04 05 06 07 08 09 10 11 12 13

MAX" 55 MIN• 44 AVG• 51.2

E-1 54 54 54 54 55 55 54 54 54 54 54 54 52

E-2 64 54 54 54 54 50 50 51 60 50 50 46 50

E-3 44 47 50 50 49 48 47 46 45 50 50 49 49

E-4 49 49 49 49 49 49 49 49 53 53 53 54 54

E-5 E-6 E-7 E-8 E-9 E-10 E-11 E-12 E-13 E-14 E-15 E-16 E-17 E-18 E-19 E-20 E-21 E-22 E-23 E-24 E-25 E-26 E-27 E-28 E-29 E-30

J J

14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29

54 54 54 54 54 54 54 54 54 54 54 54

50 45

49 49 49 49 49 49 49 49 49 49 49 49

54 54 53 52 52 52 52 52 52 52 51 53

Note: Readings taken approximately 2" from tank edge adjacent to shell sheets. E-1, E-2, ... E-max correspond to shell course sheets.

Btm Edge Data Pg 1

Data Taken: 07/30/2002

30 31 32 33 34 35 36 37 38

SC#### 01

BOTTOM THICKNESS READINGS

THICKNESS TAKEN ON THE CHIME

BOTTOM

SC####

MAX

SC#### - SIGNIFIES THE SHELL COURSE ANO THE SHEET. THE

FIRST TWO DIGIT NUMBER IS THE SHELL COURSE NUMBER

AND THE FOLLOWING TWO DIGIT NUMBER IS THE SHEET

NUMBER.

'E-1 - CORRESPONDS WITH SC010I

E-2 - CORRESPONDS WITH SC0102

E-MAX - CORRESPONDS WITH SC0IMAX

01 - READING TAKEN ONE HALF INCH FROM THE SHELL AT VERTICAL SEAM

02-MAX - READINGS TAKEN THREE FEET APART.

Bottom Chime Thickness Readings

Client : VA HOSPITAL Location: HAMPTON, VA Thk. Ishee! 1 Sheet 2 Sheet 3 ShMl4 Sheet5

J

Sheet6 !Sheet 7 Sheet 8 lsheet9 Sheet 10 Sheet 11 Sheet 12 Point RThJckneM Width Thlcl<neu IWldth Thickness WldthlThlckneaa Width Thickness Width ThlckneM Width IThleknees Width Thleknen Width IThlckneu Width Thickness Width Thlcknen Width Thickness Width

01 1 1 1 1.125 02 1 1 48 1 1 03 1 1 1 1 04 1 1 1 1 05 1 1 50 1 1 06 1.125 1 I

07 1 1 1 08 1 1 1 09 1 I t

Thk. IShfft 13 Point IThlcknesa Width

Sheet 14 Sheet15 Sheet 16 Sheet 17 Sheet 18 Ishee! 19 Sheet 20 Ishee! 21 Sheet 22 Sheet 23 Ishee! 24 Thleknen IWldth Thlcknffa Width Thickness Width Thickness Width Thleknela Width IThlckntH Width Thickness Width IThlckneu Width Thickness Width Thlcknen Width Thleknees Width

Note: Readings taken 11pproldrnately 1/Z' from tank edge lldjaeeot to shell lheets. E-1, E-2, ... E-max eorrespond to shen course sheets. Thickness readings In hundredths ol an Inch Widths In fnches.

Sump Thickness Readings

Tank#: 3

Company: VA HOSPITAL

Location: HAMPTON, VA s

Sump Point No.(See Detail) ===>

Location 1 2 3 4 ;:,neet 11, b� ::M ::>L bL

Date Taken: 07/30/2002

Sump Thickness

Toward Row#1 Sheet#1

2 t

Readinos in 1 OO's of an inch

5 6 7 8 b2 52 b2 52 52

SECTION IV

Roof Layouts and Thicknesses

1 1 /2 ..

GAUGE HATCH

VA HOSPITAL

HAMPTON. VA

TANK #3

ROOF LAYOUT

LADDER

24"MANWAY

6"FLAME ARRESTOR/VENT

TYPICAL ROOF PLATES

POINTS FOR THICKNESS READINGS

;1 �

TYPE A TYPE s· WTYPE C

� u

�I .

TYPED TYPE E TYPE F

5 2 6 2

4 5

TYPE G TYPE H

� 0 0 I I

TYPE I TYPE J TYPE K

3 2 5

TYPE L TYPE M

Roof Plate Thlckneaa Reading•

Client: VA HOSPITAL Location: HAMPTON,VA - -

Roof Point•••>

Plate# 01 02 03 04

1·1 :>1 ::,u 51 ::,u

T-2 51 50 51 50 T-3 51 50 51 51 T-4 51 51 52 51 T-5 50 52 52 50 T-6 52 52 51 51 T-7 T-8 T-9 T-10 T-11 T-12 T-13 T-14 T-15 T-16 T-17 T-18 T-19 T-20 T-21 T-22 T-23 T-24 T-25 T-26 T-27 T-28 T-29 T-30

05 06 ::,u

Plate Roof

Tvoe Plate#

IJ hjl

E T-32 E T-33 E T-34 E T-35 J T-38

T-37 T-38 T-39 T-40 T-41 T-42 T-43 T-44

T-45 T-46 T--47 T-48 T-49

T-50 T-51 T-52 T-53 T-54 T-55 T-56 T-57 T-58 T-59 T-60

Point■••>

01 02 03 04

Overall Min:

Overall Max:

.QverallA, ___ ___ \VJ:

Plate

05 06 Tvoo

5_0.8 --- Roof

Plate# 1-01 T-62 T-63 T-64 T-65 T-66 T-67 T-68 T-69 T-70 T-71 T-72 T-73 T-74 T-75 T-76 T-77 T-78 T-79 T-80 T-81 T-82 T-83 T-84 T-85 T-86 T-87 T-88 T-89 T-90

Point■••>

01 02

Plate

03 04 05 06 Tvoe

Readings In hundredths of an Inch Data taken: 07/30'2002

Roof Point■••>

Plate# 01 02 03 04 05 1-1:n

T-92 T-93 T-94 T-95 T-98 T-97 T-98 T-99

T-100 T-101 T-102 T-103 T-104 T-105 T-106 T-107 T-108 T-109 T-110 T-111 T-112 T-113 T-114 T-115 T-116 T-117 T-118 T-119 T-120

Plate

06 Tvoe

SECTIONV

Nozzle Layouts

Nozzle Reinforcement Calculations and Layout

A

VA HOSPITAL

HAMPTON. VA

TANK #3

NOZZLE LAYOUT

B

C l

Nozzle Reinforcement Cales

See APl-653 Section 7.7 and APl-650 Section 3.7.2

Tank#: 3

Cllent: VA HOSPITAL

Location: HAMPTON, VA THE REINFORCING CROSS-SECTIONAL AREA ( Xx Y) MUST BE LESS THAN THE FOLLOWING:

(SEE NEXT PAGE FOR DEFINITIONS)

X(Y) < (A)(B-X) + (4)(T)(T)(2) + (2)(T}(Y)

Size Sheet Co-ord. ft Nozzle Thick inches Tag In. Service ID Tao X-Axls Y-Axls Too Left Btm Rlaht A 4 t"Kl...'!...'t..!'-I SC0101 1.4 o.ou 0.20 0,Lo'J 0.24 0.20

B 2 VALVE SC0101 11.7 0.45 0.21 0,20 0.20 0.21

C 24 MANWAY SC0101 22.8 1.20 0.40 0.38 0.39 0.41

D E F G H

I J K L M N p Q R s

T

Nozzle Reinforcement - Pg 1

Re-pad Thk. in B in X In u.�, 12.U 4.0

2.38

0.65 40.8 24

NOTE: Nozzle Ht. per APl:;650 column le for Informational purposes only.

Y In U.35 0.38 0.13

Thie column lndleatea whether the height of the nozzle meets the preeent APl-650 normal height requirement, but dOas not Indicate whether It Is In vlolatlon of APl-653.

XxY RelnfArea Approv'd Nozz Ht A In T In Sa. In. Sa. In. oar APl-653 oar APl-650 o.�, U.24 1,0L 3.41 Tl:� ==NU==

0.86 Not Rea'd ==NO==

0.65 0.38 3.17 12.14 YES ==NO==

NOZZLE REINFORCEMENT REQUIREMENTS

y

X

(Xl (Yl = AREA OF SHELL REMOVED

(Al (8 - Xl = AREA OF REINFORCEMENT PLATE

(4l (Tl (Tl (2l + (2l (Tl (Yl = AREA OF NOZZLE USED FOR REINFORCEMENT

(Xl (Yl � (Al (8 - Xl + 4[Tl (Tl (2l + (2) [Tl (Yl

2" AND SMALLER NOZZLES DO NOT REQUIRE REINFORCEMENT PER API-653.

TYPE

I< ;,,,,I l

TYPE I A

IE ;,,.I

e i----1 l

TYPE 5

A

I< ➔I l

TYPE 8

TYPE BA

REINFORCEMENT PAD TYPE

D [

D [

TYPE 2

A

I< ;:,.-I

TYPE 2A

I< B r---1

TYPE 6

I<:

A

TYPE 9

IX, YI

;,,,,I

,..1

TYPE 11

IX. YI

r J.�

J

1-

........ EOTTOM OF' TANK

....... BOTTOM OF T J\NK

TYPE 3

TYPE 4

1-E ;;.,,I

(� Yl

1-E

TYPE 7

A

;..,I

R l�Yl

TYPE 10

I<

IX. Y)

TYPE 12

I<:

IX, YI

I-

I·

B

........_ BOTTOM CR TAM<'

BOTTOM fx TAN<

TYPE

1...- _,..1 l

TYPE IA

IE > I

e r-----1

TYPE 5

I< :;...I l

TYPE 8

TYPE BA

REINFORCEMENT PAD TYPE

D [

0 I

TYPE 2

A

1-c:: :;.. I i-----1

TYPE 2A

I..-::

e i----1

TYPE 6

I<:

A

TYPE 9

IX, YI

;,,,,I

;,,,I

TYPE 11

IX, YI

J, i!-'ST l

J-

.....,_ EOTTDM OF TANK

::,,..1

'-, BOTT0/1 OF' TANK

TYPE 3

;,,,I

TYPE 4

I< >I

IX.Yl

I<

TYPE 7

A

;:,,,I

R

IX.Yl

TYPE 10

IX. YI

TYPE 12

I-

I-a

'BOTTOM c,;t TAt-1<'

;,,, I

IX. YI

BOTTOM a: TMK

Out-of-Service Tank Report

Nozzle Reinforcement Pad Layout Client: VA HOSPITAL Tank#: 3 Location- HAMPTON, VA

Nozzle Repad Measurement Location-measurement in feet Letter Type A B C D R

A 1 1.30 0.50 1.00

C 1 5.40 1.90 3.40

SECTION VI

Settlement Surveys

Out-of-Plane Calculations

Elevation Surveys

Out-of-Plane Edge Deflection VA HOSPITAL-HAMPTON, VA:Tk# 3

0.050 --,----------------------r--------, =_ 0.040 C

·g_ � 0.030 ro 0.020 C s u, 0 0.010

• •···········�································.I

Measured Data

. / � : �:n: Curve I \

···1

I \/ \ ·--··-·····--.J

IF

I \

/ ' " 0.000 _J_--�--1----1----1-----11----1----1----t---__..F--_

6 7 8 1 2 3

Station No.

4 5 6

Out-of-Plane Edge Deflection VA HOSPITAL-HAMPTON, VA:Tk# 3

0.050 -,--------------------r----�-----, =� 0.040 +■I

C

·g_ � 0.030 i 0.020

C m

� 0.0100

Measured Data

/'/ -..., I ...... , r �

I Cosine Curve

I \ / \ j'

I \

I "\

0.000 1 if" I I I I I I I ,., 1

6 7 8 1 2 3

Station No.

4 5 6

J

Out-of-Plane Edge Deflection Analysis - APl-653 Appendix B

Tank No.: 3

Fonnula for Out-of-Plane Deflection: IS) < or= (L z x Y x 11) / [2(E x H)]

Where:

S = deflection, in feet

L = arc length, in feet 0.016 feet= 0.19 inches

Y = yield strength, in psi L: 11.2 feet

E = Young's modulus, in psi Y: 30,000 psi

H = tank height, in feet E: 29.5 X 10"6 psi

H: 31.75 feet

Sallow: 0.022 feet

Out-of-Plane edge settlement is acceptable per APl-653.

Sequence Equiv. Data Cos Averaged No. Station Angle, deg feet Curve Diff. Diff.

0 6 0 0.000 0.000 0.000 0.007

1 7 45 0.020 0.006 -0.014 0.004

2 8 90 0.040 0.020 -0.020 0.010

3 I 135 0.040 0.034 -0.006 0.006

4 2 180 0.020 0.040 0.020 0.016

5 3 225 0.020 0.034 0.014 0.004

6 4 270 0.020 0.020 0.000 0.000

7 5 315 0.020 0.006 -0.014 0.014

8 6 360 0.000 0.000 0.000 0.007

OOP-Pg 1

0.02·

0.05'

0.04' 0.03' 0.02·

0. 01.

0.00·

0.02·

0.02· t==:

N (Y') s;;r-z z z z 0 0 0 0

I- I- I- I- I- I- I- I-

(f) (f) (f) (f)

VA HOSPITAL

HAMPTON. VA

TANK #3

ELEVATION SURVEY

0.04'

0.02·

PLAN VIEW

�I�

lf) (,D ('i... OJ z z z z 0 0 0 0

I- I- I- I- I- I- I- I-

(f) (f) (f) (f)

0.04'

0.00· t z

I- I- (f)

STATION 1 CORRESPONDS WITH VERTICAL SHELL SEAM 1 ON THE

TANK SHELL LAYOUT. ALL FOLLOWING STATIONS ARE AT EQUAL

INTERVALS AROUND THE TANK.

NOTE: ELEVATIONS ARE BASED ON LOWEST STATION POINT

AT THE SHELL BEING 0.00·

0.02·

0.05'

0.04' 0.03' 0.02·

0.01.

0.00· l J J

CORRECTED DATA· Readings In feet.

Tank#: 3

Tank Dia: 29 ft

Max Reading: 5.43 ft at edge, used to correct data

Distance across tank from edge a•> -· -seam edae 10 ft center

1 0.04 0.12 0.04

2 0.02 0.12

3 0.02 0.10

4 0.02 0.02

5 0.02 0.04

6 0.00 0.09

7 0.02 0.03

8 0.04 0.02

Data taken: 07/30/2002

Elevations - Pg 1

J l l l l J

NOTE: Elevations are based on lowest station point at the shell being 0.00'

HAMPTON. VA

TANK #3

ELEVATION SURVEY

0.20·

0. 10 · T _____ __ 0.00· �

0.20· + 0.10' 9 0' 00' w C) w

STATION 1

z et:

w 1-z w u z lSI w (_'J w

STATION 5

STATION 1 COORESPONDS WITH VERTICAL SHELL SEAM 1 ON THE TANK

SHELL LAYOUT. ALL FOLLOWING STATIONS ARE AT EOUAL INTERVALS

AROUND THE TANK.

0. 20 •

0 . 10 •

0. 00 w w

STATION 2

z

ISi

VA HOSPITAL

HAMPTON. VA

TANK #3

ELEVATION SURVEY

O::'.

w 1-z w u z w w

STATION 6

STATION 1 COORESPONDS WITH VERTICAL SHELL SEAM 1 ON THE TANK

SHELL LAYOUT. ALL FOLLOWING STATIONS ARE AT EQUAL INTERVALS

AROUND THE TANK.

0. 20 •

0 . 1 0 •

0. 00.

0. 20

0. 00 • w l') w

STATION 3

z lSl

VA HOSPITAL

HAMPTON. VA

TANK #3

ELEVATION SURVEY

O::'.

w f z w u z w l') w

STATION 7

STATION 1 COORESPONDSWITH VERTICAL SHELL SEAM 1 ON THE TANK

SHELL LAYOUT. ALL FOLLOWING STATIONS ARE AT EQUAL INTERVALS

AROUND THE TANK.

0. 20 •

0. 00.

0.20·

0. 10.

0.00· w

CJ

w

STATION 4

z

VA HOSPITAL

HAMPTON. VA

TANK #3

ELEVATION SURVEY

O:'.:

w 1-z w u z lSl w w

STATION 8

STATION 1 COORESPONDS WITH VERTICAL SHELL SEAM 1 ON THE TANK

SHELL LAYOUT. ALL FOLLOWING STATIONS ARE AT EQUAL INTERVALS

AROUND THE TANK.

0.20·

0. 10.

0.00·

SECTION VII

Checklists

FIXED ROOF

Fixed and Floating Roof Evaluation

Tank Number: 3

1. Type and size of center roof vent: iv k

7,-'1 2. Size of the roof manway:

3. Is the roof manway@,r unbolted: ___________________ _

4. Is the roof manwa�r ungasketed: __________________ t,-, +-,t I-, ,,

5. Size of the gauge-Yv'ell:_·_,x_'z. ______________________ _

7. Number and size of air scoops:_lv_A ____________________ _

8. Number and size of overflow vents: ,v.-4

9. Number of pressure/vacuum vents:��--4 ___________________ _

10. Size and type of pressure/vacuum vents:_/r/._A-..;__ _______________ _

11. Describe internal inspections of pressure/vacuum vents:_,v:_��· __________ _

12. Is there a flame arrestor: Y-r:-J

13. Size and type of flame arrestor:_8_--'.t'-"-,,.-�_? ________________ _

14. Describe any other roof fittings:_--_· ___________________ _

FRC Pagel

SECTION VIII

Photo Pages r-i I

'7

File details come from the government source that posted it. Updated .