A600-ED101.pdf

PDF 18 MB Posted

Attached to
Z2DZ--Renovate And Replace Pharmacy AHUs Federal contract opportunity
Solicitation number
36C24620R0152
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6

About this file

This document provides details of a federal contract opportunity for renovation work at the Durham VA Medical Center in North Carolina. The Department of Veterans Affairs is seeking a contractor to renovate the main and satellite compounding pharmacies at the medical center, including replacing two air handling units. The work is to be completed in two phases with an estimated value between $1 million and $5 million. It is anticipated to be a set-aside for service-disabled veteran-owned small businesses. The solicitation will be issued on September 29th with proposals due approximately 30 days later. A site visit is scheduled for October 5th. Interested parties should register on the website and check for any amendments, with the point of contact being Desiree Mills-Hicks.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DZ--Renovate And Replace Pharmacy AHUs, newest first.
File Type Posted
Design Narratives-Final.pdf PDF
SOW.pdf PDF
ED102-T602.pdf PDF
A000-A500.pdf PDF
36C24620R0152_2.docx DOCX document
Specifications-Final.pdf PDF
36C24620R0152_1.docx DOCX document
36C24620R0152.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL FINISH:

PTM: PATCH TO MATCH EXISTING FINISH.

CT: CERAMIC TILE

FLOORING FINISH:

RF: RUBBER FLOORING.

RF: INTEGRAL BASE - 4".

RB: RESILIANT BASE - 4".

CPT: CARPET.

WALL FINISH:

P: PAINT

RES-W2: SPECIAL COATING - HIGH BUILD GLAZED EPOXY

COATING.

CEILING FINISH:

AT: ACOUSTICAL CEILING TILE.

GWB: GYPSUM WALL BOARD.

NOTE: GC TO PROVIDE SAMPLES FOR ALL FINAL COLOR

SELECTIONS & APPROVAL

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management

558-17-233

Durham VAMC Durham NC

REPLACE PHARMACY AHUS

RENOVATE F1204 & N1004

COMPOUNDING PHARMACIES

102 THIRD AVENUE NORTHEAST

HICKORY, NORTH CAROLINA 28601

PHONE: 828.315.9962

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CHARLOTTE | 704.295.4263

705 EAST MOREHEAD STREET, 28202

NC License No: C‐2848 AME Project No: 18104

VA FORM 08-6231

F

E

D

C

B

A

PLAN NORTH TRUE NORTH A600

DesignerChecker

FINISH INFORMATION

FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY

June 30, 2020 June 30, 2020

WALL & DOOR PROTECTION SCHEDULE

TAG DESCRIPTION COMMENTS

CG-1 CORNER GUARD STAINLESS STEEL

CG-2 CORNER GUARD STAINLESS STEEL

RWC RIGID VINYL WALL COVERING 8' HIGH SHEET

RWC1 RIGID VINYL WALL COVERING 42" HIGH SHEET

FINISH LEGEND

FLOORING FINISH SCHEDULE

ROOM BASE FINISH

LEVEL NUMBER NAME

FLOORING

CODE FLOORING TYPE FLOORING PATTERN FLOORING COLOR FLOORING SIZE ACCENT BASE CODE BASE TYPE BASE STYLE BASE COLOR

LEVEL 01 F1204 PHARMACY PTM PTM PTM PTM PTM PTM PTM PTM PTM PTM

LEVEL 01 F1204D OMNICELL/795 AREA RF Mannington Smooth Welded Rubber Sheet Flooring N/A Light Beige/Gray Taupe Continuous N/A RF Integral Flash Cove Base with Aluminum Extrusion top cap edge Match Flooring Color LEVEL 01 F1204J HAZARDOUS STORAGE RF Mannington Smooth Welded Rubber Sheet Flooring N/A Light Beige/Gray Taupe Continuous N/A RF Integral Flash Cove Base with Aluminum Extrusion top cap edge Match Flooring Color LEVEL 01 F1204K ANTE ROOM RF Mannington Smooth Welded Rubber Sheet Flooring SOLID W/ ACCENT AT DOOR Medium Grey/Taupe Continuous LIGHT GREY/TAUPE RF Integral Flash Cove Base with Aluminum Extrusion top cap edge Match Flooring Color LEVEL 01 F1204L HAZARDOUS COMPOUNDING RF Mannington Smooth Welded Rubber Sheet Flooring SOLID W/ ACCENT AT DOOR Light Beige/Gray Taupe Continuous MEDIUM GREY/TAUPE RF Integral Flash Cove Base with Aluminum Extrusion top cap edge Match Flooring Color LEVEL 01 F1204M NON HAZARDOUS COMPOUNDING RF Mannington Smooth Welded Rubber Sheet Flooring N/A Light Beige/Gray Taupe Continuous N/A RF Integral Flash Cove Base with Aluminum Extrusion top cap edge Match Flooring Color LEVEL 01 F1204N STERILE STORAGE RF Mannington Smooth Welded Rubber Sheet Flooring N/A Light Beige/Gray Taupe Continuous N/A RF Integral Flash Cove Base with Aluminum Extrusion top cap edge Match Flooring Color

LEVEL 01 F1217 LOCKER/BREAK ROOM PTM PTM PTM PTM PTM PTM PTM PTM PTM PTM

LEVEL 01 F1217B SHARED OFFICE CPT Armstrong MedIntone Homogeneous Sheet Flooring TBD Light Beige/Gray Taupe Continuous N/A RB Applied Resiliant Base TBD LEVEL 01 F1217C OFFICE CPT Armstrong MedIntone Homogeneous Sheet Flooring TBD Light Beige/Gray Taupe Continuous N/A RB Applied Resiliant Base TBD

LEVEL 01 N1002 CHEMOTHERAPY PTM PTM PTM PTM PTM PTM PTM PTM PTM PTM

LEVEL 01 N1002B WORK AREA PTM PTM PTM PTM PTM PTM PTM PTM PTM PTM

LEVEL 01 N1004 VESTIBULE RF Mannington Smooth Welded Rubber Sheet Flooring N/A Medium Grey/Taupe Continuous N/A RF Integral Flash Cove Base with Aluminum Extrusion top cap edge Match Flooring Color LEVEL 01 N1004A ANTE ROOM RF Mannington Smooth Welded Rubber Sheet Flooring SOLID W/ ACCENT AT DOOR Light Beige/Gray Taupe Continuous MEDIUM GREY/TAUPE RF Integral Flash Cove Base with Aluminum Extrusion top cap edge Match Flooring Color LEVEL 01 N1004B HAZARDOUS DRUG STORAGE RF Mannington Smooth Welded Rubber Sheet Flooring N/A Light Beige/Gray Taupe Continuous N/A RF Integral Flash Cove Base with Aluminum Extrusion top cap edge Match Flooring Color LEVEL 01 N1004C HAZARDOUS COMPOUNDING RF Mannington Smooth Welded Rubber Sheet Flooring SOLID W/ ACCENT AT DOOR Light Beige/Gray Taupe Continuous MEDIUM GREY/TAUPE RF Integral Flash Cove Base with Aluminum Extrusion top cap edge Match Flooring Color

LEVEL 01 N1006 PHYSICAL THERAPY ROOM PTM PTM PTM PTM PTM PTM PTM PTM PTM PTM

LEVEL 01 N1006A STORAGE PTM Mannington Smooth Welded Rubber Sheet Flooring N/A Light Beige/Gray Taupe Continuous N/A PTM Integral Flash Cove Base with Aluminum Extrusion top cap edge Match Flooring Color LEVEL 01 N1006B VESTIBULE PTM Mannington Smooth Welded Rubber Sheet Flooring N/A Medium Grey/Taupe Continuous N/A PTM Integral Flash Cove Base with Aluminum Extrusion top cap edge Match Flooring Color

LEVEL 01 N1008B MECHANICAL PTM PTM PTM PTM PTM PTM PTM PTM PTM PTM

WALL FINISH SCHEDULE

ROOM WALL FINISH

LEVEL NUMBER NAME

WALL FINISH

CODE WALL FINISH TYPE WALL FINISH COLOR SIZE / COMMENTS

LEVEL 01 F1217 LOCKER/BREAK ROOM PTM Paint to match existing Paint to match existing N/A LEVEL 01 F1204J HAZARDOUS STORAGE RES-W2 Paint Glazed Finish Off White Finish - Submit for approval Similar to PPG Parchment Paper or Sherwin Williams Navajo White LEVEL 01 F1217C OFFICE P Paint Eggshell Finish PPG Parchment Paper - PPG # 1095-1 LEVEL 01 F1204M NON HAZARDOUS COMPOUNDING RES-W2 Paint Glazed Finish Off White Finish - Submit for approval Similar to PPG Parchment Paper or Sherwin Williams Navajo White LEVEL 01 F1204N STERILE STORAGE RES-W2 Paint Glazed Finish Off White Finish - Submit for approval Similar to PPG Parchment Paper or Sherwin Williams Navajo White LEVEL 01 F1204K ANTE ROOM RES-W2 Paint Glazed Finish Off White Finish - Submit for approval Similar to PPG Parchment Paper or Sherwin Williams Navajo White LEVEL 01 F1204L HAZARDOUS COMPOUNDING RES-W2 Paint Glazed Finish Off White Finish - Submit for approval Similar to PPG Parchment Paper or Sherwin Williams Navajo White LEVEL 01 F1204D OMNICELL/795 AREA RES-W2 Paint Glazed Finish Off White Finish - Submit for approval Similar to PPG Parchment Paper or Sherwin Williams Navajo White LEVEL 01 N1004C HAZARDOUS COMPOUNDING RES-W2 Paint Glazed Finish Off White Finish - Submit for approval Similar to PPG Parchment Paper or Sherwin Williams Navajo White LEVEL 01 N1004A ANTE ROOM RES-W2 Paint Glazed Finish Off White Finish - Submit for approval Similar to PPG Parchment Paper or Sherwin Williams Navajo White LEVEL 01 F1217B SHARED OFFICE P Paint Eggshell Finish PPG Parchment Paper - PPG # 1095-1 N/A LEVEL 01 N1004 VESTIBULE RES-W2 Paint Glazed Finish Off White Finish - Submit for approval Similar to PPG Parchment Paper or Sherwin Williams Navajo White LEVEL 01 N1006B VESTIBULE PTM Paint to match existing Paint to match existing N/A LEVEL 01 N1006A STORAGE P Paint Eggshell Finish PPG Parchment Paper - PPG # 1095-1 N/A LEVEL 01 N1004B HAZARDOUS DRUG STORAGE RES-W2 Paint Glazed Finish Off White Finish - Submit for approval Similar to PPG Parchment Paper or Sherwin Williams Navajo White LEVEL 01 N1002B WORK AREA PTM Paint to match existing Paint to match existing N/A LEVEL 01 N1006 PHYSICAL THERAPY ROOM PTM Paint to match existing Paint to match existing N/A LEVEL 01 N1002 CHEMOTHERAPY PTM Paint to match existing Paint to match existing N/A LEVEL 01 F1204 PHARMACY PTM Paint to match existing Paint to match existing N/A LEVEL 01 N1008B MECHANICAL PTM Paint to match existing Paint to match existing N/A

CEILING FINISH SCHEDULE

ROOM GENERAL CEILING FINISH

LEVEL NUMBER NAME CEILING CODE CEILING TYPE CEILING STYLE CEILING COLOR / GRID COLOR CEILING SIZE

LEVEL 01 F1204 PHARMACY PTM PTM PTM PTM PTM

LEVEL 01 F1204D OMNICELL/795 AREA AT-1 ACT Armstrong Unperforated VL Tile White 2' X 2' LEVEL 01 F1204J HAZARDOUS STORAGE GWB RES-W2 Paint Glazed Finish White N/A LEVEL 01 F1204K ANTE ROOM GWB RES-W2 Paint Glazed Finish White N/A LEVEL 01 F1204L HAZARDOUS COMPOUNDING GWB RES-W2 Paint Glazed Finish White N/A LEVEL 01 F1204M NON HAZARDOUS COMPOUNDING GWB RES-W2 Paint Glazed Finish White N/A LEVEL 01 F1204N STERILE STORAGE GWB RES-W2 Paint Glazed Finish White N/A

LEVEL 01 F1217 LOCKER/BREAK ROOM PTM PTM PTM PTM PTM

LEVEL 01 F1217B SHARED OFFICE AT-1 ACT Armstrong Unperforated VL Tile White 2' X 2' LEVEL 01 F1217C OFFICE AT-1 ACT Armstrong Unperforated VL Tile White 2' X 2'

LEVEL 01 N1002 CHEMOTHERAPY PTM PTM PTM PTM PTM

LEVEL 01 N1002B WORK AREA PTM PTM PTM PTM PTM

LEVEL 01 N1004 VESTIBULE AT-1 ACT Armstrong Unperforated VL Tile White 2' X 2' LEVEL 01 N1004A ANTE ROOM GWB RES-W2 Paint Glazed Finish White N/A LEVEL 01 N1004B HAZARDOUS DRUG STORAGE GWB RES-W2 Paint Glazed Finish White N/A LEVEL 01 N1004C HAZARDOUS COMPOUNDING GWB RES-W2 Paint Glazed Finish White N/A

LEVEL 01 N1006 PHYSICAL THERAPY ROOM PTM PTM PTM PTM PTM

LEVEL 01 N1006A STORAGE AT-1 ACT Armstrong Unperforated VL Tile White 2' X 2' LEVEL 01 N1006B VESTIBULE AT-1 ACT Armstrong Unperforated VL Tile White 2' X 2'

LEVEL 01 N1008B MECHANICAL PTM PTM PTM PTM PTM

MILLWORK FINISH SCHEDULE

ROOM MILLWORK CABINET COUNTERTOP

LEVEL NUMBER NAME CABINET CODE CABINET TYPE CABINET MATERIAL

CABINET

COLOR CABINET SIZE/COMMENT

COUNTERTOP

TYPE

COUNTERTOP

MATERIAL

COUNTERTOP

COLOR

LEVEL 01 F1204 PHARMACY MILLWORK N/A N/A N/A COUNTERTOP ONLY Solid Surface Corian - Grade B Savannah LEVEL 01 F1217 LOCKER/BREAK ROOM MILLWORK Plastic Laminate Wilsonart Shaker Cherry # 7935K-07 Silver Wire Pulls Solid Surface Corian - Grade B Savannah LEVEL 01 N1002 CHEMOTHERAPY MILLWORK N/A N/A N/A COUNTERTOP ONLY Solid Surface Corian - Grade B Savannah

ACCEPTABLE MANUFACTURERS

SPECIFIED PRODUCT

LAVATORY

STAINLESS STEEL SINKS

CARRIERS

FAUCETS

CLEANOUTS

VALVES (SAME MANUFACTURER)

INSULATION

WATER SUPPLY BOX

ACCEPTED MANUFACTURERS

AMERICAN STANDARD, CRANE, KOHLER

ELKAY, JUST

JOSAM, SMITH, WADE, ZURN

CHICAGO, KOHLER, SPEAKMAN, T&S BRASS

JOSAM, SMITH, WADE, ZURN, MIFAB

APOLLO, CRANE, ITT GRINELL, NIBCO, MILWAUKEE

ARMSTRONG, CERTAINTEED, KNAUF, JOHNS-MANVILLE

GUY GRAY, SIOUX CHIEF

PLUMBING ABBREVIATIONS

DESCRIPTIONTYPE

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

BFF BELOW FINISH FLOOR

CI CAST IRON

FF FINISH FLOOR

FT FEET

GAL GALLON

HW HOT WATER

LAV LAVATORY

MAX MAXIMUM

MIN MINIMUM

TYP TYPICAL

WC WATER CLOSET

°F DEGREE FAHRENHEIT

GC GENERAL CONTRACTOR

PC PLUMBING CONTRACTOR

DWV DRAIN, WASTE & VENT

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

ASSE AMERICAN SOCIETY OF SAFETY ENGINEERS

ASTM AMERICAN SOCIETY FOR TESTING & MATERIALS

DIAM DIAMETER

IN INCH

SF SQUARE FEET

VTR VENT THROUGH ROOF

1. ALL PLUMBING VENTS IN EXTERIOR WALLS SHALL BE OFFSET A MINIMUM OF 3'-0"

AT ROOF BEFORE ROOF PENETRATION.

2. ALL PLUMBING VENTS SHALL BE LOCATED NO CLOSER THAN 15'-0" FROM ANY

MECHANICAL UNIT OR OUTDOOR AIR INTAKE. COORDINATE WITH MECHANICAL

CONTRACTOR.

3. ALL PLUMBING AND PLUMBING MATERIALS SHALL MEET THE REQUIREMENTS OF THE

STATE AND LOCAL PLUMBING CODES.

4. THE USE OF HORIZONTAL CLEANOUTS ON SANITARY SEWERS IS PROHIBITED. USE

FLOOR OR WALL CLEANOUT.

5. ALL WALL HYDRANTS SHALL BE MOUNTED 24" ABOVE FINISHED GRADE UNLESS

OTHERWISE SPECIFIED.

6. ALL PIPING SHALL BE ROUTED TO AVOID CONFLICTS WITH OTHER TRADES.

7. COORDINATE WITH ARCHITECTURAL WORKING DRAWINGS BEFORE ROUGHING-IN

PLUMBING FIXTURES.

8. MAKE PROPER HOT AND COLD WATER, WASTE, AND VENT ETC., PIPING

CONNECTIONS TO ALL FIXTURES AND EQUIPMENT EVEN THOUGH ALL BRANCHES,

FITTINGS AND CONNECTIONS MAY NOT BE SHOWN.

9. COORDINATE LOCATION OF ALL EQUIPMENT, FIXTURES AND PIPING WITH

STRUCTURAL AND ALL OTHER TRADES. PIPING ROUTED ABOVE CEILING SHALL BE

ROUTED AS HIGH AS POSSIBLE.

10. ALL OPENINGS IN CEILINGS AND PLENUM WALLS FOR PLUMBING PIPES SHALL BE

SEALED AIR TIGHT.

11. THE USE OF DOUBLE SANITARY "WYE" FITTINGS IS PROHIBITED. USE SINGLE

"WYE" FITTINGS ONLY.

12. ALL HOT AND COLD WATER PIPING INDICATED TO ROUTED ABOVE FINISHED

CEILINGS OR IN EXTERIOR WALLS SHALL BE INSTALLED ON THE CONDITIONED

SPACE SIDE OF THE BUILDING INSULATION.

13. SLOPES AND INVERT ELEVATIONS OF EXISTING SEWERS, ETC., SHALL BE

ESTABLISHED AND VERIFIED BY PLUMBING CONTRACTOR BEFORE ANY PIPING IS

INSTALLED IN ORDER THAT PROPER SLOPES WILL BE MAINTAINED AND NECESSARY

INVERT ELEVATIONS OBTAINED.

14. IT IS THE INTENTION OF THESE DRAWINGS TO COVER ALL WORK AND MATERIAL

FOR A COMPLETE FIRST CLASS INSTALLATION. ANY EQUIPMENT, PLUMBING

FIXTURE, TRIM HARDWARE AND/OR DEVICES USUALLY UTILIZED IN THE CLASS OF

WORK, THOUGH NOT SPECIFICALLY MENTIONED OR SHOWN ON THE DRAWINGS,

BUT WHICH MAY BE NECESSARY FOR THE SATISFACTORY COMPLETION OF THE

WORK (AS DETERMINED BY THE ARCHITECT) SHALL BE FURNISHED AND INSTALLED

BY THE CONTRACTOR AS PART OF HIS TOTAL WORK.

15. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK OR ORDERING

EQUIPMENT, PIPING, FIXTURES, ETC.

16. SEAL AROUND ALL WALL PENETRATIONS AIR TIGHT AT FIRE RATED WALLS AND FILL

ANY VOIDS APPROVED FIRESTOPPING.

17. INSTALL ALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS AND ALL APPLICABLE LISTING REQUIREMENTS. COORDINATE

BLOCKING AND NECESSARY SUPPORTS WITH THE GENERAL CONTRACTOR. PROVIDE

AND INSTALL UNLESS SPECIFICALLY ASSIGNED BY THE G.C. TO ANOTHER

CONTRACTOR.

18. ANY PIPES PENETRATING RATED WALLS, SMOKE WALLS, SMOKE BARRIERS, ETC.,

SHALL BE SEALED WITH A CODE COMPLIANT U.L. RATED ASSEMBLY THAT

MAINTAINS THE INTEGRITY AND FUNCTION OF THE WALL WHILE ACCOUNTING FOR

THE PIPE MATERIAL, SIZE AND INSULATION.

19. ALL PIPING, FITTINGS, VALVES, ETC. USED IN DOMESTIC WATER SYSTEMS SHALL

BE NSF 61 CERTIFIED.

20. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO DETERMINE FIELD

CONDITIONS AND EXTENT OF THE WORK UNDER THIS CONTRACT. LACK O

FKNOWLEDGE OF EXISTING FIELD CONDITIONS WILL NOT BE CONSIDERED A BASIS

FOR CHANGE ORDERS.

PLUMBING GENERAL NOTES

PIPE TURN UP

PIPE TURN DOWN

PIPE DROP OFF BOTTOM OF MAIN PIPE

DOMESTIC COLD WATER PIPE (CW)

DOMESTIC HOT WATER PIPE (HW)

SANITARY WASTE PIPE (S)

SANITARY VENT PIPE (V)

DESIGNATION DESCRIPTION

PLUMBING LEGENDPLUMBING FIXTURE SCHEDULE

NOTES:

1. PROVIDE WITH OFFSET TAILPIECE, CHROME TRAP AND CLEANOUT, AND CHROME SUPPLIES WITH 1/4 TURN STOPS.

2. PROVIDE WITH J-35-SSF DRAIN, JTM-47 THERMOSTATIC MIXING VALVE, JG1800 EYE WASH, AND JMXE-300 EYEWASH MIXING VALVE.

3. PROVIDE WITH ASSE CERTIFIED THERMOSTATIC MIXING VALVE MOUNTED ABOVE CEILING.

FLOOR CLEAN OUT (FCO)/GRADE CLEANOUT (GCO)

FLOOR DRAIN (FD)

FULL PORT BALL VALVE

NEW WORK

DESIGNATION DESCRIPTION

PLUMBING NEW/EXISTING LEGEND

EXISTING TO REMAIN (ETR)

EXISTING TO BE DEMOLISHED (ETBD)

BEGINNING OR END OR NEW WORK OR

CONNECTION TO EXISTING (CTE)

CW COLD WATER

S SANITARY

V VENT

ETBD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

CTE CONNECT TO EXISTING

SUSPENDED PIPE ON TRAPEZE

RESTRAIN IF ANY PIPE

ON TRAPEZE >2"

RESTRAIN IF TOTAL

WEIGHT OF PIPES ON

TRAPEZE>10LBS/FT

(SEE NOTE 2)

13.6.8.3.1

REQUIRED

(SEE NOTE 4)

(CAST IRON, PLASTIC, CERAMIC)

(STEEL, AL, CU, ETC.)

RESTRAIN IF>2"

(SEE NOTE 2)

13.6.7

RESTRAIN ALL

PIPE

EQUIPMENT

RESTRAIN IF >75LBS

PROVIDE FLEX CONN.

(SEE NOTE 1)

13.1.4.5

13.6.5

13.1.4.5

13.1.4.5

13.1.4.5RESTRAIN ALL

COMPONENT SUPPORTS

WALL MOUNTED

FLOOR MOUNTED

ROOF MOUNTED

COMPONENT IDENTIFICATION

REQUIREMENT REFERENCE

1.5

COMPONENT IMPORTANCE FACTOR (Ip)

SEISMIC DESIGN CATEGORY C

SEISMIC AND WIND REQUIREMENTS

FOR PLUMBING SYSTEMS

COMPONENT CERTIFICATION

SUSPENDED NON DUCTILE PIPING

SUSPENDED DUCTILE PIPING

NOT INLINE W/

SUSPENDED

SEISMIC RESTRAINT ASCE 7-16

PIPE

INLINE W/

13.2.2

TABLE NOTES:

1. FLEXIBLE CONNECTIONS REQUIRED FOR PIPE CONNECTIONS ONLY.

2. RESTRAINT IS NOT REQUIRED IF THE PIPING IS SUPPORTED BY HANGERS WHERE EACH HANGER IS 12 INCHES OR LESS IN

LENGTH FROM THE TOP OF THE PIPE OR DUCT TO THE SUPPORTING STRUCTURE. WHERE PIPES ARE SUPPORTED ON A TRAPEZE, THE TRAPEZE SHALL BE SUPPORTED BY HANGERS HAVING A LENGTH OF 12 INCHES OR LESS. WHERE ROD

HANGERS ARE USED, THEY SHALL BE EQUIPPED WITH SWIVELS, EYES NUTS OR OTHER DEVICES TO PREVENT BENDING IN

THE ROD.

3. ALL PIPING, REGARDLESS OF SIZE, DESIGNED TO CARRY TOXIC, HIGHLY TOXIC, OR EXPLOSIVE GASES MUST BE

RESTRAINED.

4. COMPONENT CERTIFICATION MUST BE SUPPLIED BY THE EQUIPMENT MANUFACTURER AT THE TIME OF SUBMITTAL FOR

REVIEW BY ENGINEER OF RECORD.

A. PER 2018 INTERNATIONAL BUILDING CODE, MECHANICAL EQUIPMENT AND COMPONENTS, INCLUDING THEIR SUPPORTS AND ATTACHMENTS, SHALL BE DESIGNED FOR SEISMIC FORCES IN ACCORDANCE WITH CHAPTER 13 OF ASCE 7-16.

B. EXTERIOR EQUIPMENT (INCLUDING ROOF CURBS AND ROOF RAILS) EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED

TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH CHAPTERS 26 THROUGH 29 OF ASCE 7-16.

C. WHERE DESIGN FOR SEISMIC AND WIND LOADS IS REQUIRED, THE MORE DEMANDING FORCE MUST BE USED.

D. REFERENCE THE STRUCTURAL DRAWINGS FOR SITE SPECIFIC INFORMATION ON SEISMIC DESIGN CATEGORY, WIND SPEED, ETC.

E. USE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH COMPONENT.

F. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND ATTACHMENTS SHALL BE

DESIGNED BY A REGISTERED DESIGN PROFESSIONAL.

G. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF EQUIPMENT UNDER THIS CONTRACT MUST BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT POUR ANY HOUSEKEEPING PADS PRIOR TO THE

RECEIPT OF APPROVED SEISMIC SUBMITTAL.

H. SEISMIC RESTRAINTS FOR DUCTWORK, PIPING AND CONDUIT MUST BE SHOWN ON SEISMIC SUBMITTAL LAYOUT DRAWINGS SHOWING SPECIFIC RESTRAINT LOCATIONS ALONG WITH ACCOMPANYING DETAILS AND CALCULATIONS.

INFORMATION FOR / IBC-2018 / ASCE 7-16

RISK CATEGORY IV

RESTRAIN ALL

RESTRAIN ALL

RESTRAIN ALL

RESTRAIN IF>2"

(SEE NOTE 2)

13.6.8.3.3.a

13.6.8.3.3

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management

558-17-233

Durham VAMC Durham NC

REPLACE PHARMACY AHUS

RENOVATE F1204 & N1004

COMPOUNDING PHARMACIES

102 THIRD AVENUE NORTHEAST

HICKORY, NORTH CAROLINA 28601

PHONE: 828.315.9962

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CHARLOTTE | 704.295.4263

705 EAST MOREHEAD STREET, 28202

NC License No: C-2848

AME Project No: 18104

VA FORM 08-6231

F

E

D

C

B

A

PLAN NORTH TRUE NORTH

P-001

DBWFFR

PLUMBING - GENERAL NOTES, SCHEDULES

AND LEGENDS

FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY

June 30, 2020

MARK DESCRIPTION

CONNECTION SIZES

MANUFACTURER MODEL TRIM MOUNTING NOTESWASTE VENT CW HW

P-4 PHARMACY WASH UP

SINK

2" 1-1/2" 1/2" 1/2" JUST MFG. JPH-ADA-2224-CT JUST JSL-46-AC WALL 2

P-6 INTEGRAL SINK 2" 1-1/2" 1/2" 1/2" EXISTING TO BE

RELOCATED

- NEW FAUCET: CHICAGO 116.103.AB.1 COUNTER 1

P-8 CONDENSATE DRAIN

BOX

1-1/2" 1-1/2" - - SIOUX CHIEF OX BOX 696 N/A WALL

P-9 EMERGGENCY

EYEWASH

FD - 1" 1" HAWS

CORPORATION

7360BT - FLOOR 3

FCO FLOOR CLEANOUT 2" 1-1/2" - - ZURN ZN1400-IC3 - FLOOR

DEMOLISH EXISTING

SINK COMPLETE

(ETR) (ETR)

(ETR)

(ETR)

EXISTING S RISER

EXISTING V RISER (ETR)4" S

(ETR)2" V

(ETR)

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management

558-17-233

Durham VAMC Durham NC

REPLACE PHARMACY AHUS

RENOVATE F1204 & N1004

COMPOUNDING PHARMACIES

102 THIRD AVENUE NORTHEAST

HICKORY, NORTH CAROLINA 28601

PHONE: 828.315.9962

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CHARLOTTE | 704.295.4263

705 EAST MOREHEAD STREET, 28202

NC License No: C-2848

AME Project No: 18104

VA FORM 08-6231

F

E

D

C

B

A

PLAN NORTH TRUE NORTH

PD101

DBWFFR

PLUMBING - DEMOLITION PLAN - LEVEL 01 -

F1204

FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY

June 30, 2020

1/4" = 1'-0"

PLUMBING - DEMOLITION PLAN - LEVEL 01 - F1204

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

EXISTING OXYGEN AND

MEDICAL VACUUM OUTLETS

AND ASSOCIATED SLIDE

SHALL BE DEMOLISHED.

ASSOCIATED MEDICAL GAS

PIPING SHALL BE

DEMOLISHED BACK TO MAIN

AND CAPPED. ALL AFFECTED

PIPING SHALL BE

RECERTIFIED AS PER

NFPA-99.

DEMOLISH EXISTING

EMERGENCY SHOWER/

EYEWASH COMPLETE

DEMOLISH

EXISTING WALL

HUNG SINK

COMPLETE.

EXISTING SINK AND CABINET

TO BE RELOCATED. REMOVE

EXISTING FAUCET, TRAP AND

SUPPLIES COMPLETE.

DEMOLISH MOP

SINK COMPLETE.

(ETR) S AND V STACK

(ETR)FCO

2" S(ETR)

S (ETR)

3" S(ETR)

BFF

BFF

BFF BFF

BFFBFF

B F F

B F F

BFF

2 1/2" HW

4" CW

2 1/2" HW

4" CW

(ETR)

(ETR)

(ETR)

(ETR)

1/2" HW

1/2" HW(ETBR)

(ETBR)

1 1/2" V (ETBR)

2" S(ETBR)

1/2" HW

1/2" CW (ETBR)

(ETBR)

1" CW(ETBR)

1" CW

1" HW

(ETR)

(ETR)

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management

558-17-233

Durham VAMC Durham NC

REPLACE PHARMACY AHUS

RENOVATE F1204 & N1004

COMPOUNDING PHARMACIES

102 THIRD AVENUE NORTHEAST

HICKORY, NORTH CAROLINA 28601

PHONE: 828.315.9962

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CHARLOTTE | 704.295.4263

705 EAST MOREHEAD STREET, 28202

NC License No: C-2848

AME Project No: 18104

VA FORM 08-6231

F

E

D

C

B

A

PLAN NORTH TRUE NORTH

PD102

DBWFFR

PLUMBING - DEMOLITION PLAN - LEVEL 01 -

N1004

FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY

June 30, 2020

1/4" = 1'-0"

PLUMBING - DEMOLITION PLAN - LEVEL 01 - N1004

OFFICE

F1217C

SHARED

OFFICE

F1217B

HAZARDOUS

COMPOUNDING

F1204L

HAZARDOUS

STORAGE

F1204J

ANTE

ROOM

F1204K

NON

HAZARDOUS

COMPOUNDING

F1204M

STERILE

STORAGE

F1204N

PHARMACY

F1204

OMNICELL/795

AREA

F1204D

LOCKER/BREAK

ROOM

F1217

(ETR) (ETR)

(ETR)

(ETR)

2" V2" S

P-4

(ETR)4" S

(ETR)2" V

(ETR)4" S

(ETR)2" V

SMOKE TIGHT PARTITION

RATED WALL LEGEND

1 HOUR FIRE BARRIER

2 HOUR FIRE BARRIER

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management

558-17-233

Durham VAMC Durham NC

REPLACE PHARMACY AHUS

RENOVATE F1204 & N1004

COMPOUNDING PHARMACIES

102 THIRD AVENUE NORTHEAST

HICKORY, NORTH CAROLINA 28601

PHONE: 828.315.9962

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CHARLOTTE | 704.295.4263

705 EAST MOREHEAD STREET, 28202

NC License No: C-2848

AME Project No: 18104

VA FORM 08-6231

F

E

D

C

B

A

PLAN NORTH TRUE NORTH

PL101

DBWFFR

PLUMBING - NEW WORK PLAN - LEVEL 01 -

F1204 - WASTE AND VENT PIPING

FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY

June 30, 2020

1/4" = 1'-0"

PLUMBING - NEW WORK PLAN - LEVEL 01 - F1204 - WASTE AND VENT PIPING

STORAGE

N1006A

HAZARDOUS

DRUG

STORAGE

N1004B

HAZARDOUS

COMPOUNDING

N1004C

ANTE

ROOM

N1004A

VESTIBULE

N1004

VESTIBULE

N1006B

PHYSICAL

THERAPY

ROOM

N1006

CHEMOTHERAPY

N1002

WORK

AREA

N1002B

(ETR)FCO

P-6

3" S

2" S

S

3" V

(ETR)

(ETR)

(ETR)

(ETR)

(ETR) S AND V STACK

1 1/2" V

2" S

1 1/2" V

P-4

P-9

1 1/2" V

P-8

SMOKE TIGHT PARTITION

RATED WALL LEGEND

1 HOUR FIRE BARRIER

2 HOUR FIRE BARRIER

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management

558-17-233

Durham VAMC Durham NC

REPLACE PHARMACY AHUS

RENOVATE F1204 & N1004

COMPOUNDING PHARMACIES

102 THIRD AVENUE NORTHEAST

HICKORY, NORTH CAROLINA 28601

PHONE: 828.315.9962

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CHARLOTTE | 704.295.4263

705 EAST MOREHEAD STREET, 28202

NC License No: C-2848

AME Project No: 18104

VA FORM 08-6231

F

E

D

C

B

A

PLAN NORTH TRUE NORTH

PL102

DBWFFR

PLUMBING - NEW WORK PLAN - LEVEL 01 -

N1004 - WASTE AND VENT PIPING

FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY

June 30, 2020

1/4" = 1'-0"

PLUMBING - NEW WORK PLAN - LEVEL 01 - N1004 - WASTE AND VENT PIPING

(ETR) (ETR)

(ETR)

(ETR)

P-4

HAZARDOUS

STORAGE

F1204J

OFFICE

F1217C

NON

HAZARDOUS

COMPOUNDING

F1204M

STERILE

STORAGE

F1204N

ANTE

ROOM

F1204K

HAZARDOUS

COMPOUNDING

F1204L

OMNICELL/795

AREA

F1204D

SHARED

OFFICE

F1217B

PHARMACY

F1204

1/2" HW

1/2" CW

(ETR)CW AND HW RISERS

IN CHASE TO FIXTURES

1/2"CW UP TO AHU-1204 ON

INTERSTITIAL SPACE ABOVE.

PROVIDE BACKFLOW DEVICE

EQUAL TO ZURN/WILKINS

375ST - 1/2". MOUNT ON WALL

ADJACENT TO UNIT. PROVIDE FUNNEL

DRAIN AND INDIRECT WASTE

PIPING TO FLOOR DRAIN FOR AHU.

1/2" CW

1/2" CW

1/2" HW

SMOKE TIGHT PARTITION

RATED WALL LEGEND

1 HOUR FIRE BARRIER

2 HOUR FIRE BARRIER

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management

558-17-233

Durham VAMC Durham NC

REPLACE PHARMACY AHUS

RENOVATE F1204 & N1004

COMPOUNDING PHARMACIES

102 THIRD AVENUE NORTHEAST

HICKORY, NORTH CAROLINA 28601

PHONE: 828.315.9962

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CHARLOTTE | 704.295.4263

705 EAST MOREHEAD STREET, 28202

NC License No: C-2848

AME Project No: 18104

VA FORM 08-6231

F

E

D

C

B

A

PLAN NORTH TRUE NORTH

PL201

DBWFFR

PLUMBING - NEW WORK PLAN - LEVEL 01 -

F1204 - WATER SUPPLY PIPING

FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY

June 30, 2020

1/4" = 1'-0"

PLUMBING - NEW WORK PLAN - LEVEL 01 - F1204 - WATER SUPPLY PIPING

P-6

B F F

B F F

BFF

BFF

B F F

B F F

BFF

BFF BFF

BFF

B F F

1/2" HW

1/2" CW

1/2" HW

1/2" CW

1" HW

1" CW (ETR)

(ETR)

2 1/2" HW

4" CW

(ETR)

(ETR)

B F F

HAZARDOUS

COMPOUNDING

N1004C

ANTE

ROOM

N1004A

VESTIBULE

N1004

VESTIBULE

N1006B

STORAGE

N1006A

HAZARDOUS

DRUG

STORAGE

N1004B

WORK

AREA

N1002B

PHYSICAL

THERAPY

ROOM

N1006

CHEMOTHERAPY

N1002

P-4

BFF

BFF

P-9

B F F

1" CW

1" HW

1/2" CW

1/2"CW UP TO AHU-N1004

ON ROOF. ROUTE CW UP

THROUGH ROOF CURB TO

UNIT. FINAL CONNECTION

BY MECH. CONTRACTOR.

1/2"CW UP

TO ABOVE

CEILING.

BACKFLOW DEVICE EQUAL TO

ZURN/WILKINS 375ST - 1/2"

PROVIDE FUNNEL DRAIN AND

INDIRECT WASTE PIPING TO

DRAIN BOX P-8

SMOKE TIGHT PARTITION

RATED WALL LEGEND

1 HOUR FIRE BARRIER

2 HOUR FIRE BARRIER

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management

558-17-233

Durham VAMC Durham NC

REPLACE PHARMACY AHUS

RENOVATE F1204 & N1004

COMPOUNDING PHARMACIES

102 THIRD AVENUE NORTHEAST

HICKORY, NORTH CAROLINA 28601

PHONE: 828.315.9962

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CHARLOTTE | 704.295.4263

705 EAST MOREHEAD STREET, 28202

NC License No: C-2848

AME Project No: 18104

VA FORM 08-6231

F

E

D

C

B

A

PLAN NORTH TRUE NORTH

PL202

DBWFFR

PLUMBING - NEW WORK PLAN - LEVEL 01 -

N1004 - WATER SUPPLY PIPING

FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY

June 30, 2020

1/4" = 1'-0"

PLUMBING - NEW WORK PLAN - LEVEL 01 - N1004 - WATER SUPPLY PIPING

2" V

2" S

1/2" CW

1/2" HW

P-4

1/2" CW

2" S

2" V

1/2" HW

P-8

1 1/2" V

P-6

1 1/2" V

1/2" CW

1/2" HW

2" S

(ETR)1" CW

(ETR)1" HW

(ETR)4" S

(ETR)4" V

(ETR)4" S

(ETR)3" S

FCO

P-9

2" S

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management

558-17-233

Durham VAMC Durham NC

REPLACE PHARMACY AHUS

RENOVATE F1204 & N1004

COMPOUNDING PHARMACIES

102 THIRD AVENUE NORTHEAST

HICKORY, NORTH CAROLINA 28601

PHONE: 828.315.9962

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CHARLOTTE | 704.295.4263

705 EAST MOREHEAD STREET, 28202

NC License No: C-2848

AME Project No: 18104

VA FORM 08-6231

F

E

D

C

B

A

PLAN NORTH TRUE NORTH

P-501

DBWFFR

PLUMBING - RISERS

FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY

June 30, 2020

NTS

WASTE AND VENT RISER SCHEMATIC -F1204 PHARMACY

NTS

WASTE AND VENT RISER SCHEMATIC - N1004 SATELITE PHARMACY

CLAMP MUST BE LOCATED

MAXIMUM OF 3" FROM

JOIST

PANEL POINT. IF NOT,

PROVIDE

VERTICAL ANGLE IRON

SUPPORT FRONT AND BACK

TO STRENGTHEN.

B-LINE OR EQUAL TOP

BEAM CLAMP. (USE ONLY

ON

LEVEL JOIST MEMBERS)

B-LINE B3100 OR

EQUAL CLEVIS

HANGER.

PIPE INSULATION. REFER

TO SPECIFICATIONS FOR

DETAILS.

PIPING. REFER TO

SPECIFICATIONS

FOR

DETAILS.

B-LINE B3151 OR

EQUAL SHEET METAL

INSULATION SHIELD.

NOTES:

1. PIPE HANGER SPACING SHALL BE IN ACCORDANCE WITH 2018 INTERNATIONAL

BUILDING CODE.

2. PROVIDE UNISTRUT OR ANGLE IRON BRIDGING SPANNING MULTIPLE BAR

JOISTS AS REQUIRED.

3. PRIME OR PAINT ALL HANGERS, PIPE WELDS, AND OTHER ITEMS SUBJECT

TO RUSTING.

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management

558-17-233

Durham VAMC Durham NC

REPLACE PHARMACY AHUS

RENOVATE F1204 & N1004

COMPOUNDING PHARMACIES

102 THIRD AVENUE NORTHEAST

HICKORY, NORTH CAROLINA 28601

PHONE: 828.315.9962

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CHARLOTTE | 704.295.4263

705 EAST MOREHEAD STREET, 28202

NC License No: C-2848

AME Project No: 18104

VA FORM 08-6231

F

E

D

C

B

A

PLAN NORTH TRUE NORTH

P-701

DBWFFR

PLUMBING - DETAILS

FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY

June 30, 2020

NTS

INDIVIDUAL PIPE HANGER METAL FRAMING DETAIL

PIPE TURN UP (UP)

PIPE TURN DOWN (DN)

MECHANICAL PIPING LEGEND

CONDENSATE DRAIN PIPINGCD

HEATING EFFICIENCY: SEE SCHEDULES

COOLING EFFICIENCY: SEE SCHEDULES

MECHANICAL SPACING CONDITIONING SYSTEM

BUILDING COOLING LOAD: EXISTING - NO CHANGE

BUILDING HEATING LOAD: EXISTING - NO CHANGE

EXISTING - NO CHANGE

MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT.

SUMMER WET BULB: 74.0°F

METHOD OF COMPLIANCE: PRESCRIPTIVE

CODE ENFORCEMENT JURISDICTION: VAMC

NAME OF PROJECT: DURHAM VAMC REPLACE PHARMACY AIR

HANDLER UNITS

BUILDING OCCUPANCY: I-2

OWNER/CONTACT PERSON: DEREK GROTHEER

ADDRESS: 508 FULTON STREET DURHAM, NC 27705

EXTERIOR DESIGN CONDITIONS:

WINTER DRY BULB: 17.5°F

SUMMER DRY BULB: 93.2°F

THERMAL ZONE: 4A

GROSS BUILDING AREA:

PROPOSED USE: HOSPITAL

MECHANICAL CODE SUMMARY

RELATIVE HUMIDITY: 50% R.H.

INTERIOR DESIGN CONDITIONS (PHARMACY COMPOUNDING):

WINTER DRY BULB: 64°F

SUMMER DRY BULB: 64°F

DESCRIPTION OF UNIT: MODULAR ROOFTOP & INDOOR AIR

HANDLING UNITS, LAB EXHAUST FANS

COOLING OUTPUT OF SYSTEMS: SEE SCHEDULES

HEAT OUTPUT OF SYSTEMS: SEE SCHEDULES

DESIGNATION DESCRIPTION

EXISTING TO REMAIN

(EQUIPMENT, DUCTWORK, PIPING, ETC.)

EXISTING/DEMO/NEW LEGEND

EXISTING TO BE DEMOlLISHED OR RELOCATED -

REFER TO PLAN NOTES PRIOR TO DEMOLITION

(EQUIPMENT, DUCTWORK, PIPING, ETC.)

NEW

(EQUIPMENT, DUCTWORK, PIPING, ETC.)

BEGINNING OR END OF NEW WORK -OR-

CONNECT TO EXISTING

MECHANICAL GENERAL NOTES

GENERAL ITEMS

1. GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH HVAC

DRAWING OF THIS SET. SEE EACH DRAWING FOR SPECIFIC NOTES

APPLICABLE TO THAT DRAWING.

2. OVERHEAD PIPING AND DUCTWORK IN SPACES WITHOUT HUNG CEILINGS

SHALL BE RUN AS CLOSE TO ROOF DECK AS PRACTICAL, AS CLOSE TO

PARALLEL JOISTS AS POSSIBLE AND ABOVE LIGHTING FIXTURES TO

CONCEAL PIPING.

3. OVERHEAD DUCTWORK AND PIPING IN SPACES WITH CEILINGS SHALL BE

CONCEALED UNLESS OTHERWISE NOTED.

4. COORDINATE LOCATION OF GRILLES, REGISTERS, DIFFUSERS,

THERMOSTATS AND OTHER WALL OR CEILING MOUNTED HVAC

ACCESSORIES WITH REFLECTED CEILING PLAN, LIGHTING FIXTURE

LAYOUT AND ACCESSORIES INSTALLED BY OTHER TRADES SO AS TO

PRESENT A NEAT AND ATTRACTIVE INSTALLATION THROUGHOUT THE

ENTIRE BUILDING. IT IS THE INTENT FOR GRILLES, REGISTERS AND

DIFFUSERS TO BE INSTALLED IN THE CENTER OF CEILING PANELS.

5. ARRANGE PIPING AND DUCTWORK, PARTICULARLY ABOVE CEILING AS

REQUIRED TO CLEAR STRUCTURE, DUCTS, CONDUITS, ETC. ALLOWING

SPACE FOR PIPE HANGERS, ACCESS TO VALVES, FILTERS, AND

MAINTENANCE OF EQUIPMENT.

6. EQUIPMENT WITH FILTERS SHALL BE INSTALLED SO THAT FILTERS CAN BE

EASILY REMOVED AND REPLACED.

7. COORDINATE LOCATION AND INSTALLATION OF EQUIPMENT WITH OTHER

TRADES.

8. DO NOT SCALE DRAWINGS. SEE ARCHITECTURAL DRAWINGS FOR EXACT

LOCATIONS OF DOORS, WINDOWS, ETC.

9. THERMOSTATS SHALL BE LOCATED IN THE ROOMS INDICATED. INSTALL

AT 48" ABOVE FINISH FLOOR.

10. PIPING, DUCTWORK, VENTS, ETC., EXTENDING THROUGH EXTERIOR

WALLS AND ROOF SHALL BE FLASHED AND COUNTER FLASHED IN A

WEATHERPROOF MANNER.

11. PIPING AND DUCTWORK INSULATION SHALL RUN CONTINUOUSLY

THROUGH NON-RATED FLOORS, WALLS, ROOF AND PARTITIONS, UNLESS

OTHERWISE INDICATED.

12. FLEXIBLE AIR DUCTS SHALL HAVE UL 181 LISTING, FIBERGLASS SCRIM,

R-6 INSULATION, AND MAXIMUM DISTANCE OF 6'-0".

13. NO PIPING SHALL BE SMALLER THAN 3/4" UNLESS OTHERWISE NOTED.

14. PROVIDE UNION OR FLANGED CONNECTIONS AT EACH PIECE OF

EQUIPMENT AND ON BOTH SIDES OF CONTROL VALVES AND PRESSURE

REGULATING VALVES. PROVIDE SHUT-OFF VALVES ON BOTH SIDES OF

AUTOMATIC VALVES.

15. PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH THE

SPECIFICATIONS. ADDITIONAL SUPPORTS OR HANGERS SHALL BE

ADJACENT TO ELBOWS TO PREVENT WEIGHT OF PIPING BEING PLACED

ON EQUIPMENT.

16. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE

WITH THE LATEST EDITION OF SMACNA'S "HVAC DUCT CONSTRUCTION

STANDARDS - METAL AND FLEXIBLE."

17. PROVIDE BEARING PLATES AND OTHER NECESSARY REINFORCEMENT AT

DUCTWORK SUPPORTS TO ENSURE THAT DUCT INSULATION MAINTAINS

REQUIRED "R" VALUES.

18. PROVIDE ACCESS DOORS IN DUCTWORK WHERE INDICATED OR

REQUIRED FOR ACCESS TO SYSTEM COMPONENTS INCLUDING THE

FOLLOWING:

A. DAMPER MOTORS AND/OR MOTOR OPERATED DAMPERS

B. FILTERS

C. FIRE DAMPERS AND SMOKE DAMPERS

D. SMOKE DETECTORS

19. PROVIDE A MINIMUM OF THREE TIMES THE FAN DIAMETER OF STRAIGHT

DUCTWORK OFF THE SUPPLY AIR FAN DISCHARGE BEFORE ANY TAKEOFFS

OR ELBOWS.

20. PROVIDE EXTENDED VOLUME DAMPER CONTROL RODS SO THAT HANDLES

ARE WELL CLEAR OF DUCT INSULATION.

DESIGNATION DESCRIPTION

TEST AND BALANCE NOTE

1. THE CONTRACTOR SHALL HIRE AN APPROVED TEST

AND BALANCE AGENCY TO PERFORM A FULL TEST

AND BALANCE OF THE RENOVATED AREAS AFTER

CONSTRUCTION IS COMPLETE. TEST AND BALANCE

SHALL INCLUDE (BUT NOT LIMITED TO) MODULAR AIR

HANDLING UNITS, EXHAUST FANS, VAV TERMINAL

UNITS, CHILLED WATER COILS, STEAM HEATING

COILS, STEAM HUMIDIFIERS, HEATING HOT WATER

COILS, AND EXISTING EQUIPMENT TO REMAIN.

2. THE CONTRACTOR IS RESPONSIBLE FOR TEST AND

BALANCE OF ALL SYSTEMS WITHIN THE RENOVATED

AREAS (INCLUDING EXISTING TO REMAIN

EQUIPMENT) TO ACHIEVE THE AIRFLOWS AND FLOW

RATES INDICATED ON THESE CONSTRUCTION

DOCUMENTS.

3. THESE DRAWINGS ARE BASED ON EXISTING

DOCUMENTS AND LIMITED FIELD OBSERVATIONS.

THE CONTRACTOR SHALL CONDUCT A TEST OF

EXISTING SYSTEMS PRIOR TO STARTING WORK TO

ESTABLISH AIRFLOWS FOR ALL EXISTING AIR

DISTRIBUTION DEVICES AND TO VERIFY SUFFICIENT

AIRFLOW IS AVAILABLE TO ACHIEVE THE AIRFLOWS

INDICATED ON THESE DRAWINGS. UPON

COMPLETION OF WORK, ALL AIR DISTRIBUTION

DEVICES NOT SPECIFICALLY TAGGED SHALL BE

BALANCED TO THEIR ORIGINAL AIRFLOWS. REPORT

ANY DEFICIENCIES TO THE VA COR AND ENGINEER

PRIOR TO STARTING WORK.

HOT WATER RETURN (HEATING)HWR

HOT WATER SUPPLY (HEATING)HWS

CHILLED WATER RETURNCWR

CHILLED WATER SUPPLYCWS

2-WAY CONTROL VALVE

BUTTERFLY VALVE

UNION

DIRECTION OF FLOW

FULL PORT BALL VALVE

AUTOMATIC FLOW LIMITING VALVE

AF

CHECK VALVE

Y-STRAINER

FS FLOW SWITCH

FM FLOW METER

TS TEMPERATURE SENSOR

PS PRESSURE SENSOR

RELATIVE HUMIDITYRH

RETURN AIRRA

PHASEPH

PRESSURE DROPPD

OUTDOOR AIROA

MINIMUM CIRCUIT AMPACITYMCA

MECHANICAL CONTRACTORM.C.

1000 BTU PER HOURMBH

MAXIMUMMAX

LEAVING AIR TEMPERATURELAT

FAN FILTER UNITFFU

CUBIC FEET PER MINUTECFM

BIOLOGICAL SAFETY CABINETBSC

SUPPLY AIR

NOISE CRITERIA

MAXIMUM OVER CURRENT PROTECTION

INCHES WATER GAUGE (PRESSURE)

FULL LOAD AMPS

SA

NC

MOCP

EXTERNAL STATIC PRESSURE

ALARM

AIR HANDLING UNIT

ABOVE FINISHED FLOOR

IN. WG.

FLA

ESP

AL

AHU

AFF

MECHANICAL ABBREVIATIONS

VARIABLE AIR VOLUMEVAV

SP STATIC PRESSURE

DESCRIPTIONDESIGNATION

ENTERING AIR TEMPERATUREEAT

SENSIBLESENS

EXHAUST FANEF

WET BULB TEMPERATUREWB

DRY BULB TEMPERATUREDB

ENGINEERING CONTROL CENTER (BAS)ECC

CONTROLS CONTRACTORC.C.

DIFFERENTIAL PRESSUREDP

VARIABLE FREQUENCY DRIVEVFD

TSP TOTAL STATIC PRESSURE

UNLESS NOTED OTHERWISEUNO

HORSEPOWERHP

SUPPLY AIR DUCT WITH TURNING VANES

TURNING UP/DOWN

DESIGNATION DESCRIPTION

RETURN AIR DUCT WITH TURNING VANES

TURNING UP/DOWN

MITERED 90 ELBOW WITH TURNING VANES

EXHAUST AIR DUCT WITH TURNING VANES

TURNING UP/DOWN

MECHANICAL SYMBOL LEGEND

DD

MANUAL VOLUME DAMPER WITH EXTENDED

CONTROL ROD

DUCT

CEILING MOUNTED SUPPLY DIFFUSER

CEILING MOUNTED RETURN GRILLE

CEILING MOUNTED EXHAUST GRILLE

T

TEMPERATURE SENSOR. MOUNT 4'-0" A.F.F. PER

THE ACCESSIBILITY CODE.

COMBINATION FIRE/SMOKE DAMPER, WITH 24V

ACTUATOR, VERTICAL, WITH ACCESS DOOR AND

DUCT SMOKE DETECTOR, UL 555 AND UL 555S.

F/S

FIRE DAMPER, VERTICAL, DYNAMIC TYPE WITH

BLADES OUT OF AIRSTREAM, WITH ACCESS DOOR,

UL 555.

FD

SMOKE DAMPER, VERTICAL, WITH ACCESS DOOR

AND DUCT SMOKE DETECTOR, UL 555.

SD

DUCT ACCESS DOOR LOCATION

DUCT SMOKE DETECTOR ASSEMBLY INCLUDING

SAMPLING TUBE AND SHUTDOWN RELAY.

INSTALLATION PER SECTION 907.3.1 OF THE 2018

INTERNATIONAL FIRE CODE

M

MOTORIZED CONTROL DAMPER WITH 24V

ACTUATOR

AD

COMPONENT

CERTIFICATION

ROOF MOUNTED

COMPONENT

IDENTIFICATION

TABLE NOTES:

1. FLEXIBLE CONNECTIONS REQUIRED FOR PIPE CONNECTIONS ONLY.

2. RESTRAINT IS NOT REQUIRED IF THE PIPING OR DUCTWORK IS SUPPORTED BY HANGERS WHERE EACH

HANGER IS 12 INCHES OR LESS IN LENGTH FROM THE TOP OF THE PIPE OR DUCT TO THE SUPPORTING

STRUCTURE. WHERE PIPES OR DUCTS ARE SUPPORTED ON A TRAPEZE, THE TRAPEZE SHALL BE

SUPPORTED BY HANGERS HAVING A LENGTH OF 12 INCHES OR LESS. WHERE ROD HANGERS ARE

USED, THEY SHALL BE EQUIPPED WITH SWIVELS, EYE NUTS OR OTHER DEVICES TO PREVENT BENDING

IN THE ROD.

3. ALL PIPING AND DUCTWORK, REGARDLESS OF SIZE, DESIGNED TO CARRY TOXIC, HIGHLY TOXIC, OR

EXPLOSIVE GASES OR USED FOR SMOKE CONTROL MUST BE RESTRAINED.

4. COMPONENT CERTIFICATION MUST BE SUPPLIED BY THE EQUIPMENT MANUFACTURER AT THE TIME OF

SUBMITTAL FOR REVIEW BY THE ENGINEER OF RECORD.

SEISMIC AND WIND REQUIREMENTS

FOR MECHANICAL SYSTEMS

INFORMATION FOR IBC-2018/ASCE 7-16

SEISMIC DESIGN CATEGORY: C

RISK CATEGORY: IV

FLOOR MOUNTED

WALL MOUNTED

COMPONENT SUPPORTS

NOT INLINE W/

DUCT/PIPE

INLINE W/

DUCT/PIPE

SUSPENDED

EQUIPMENT

REQUIRED

(SEE NOTE 4)

RESTRAIN ALL

SEISMIC

RESTRAINT

REQUIREMENT

1.5

RESTRAIN ALL

RESTRAIN IF > 75 LBS

PROVIDE FLEX .

CONN. (SEE NOTE 1)

13.2.2

13.1.4.5

ASCE 7-16

REFERENCE

13.1.4.5

13.1.4.5

13.6.5

13.1.4.5

13.6.7

COMPONENT IMPORTANCE

FACTOR (Ip)

SUSPENDED DUCTILE

PIPING

(STEEL, AL, CU, ETC.)

RESTRAIN IF > 2"

(SEE NOTE 2)

13.6.8.3.3.a

SUSPENDED NON-DUCTILE

PIPING (CAST IRON,

PLASTIC, CERAMIC)

RESTRAIN ALL

(SEE NOTE 2)

13.6.8.3.3

SUSPENDED PIPE

ON TRAPEZE

RESTRAIN IF ANY PIPE

ON TRAPEZE >2"

RESTRAIN IF TOTAL

WEIGHT OF PIPES ON

TRAPEZE >10 LBS/FT

(SEE NOTE 2)

13.6.8.3.1

DUCTWORK

RESTRAIN IF > 6 SQ.

FT. OR > 17 LBS/FT

(SEE NOTES 2,3)

13.6.7

MULTIPLE DUCTS ON

TRAPEZE

RESTRAIN IF TOTAL

WEIGHT OF DUCTS ON

TRAPEZE > 10 LBS/FT

(SEE NOTES 2,3)

13.6.7

1. PER 2018 INTERNATIONAL BUILDING CODE, MECHANICAL EQUIPMENT AND COMPONENTS,

INCLUDING THEIR SUPPORTS AND ATTACHMENTS, SHALL BE DESIGNED FOR SEISMIC FORCES IN

ACCORDANCE WITH CHAPTER 13 OF ASCE 7-16.

2. EXTERIOR EQUIPMENT (INCLUDING ROOF CURBS AND ROOF RAILS) EXPOSED TO WIND SHALL BE

DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH

CHAPTERS 26 THROUGH 29 OF ASCE 7-16.

3. WHERE DESIGN FOR SEISMIC AND WIND LOADS IS REQUIRED, THE MORE DEMANDING FORCE MUST

BE USED.

4. REFERENCE THE STRUCTURAL DRAWINGS FOR SITE SPECIFIC INFORMATION ON SEISMIC DESIGN

CATEGORY, WIND SPEED, ETC.

5. USE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH COMPONENT.

6. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND

ATTACHMENTS SHALL BE DESIGNED BY A REGISTERED DESIGN PROFESSIONAL.

7. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION

OF EQUIPMENT UNDER THIS CONTRACT MUST BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT

POUR ANY HOUSEKEEPING PADS PRIOR TO THE RECEIPT OF APPROVED SEISMIC SUBMITTAL.

8. SEISMIC RESTRAINTS FOR DUCTWORK, PIPING AND CONDUIT MUST BE SHOWN ON SEISMIC

SUBMITTAL LAYOUT DRAWINGS SHOWING SPECIFIC RESTRAINT LOCATIONS ALONG WITH

ACCOMPANYING DETAILS AND CALCULATIONS.

RESTRAIN ALL

RESTRAIN ALL

RESTRAIN ALL

AIR CONTROL VALVEACV

EXISTING TO BE DEMOLISHEDETBD

EXISTING TO REMAINETR

MEDIUM PRESSURE STEAM (30 PSI)MPS

MEDIUM PRESSURE STEAM (30 PSI)

CONDENSATE RETURN

MPR

VARIABLE FREQUENCY DRIVE

(VFD) NOTES

1. ALL VFD'S SHALL COMPLY WITH IEEE 519-2993. VFD

MANUFACTURER SHALL PROVIDE A DISTORTION

ANALYSIS.

2. ALL VFD'S SHALL BE LIMITED TO A MAXIMUM 60 HZ.

THE TEST AND BALANCE FIRM MAY NOT INCREASE THE

FREQUENCY ON ANY VFD ABOVE 60 HZ TO ACHIEVE

THE AIRFLOWS SHOWN ON THESE CONSTRUCTION

DOCUMENTS.

DUCT SEALING REQUIREMENTS

4.0" PRESSURE CLASSMEDIUM PRESSURE SUPPLY

DUCT PRESSURE REQUIREMENTS

PRESSURE CLASSDUCT SYSTEM

2.0" PRESSURE CLASSLOW PRESSURE SUPPLY

LOW PRESSURE RETURN

LOW PRESSURE EXHAUST

1. ALL DUCTWORK SHALL BE SEALED IN ACCORDANCE WITH

SEAL CLASS "A"

2. SEAL ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, WALL

PENETRATIONS, AND DUCT CONNECTIONS. PRESSURE SENSITIVE

TAPE SHALL NOT BE USED AS THE PRIMARY SEALANT, UNLESS IT

HAS BEEN CERTIFIED TO COMPLY WITH UL-181A OR UL181B BY AN

INDEPENDENT TESTING LABORATORY AND THE TAPE IS USED IN

ACCORDANCE WITH THAT CERTIFICATION.

3. LONGITUDINAL SEAMS ARE JOINTS ORIENTED IN THE

DIRECTION OF AIRFLOW. TRANSVERSE JOINTS ARE CONNECTIONS

OF TWO DUCT SECTIONS ORIENTED PERPENDICULAR TO AIRFLOW.

DUCT WALL PENETRATIONS ARE OPENINGS MADE BY ANY SCREW

FASTENER, PIPE, ROD, OR WIRE. SPIRAL LOCK SEAMS IN ROUND

DUCTS NEED NOT BE SEALED. ALL OTHER CONNECTIONS ARE

CONSIDERED TRANSVERSE JOINTS, INCLUDING BUT NOT LIMITED

TO SPIN-INS, TAPS AND OTHER BRANCH CONNECTIONS, ACCESS

DOORS FRAMES AND JAMBS, DUCT CONNECTIONS TO EQUIPMENT,

ETC.

2.0" PRESSURE CLASS

2.0" PRESSURE CLASS

PHASING & PRE-CONSTRUCTION NOTES

1. CONTRACTOR SHALL REVIEW THE PHASING REQUIREMENTS AND NOTES

INDICATED ON PHASING SHEET A051. SOME EXISTING AREAS SHALL

REMAIN OCCUPIED MONDAY-SUNDAY. COORDINATE PHASING,

DEMOLITION, NEW WORK, AND ANY SHUT-DOWN OF EXISTING SYSTEMS

WITH THE VA COR.

2. PRIOR TO BIDDING, THE CONTRACTOR SHALL CONDUCT A THOROUGH

SURVEY OF EXISTING CONDITIONS. DISCREPANCIES BETWEEN THE

CONTRACT DOCUMENTS AND EXISTING CONDITIONS SHALL BE BROUGHT

TO THE ATTENTION OF THE VA COR, ARCHITECT, AND ENGINEER AT

LEAST ONE WEEK PRIOR TO THE BID DATE. SUBMISSION OF A BID

INDICATES THE CONTRACTOR IS FAMILIAR WITH EXISTING CONDITIONS

AND HAS INCLUDED IN HIS BID ALL WORK NECESSARY TO INSTALL THIS

PROJECT.

3. PRIOR TO BIDDING, THE CONTRACTOR SHALL CAREFULLY EXAMINE AND

FAMILIARIZE HIMSELF WITH THE PHASING REQUIREMENTS, EXISTING

CONDITIONS, AND NEW WORK SHOWN ON THE CONSTRUCTION

DOCUMENTS. SUBMISSION OF A PROPOSAL SHALL BE CONSIDERED AS

EVIDENCE THAT SUCH A REVIEW AND EXAMINATION HAS BEEN

PERFORMED.

4. THE CONTRACTOR SHALL PROVIDE TEMPORARY HEATING & COOLING AS

REQUIRED TO ALLOW THE AREAS INDICATED ON PHASING SHEET A051

TO REMAIN OCCUPIED DURING CONSTRUCTION. PORTABLE HVAC UNITS

SHALL BE PROVIDED AS REQUIRED. THE CONTRACTOR HAS THE OPTION

OF TYING PORTABLE HVAC UNITS INTO EXISTING SYSTEMS DURING

CONSTRUCTION.

5. THE CONTRACTOR SHALL INCLUDE IN HIS BID ALL WORK NEEDING TO BE

DONE AFTER HOURS OR ON WEEKENDS, ANY WORK REQUIRING

SHUTDOWNS, ANY WORK THAT MAY REQUIRE OVERTIME, AND ANY NEED

FOR TEMPORARY HEATING & COOLING. LATER CLAIMS FOR EXTRA

LABOR OR MATERIALS REQUIRED DUE TO DIFFICULTIES ENCOUNTERED

WILL NOT BE RECOGNIZED.

6. THE SPACE ABOVE CEILINGS IS VERY CONGESTED WITH EXISTING

MECHANICAL EQUIPMENT, DUCTWORK, MECHANICAL PIPING, PLUMBING

PIPING, SPRINKLER PIPING, ELECTRICAL CONDUIT, LIGHTS, CABLE

TRAYS, LOOSE CABLES, ABANDONED ITEMS, ETC. INSTALLATION OF

NEW EQUIPMENT, DUCTWORK, AND PIPING WILL BE CHALLENGING. THE

CONTRACTOR SHALL RELOCATE, RE-SIZE, AND/OR RE-ROUTE

EQUIPMENT, DUCTWORK, AND PIPING (INCLUDING EXISTING TO

REMAIN) AS REQUIRED FOR THE NEW WORK AND TO MAINTAIN THE

ARCHITECT'S CEILING HEIGHTS.

7. ANY AIR INTAKES ADJACENT TO WORK AREAS SHALL BE FILTERED FROM

DUST AND DEBRIS WITH MINIMUM MERV 13 FILTRATION.

8. ALL PHASES SHALL BE KEPT UNDER NEGATIVE PRESSURE AND

EXHAUSTED DIRECTLY OUTDOORS.

TB TERMINAL BOX

DOMESTIC COLD WATER FOR

MECHANICAL EQUIPMENT

(INSTALLED BY P.C.)

DCW

MECHANICAL DOMESTIC COLD WATER

FOR MECHANICAL EQUIPMENT

(INSTALLED BY M.C.)

MDCW

ELECTRICAL CONTRACTORE.C.

EXISTING TO BE RELOCATEDETBR

COORDINATION DRAWINGS

1. A MEETING SHALL BE ARRANGED BY THE CONTRACTOR AND TAKE PLACE PRIOR TO STARTING THE

COORDINATION DRAWINGS. THIS MEETING SHALL INCLUDE AT A MINIMUM THE CONTRACTOR AND THE VA SUCH THAT WE CAN CONFIRM THE REQUIREMENTS OF THE COORDINATION DRAWINGS PRIOR TO

THEM BEING SUBMITTED.

2. THE CONTRACTOR SHALL COORDINATE WITH OTHER TRADES SO THAT THE FOLLOWING LISTS OF ITEMS CAN BE INDICATED ON A COMMON SET OF PLANS. FLOOR PLANS AND SECTIONS ARE TO BE DRAWN TO

SCALE IN ALL CONGESTED AREAS (SUCH AS CORRIDORS, CHASES, AND EQUIPMENT ROOMS) AND

SPECIFIC AREAS NOTED IN THESE DOCUMENTS. THESE SHALL BE SUBMITTED COLLECTIVELY FROM ALL DISCIPLINES INTO ONE OVERALL DOCUMENT FOR REVIEW BY THE ENGINEER ON AN AS NEEDED BASIS

OR WHERE SPECIFICALLY DIRECTED WITHIN THE CONTRACT DOCUMENTS. THESE COORDINATION

DRAWINGS SHALL BE SUBMITTED FOR REVIEW PRIOR TO ANY OTHER INDIVIDUAL PRODUCT DATA OR

FABRICATION DRAWINGS. SHOW THE FOLLOWING AT A MINIMUM:

• CEILING.

• FLOOR.

• ROOF OR FLOOR DECKING ABOVE.

• STRUCTURAL ELEMENTS.

• LIGHT FIXTURES.

• LARGE ELECTRICAL OR TELECOM CONDUITS AND/OR PULL BOXES.

• HVAC DUCTWORK.

• HVAC EQUIPMENT ABOVE CEILING, INDICATING SERVICE CLEARANCES.

• HVAC PIPING.

• PLUMBING PIPING.

• SPRINKLER PIPING.

• MOUNTING RACKS AND SUPPORT ASSEMBLIES FOR ASSOCIATED PIPING/DUCTWORK.

3. IT IS IMPORTANT TO NOTE THAT DUCTWORK/PIPING/CABLE TRAY, ETC. CANNOT BE FABRICATED UNTIL THE COORDINATION DRAWINGS HAVE BEEN COMPILED, SUBMITTED, AND APPROVED. ANY MATERIAL

PROCUREMENT OR INSTALLATION WORK COMMENCED PRIOR TO APPROVAL IS TAKEN AT THE RISK OF

THE CONTRACTOR AND MAY HAVE TO BE MODIFIED/MOVED AT THEIR COST.

REMOTE OPERATED MANUAL VOLUME DAMPER

WITH MINI CEILING CABLE TERMINATION - REFER

TO DETAILDUCT

AEROSOL INJECTION PORT ASSEMBLY WITH 3/4"

FLEXIBLE TUBING TO DUCT CONNECTION PLATE

LOCATED IMMEDIATELY DOWNSTREAM OF REMOTE

OPERATED DAMPER

H

ZONE HUMIDITY SENSOR. MOUNT 4'-0" A.F.F.

PER THE ACCESSIBILITY CODE.

EXHAUST AIREA

LOUVERLVR

LOW PRESSURE STEAM (10 PSI)

FOR STEAM-TO-STEAM HUMIDIFIERS

LPS

LOW PRESSURE STEAM (10 PSI)

FOR STEAM-TO-STEAM HUMIDIFIERS

LPR

PM

PRESSURE MONITOR. MOUNT 4'-0" A.F.F. PER

THE ACCESSIBILITY CODE.

CONTRACTING OFFICER'S REPRESENTATIVECOR

P -OR-

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: PRIME CONTRACTOR: Office of Construction and Facilities Management

558-17-233

Durham VAMC Durham NC

REPLACE PHARMACY AHUS

RENOVATE F1204 & N1004

COMPOUNDING PHARMACIES

102 THIRD AVENUE NORTHEAST

HICKORY, NORTH CAROLINA 28601

PHONE: 828.315.9962

NC ENGINEERING LICENSE NO: P-0214

NC ARCHITECTURE LICENSE NO: 51254

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CHARLOTTE | 704.295.4263

705 EAST MOREHEAD STREET, 28202

NC License No: C-2848

AME Project No: 18104

VA FORM 08-6231

F

E

D

C

B

A

M-001

WEBFFR

MECHANICAL - GENERAL NOTES AND LEGENDS

FINAL CONSTRUCTION DOCUMENTS - FOR BIDDING PURPOSES ONLY

June 30, 2020

32x20

/1 x

30x16

16x14

8ø ø ø ø ø

/2 x

18x12

ETR

VAV-30-2-10

ETR

VAV-30-2-12

ETR

30-2-14

ETBR

30-2-10

24x10 x x

ETBR

VAV-30-2-16

ETBD

VAV-30-2-11

7 7

7 7

18x1215x1212x10

12x10 x

ETR

325 CFM

ETR

325 CFM

ETR

325 CFM

/1

33/16

/1

INVESTIGATIONAL

PHARMACIST

F1204

ONCOLOGY

DRUG PREP

F1204D

STORAGE

F1204F

V ADD

F1204A

HSK

F1204B

TOILET

F1204C

CHIEF

F1215

H W

S

H W

R

H W

S

H W

R

H W

S

H W

R

2 1/2" HWS

1 1/2" HWR10

/4

H

W R

/4

H

W S

/4

H

W S

/4

H

W R

/4

H

W R

/4

H

W S

ETR

EXHAUST

LOUVER

x

70x30 x x

ETBD

EF-54

x

8ø

8ø

/2 x x

34x20 x

34x20

4" CWR

4" CWS

6" CWR

ETR

RELIEF

AIR

FAN

36/18

44x30

2" MPS 2 1/2" MPS 3" MPS

2" MPR2" MPR

C W

S

C W

R

2" MPS

/2

M P R

1 1/2" MPR

2" MPS

INTERSTITIAL

MECHANICAL

SPACE

F2121

INTERSTITIAL

MECHANICAL

SPACE

F2121

SMOKE TIGHT…

This is the start of the file's text. The full file is on GovTribe.