36C24625B0020_2 0002.docx
DOCX document 128 KB Posted
- Attached to
- 659-25-510 | B11 CW Pumps & Condensate Pumps |
- Solicitation number
- 36C24625B0020_2
About this file
This document is an amendment (Amendment 0002) to Solicitation 36C24625B0020 issued by the Department of Veterans Affairs Network Contracting Office in Salisbury, NC for the replacement of Chilled Water Pumps and Condensate Pumps in Building 11. The amendment provides detailed responses to 38 contractor questions covering project specifics such as work scope, performance period, site logistics, and technical requirements. Key details include a 120-day period of performance (potentially extendable), no exterior work planned, tuberculosis testing required for workers, and VA-provided parking and workspace.
The solicitation requires replacing existing mechanical pumps on the ground floor of Building 11, with specific technical considerations including changing from pneumatic to DDC controls, potential ICRA requirements, and multiple site access and logistical accommodations. Contractors must adhere to facility quiet hours (8pm-6am), comply with vaccination/mask policies, and coordinate closely with the Contracting Officer's Representative (COR) for site-specific details. The amendment includes five attachments covering technical specifications, pump details, site visit roster, and a memo on bolt requirements, with the bid due date remaining unchanged from the original solicitation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 659-25-510_Specs-Rev1_20250513.pdf | ||
| 659-25-510_RFIs-Second Set_20250407 (003).docx | DOCX document | |
| 659-25-510_DWGs-Rev1_20250513.pdf | ||
| 36C24625B0020_2 0004.docx | DOCX document | |
| 36C24625B0020_2 0003.docx | DOCX document | |
| Attachment C_1641 Submittal Sheet.pdf | ||
| Attachment A_Requirements for Identification and Replacement of A307 Bolts Memo_Signed.pdf | ||
| Attachment B_659-25-510_Specifications_20241104-Rev 1.pdf | ||
| Attachment D_Package System.pdf | ||
| Attachment E_Pre-Bid Site Visit Attendance.pdf | ||
| 36C24625B0020_2 0001.docx | DOCX document | |
| 36C24625B0020__2.docx | DOCX document | |
| 659-25-510_Specifications_20241104.docx | DOCX document | |
| 659-25-510_DWGs_20241104.pdf |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
04-18-2025
659-25-510
Department of Veterans Affairs Network Contracting Office 6 1601 Brenner Ave Salisbury NC 28144
To all Offerors/Bidders
36C24625B0020 03-19-2025
X one The purpose of this amendment is to answer the RFI questions for this solicitation.
Also to add the site visit roster from the site visit.
This amendment contains five (5) attachments labeled A through E.
The due date and time for receipt of bids remains unchanged.
Please acknowledge this and any other amendments to this solicitation by completing Block 19 and Blocks 20a-20c of the SF 1442 on your submitted offer.
The purpose of this amendment is to answer the RFI questions for this solicitation and add the site visit sign-in sheet.
1) Please confirm that and all Basis of Design items and materials that the VA has satisfied any and all Buy American Waivers, if applicable, and sole source requirements as needed. Please provide us any Buy American Act Waivers that would be provided under this contract. This is not currently in the plans, documents, or specifications.
a) This is stated in the solicitation under FAR clause 52.225-09 and 52.225-10
2) Is the new VA memorandum on bolts for steam and hot water systems applicable to this project? To our understanding A307 bolts are no longer allowed.
a) Yes, see attachment “A”.
3) Notice to Proceed (NTP): How soon after a contract award is the NTP expected to be issued?
a) Within 15 days.
4) Parking and Staging: Will there be designated parking and staging area for contractor personnel?
a) Once awarded and the contractor has submitted their mobilization plan, the COR will coordinate locations and space requirements with said contractor.
5) Please confirm the VA will be hiring the commissioning agent.
a) If a commissioning is deemed necessary, the VA will hire the commissioning agent.
6) We’re currently reviewing the documents for the Salisbury project as we’re interested in bidding, and we noticed that the specifications for the epoxy flooring were not included in the package.
a) There was an internal mix-up. The facility no longer wants epoxy flooring and wants the surface refinished. Please refer to attachment “B” for revised specs introducing section “03 35 43 Polished Concrete Finishing”.
7) Where is the new pipe shown as there are not dotted red lines?
a) Existing piping is shown and rerouting of CW pipes is refenced with dashed lines. These are also noted with call-outs.
8) Where is the detail on the chilled water pumps?
a) Please refer to attachments’ “C” and “D”. These cutsheets are good example of the facility’s request.
9) Where is the schedule showing what size and other pertinent information on the chilled water pumps for replacement?
a) These are drawings for intent. Please reference the specifications and industry standards.
10) Where is the schedule showing what size and other pertinent information on the condensate pumps for replacement?
a) These are drawings for intent. Please reference the specifications and industry standards.
11) Where is the exterior work being done? We do not see any on the plans.
a) There is no exterior work.
12) I do not see that 120 days is enough time to do this job due to lead time on pumps and other items. Please extend to 180 days.
a) An extension can be awarded after contractor has provided the VA with an approved schedule.
13) Will DDC controls be needed for the chilled water pumps or the condensate pumps?
a) We currently have pneumatic controls and need these changed to DDC. Johnson Controls is out current controls contractor for bldg. 11.
14) Confirm what work hours will be required for each area.
a) The residence of bldg. 11 quiet time from 8pm to 6am. The overall decision will be between the Contractor and project COR after a schedule has been submitted by the Contractor.
15) Please confirm whether this project is intended to be delivered under a design-build contract structure, or if this is a design-bid-build project with completed design documents. We ask because in its current state, this project is not biddable and is missing the following (not inclusive): equipment schedules, general arrangement, multiple specifications, any reference to electrical, specifics regarding demo except the comment “remove all MEP material that are not in use..” but we have no way it knowing what is and is not in use, location of sump and details, details of “temp services” during change out,
a) This is not a renovation but preventative maintenance. The chilled water and condensate pumps are being replaced, not redesigned.
b) The purpose of a per-bid site visit is to give potential bidders an opportunity to inspect current equipment (to include power being supplied to them), see what might need to be removed, and review all items listed in the SOW and drawings.
c) After award, the CO and COR will hold a meeting with the GC and their Subs to review all work listed in the GC’s proposal. The COR, GC and Subs will then walk the project and note all differing conditions.
i) A list of differing conditions (with cost associated to each line item) will be submitted to the CO for review. The CO and COR will discuss these differing conditions, and the CO will determine if a change and its cost is warranted.
16) Please confirm if tuberculosis testing is required for this project. Yes
17) Please confirm if influenza vaccines are required for all contractors and subcontractors employees who work on the site or if masks will be required. If their shots are not up to date, they will be required to wear a mask while inside a building.
18) The period of performance (POP) on this project is given to be 120 days. However, we expect the pump expect the pump lead time could be several months. We request that the POP be extended by 90 days, assuming NTP is issued before preconstruction activities.
a) The POP date can be adjusted after a schedule has been submitted to the CO and approved.
19) Does the VA anticipate any new points would be added to the BMS as part of this project?
a) Yes
20) Please provide the point of contact information for the BMS integration contractor.
a) Our current controls contractor for bldg. 11 is Jonson Controls.
21) Is any ICRA required? If so, where?
a) Yes, wherever work will expose the facility to hazardous conditions.
22) If ICRA is required, will the VA allow a Temp Wall System (i.e., Starc Wall, Edge Guard, etc) instead of a rigid wall ICRA system?
a) Yes
23) Will the VA allow the use of Zip Wall (plastic sheathing with support poles) for barriers and containment on this project?
a) Yes
24) Is any scope of work for this project required to be performed outside of regular work hours? No
a) If so, what trades or scopes will be required to be performed outside of regular work hours?
b) If so, what will the work hours and days be for scopes required to be performed outside of regular work hours?
25) Are electrical outlets available for contractors to connect to in the construction area? Yes
a) If not, where are electrical outlets available for contractors to connect to?
26) If no temp power is available, a generator will be required, which usually adds significant cost to rent and fuel. Please confirm this is necessary if no temp power is available.
a) See previous response
27) Please confirm that per specification 01 00 00, 3.5.3, Contractors are required to set a pole and meter for electric usage. Not required for this project
a) If a pole and meter are required, please provide the location of the pole and meter.
b) If a pole and meter are required, please provide the location where power can be pulled from to feed the pole and meter.
28) Where are the designated contractors' and subcontractors' parking area?
a) To be coordinated with COR during pre-work meeting.
29) Is parking available for 2-3 vehicles for the prime contractor and each subcontractor for a total of 6-9 vehicles? To be coordinated with COR during pre-work meeting.
a) Where shall these people park if the VA cannot make 2-3 spaces available for the prime contractor and each of the subs for a total of 6-9 vehicles?
30) Will the VA provide space for the Prime Contractor’s Superintendent to set up, or should we add costs to our bid for a mobile office? There is plenty of space in the building for GC to set up.
31) Where can the mobile office be located? No need for one
32) Will the VA provide space for a 20-yard dumpster? Yes, to be coordinated with COR during pre-work meeting.
33) Will the VA allow contractors to use VA indoor restrooms? There are no working restrooms is the project’s vicinity
34) If required, can Porta Johns be placed within a 100’ radius of the job site / work area? yes
35) Can utility tie-ins be performed during regular hours? yes
36) Can system commissioning activities be performed during regular hours? yes
37) Is there any work not included in the drawings or contract documents that will need to be performed under the contract? no
38) Is temporary construction fencing required anywhere on the project or at the laydown area? Plan for a chain link privacy fence at least 7’ tall. We recommend steaking the fence down. This tends to work better than sandbags.
See attached document: Attachment A_Requirements for Identification and Replacement of A307 Bolts Memo_Signed.
See attached document: Attachment B_659-25-510_Specifications_20241104-Rev 1.
See attached document: Attachment C_1641 Submittal Sheet.
See attached document: Attachment D_Package System.
See attached document: Attachment E_Pre-Bid Site Visit Attendance.