This document is an attachment to an amendment for a Request for Quote (RFQ) issued by the Department of Veterans Affairs (VA) for plumbing, heating, and air conditioning services to upgrade the pipes in the 4th MRI room at the Hunter Holmes McGuire VA Medical Center in Richmond, Virginia.
The key details are:
- The contract is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBs) with a NAICS code of 238220 (Plumbing, Heating, & Air Conditioning Contractors).
- The scope of work includes replacing the existing 2-inch heating water piping with 2.5-inch piping, installing a new air separator and high-capacity air vent, and adding new components to the in-line pump system.
- Quotes are due by 3:00PM EDT on Friday, April 26th, and the contract performance period is 30 days after the Notice to Proceed.
- Award will be based on a comparative evaluation of price and past performance, with the most advantageous offer selected.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24624Q0659 0002.docx | DOCX document | |
| 36C24624Q0659 0001_1.docx | DOCX document | |
| 36C24624Q0659_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRST FLOOR
0' - 0"
500-1Y-HWP-2
500-1Y-HWP-1
500-1Y-HE-1
500-1Y-ET-1
500-1Y-AS-1
2" HWR
2" HWS
2 1/2" HWS
2 1/2" HWR
2" HWS
2" HWS
2" HWR
2 1/2" HWS
2 1/2" HWS
2" S-15
2" S-15
1" CR-15
1" CR-15
Drawing Title Project Title VA PROJECT NUMBER
Building Number
Office of Construction
PROJECT MANAGER
FULLY SPRINKLERED
ACG Project Number
Headquarters:
MECHANICAL ROOM PIPING PLAN NEW 4TH MRI ADDITION
BID DOCUMENTS
19-088
KEY PLAN
SCALE: NO SCALE
SCALE: N.T.S.
MECH ROOM PIPING 3D VIEW
= EXISTING PIPING
= INTALLED WITH 4TH MRI PROJECT
= NEEDS TO BE INCREASED TO 2-1/2" PIPE OR
INSTALLED (AIR SEPARATOR AND EXPANSION TANK.
OR
OR
OR
TAKE-OFF - PIPE - HHW
SYSTEM SIZE LENGTH
HWR 2 1/2" 14.91'
HWR: 4 14.91'
HWS 2 1/2" 36.13'
HWS: 20 36.13'
24 51.03' sgeorge Image sgeorge Rectangle sgeorge Arrow sgeorge Callout
CONTINUATION POINT
FIRST FLOOR
0' - 0"
1 1.4 2 2.1
MECH
1Y-133
H W
R
H W
S
2" HWR
2" HWS
H W
S
H W
R
500-1Y-HWP-2
500-1Y-ET-1500-1Y-HE-1
500-1Y-HWP-1
500-1Y-AS-1
500-1Y-HWP-2
500-1Y-HWP-1
500-1Y-HE-1
500-1Y-ET-1
500-1Y-AS-1
2" HWR
2" HWS
2 1/2" HWS
2 1/2" HWR
2" HWS
2" HWS
2" HWR
2 1/2" HWS
2 1/2" HWS
2" S-15
2" S-15
1" CR-15
1" CR-15
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:3
:5
P M
MP102
MECHANICAL ROOM PIPING PLAN
5 10SMH
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 OCTOBER 7, 2020
BID DOCUMENTS
652-CSI-20419-088
SPG
0 4 8 16
NORTH
1 PROVIDE NEW PUMPS, ACCESSORIES, AND
CONTROLS COMPLETE.
2 PIPE IN INTERSTITIAL IS CONTINUED ON
MP101.
3 EXISTING HOT WATER PIPING IN INTERSTITIAL
TO REMAIN.
4 ROUTE NEW SET OF HOT WATER PIPES
THROUGH INTERSTITIAL TO MRI EXPANSION.
5 PROVIDE STEAM TO WATER HEAT EXHANGER
FOR HEATING HOT WATER. PROVIDE WITH
CONTROL VALVE AND
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
SCALE: 1/4" = 1'-0"
FIRST FLOOR HVAC PLAN - MRI SUITE
1 ASI #11 - MECH PIPING CLARIFICATION 10/17/2022
SCALE: N.T.S.
MECH ROOM PIPING 3D VIEW
F
R P
O
SS
E
OI LNA
GNE
IN
E R
E
N
SILAS PERRY GEORGE
M O
C O
M
OHL
EA T
W
I N
A
V F
I
G I
R
Lic. No. 0402056110
DocuSign Envelope ID: A2DB3DFD-49BA-4153-A413-8C96D53BB2A2
10/17/2022
1/2" STEEL PIPE OR STEEL
TUBING TO SENSOR
DIFFERENTIAL PRESSURE
TRANSMITTER (FLOW, LEVEL)
PT
BLOWDOWN
ELEVATION
NOTES:
1. INSTALLATION OF SENSORS AND TRANSMITTERS SHALL CONFORM
TO RECOMMENDATIONS OF MANUFACTURERS OF TRANSMITTERS.
2 1/2" [65mm] DIA.
ABOVE 2" [50mm] DIA. PIPE 2" [50mm] DIA. & SMALLER
HORIZONTAL
2 1/2" [65mm] DIA.
2" [50mm] DIA. & SMALLER2" [50mm] DIA. & SMALLER
VERTICAL
TYPICAL WATER
PIPING
REDUCER, IF REQUIRED
3/4" BALL
VALVE
ADAPTER TO 3/4" HOSE
THREAD. PROVIDE
HOSE CAP NUT
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS
AND/OR PLANS, LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
TYPICAL CHILLED WATER AND HOT WATER
PIPING DRAIN VALVE CONNECTIONS
ELEVATION:
THREADED PIPING
ELEVATION:
WELDED PIPING
1/4" COPPER TUBING
1/2" X 4" NIPPLE
AIR VENT
1/2" BALL VALVE
MV
OR
AV
CIRCULATING WATER
PIPING
ELEVATION
NOTES:
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
TYPICAL MANUAL AIR VENT
COIL
REDUCER IF REQUIRED
SHUTOFF VALVE
WATER RETURN
WATER SUPPLY
MODULATION CONTROL VALVE
MANUAL AIR VENT
TEST PLUG (TYP.)
UNION CONNECTIONS (TYP.)
DRAIN WITH HOSE
CONNECTION
MV
LOAD RATED
FASTENERS
BAND OF SAME
SIZE AS HANGER
STRAP
50"Ø & UNDER
HANGER RODS
BAND
OVER 50"Ø
NOTE:
TABULATED DATA FROM SMACNA
ALLOWS FOR DUCT REINFORCING AND
INSULATION, BUT NOT EXTERNAL LOAD
MAX
DUCT Ø
(IN.)
QUANTITY/SIZE (IN.) MAX LOAD
(LBS.)
MAX SPACING
(IN.)
ONE 1 x 22 GA STRAP
ONE 1 x 18 GA STRAP
ONE 1 x 16 GA STRAP
TWO 3/8 Ø RODS
TWO 1/2 Ø RODS
HANGER STRAPS OR RODS
NOM. SIZE (IN.)
PIPE (FT.)
TUBING (FT.)
5 FT
THRU 3/4
1 1 1/4
1 1/2
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR
LOW TEMPERATURE
PIPE)
PROVIDE HIGH
COMPRESSIVE
STRENGHT
INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD AT
HANGER
WELD
SADDLE
ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE
SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE
SPECIFICATIONS
1/2" DIA. HANGER RODS WITH 36"
MAX. SPACING ON EACH CHANNEL
BAND
1-5/8" 12 GAUGE CHANNEL
OR 2" x 2" x 1/4" ANGLE
NOTES:
SEE SPECIFICATIONS FOR
DETAILED HANGER
REQUIREMENTS. SIDE VIEW TRAPEZE HANGER
FOR UP TO 1000 LB. UNIFORM
LOAD
1" MAX.
PROVIDE INSULATION SHIELD &
INSERT FOR ALL PIPING (8" MIN.)
2 2 1/2 3 4 5 6 8 10 12
11 12 14 16 17 19 22 23
9 10 12 13 14 16 - -
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE
MAXIMUM PIPE/TUBING SUPPORT SPACING
3/4"
MAKE-UP WATER
BACKFLOW PREVENTER
HUMIDIFIER
(E) FLOOR DRAIN
IN UNDERFLOOR
PLENUM
3/4"
STEAM MANIFOLD
12"
4"
4"
40"
MOUNT UNIT A
MINIMUM OF 8' AFF
BOLT UNIT TO FRAME (TYP.)
UNISTRUT FRAME
DENOTES
CLEARANCES
(TYP.)
REFRIGERANT
LIQUID AND SUCTION
LINES INTO ROOM
EXTERIOR W
ALL
PRESSURE
GAGE
(TYP.)
1/2" [ 15mm ]
STRAINER
BALL OR
BUTTERFLY
(TYP.)
NOTES:
1. SUPPORT PUMP FROM PIPING OR VOLUTE. DO NOT SUPPORT PUMP FROM MOTOR.
FLEXIBLE
CONNECTIONS
(TYP.)
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:3
:5
P M
M-502
MECHANICAL DETAILS
7 10SMH
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 OCTOBER 7, 2020
BID DOCUMENTS
652-CSI-20419-088
SPG
SCALE: N.T.S.
PRESSURE TRANSMITTER INSTALLATION
SCALE: N.T.S.
INSTALLATION OF THERMOMETER WELLS
SCALE: N.T.S.
DRAIN VALVE AND AIR VENT CONNECTIONS (HYDRONIC
SYSTEMS)
SCALE: N.T.S.
TERMINAL UNIT WATER COILS - PIPING CONNECTIONS
SCALE: N.T.S.
ROUND DUCT HANGERS
UNLESS OTHERWISE STATED THE
CONTRACTOR IS RESPONSIBILE FOR ALL
DETAILS SHOWN AND ANY REQUIREMENTS
STATED THEREIN
SCALE: N.T.S.
PIPE HANGER1
SCALE: N.T.S.
HUMIDIFIER PIPING DIAGRAM
SCALE: N.T.S.
CONDENSING UNIT INSTALLATION DETAIL
1 ASI #11 - MECH PIPING CLARIFICATION 10/17/2022
SCALE: 3/8" = 1'-0"
IN-LINE PUMPS - CONNECTIONS
F
R P
O
SS
E
OI LNA
GNE
IN
E R
E
N
SILAS PERRY GEORGE
M O
C O
M
OHL
EA T
W
I N
A
V F
I
G I
R
Lic. No. 0402056110
DocuSign Envelope ID: A2DB3DFD-49BA-4153-A413-8C96D53BB2A2
10/17/2022
| photo |
| ASI 11 A_E - color sketch with takeoff |
| Sheets |
| MP102 - MECHANICAL ROOM PIPING PLAN |
| ASI_011_-_Mech_Piping_Clarification |
| Sheets |
| MP102 - MECHANICAL ROOM PIPING PLAN |
| Sheets |
| M-502 - MECHANICAL DETAILS |
File details come from the government source that posted it. Updated .