36C24619B0023-0003003.pdf
PDF 653 KB Posted
- Attached to
- Relocate Agent Cashier B-137A Project 590-18-201
- Solicitation number
- 36C24619B0023
About this file
36C24619B0023 0003 Revised Drawings.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24619B0023-0004000.docx | DOCX document | |
| 36C24619B0023-0003000.docx | DOCX document | |
| 36C24619B0023-0003002.pdf | ||
| 36C24619B0023-0003001.pdf | ||
| 36C24619B0023-0002000.docx | DOCX document | |
| 36C24619B0023-0001000.docx | DOCX document | |
| 36C24619B0023-006.pdf | ||
| 36C24619B0023-005.pdf | ||
| 36C24619B0023-004.docx | DOCX document | |
| 36C24619B0023-003.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
348 SF
MENTAL HEALTH
PATIENT TRAVEL
A11B
163 SF
AGENT CASHIER
A11
59 SF
CORRIDOR
A11A
AE1011.1
AE101 1.2
17' - 0" +/- 6' - 2"
A11
/2
A11B
M351 M352_1
M352_1
M352_1
M352_1
M351
2 3
758 SF
WAITING AREA
A11C
4' - 5" 1' - 3"
PASS THRU
BOX
EXISTING
GWB
SOFFIT 8' - 0"
8' - 0"
8' - 0"
A11B
A11 A11A
REPAIRED
CEILING
REPAIRED CEILING
MENTAL HEALTH
PATIENT TRAVEL
A11B
AGENT CASHIER
A11
CORRIDOR
A11A
CWS
CWS
SB
SB
CWS
AE1011.1
AE101 1.2
CP
DPH
DPH
DPH
PTB
PRT
SAFE
FAX PRT
FAX
Level 1 0"
PASS THRU
BOX
COILING
COUNTER DOOR
COILING
COUNTER DOOR
Level 1 0"
TRAVEL CASHIER
EXISTING GWB SOFFIT
EXISTING
WINDOW
REINSTALL
EXISTING
WINDOW
REINSTALL
EXISTING
COUNTERTOP
BOSCH 360
SECURITY
CAMERA
UL 752 LEVEL 3
BULLET PROOF
TELLER WINDOW
VINYL BASE
BULLET RESISTANT
GLAZING
TYP
TYP
TYP
TYP
D-A11
D-A13
D-CA1
DEMOLITION NOTES AND REMARKS
1.ICRA TEMPORARY, 1 HOUR RATED, FULL HEIGHT PARTITION. DEMOLISH AFTER THE COMPLITION OF
NEW WORK.
2. REMOVE WALL ONLY AS INDICATED ON PLAN.
3.REMOVE FINISHES AND FLOORING ONLY AS REQUIRED TO ACCOMODATE NEW WORK.
4. REMOVE COMPLETE CEILING AND CEILING SYSTEM INCLUDING BUT NOT LIMITED TO TILES, GRIDS, AND SUPPORTS.
5.REMOVE EXISTING WINDOW AND FRAME IN ITS ENTIRETY. STORE AND PROTECT FOR REUSE.
6.REMOVE EXISTING WINDOW AND ITS FRAME IN ITS ENTIRETY AND STORE @ DIRECTION OF COR.
7.REMOVE EXISTING SYSTEM FURNITURE PARTITIONS AND STORE @ DIRECTION OF COR.
8.REMOVE EXISTING COUNTERTOP. STORE AND PROTECT FOR REUSE.
9. REMOVE CEILING AS REQUIRED TO PLACE FULL HEIGHT ICRA TEMPORARY PARTITION.
10.REMOVE FLOORING TO REPLACE WITH NEW FLOORING.
(DOOR A11)
F
1 HR RATED FLUSH
SOLID CORE WOOD
S C
H E
D U
L E
D H
E
IG
H T
SCHEDULED WIDTH
1 HR
RATED
DOOR
(DOOR A11A)
FNV
FLUSH VISION
SOLID CORE WOOD
1' - 10" 7"
S C
H E
D U
L E
D H
E
IG
H T
SCHEDULED WIDTH
1/4"
TEMPERED
GLASS
LEVEL3
UL 752
RATED
DOOR
KEY PLAN
AREA OF SCOPE
EXISTING
COUNTERTOP
MOUNTED TO
PLYWOOD
BASE AS
SCHEDULED
FINISH FLOOR AS
SCHEDULED
RATED GWB AS
SCHEDULED
F O
R C
O U
N T
E R
T O
P H
E
IG
H T
S E
E
E
L E
V A
T
IO
N
RATED GWB AS
SCHEDULED
7/16'' THICK BULLET
RESISTANT FIBERGLASS
WALL PANEL
3 5/8'' 16 GAUGE
METAL STUD @ 16''
O.C.
MINERAL WOOL
INSULATION
CEILING AS
SCHEDULED
CONT. FIRE RESISTANT
SPRAY SEAL, BOTH
SIDES, TYP.
METAL STRAP
@ 24'' O.C.
EXISTING
GWB SOFFIT
SEE CEILING PLAN
EXISTING DECK
REINSTALL
EXISTING
STEEL ANGLE
PLYWOOD
7/16'' THICK BULLET
RESISTANT FIBERGLASS
WALL PANEL
RATED GWB AS
SCHEDULED
INSULATION
PER WALL TYPE
BOX HEADER
CAULK @ BOTH
SIDES
PTD HOLLOW METAL
FRAME
1/2"
SEE WALL TYPE
CEILING LEGEND
RETURN AIR DIFFUSER
LINEAR SUPPLY AIR DIFFUSER
2 X 4 INDIRECT LED LIGHT FIXTURE
RECESSED CEILING LIGHT
EXIT SIGN
EXHAUST AIR DIFFUSER
SECURITY CAMERAS
VINYL COVE CAP
WALL AS
SCHEDULED
SHEET VINYL BASE
AS SCHEDULED
RUBBER FILLET
STRIP
FLOORING AS
SCHEDULED
FINISH FLOOR
E X
IS
T
IN
G
H E
IG
H
T
M A
T C
H W
IT
H
CAULK
GENERAL FINISH NOTES
• PROVIDE ONE-PIECE VINYL TRANSITION STRIP AT ALL FLOOR FINISH TRANSITIONS. COLOR SHALL MATCH ADJAENT RUBBER BASE.
• ALL FLOOR FINISH TRANSITIONS SHALL BE CONCEALED BY A CLOSED DOOR.
• ALL FINISHES LISTED ARE NEW UNLESS SPECIFIALLY NOTED AS EXISTING.
• WALL BASE SHALL BE RESILIENT, MATCHING EXISTING BASE.
• WHERE PAINTED GWB ARE INDICATED, PAINTING INCLUDES ALL PREVIOUSLY PAINTED SURFACES AND TRIM.
• ALL WALLS TO BE PAINTED PNT #1, WHISKERS, UNLESS OTHERWISE NOTED. SEE FINISH COLORS FOR INFORMATION.
• ALL TRIM TO BE PAINTED PNT#2, SEMI-GLOSS, UNLESS OTHERWISE NOTED. SEE FINISH COLORS FOR INFORMATION.
• ALL EPOXY BASE HEIGHT SHALL MATCH TO EXISTING BASE HEIGHT UNLESS OTHERWISE NOTED.
FINISH REMARKS
1. ACCENT PAINT [PNT#2] THIS WALL. SEE
FINISH COLOR FOR MORE INFORMATION.
2. CORNER GUARD THIS CORNER. SEE NEW
WORK NOTES FOR MORE DETAILS.
3. NEW FLOORING. SEE FINISH COLORS AND
SCHEDULE FOR MORE INFORMATION.
FINISH COLORS
FLOOR
LVT#1 MOHAWK - ANTIEK 131 BISQUE
BASE
SV#1 JOHNSONITE - 121 CEMENT
WALL AND CEILING
PNT#1 (FIELD) PPG1025 - 3 WHISKERS
PNT#2 (ACCENT) PPG1158 - 4 SERENA SEA
ACT#1 (WHITE) 24" X 24" TILE
EXISTING
COUNTERTOP
MOUNTED TO
PLYWOOD
REINSTALL
EXISTING STEEL
ANGLE
PLYWOOD
7/16'' THICK BULLET
RESISTANT
FIBERGLASS WALL
PANEL
RATED GWB AS
SCHEDULED
HAT CHANNELS
@16'' O.C.
A Se rv ic e D i s a b l e d Vet e r an Owned
S m a l l B u s iness
SDVOSB
CVE
B
A
C
D
E
F www.pfa-architect.com
ARCHITECTURE, PLANNING, INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510
Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO:
B
A
C
D
E
F
NO. DESCRIPTION DATE
FULLY SPRINKLERED
Department of
Veterans Affairs
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
PFA Project #:
C U s e rs
\m tu rn ip s e e d
\D o c u m e n ts
\2
V
A M
C H a m p to n C a s h ie r R e n o v a ti o n m tu rn ip s e e d
.r v t
/2
/2
:2
:5
P
M
MATJG
AE101
PLANS, ELEVATIONS, DETAILS, WALL
SECTION, AND SCHEDULES
590-18-201RELOCATE AGENT
CASHIER BLDG. 137A
260218
BID DOCUMENTS
03-28-2019
HAMPTON VAMC, HAMPTON, VA
137A
03-28-2019
GENERAL NEW WORK NOTES
NEW WORK NOTES
WALL TYPE SCHEDULE
TYPE STC DESCRIPTION
FIRE
RATING UL REMARKS
M351 51 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES AND 3" MINERAL WOOL INSULALTION. EXTEND WALL
ASSEMBLY TO UNDERSIDE OF DECK ABOVE
N/A NA PROVIDE SOUND INSULATION WHERE COMPONENTS MEET DECK ABOVE. PROVIDE ACOUSTICAL SEALANT AT
RUNNER AND HEAD PRIOR TO INSULATION OF GWB. PROVIDE ACOUSTICAL SEALANT AT ALL WALL
PENETRATIONS.
M352_1 N/A 3 5/8" 16 GAUGE METAL STUDS AT 16" O.C. MAX. 5/8" FIRE RATED GWB BOTH SIDES AND 3'' MINERAL WOOL INSULATION..REINFORCE METAL STUDS SLAB TO SLAB WITH BULLET RESISTANT FIBERGLASS WALL PANEL THAT SHALL BE SOLIDLY AND PERMANENTLY ATTACHED TO THE FLOOR SLAB AND THE CEILING SLAB.
1 HR 752 PROVIDE 3" STENCILED WITH 3/8" STROKE TEXT EVERY 8' O.C. READING "1 HR FIRE RATED BARRIER" AS REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS MEET DECK ABOVE. PROVIDE
SEALANT AT RUNNER AND HEAD PRIOR TO INSTALLATION OF GWB
-ROOM LEGEND-
NUMBER NAME
A11 AGENT CASHIER
A11A CORRIDOR
A11B MENTAL HEALTH PATIENT TRAVEL
A11C WAITING AREA
• CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR FOR A RESOLUTION. ADJUSTMENTS
TO DIMENSIONS AND CONDITIONS SHOWN MAY BE REQUIRED.
• ALL DIMENSIONS ARE REFERENCED FROM FACE OF STUD AT NEW CONSTRUCTION UNLESS OTHERWISE NOTED.
DIMENSIONS ARE REFERENCED FROM FACE OF FINISH AT EXISTING CONSTRUCTION.
• ALL DIMENSIONS INDICATED +/- ARE APPROXIMATE AND MUST BE FIELD VERIFIED PRIOR TO THE START OF
CONSTRUCTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL ACCESSORIES, PARTS AND/OR
SERVICES TO BE READY FOR ITS INTENDED USE.
• WHERE WORK ABUTS OR ADJOINS EXISTING SURFACES WHICH WILL REMAIN EXPOSED, ALIGN NEW WORK FLUSH
WITH EXISTING ADJACENT SURFACES.
• THE CONTRACTOR SHALL MAINTAIN THE EXISTING BUILDING IN A WATER TIGHT CONDITION THROUGHOUT THE ENTIRE CONSTRUCTION PERIOD. REPAIR DAMAGE CAUSED BY CONSTRUCTION OPERATIONS. TAKE ALL PRECAUTIONS NECESSARY TO PROTECT THE BUILDING AND ITS OCCUPANTS DURING THE CONSTRUCTION PERIOD.
• CONTRACTOR SHALL PROVIDE TEMPORARY BARRIERS, ICRA WALLS TO PREVENT ENTRY TO THE CONSTRUCTION
AREA. BARRIERS SHALL NOT INTERFERE WITH THE OWNERS USE OF THE SITE.
• THE CONTRACTOR SHALL PROVIDE ICRA WALLS CONSTRUCTED IN SUCH A MANNER TO MAINTAIN CONSTANT NEGATIVE PRESSURE IN THE AREA OF RENOVATION TO PREVENT THE SPREAD OF DUST TO OCCUPIED AREAS OF THE
BUILDING.
• CONTRACTOR SHALL PROVIDE ICRA WALL LAYOUT AND CONSTRUCTION DETAILS TO COR FOR APPROVAL.
• APPROVED ICRA WALLS SHALL BE INSTALLED TO APPROVED LAYOUT PRIOR TO THE START OF DEMOLITION.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS ONLY UNLESS OTHERWISE NOTED.
• ALL DOORS TO BE MOUNTED 4" FROM FACE OF FINISH UON.
• ALL DEMOLITION AND WORK THAT CAUSES EXCESSIVE DUST SHALL BE COMPLETED BETWEEN 5PM AND 6AM OR
WEEKEND AS APPROVED BY COR.
1 PROVIDE NEW GWB AND METAL STUD FURRING TO MATCH EXISTING.
2 ALIGN NEW GWB OF NEW WALL WITH EXISTING GWB OF EXISTING WALL.
3 ICRA TEMPORARY, 1 HR RATED, FULL HEIGHT PARTITION. DEMOLITION AFTER THE COMPLETION OF NEW WORK.
4 REINSTALL EXISTING WINDOW AND MATCH THE INSTALLATION WITH THE EXISTING WINDOW.
5 REINSTALL EXISTING COUNTERTOP AS INDICATED.
1/4" = 1'-0"
NEW WORK PLAN - FIRST FLOOR
1/4" = 1'-0"
CEILING PLAN - FIRST FLOOR
1/4" = 1'-0"
EQUIPMENT PLAN - FIRST FLOOR
EQUIPMENT SCHEDULE
NAMEMARK
NOTE: ALL EQUIPMENT PROVIDE BY OWNER.
VAFCI VAFOI CFCI COMMENTS
CP COPIER PROVIDE POWER AND DATA
CWS COMPUTER WORK STATION PROVIDE POWER AND DATA
DPH DESK PHONE PROVIDE POWER AND DATA
FAX FAX PROVIDE POWER AND DATA
PRT PRINTER PROVIDE POWER AND DATA
PTB PASS THROUGH BOX (LEVEL 3 BALLISTIC & 1 HR RTD.) 16''x15'' WALL OPENING
SAFE SAFETY BOX
SB SHRED BOX PROVIDE POWER
3/8" = 1'-0"AE101
1.1 ELEVATION 1
3/8" = 1'-0"AE101
1.2 ELEVATION 2
1/4" = 1'-0"
DEMOLITION PLAN - FIRST FLOOR
DEMOLITION SCHEDULE
*** ALL FINISHES LISTED IN SCHEDULE ARE TO BE REMOVED
COMPLETELY UNLESS OTHERWISE NOTED ***
NUMBER FLOOR BASE WALL CEILING REMARKS
D-A11 CPT RB PTD GWB ACT 2,3,4,5,6,7
D-A13 CPT RB PTD GWB ACT 1,8,9,10
D-CA1 SV RB PTD GWB ACT 1,9
3/8" = 1'-0"
DOOR TYPES
DOOR SCHEDULE
NUMBER
DOOR FRAME
FIRE
RATING HARDWARE REMARKSTYPE WIDTH
CLEAR
OPENING HEIGHT THICKNESS TYPE HEAD JAMB SILL
A11 F 3' - 0" 7' - 0" 1 3/4" 5/AE101 5/AE101 1 HR SH-3H
A11B FNV 3' - 0" 7' - 0" 1 3/4" 5/AE101 5/AE101 - 4G
1" = 1'-0"
CASHIER WALL SECTION - TYP.
1 1/2" = 1'-0"
5 HEAD / JAMB DETAIL
1 PROVIDE INTEGRATED CEILING SYSTEM AS SPECIFIED.
2 PROVIDE 1 1/2" CEILING EXPANSION JOINT, ADJACENT TO WALL.
3 ALIGN WALL WITH EDGE OF ADJACENT.
4 PROVIDE 1 1/2" CEILING EXPANSION JOINT.
5 REWORK EXISTING CEILING AS REQUIRED TO INSTALL NEW
WORK CEILING TO MATCH EXISTING.
GENERAL CEILING NOTES
- FINISH SCHEDULE -
NUMBER ROOM NAME
FLOOR BASE WALL CEILING
REMARKSMTL COLOR MTL COLOR MTL COLOR MTL COLOR HEIGHT
A11 AGENT CASHIER VINYL LVT#1 VINYL SV#1 PTD GWB PNT#1, PNT#2 ACT ACT#1 1,3
A11A CORRIDOR VINYL LVT#1 VINYL SV#1 PTD GWB PNT#1 ACT ACT#1 3
A11B MENTAL HEALTH PATIENT TRAVEL VINYL LVT#1 VINYL SV#1 PTD GWB PNT#1, PNT#2 ACT ACT#1 1,3
A11C WAITING AREA VINYL LVT#1 VINYL SV#1 PTD GWB PNT#1, PNT#2 ACT, GWB ACT#1 1,2,3
3" = 1'-0"
COVE BASE DETAIL
• DEMOLITION DRAWINGS INDICATE IN GENERAL, THE EXTENT OF DEMOLITION. REMOVE ALL ASSOCIATED APPURTENANCES NOT REQUIRED IN THE NEW WORK, ALL ABANDONED ITEMS, AND ALL ITEMS REQUIRED FOR THE INSTALLATION OF NEW WORK, TO PROVIDE FOR A COMPLETE PROJECT. ITEMS NOT SPECIFICALLY INDICATED THAT ARE QUESTIONABLE FOR
REMOVAL SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR A DECISION.
• THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO THE START OF
CONSTRUCTION.
• THE CONTRACTOR SHALL PATCH ALL EXISTING SURFACES TO MATCH EXISTING WHERE AFFECTED BY CONSTRUCTION OPERATIONS, INCLUDING BUT NOT LIMITED TO PLUMBING, MECHANICAL AND ELECTRICAL WORK.
• THE CONTRACTOR SHALL PATCH NAIL HOLES, ETC, AND REMOVE MISCELLANEOUS APPURTENANCES ON EXISTING WALLS
TO BE PAINTED OR COVERED WITH WALL COVERING.
• ALL EXISTING FLOORING MATERIALS WHICH ARE TO REMAIN IN PLACE SHALL BE COMPLETELY CLEANED AND STRIPPED OF
WAX IN ORDER TO RECEIVE NEW FINISHES.
• ALL NEW WORK SHALL ALIGN WITH EXISTING WHERE THEY INTERSECT UNLESS OTHERWISE NOTED.
• THE CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING SURFACES WHICH WERE PREVIOUSLY DAMAGED PRIOR TO CONSTRUCTION OPERATIONS IF VISIBLE AFTER NEW WORK IS COMPLETE, REGARDLESS IF THE ITEM WAS SPECIFICALLY
NOTED OR NOT.
• THE CONTRACTOR SHALL REMOVE AND PATCH ANY AREAS UNCOVERED WHERE WOOD NAILERS OR GROUNDS ARE FOUND TO EXIST BEHIND ANY TRIM ITEMS OR EQUIPMENT REMOVED. WALLS SHALL BE MADE FLUSH WITH EXISTING ADJACENT
SURFACES AND READY TO RECEIVE NEW FINISHES.
• IF ANY ASBESTOS CONTAINING MATERIAL IS ENCOUNTERED DURING THE COURSE OF CONSTRUCTION OPERATIONS WHICH IS NOT INDICATED ON THE CONTRACT DOCUMENTS THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY.
• WHERE EXISTING VINYL WALL COVERING IS REMOVED ON EXISTING WALLS TO REMAIN, THE CONTRACTOR SHALL PATCH AND REPAIR WALL AS REQUIRED TO PROVIDE A LEVEL AND TRUE SURFACES ON WHICH TO INSTALL NEW FINISHES.
• ALL SIGNAGE WHICH OCCURS ON WALL OR ON DOORS TO BE REMOVED SHALL BE REMOVED BY THE CONTRACTOR AND
TURNED OVER TO THE COR.
• ALL FINISHES LISTED IN THE DEMOLITION SCHEDULE SHALL BE REMOVED COMPLETELY UNLESS INDICATED OTHERWISE.
DEMOLITION SHALL INCLUDE BACKINGS, MASTIC AND GLUES, SETTING BEDS, AND SUBSTRATE AS REQUIRED TO PREPARE
THE MATERIAL FOR NEW WORK AND/OR FINISHES.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS SHEET ONLY UNLESS OTHERWISE NOTED.
• EXISTING HAND RAIL AND BUMPER GUARD SHALL BE REMOVED AND TURNED OVER TO THE OWNER.
• ALL EXISTING NURSE CALL, SMOKE DETECTORS, AND SPEAKERS TO REMAIN AND REWORKED WITH NEW CEILING SYSTEM.
• EXISTING WALL FINISHES TO BE VERIFIED AND PREPPED ACCORDINGLY FOR NEW FINISHES SCHEDULES - BY CONTRACTOR.
• REMOVE CEILING AS REQUIRED.
• THESE DEMOLITION NOTES ARE FOR ARCHITECTURAL WORK ONLY. SEE ALL OTHER DRAWINGS FOR DEMOLITION
INFORMATION PERTAINING TO OTHER DISCIPLINES.
DEMOLITION GENERAL NOTES
• ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE AND LOCAL CODES AND ORDINANCES.
• CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR FOR A RESOLUTION.
• EACH SUB CONTRACTOR SHALL REVIEW THE CONSTRUCTION DOCUMENTS AND EVALUATE THE SCOPE OF WORK REQUIRED BY THEIR RESPECTIVE TRADE AND ANY CONFLICTS WITH OTHER TRADES. ANY CONFLICTS WILL BE BROUGHT TO THE
IMMEDIATE ATTENTION OF THE COR FOR A RESOLUTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL ACCESSORIES, PARTS AND/OR
SERVICES TO BE READY FOR ITS INTENDED USE.
• CONTRACTOR SHALL COORDINATE ALL REQUIRED CONDUIT, PIPING AND CHASES FOR OWNER FURNISHED OWNER
INSTALLED EQUIPMENT WITH THE OWNER.
• CONTRACTOR SHALL COORDINATE WITH WORK BEING PERFORMED UNDER SEPARATE CONTRACT BY OWNER.
• SEE FIRE PLAN FOR FIRE WALL AND SMOKE PARTITION LOCATIONS.
• ALL ABUTTING DISSIMILAR MATERIALS ARE TO BE SEALED. COLOR TO MATCH ADJACENT MATERIALS.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS SHEET ONLY UNLESS OTHERWISE NOTED.
CEILING REMARKS
3" = 1'-0"
COUNTERTOP SUPPORT DETAIL
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
VHAHAMNegroV Polygon