Attachment A_Requirements for Identification and Replacement of A307 Bolts Memo_Signed.pdf
PDF 379 KB Posted
- Attached to
- 659-25-510 | B11 CW Pumps & Condensate Pumps |
- Solicitation number
- 36C24625B0020_2
About this file
This is a Department of Veterans Affairs memorandum providing urgent requirements for identifying and replacing ASTM A307 bolts on steam and hot water piping systems at VA medical centers (VAMCs). The memo details that ASTM A307 bolts are considered inadequate for high-temperature piping systems and must be replaced with ASTM A193 bolts. Network Directors must immediately review project specifications, modify ongoing construction contracts to remove A307 bolts, and ensure all VAMCs develop comprehensive surveys of existing piping systems by June 18, 2025. VISN Capital Asset Managers are required to provide a list of impacted construction projects to the Office of Healthcare Engineering by January 3, 2025, and all VAMCs must prioritize high and medium pressure steam and hot water piping systems operating over 50 pounds per square inch for inspection and potential replacement.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 659-25-510_Specs-Rev1_20250513.pdf | ||
| 659-25-510_RFIs-Second Set_20250407 (003).docx | DOCX document | |
| 659-25-510_DWGs-Rev1_20250513.pdf | ||
| 36C24625B0020_2 0004.docx | DOCX document | |
| 36C24625B0020_2 0003.docx | DOCX document | |
| Attachment C_1641 Submittal Sheet.pdf | ||
| Attachment B_659-25-510_Specifications_20241104-Rev 1.pdf | ||
| 36C24625B0020_2 0002.docx | DOCX document | |
| Attachment D_Package System.pdf | ||
| Attachment E_Pre-Bid Site Visit Attendance.pdf | ||
| 36C24625B0020_2 0001.docx | DOCX document | |
| 36C24625B0020__2.docx | DOCX document | |
| 659-25-510_Specifications_20241104.docx | DOCX document | |
| 659-25-510_DWGs_20241104.pdf |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department of Veterans Affairs
Memorandum
Date:
From: Acting Assistant Under Secretary for Health for Support (19)
Subj: URGENT: For Action: Requirements for Identification and Replacement of A307
Bolts on Steam and Hot Water Piping Systems (VIEWS 12473639)
To: Veterans Integrated Service Network (VISN) Directors (10N1-23)
1. PURPOSE: This memorandum provides notification and information on requirements for the identification and replacement of American Society for Testing and Materials (ASTM) A307 bolts (all grades) on steam and hot water piping systems for all Department of Veterans Affairs (VA) medical centers (VAMC).
2. BACKGROUND: Veterans Health Administration (VHA) Master Specifications for Hydronic Piping (Specification 23 21 13, Section 2.3) and Steam and Condensate Heating Piping (Specification 23 22 13, Section 2.3) indicate ASTM A307 bolts for use on steam and hot water pipe flanges. However, the ASTM A307 bolt (all grades) is considered a general-purpose bolt and does not possess the necessary material strength at elevated temperatures for use on steam and hot water piping systems.
These specifications are being updated to indicate ASTM A193 bolts as the appropriate fastener for steam and hot water piping systems. The current VHA Master Specifications can be accessed at:
https://www.cfm.va.gov/TIL/spec.asp.
All VAMCs must complete a survey of their existing steam and hot water piping systems and develop a replacement plan, prioritizing high and medium pressure steam and hot water piping systems operating over 50 pounds per square inch. If ASTM A307 bolts (all grades) are identified, an Interim Safety Measure must be developed to ensure the safety of staff and the facility until replacement is complete.
3. DECISION: Effective immediately, Network Directors must ensure all VAMCs in their VISN review their specifications for projects in design and correct any references to ASTM A307 bolts, and for projects in construction, assess if ASTM A307 bolts are specified for use on any steam or hot water piping system. If ASTM A307 bolts are indicated, the construction contract must be modified to remove the ASTM A307 bolts. VISN Capital Asset Managers (CAM) must provide a list of impacted construction projects via email to the Office of Healthcare Engineering (OHE) at VHAHealthcareEng@va.gov by Friday, January 3, 2025.
All VAMCs must develop a plan to survey existing steam and hot water piping systems by Wednesday, June 18, 2025, and notify their VISN CAM upon completion of the survey.
Page 2.
Subj: For Action: Requirements for Identification and Replacement of A307 Bolts on Steam and Hot Water Piping Systems (VIEWS 12473639)
4. For additional information or questions regarding this memorandum, please contact OHE at VHAHealthcareEng@va.gov.