36C24618R0840-003.pdf
PDF 18 MB Posted
- Solicitation number
- 36C24618R0840
About this file
36C24618R0840 CONTRACT ATTACHMENT A - DRAWINGS FILE 2 - 20180626.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24618R0840-0004001.pdf | ||
| 36C24618R0840-0004000.docx | DOCX document | |
| 36C24618R0840-0004002.pdf | ||
| 36C24618R0840-0003000.docx | DOCX document | |
| 36C24618R0840-0002001.pdf | ||
| 36C24618R0840-0002000.docx | DOCX document | |
| 36C24618R0840-006.pdf | ||
| 36C24618R0840-004.pdf | ||
| 36C24618R0840-001.docx | DOCX document | |
| 36C24618R0840-002.pdf | ||
| 36C24618R0840-005.docx | DOCX document | |
| 36C24618R0840-000.docx | DOCX document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SIDEWALL RETURN REGISTER
CEILING RETURN GRILLE/
SIDEWALL EXHAUST REGISTER
CEILING EXHAUST GRILLE/
DUCTWORK W/O DUCTLINER
SIDEWALL SUPPLY REGISTER
CEILING SUPPLY DIFFUSER/
MOTOR OPERATED DAMPER
DAMPER WITH ACCESS DOOR
COMBINATION FIRE/SMOKE
DRAWING NUMBER WHERE SECTION
DUCT SYMBOL: FLAT OVAL
EMERGENCY STOP SWITCH
DIRECTION OF AIR FLOW
THERMOMETER WELL AND CAP ONLY
THERMOMETER WITH WELL
12x10 DUCT SYMBOL: RECTANGULAR
THERMOSTAT
IS LOCATED
T
M4.1
SECTION NUMBER
HUMIDISTAT
H
ESS
MISCELLANEOUS
CFM
ARROW AND CFM
DUCT SYMBOL: ROUND
12/12
UNION
FSD
DOOR
ACCESS DOOR
DETECTOR WITH ACCESS
DUCT MOUNTED SMOKE
SMOKE DAMPER WITH
SD
WITH ACCESS DOOR
MANUAL DAMPER
ACCESS DOOR
FIRE DAMPER WITH
M
LINE PRESSURE RELIEF VALVE
GAUGE CONNECTION ONLY
PRESSURE GAGE WITH COCK
MANUAL AIR VENT POINT ON PIPE
LOW PRESSURE DRIP ASSEMBLY
MEDIUM PRESSURE
AUTOMATIC FLOW LIMITING DEVICE
PLUG VALVE WITH PRESSURE
REDUCED PRESSURE
PIPE UP
PIPE DOWN
STRAINER
BACKFLOW PREVENTER
(SEE SPECS)
FLOW SWITCH
DRIP ASSEMBLY
ACCESSORIES
DIRECTION OF FLOW
FLOW CONTROL DEVICE
ECCENTRIC REDUCER
DRAIN POINT OF PIPE
DIRECTION OF SLOPE
GLOBE VALVE
THREE WAY VALVE
ANCHOR POINT
CONCENTRIC REDUCER
DOUBLE LINE
EQUIPMENT
TRANSITION
DESCRIPTION
OVAL TRANSITION
SQUARE TO ROUND/
CONICAL TAKEOFF
RECTANGULAR DUCT
MITERED TAKEOFF
(SEE SCH)
(SEE SCH)
REGISTER (SEE SCH)
AUTOMATIC CONTROL VALVE
VALVES
BALL VALVE
GATE VALVE
CHECK VALVE
BUTTERFLY VALVE
DOUBLE LINE
DUCTWORK
(SEE SCH)
REGISTER (SEE SCH)
REGISTER (SEE SCH)
DESCRIPTION
LOW PRESSURE STEAM SUPPLY
LOW PRESSURE STEAM CONDENSATE
PC
LPS
LPC
HWR
HWS
PUMPED CONDENSATE
HOT WATER SUPPLY
HOT WATER RETURN
D
CHWS
CHWR
DRAIN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
BOX NUMBER (C OR V INDICATES
500 CFM
1-4-XC
VARIABLE OR CONSTANT VOLUME BOX WITH REHEAT
NO SCALE
HOT WATER GPM
CONSTANT OR VARIABLE FLOW)
24" OF ROUND HARD DUCTWORK
VARIABLE OR CONSTANT REGULATOR
SUPPLY CFM
REHEAT COIL
FLOOR
AIR HANDLING UNIT NUMBER
PIPING
1 GPM
AIR FLOW MONITORING
STATION
FD
M4
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
EXHAUST DUCT UP
SUPPLY AND RETURN SIMILAR
RETURN DUCT DOWN
SUPPLY AND EXHAUST SIMILAR
SUPPLY DUCT, UP THROUGH ROOF
RETURN AND EXHAUST SIMILAR
TO REMAIN
EXISTING EQUIPMENT
CONNECT TO EXISTING
TO REMAIN
EXISTING PIPING
TO REMAIN
EXISTING DUCT
NEW EQUIPMENT
NEW PIPING
LEGEND
NEW
DUCTWORK
GENERAL NOTES
TEMPERATURE SENSOR
UNDERWRITER'S LABORATORIES
UNLESS OTHERWISE NOTED
SYMBOL OR SYMMETRICAL
TEST, ADJUST, BALANCE
TRANSFER DUCT
SUPPLY REGISTER
STANDARD CUBIC FEET PER MINUTE
SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION
STATIC PRESSURE
VARIABLE SPEED
WEATHER PROOF
VARIABLE SPEED DRIVE
VARIABLE VOLUME
WET BULB TEMPERATUREWb
GP
INSUL
INV
LAT
LB/HR
KW
HTG
HVAC
HORZ
HR
HP
GPM
IB
IN
ID
HEATING, VENTILATING, AND AIR CONDITIONING
INVERTED BUCKET
INSIDE DIAMETER
LEAVING AIR TEMPERATURE
POUNDS PER HOUR
INSULATED
INVERT
KILOWATT
HEATING
INCH
HORSEPOWER
GALLONS PER MINUTE
HORIZONTAL
HOUR
GUIDE POINT
WP
WG WATER GAGE
FCV
GALV
GAL
FSD
FT
FV
FS
FPC
FPM
FPS
FP
FLEX
FLG
FD
FACP
F&T
F.D.
FC
EQUIP
ESP
EWT
EXH
ER
EFF
ELEC
EL
EQ
EAT
EA
F
EJ
FIRE PROTECTION CONTRACTOR
FEET PER SECOND
FLOW SWITCH/SENSOR
COMBINATION FIRE/SMOKE DAMPER
FEET PER MINUTE
FEET
GALVANIZED
GALLON(S)
FLOW VALVE
FLOW CONTROL VALVE
FIRE PROTECTI0N
FLANGE
FIRE DAMPER
FLEX
VERT
VSD
VOL
VS
VLV
VERTICAL
VOLUME
VALVE
THRU
T'STAT
UL
V
UON
TYP
TS
THERMOSTAT
TYPICAL
THROUGH
EXHAUST REGISTER
EXTERNAL STATIC PRESSURE
ENTERING WATER TEMPERATURE
FIRE ALARM CONTROL PANEL
FLOAT AND THERMOSTATIC
FLOW CONTROLLER
FAHRENHEIT
FLOOR DRAIN
EXHAUST
ENTERING AIR TEMPERATURE
EXPANSION JOINT
ELEVATION
ELECTRICAL
EQUAL
EQUIPMENT
EXHAUST AIR
EFFICIENCY
SPRINKLERSPR
STRUCT
TAB
T/D
SYM
SYS
STL
STM
SR
SQ
STRUCTURAL
SYSTEM
STEEL
STEAM
SQUARE
SMACNA
SPEC
SECT
SCFM
SP
SCH
SD
SA
SECTION
SPECIFICATION
SMOKE DAMPER
SCHEDULE
SUPPLY AIR
LEAVING WATER TEMPERATURE
RELATIVE HUMIDITY
REVOLUTIONS PER MINUTE
POUNDS PER SQUARE INCH ABSOLUTE
POUNDS PER SQUARE INCH GAGE
REFLECTED CEILING PLAN
POLYVINYL CHLORIDE
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH
PRESSURE REDUCING STATION
OUTSIDE DIAMETER
MOTOR OPERATED DAMPER
NATIONAL ELECTRIC CODE
NATIONAL ELECTRICAL MANUFACTURER'S
NATIONAL FIRE PROTECTION ASSOCIATION
NET POSITIVE SUCTION HEAD
NOT IN CONTRACT
NORMALLY OPEN
NORMALLY CLOSED
MANUAL AIR VENT
MANUAL DAMPER
MANUFACTURERMFR
ARCH ARCHITECTURAL
DWG
DWV
Db
DEG(°)
DPR
DTF
DP
DN
CU.FT.
CTR
CU.YD.
DD
CU
CONN
CONT
CONTR
CONST
COORD
CFH
CLG
CONC
ASHRAE
BFP
BDD
ASME
BHP
AUTO
BTUH
BTU
BV
C
CUBIC YARD
DRAIN, WASTE, AND VENT
DOWN THRU FLOOR
DUCT MOUNTED SMOKE DETECTOR
DRAIN POINT
DRAWING
DAMPER
DRY BULB TEMPERATURE
DEGREE(S)
DOWN
CONSTRUCTION
COPPER
CUBIC FEET
CENTER
CONNECTION
CONTINUATION
CONTRACTOR
COORDINATE
RECIRC
REINF
REQD
RH
RPM
RM
REV
RD
RA
RCP
REQUIRED
ROOM
REVISION
RETURN AIR
RECIRCULATING
REINFORCING
ROUND
PLBG
PSIG
QTY
PVC
PSI
PSIA
PRV
PRS
QUANTITY
PLUMBING
AMERICAN SOCIETY OF MECHANICAL ENGINEERS
CONSTANT VOLUME
CUBIC FEET PER HOUR
BRITISH THERMAL UNIT PER HOUR
BRITISH THERMAL UNIT
BUTTERFLY VALVE
CEILING
CONCRETE
BACKFLOW PREVENTER
BACKDRAFT DAMPER
AND AIR CONDITIONING ENGINEERS
BRAKE HORSEPOWER
AUTOMATIC
NIC
OPNG
NPSH
OA
OD
OC
NTS
NO.
NO
OUTSIDE AIR
ON CENTER
OPENING
NOT TO SCALE
NUMBER
NFPA
NEMA
NC
NEC
MOD
MTD
MIN
ASSOCIATION
MOUNTED
MINIMUM
AD
AFMS
ALUM
AFF
AC/HR
AP
ANSI
APPROX
AMCA
ABV.CLG.
AIR MOVEMENT AND CONTROL ASSOCIATION
AMERICAN NATIONAL STANDARDS INSTITUTE
ABBREVIATIONS
ANCHOR POINT
AIR FLOW MONITORING STATION
ACCESS DOOR
ABOVE FINISHED FLOOR
AIR CHANGES PER HOUR
ALUMINUM
APPROXIMATE
ABOVE CEILING
POUNDS OR NUMBER
ROUND, DIAMETER OR PHASE
MECH
MFG
MD
MAX
MBH
MAV
MANUFACTURING
MECHANICAL
MAXIMUM
BTUH x 1000
LF
LP
LWT
LINEAR FEET
LOW PRESSURE
SS SAFETY SWITCH
MRS MOTOR RATED SWITCH
W WATTS
ACU-1 AIR CONDITIONING UNIT & TAG
CC COOLING COIL
CP-1 CONDENSATE PUMP & TAG
DB DECIBELS
Dp DEWPOINT TEMPERATURE
CW COLD WATER (DOMESTIC)
EF-1 EXHAUST FAN & TAG
E or EX. EXISTING
FCU-1 FAN COIL UNIT & TAG
NOT ALL ALL ABBREVIATIONS
SHOWN IN THIS LIST WERE
UTILIZED FOR THIS PROJECT.
AMERICAN SOCIETY OF HEATING, REFRIGERATING,
AFLD AUTOMATIC FLOW LIMITING DEVICE
S/S STAINLESS STEEL
GA GAGE
EDB ENTERING DRY BULB
EWB ENTERING WET BULB
COTR CONTRACTING OFFICER TECHNICAL REPRESENTATIVE
HPS
HPC
HIGH PRESSURE STEAM CONDENSATE
HIGH PRESSURE STEAM SUPPLY
FTL FILTER
H
S
WITH ACCESS DOOR
DUCT MOUNTED HUMIDISTAT
PRESSURE SENSOR
DUCT MOUNTED STATIC
WITH ACCESS DOOR
DD
12ø
VFD VARIABLE FREQUENCY DRIVE
Ø
A. ALL DUCTS, PIPE, AND EQUIPMENT SHALL BE LATERALLY RESTRAINED TO
COMPLY WITH THE NORTH CAROLINA BUILDING CODE. PROVIDE FOR
SEISMIC DESIGN CLASS "D."
B. BEFORE FABRICATING ANY SHEET METAL DUCTWORK, COORDINATE
LOCATION AND SIZE WITH SPRINKLER & PLUMBING PIPING, CONDUITS,
LIGHT FIXTURES, STRUCTURAL, ETC. PLANS ARE SCHEMATIC AND ARE
NOT SHOP DRAWINGS. SUBMIT DUCTWORK COORDINATION DRAWINGS,
AS SPECIFIED.
C. BEFORE SUBMITTING SHOP DRAWINGS, COORDINATE VOLTAGES
AVAILABLE FOR MECHANICAL EQUIPMENT AND PROVISION OF ALL
STARTERS AND DISCONNECT SWITCHES WITH CONTRACTOR.
D. CONTRACTOR SHALL MAKE PROVISIONS FOR PROVIDING A CONDENSATE
DRAIN TRAP A MINIMUM OF 4" DEEP OR 12" PLUS THE STATIC PRESSURE
OF THE UNIT SUPPLY FAN.
E. ALL EQUIPMENT SHALL BE U.L. LISTED.
F. FIRE AND SMOKE DAMPERS SHALL BE INSTALLED IN COMPLETE
ACCORDANCE WITH THE MFR'S. U.L. LISTING AND INSTALLATION
INSTRUCTIONS. FIRE AND SMOKE DAMPERS SHALL HAVE SPECIFIC U.L.
LISTING FOR THE CONSTRUCTION IN WHICH THEY ARE INSTALLED.
PROVIDE DYNAMIC FIRE DAMPERS.
G. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH
OTHER TRADES TO ELIMINATE CONFLICT WITH OTHER TRADES. ANY
WORK INSTALLED BY THE CONTRACTOR THAT RESULTS IN CONFLICT,
DUE TO LACK OF COORDINATION BETWEEN TRADES, SHALL BE CHANGED
AS DIRECTED BY THE ARCHITECT/ENGINEER WITHOUT ADDITIONAL
COMPENSATION TO THE CONTRACTOR.
H. SMOKE DETECTORS SHALL BE FURNISHED AND INSTALLED BY THE
CONTRACTOR. PROVIDE DUCT ACCESS DOOR AT EACH DETECTOR.
INSTALL DETECTORS IN COMPLETE ACCORDANCE WITH THE
MANUFACTURER'S INSTRUCTIONS.
I. CONTRACTOR SHALL COORDINATE EXACT HEIGHT OF ROOF CURB WITH
NEW ROOF INSTALLATION REQUIREMENTS.
J. CONTRACTOR SHALL COORDINATE ROUTING OF DUCTWORK TO ENSURE
DUCTWORK DOES NOT PASS OVER ELECTRICAL PANELS.
K. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES.
THE SCALE, WHEN INDICATED IS INTENDED FOR GENERAL REFERENCE
ONLY.
L. LEAVE A MINIMUM CLEARANCE OF 2 INCHES ABOVE DUCTS INSTALLED IN
RATED PARTITIONS TO ALLOW SPACE FOR THE CONTRACTOR TO SEAL
THE WALL ABOVE THE DUCTS. DO NOT INSTALL FLEXIBLE DUCT
THROUGH RATED WALLS, BARRIERS OR PARTITIONS.
M. PROVIDE REMOVABLE ACCESS DOORS AT ALL MOTOR OPERATED
DAMPERS, FIRE DAMPERS, SMOKE DAMPERS, DUCT COILS, SMOKE
DETECTORS, AND SIMILAR ITEMS REQUIRING MAINTENANCE OR
ADJUSTMENT.
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100
Charlotte, NC 28212 704 531 3000
704 531 3001 FAX
Firm License Number: F-0674
This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.
It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.
It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.
Project
Salisbury, NC City, State
VA Contract Number
Drawn By
Checked By
Seal / Signature
Sheet Title
Date
Sheet Number
Architect of Record
5960 Fairview Road Suite 500 Charlotte, NC 28210
887.3500
887.3507 fax
Issued For
December 29, 2015
CONSTRUCTION
COLEJENEST & STONE, P.A.
200 South Tryon Street, Suite 1400 Charlotte, North Carolina 28202
704.376.1555 PHONE
704.376.7851 FAX
CIVIL/LANDSCAPING:
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212
704.531.3000 PHONE
MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:
Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031
704.987.9114 PHONE
704.987.9938 FAX
STRUCTURAL:
Program Manager
13620 Reese Blvd.
Suite 100
Huntersville, NC 28078
401.2040
401.2067 fax
CE PROJ # 3132
VAMC Salisbury Building 11 - Additions & Renovations
VA246-12-C-0089
M-001
MECHANICAL - NOTES,
LEGENDS AND SYMBOLS
SMN
GAT
Item Date Description
SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY CONDITIONS AND DIVISION 01 SPECIFICATIONS SECTIONS, APPLY TO THIS SECTION. OTHER SECTIONS OF THE SPECIFICATION APPLY TO THIS SECTION AND IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
REVIEW AND INCORPORATE THE ENTIRE SPECIFICATION INTO THE SCOPE OF WORK.
1.2 SUMMARY
A. THIS SECTION INCLUDES CONTROL SEQUENCES FOR HVAC SYSTEMS, SUBSYSTEMS, AND EQUIPMENT.
1.3 DEFINITIONS
A. DDC: DIRECT DIGITAL CONTROL.
B. VAV: VARIABLE AIR VOLUME.
PART 2 - PRODUCTS (NOT APPLICABLE)
PART 3 - EXECUTION
A. VAV TERMINALS
1. THE VAV DDC CONTROLLER SHALL MODULATE THE SUPPLY AIR DAMPER AND THE HOT WATER REHEAT
IN SEQUENCE AS REQUIRED TO MAINTAIN TEMPERATURE SET-POINT.
2. A CUSTOMER ADJUSTABLE DEAD BAND SHALL BE PROVIDED IN THE BAS, BETWEEN HEATING AND
COOLING MODES.
3. COOLING MODE: UPON RECEIPT OF SIGNAL FROM ROOM TEMPERATURE SENSOR CALLING FOR
COOLING, THE SUPPLY AIR DAMPER SHALL MODULATE OPEN UP TO 100%, AS REQUIRED, TO SATISFY ROOM TEMPERATURE SET POINT. ONCE COOLING SETPOINT IS SATISFIED, THE SUPPLY AIR DAMPER SHALL BEGIN TO MODULATE CLOSED. WHEN COOLING SET POINT REMAINS SATISFIED, THE SUPPLY AIR DAMPER SHALL CONTINUE TO MODULATE CLOSED UNTIL IT REACHES MINIMUM FLOW (VENTILATION RATE).
4. HEATING MODE: UPON RECEIPT OF A SIGNAL FROM ROOM TEMPERATURE SENSOR CALLING FOR HEAT, THE SUPPLY AIR DAMPER SHALL MOVE TO 50% OF MAXIMUM FLOW, AND THE HOT WATER REHEAT CONTROL VALVE SHALL MODULATE OPEN. IF THE ROOM TEMPERATURE SENSOR REMAINS UNSATISFIED
THE SUPPLY AIR DAMPER SHALL MODULATE OPEN TO 100% MAXIMUM FLOW. ONCE THE ROOM
TEMPERATURE SENSOR IS SATISFIED THE SUPPLY AIR DAMPER SHALL BEGIN TO MODULATE CLOSED UNTIL 50% OF MAXIMUM FLOW IS REACHED. IF THE ROOM SENSOR REMAINS SATISFIED, THE HOT
WATER REHEAT CONTROL VALVE SHALL MODULATE CLOSED.
B. EXHAUST FANS SHALL HAVE THE CAPABILITY OF BEING STARTED AND STOPPED BY THE BAS. UNDER
NORMAL OPERATION, THE EXHAUST FANS SHALL BE CONTROLLED AS FOLLOWS:
3.2 POINT SCHEDULE MATRIX - I/0 SUMMARY
A. THE CONTRACTOR SHALL COLLABORATE WITH THE OWNER DIRECTLY TO DETERMINE THE OWNER'S PREFERENCE FOR NAMING CONVENTIONS, ETC. BEFORE ENTERING THE DATA IN TO THE SYSTEM.
3.3 START-UP AND COMMISSIONING
A. WHEN INSTALLATION OF THE SYSTEM IS COMPLETE, CALIBRATE EQUIPMENT AND VERIFY TRANSMISSION MEDIA OPERATION BEFORE THE SYSTEM IS PLACED ON-LINE. ALL TESTING, CALIBRATING, ADJUSTING AND FINAL FIELD TESTS SHALL BE COMPLETED BY THE INSTALLER. VERIFY THAT ALL SYSTEMS ARE OPERABLE FROM LOCAL CONTROLS IN THE SPECIFIED FAILURE MODE UPON PANEL FAILURE OR LOSS OF POWER.
B. PROVIDE ANY RECOMMENDATION FOR SYSTEM MODIFICATION IN WRITING TO OWNER. DO NOT MAKE ANY SYSTEM MODIFICATION, INCLUDING OPERATING PARAMETERS AND CONTROL SETTINGS, WITHOUT PRIOR
APPROVAL OF OWNER.
3.4 TRAINING
A. THE CONTRACTOR SHALL PROVIDE FACTORY TRAINED INSTRUCTOR TO GIVE FULL INSTRUCTION TO DESIGNATED PERSONNEL IN THE OPERATION OF THE SYSTEM INSTALLED. INSTRUCTORS SHALL BE THOROUGHLY FAMILIAR WITH ALL ASPECTS OF THE SUBJECT MATTER THEY ARE TO TEACH. THE CONTRACTOR SHALL PROVIDE ALL STUDENTS WITH A STUDENT BINDER CONTAINING PRODUCT SPECIFIC TRAINING MODULES FOR THE SYSTEM INSTALLED. ALL TRAINING SHALL BE HELD DURING NORMAL
WORKING HOURS OF 8:00 AM TO 4:30 PM WEEKDAYS.
B. PROVIDE 16 HOURS OF TRAINING FOR OWNER'S DESIGNATED OPERATING PERSONNEL. TRAINING SHALL
INCLUDE:
1. EXPLANATION OF DRAWINGS, OPERATIONS AND MAINTENANCE MANUALS.
2. WALK-THROUGH OF THE JOB TO LOCATE CONTROL COMPONENTS.
3. OPERATOR WORKSTATION AND PERIPHERALS.
4. DDC CONTROLLER AND ASC OPERATION/FUNCTION.
5. OPERATOR CONTROL FUNCTIONS INCLUDING GRAPHIC GENERATION AND FIELD PANEL PROGRAMMING.
6. OPERATION OF PORTABLE OPERATOR'S TERMINAL.
7. EXPLANATION OF ADJUSTMENT, CALIBRATION AND REPLACEMENT PROCEDURES.
8. STUDENT BINDER WITH TRAINING MODULES.
C. SINCE THE OWNER MAY REQUIRE PERSONNEL TO HAVE MORE COMPREHENSIVE UNDERSTANDING OF THE HARDWARE AND SOFTWARE, ADDITIONAL TRAINING MUST BE AVAILABLE FROM THE CONTRACTOR. IF SUCH
TRAINING IS REQUIRED BY THE OWNER, IT WILL BE CONTRACTED AT A LATER DATE.
END OF SECTION
3.1 SEQUENCE OF OPERATION
SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
AHU SEQUENCE
GENERAL - THE SCHEDULING PROGRAM AUTOMATICALLY INDEXES THE VAV BOXES AND AIR HANDLING UNIT AHU TO EITHER THE “OCCUPIED” OR “UNOCCUPIED” MODE. WHEN THE AHU IS INDEXED TO THE “OCCUPIED” MODE, IT OPERATES CONTINUOUSLY AS DESCRIBED BELOW AND THE ZONE THERMOSTATS ON ITS VAV BOXES MAINTAIN THEIR “OCCUPIED” HEATING AND COOLING SETPOINTS. WHEN THE AHU IS INDEXED TO THE “UNOCCUPIED” MODE, THE AHU SHUTS DOWN UNLESS ZONE TEMPERATURE FOR ANY ASSOCIATED VAV EXCEEDS ITS “UNOCCUPIED” HEATING SETPOINT OF 60 DEGREES (ADJUSTABLE) OR ITS “UNOCCUPIED” COOLING SETPOINT OF 80 DEGREES (ADJUSTABLE). WHEN THIS OCCURS, THE AHU STARTS AND RUNS UNTIL ALL ZONES ARE SATISFIED. DURING THE “UNOCCUPIED” MODE, AN OVERRIDE PUSHBUTTON ON EACH THERMOSTAT ALLOWS THAT VAV BOX AND ITS AHU TO BE RETURNED TO NORMAL “OCCUPIED” OPERATION FOR A PRESET PERIOD OF 120 MINUTES (ADJUSTABLE). THE “UNOCCUPIED” HEATING AND COOLING SETPOINTS, THE PUSHBUTTON OVERRIDE TIME, AND THE “OCCUPIED” SETPOINT ADJUSTMENT LIMITS ON THE VAV THERMOSTATS ADJUSTABLE ON THE GRAPHICS INTERFACE WITHIN THE BAS.
FAN CONTROL AND SAFTIES - ON AHU STARTUP, THE SUPPLY AND EXHAUST FANS START THROUGH THE VFD AT MINIMUM SPEED AND RAMP-UP AS REQUIRED TO MAINTAIN SUPPLY DUCT PRESSURE SETPOINT. THE EXHAUST FAN SHALL OPERATE TO MAINTAIN AIRFLOW CALCULATED UTILIZING AN OFFSET AIRFLOW VALUE. THIS VALUE SHALL BE CALCULATED BY THE TEST AND BALANCE CONTRACTOR AT THE OCCURANCE OF THE INITIAL TEST AND BALANCE. THE VALUE FOR THE OFFSET AIRFLOW SHALL BE DETERMINED USING THE EXHAUST VALUE OF THE PORTION OF THE BUILDING SERVED BY THE UNIT AS A STARTING POINT AND INCREASING THE AIRFLOW VALUE (THERE-BY REDUCING THE RETURN AIRFLOW) UNTIL THE BUILDING OPERATES AT A SATISFACTORY POSITIVE PRESSURE. ONCE THE VALUE IS DETERMINED, THEN THE EXHAUST FAN AIRFLOW SHALL BE MAINTAINED AT THIS OFFSET AIRFLOW VALUE WITH RESPECT TO THE SUPPLY AIRFLOW THROUGHOUT THE OPERATING RANGE. CURRENT SWITCHES SHALL INPUT THE STATUS OF EACH FAN TO CONTROLLER AHU FOR READOUT. AN ALARM IS GENERATED IF A FAN FAILS TO OPERATE WHEN COMMANDED TO RUN. WHEN THE SUPPLY FAN IS OPERATING A CURRENT SWITCH ACTIVATES AND THE AHU CONTROLS OPERATE AS DESCRIBED BELOW. WHEN THE SUPPLY FAN SHUTS DOWN, ALL VALVES AND DAMPERS GO TO THEIR NORMAL POSITIONS WITH THE OUTSIDE DAMPERS CLOSED, THE RETURN DAMPER OPEN, THE STEAM VALVE OPEN, AND THE CHILLED WATER VALVE CLOSED. ALSO, THE EXHAUST FAN SHUTS DOWN AND THE RETURN DAMPER CLOSES.
THE AHU SHALL SHUTDOWN AND AN ALARM SHALL BE COMMUNICATED TO THE CONTROLLER IF ANY OF THE FOLLOWING SAFETY
CONTROLS ACTIVATE:
1) A MANUALLY RESET HIGH PRESSURE SWITCH ON THE SUPPLY FAN TRIPS
2) A MANUALLY RESET FREEZESTAT AT THE COOLING COIL INLET TRIPS
3) A FIRE ALARM SYSTEM RELAY ACTIVATES
A DIFFERENTIAL PRESSURE SWITCH SHALL GENERATE A MAINTENANCE ALARM IF PRESSURE DROP ACROSS THE FILTERS EXCEEDS
THE SETPOINT OF THE SWITCH.
SUPPLY DUCT PRESSURE CONTROL - A PRESSURE TRANSMITTER SHALL BE LOCATED IN THE SUPPLY DUCT AND CONTROLLER AHU MODULATE THE SPEED OF THE SUPPLY FAN AS REQUIRED TO MAINTAIN THE SUPPLY AIR STATIC PRESSURE SETPOINT. UPON A DECREASE IN DUCT PRESSURE BELOW SETPOINT, THE SPEED OF THE SUPPLY FAN SHALL BE INCREASED. THE SETPOINT IS OPTIMIZED ONCE EVERY 15 MINUTES BY A CALCULATION IN THE CONTROLLER WHICH MONITORS THE POSITION OF THE FLOW DAMPERS ON ANY ASSOCIATED VAV BOX WHICH IS OPERATING IN THE “OCCUPIED” OR “UNOCCUPIED” MODE. WHEN THE CALCULATION RUNS AND ANY DAMPER IS >90% OPEN, THE STATIC PRESSURE SETPOINT IS INCREMENTED UPWARD BY +0.10” W.C., UNLESS THE FAN IS ALREADY RUNNING AT ITS MAXIMUM SPEED. WHEN THE CALCULATION RUNS AND ALL DAMPERS ARE <80% OPEN, THE STATIC PRESSURE SETPOINT IS DECREMENTED DOWNWARD BY -0.10” W.C., UNLESS THE FAN IS ALREADY RUNNING AT ITS MINIMUM SPEED. THE RESET OF THE SETPOINT IS LIMITED IN SOFTWARE TO 0.8” W.C. MINIMUM AND 3.0” W.C. MAXIMUM (ADJUSTABLE). ON STARTUP OF THE SUPPLY FAN, THE SETPOINT IS INITIALLY SET TO THE MAXIMUM LIMIT AND THEN THE CALCULATION BEGINS TO RESET THE SETPOINT TO THE OPTIMUM VALUE. THE MAXIMUM SETPOINT LIMIT, THE MINIMUM SETPOINT LIMIT, THE INCREMENT & DECREMENT AMOUNT, THE UPPER & LOWER DAMPER POSITIONS TO INCREASE OR DECREASE THE SETPOINT, AND THE FREQUENCY OF THE CALCULATION SHALL EACH BE ADJUSTABLE ON A DETAIL PAGE OF THE AHU GRAPHIC WITHIN THE BAS. THIS GRAPHIC PAGE SHALL ALSO DISPLAY THE ACTUAL STATIC PRESSURE, THE CALCULATED SETPOINT, AND THE CURRENT POSITION OF EACH VAV BOX DAMPER. IN ADDITION, THIS GRAPHIC SHALL “HIGHLIGHT” THE TERMINAL BOX BEING USED TO INCREMENT OR DECREMENT THE SETPOINT. AN ENABLE/DISABLE POINT TO INCLUDE OR EXCLUDE EACH BOX IN THE CALCULATION IS PROVIDED. A MASTER ENABLE/DISABLE POINT SHALL BE PROVIDED FOR THE OPTIMIZATION CALCULATION. IF IT
IS DISABLED, THE SETPOINT GOES TO THE MAXIMUM SETPOINT VALUE.
OA FLOW MODE CONTROL - AN OUTSIDE AIR FLOW STATION AND A SUPPLY AIR FLOW STATION ON THE UNIT INPUT FLOW SIGNALS TO THE UNIT CONTROLLER FOR READOUT AND CONTROL. THE AIR HANDLING UNIT TO DETERMINE IF THE UNIT SHOULD OPERATE
ON THE “MIN OA” MODE OR THE “ECONOMIZER” MODE AS DESCRIBED BELOW.
WHEN THE AHU FIRST STARTS, IT INITIALLY OPERATES IN THE "NORMAL" MODE. IN THIS MODE THE MINIMUM OUTSIDE AIR DAMPER IS OPEN AND THE EXHAUST FAN IS SET TO ITS MINIMUM FLOW. EITHER THE HEATING VALVE OR CHILLED WATER VALVE SHALL
MODULATE FOR TEMPERATURE CONTROL.
WHEN THE AHU REQUIRES MORE OUTSIDE AIR THAN ITS MINIMUM OUTSIDE AIR FLOW TO MAINTAIN ITS SUPPLY AIR TEMPERATURE CONDITIONS BASED ON COMPARISON OF OUTSIDE AIR AND RETURN AIR ENTHALPY (AS DESCRIBED BELOW) THEN "ECONOMIZER" MODE SHALL BE INITIATED IN THIS MODE THE POWERED EXHAUST FAN SHALL INCREASE TO A MAX FLOW AND THE ECONOMIZER
OUTSIDE AIR DAMPER SHALL MODULATE OPEN.
WHEN OUTSIDE AIR ENTHALPY EXCEEDS RETURN AIR ENTHALPY, THE AIR HANDLING UNIT SHALL BE SWITCHED BACH TO THE "NORMAL" MODE. THE ECONOMIZER OUTSIDE AIR DAMPER SHALL MODULATE CLOSED AND THE POWERED EXHAUST FAN SHALL BE REDUCE TO A MINIMUM SPEED. WHEN OUTSIDE AIR ENTHALPY AGAIN FALLS BELOW RETURN AIR ENTHALPY, THE UNIT SWITCHES
BACK TO THE "ECONOMIZER" MODE AS DESCRIBED ABOVE.
SPACE PRESSURE CONTROL - SPACE PRESSURE CONTROL SHALL BE ACCOMPLISHED THROUGH AN AIRLOW TRACKING UTILIZING
AN OFFSET AIRFLOW FOR EXHAUST FAN CONTROL. THIS SEQUENCE IS DESCRIBED ABOVE.
“OCCUPIED” TEMPERATURE CONTROL - DURING THE “OCCUPIED” MODE, SENSOR IN SUPPLY AIR AND CONTROLLER AHU MODULATE HEATING VALVE, AND THE CHILLED WATER VALVE IN SEQUENCE AS REQUIRED TO MAINTAIN THE SUPPLY AIR SETPOINT.
THE INITIAL SETPOINT IS 55 DEGREES; HOWEVER, THE CONTROLLER GRADUALLY RESETS THE SUPPLY SETPOINT FROM 55 TO 60 DEGREES AS OUTSIDE AIR TEMPERATURE FALLS FROM 45 DEGREES TO 20 DEGREES. THE RESET PARAMETERS ARE ALL
ADJUSTABLE FROM THE UNIT GRAPHIC.
REGARDLESS OF THE OPERATING MODE OF THE AHU, THE LOW LIMIT SENSOR AT THE HEATING COIL DISCHARGE OF THE UNIT AND CONTROLLER AHU FUNCTION AS A LOW LIMIT BY OVERCALLING THE SUPPLY AIR SIGNAL AND MODULATING HEATING VALVE OPEN AS REQUIRED TO PREVENT AIR TEMPERATURE ENTERING THE COOLING COIL FROM FALLING BELOW 50 DEGREES (ADJUSTABLE)
UNTIL SUPPLY SENSOR DOWNSTREAM OF THE SUPPLY CAN TAKE CONTROL.
WHEN THE UNIT FIRST SWITCHES TO THE “OCCUPIED” MODE AND RETURN AIR TEMPERATURE AT THE AHU IS LESS THAN THE WARM-UP SETPOINT OF 70 DEGREES (ADJUSTABLE), THE POWERED EXHAUST FAN SHALL REMAIN OFF AND OUTSIDE AIR DAMPERS SHALL CLOSE UNTIL SETPOINT IS ACHIEVED. REHEAT COILS ON THE VAV BOXES THEN HEAT UNTIL RETURN AIR TEMPERATURE RISES ABOVE THIS SETPOINT. WHEN RETURN AIR ON THE UNIT RISES ABOVE THE SETPOINT, THE UNIT GOES TO THE “NORMAL” MODE WITH ERU RUNNING AND THE UNIT BEGINS TO MAINTAIN THE SUPPLY AIR SETPOINT AS DESCRIBED ABOVE.
“UNOCCUPIED” TEMPERATURE CONTROL - DURING THE “UNOCCUPIED” MODE, IF THE UNIT STARTS FOR LOW LIMIT OPERATION, RETURN AIR TEMPERATURE WILL BE BELOW THE WARM UP SETPOINT OF 70 DEGREES AND COOLING WILL BE LOCKED OUT WHILE THE UNIT RUNS AND THE REHEAT COILS ON THE VAV BOXES WILL PROVIDE HEATING. HOWEVER, IF THE SUPPLY FAN STARTS FOR HIGH LIMIT OPERATION, THE UNIT OPERATES ON 100% RETURN AIR AND THE CONTROLLER MAINTAINS THE SUPPLY AIR SETPOINT
BY MODULATING THE CHILLED WATER VALVE TO ALLOW INDIVIDUAL VAV BOXES TO COOL.
FIRE ALARM - IF THE FIRE ALARM SYSTEM GOES INTO ALARM, AN ALARM IS INPUT TO THE AHU CONTROLLER AND BOTH FANS STOP AND ALL DAMPERS CLOSE. WHEN THE FIRE ALARM SYSTEM IS RESET, THE FANS ARE AGAIN ALLOWED TO RUN, ONCE ALL DISCHARGE AND RETURN DAMPERS ARE POWERED OPEN. IF SUPPLY DUCT STATIC PRESSURE EXCEEDS THE SETPOINT OF A MANUAL RESET HIGH PRESSURE SWITCH, AN ALARM IS INPUT TO THE CONTROLLER AND ONLY THE SUPPLY FAN STOPS. WHEN IT IS
RESET, THE SUPPLY FAN IS AGAIN ALLOWED TO RUN.
FREEZE PROTECTION - IF FREEZESTAT LL-1 AT THE INLET TO THE COOLING COIL TRIPS, AN ALARM IS INPUT TO CONTROLLER AHU.
THIS CAUSES THE HEATING COIL VALVE CV-HC TO GO 100% OPEN REGARDLESS OF WHETHER THE UNIT FAN IS RUNNING. WHEN THE
FREEZESTAT IS RESET, THE HEATING VALVE IS AGAIN CONTROLLED AS DESCRIBED ABOVE.
END OF SECTION
REMARKS:
SERVES
WATER PRESSURE DROP (FEET WG)
AIR PRESSURE (IN WG)
WHEEL DIAMETER
FILTER PRESSURE DROP (INWG)
FILTER AREA (SQUARE FEET)
FILTER MINIMUM EFFICIENCY
FILTER TYPE
REMARKS:
TYPE UNIT
LOCATION
SYSTEM NO.
VSD
REMARKS:
TYPE FAN
REMARKS:
VSD
REMARKS:
TYPE FAN
REMARKS:
PREFILTER MIN. EFF.
PREFILTER TYPE
PREFILTER AREA - SQ FT.
FINAL FILTER MIN. EFF.
FINAL FILTER TYPE
FINAL FILTER AREA - SQ FT.
ACCESS SECTION W/AD
SUPPORT BASE
VIBRATION ISOLATORS
MOTOR OPER. SMOKE DAMPERS
DISCHARGE AIR PLENUM W/AD
RETURN AIR PLENUM W/AD
MIXING SECTION W/AD
SENSIBLE LOAD (MBH)
E.A.T. D.B./W.B. (°F)
L.A.T. D.B./W.B. (°F)
FINS PER FOOT MIN.
SQ. FT. FACE AREA MIN.
FACE VELOCITY MAX. (FPS)
E.W.T. °F
ROWS MIN.
TYPE COIL
WHEEL DIAMETER MIN. (in.)
RPM APPROX.
TYPE DRIVE
HP MIN/VOLT/PH/HZ
ARRANGEMENT
RPM APPROX.
HP MIN/VOLT/PH/HZ
TYPE DRIVE
TOTAL EXTERNAL STATIC PRESSURE (IN WG)
TOTAL CFM (MAX/MIN)
TOTAL LOAD (MBH)
ARRANGEMENT
TOTAL CFM
TOTAL CFM (DESIGN/CONNECTED)
TOTAL EXTERNAL STATIC PRESSURE (IN W.G.)
SYSTEM TYPE
PR
EF
IL
TE
R
YES
NO
YES
YES
YES
2940/910
VARIABLE VOLUME
(CSAA) VAV
1ST FLOOR
AREA A ROOF
ECONOMIZER YES
OUTSIDE AIR (CFM) VENT/ECONOMIZER 910/3850
YES
L.W.T. °F
3850/3500
2.5
YES
183.60
CHILLED WATER
BELT
MERV 8
BELT
MERV 8
0.5
2/208/3Ø/60
80/67
51/51
7.99
0.894
4.76
7.5/208/3Ø/60
AIRFOIL
DRAW-THROUGH
2" PLEATED
MERV 15
CARTRIDGE
8.00
YES
YES
ANGLED
11.11
0.590
DRAW-THROUGH
FORWARD CURVED
ROOF TOP UNIT SCHEDULE
EX
HA
US
T
FA
NS
FI
NA
L
FI
LT
ER
SU
PP
LY
F
AN
AC
CE
SS
CO
OL
IN
G
CO
IL
GPM AT 16°F DT
HE
AT
IN
G
CO
IL
TOTAL CFM 3850
TOTAL LOAD (MBH) 141.96
EAT/LAT (°F) 45/79
TYPE COIL STEAM
ROWS MIN 1
FINS PER FOOT MIN 43
SQ FT FACE AREA 6.50
FACE VELOCITY MAX (FPS) 592
STEAM PSI 15
STEAM #/HR @ 15PSI 145
AIR PRESSURE DROP (IN H20) 0.107
REMARKS:
ROOF TOP UNIT
PERFORMANCE CLIMATE CHANGER
1ST FLOOR
AREA A ROOF
RTU-1A
1ST FLOOR
AREA B ROOF
RTU-1B
1ST FLOOR
AREA B ROOF
RTU-1C
1ST FLOOR
AREA C ROOF
RTU-2A
1ST FLOOR
AREA C ROOF
RTU-2B
1ST FLOOR
AREA C ROOF
RTU-2C RTU-2D
YES
4550/4135
2.5
192.00
CHILLED WATER
BELT
MERV 8
80/67
53/53
9.98
0.603
4.75
7.5/208/3Ø/60
AIRFOIL
DRAW-THROUGH
2" PLEATED
8.67
MERV 15
CARTRIDGE
8.67
YES
YES
167.77
45/79
STEAM
8.17
0.092
3475/1075
VARIABLE VOLUME
(CSAA) VAV
1075/4550
YES
BELT
MERV 8
0.5
2/208/3Ø/60
ANGLED
13.89
0.584
DRAW-THROUGH
FORWARD CURVED
ROOF TOP UNIT
PERFORMANCE CLIMATE CHANGER
YES
9300/8435
2.5
420.00
CHILLED WATER
BELT
MERV 8
80/67
53/53
20.81
0.627
11.96
20/208/3Ø/60
AIRFOIL
DRAW-THROUGH
2" PLEATED
8.67
MERV 15
CARTRIDGE
8.67
YES
YES
368.73
45/79
STEAM
17.00
0.105
9300/5815
VARIABLE VOLUME
(CSAA) VAV
3025/9300
YES
BELT
MERV 8
0.5
2/208/3Ø/60
ANGLED
33.33
0.574
DRAW-THROUGH
FORWARD CURVED
ROOF TOP UNIT
PERFORMANCE CLIMATE CHANGER
YES
2.5
277.95
CHILLED WATER
BELT
MERV 8
80/67
53/53
13.65
0.646
8.46
10/208/3Ø/60
AIRFOIL
DRAW-THROUGH
2" PLEATED
13.44
MERV 15
CARTRIDGE
13.44
YES
YES
244.27
45/79
STEAM
12.5
0.081
6600/1560
VARIABLE VOLUME
(CSAA) VAV
1560/6600
YES
BELT
MERV 8
0.5
2/208/3Ø/60
ANGLED
18.06
0.597
DRAW-THROUGH
FORWARD CURVED
ROOF TOP UNIT
PERFORMANCE CLIMATE CHANGER
YES
NO
YES
YES
YES
YES
1050/4500805/35004185/10,000
10,000/5815 3500/910 4500/1075
YES
NO
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
10,000/9095
2.5
10,000
420.00
CHILLED WATER
BELT
MERV 8
80/67
53/53
20.81
0.627
11.96
20/208/3Ø/60
AIRFOIL
DRAW-THROUGH
2" PLEATED
8.67
MERV 15
CARTRIDGE
8.67
YES
YES
10,000
368.73
45/79
STEAM
17.00
0.105
YES
BELT
MERV 8
2/208/3Ø/60
ANGLED
33.33
0.574
DRAW-THROUGH
FORWARD CURVED
YES
NO
YES
YES
YES
YES
0.5
YES
NO
YES
YES
YES
YES
YES
3500/3085
2.5
YES
183.60
CHILLED WATER
BELT
MERV 8
BELT
MERV 8
0.5
2/208/3Ø/60
80/67
51/51
7.99
0.894
4.76
7.5/208/3Ø/60
AIRFOIL
DRAW-THROUGH
2" PLEATED
MERV 15
CARTRIDGE
8.00
YES
YES
ANGLED
11.11
0.590
DRAW-THROUGH
FORWARD CURVED
141.96
45/79
STEAM
6.50
0.107
YES
4500/4030
2.5
192.00
CHILLED WATER
BELT
MERV 8
80/67
53/53
9.98
0.603
4.75
7.5/208/3Ø/60
AIRFOIL
DRAW-THROUGH
2" PLEATED
8.67
MERV 15
CARTRIDGE
8.67
YES
YES
167.77
45/79
STEAM
8.17
0.092
YES
BELT
MERV 8
0.5
2/208/3Ø/60
ANGLED
13.89
0.584
DRAW-THROUGH
FORWARD CURVED
YES
NO
YES
YES
YES
YES
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100
Charlotte, NC 28212 704 531 3000
704 531 3001 FAX
Firm License Number: F-0674
This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.
It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.
It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.
Project
Salisbury, NC City, State
VA Contract Number
Drawn By
Checked By
Seal / Signature
Sheet Title
Date
Sheet Number
Architect of Record
5960 Fairview Road Suite 500 Charlotte, NC 28210
887.3500
887.3507 fax
Issued For
December 29, 2015
CONSTRUCTION
COLEJENEST & STONE, P.A.
200 South Tryon Street, Suite 1400 Charlotte, North Carolina 28202
704.376.1555 PHONE
704.376.7851 FAX
CIVIL/LANDSCAPING:
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212
704.531.3000 PHONE
MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:
Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031
704.987.9114 PHONE
704.987.9938 FAX
STRUCTURAL:
Program Manager
13620 Reese Blvd.
Suite 100
Huntersville, NC 28078
401.2040
401.2067 fax
CE PROJ # 3132
VAMC Salisbury Building 11 - Additions & Renovations
VA246-12-C-0089
M-002
MECHANICAL -
SCHEDULES
SMN
TERMINAL UNIT SCHEDULE
1-1-1V
1-1-2V
1-1-3C
1-1-4V
1-1-5V
1-1-6V
1-1-7V
1-1-8V
1-1-9V
1-1-10V
1-1-11V
1-1-12V
1-1-13V
1-1-14V
1-1-15V
1-1-16V
1-1-17V
1-1-18V
1-1-19V
1-1-20C
1-1-21V
1-1-22C
2-1-23V
2-1-24C
1-1-25C
2-1-26V
2-1-27V
2-1-28V
2-1-29V
2-1-30V
2-1-31V
2-1-32V
2-1-33V
2-1-34V
2-1-35V
2-1-36V
2-1-37V
2-1-38V
2-1-39V
2-1-40V
2-1-41C
2-1-42V
TERMINAL UNIT SCHEDULE
2-1-48V
1-1-83V
2-1-47V
2-1-49V
2-1-50V
2-1-51V
2-1-52V
2-1-53V
2-1-54V
2-1-55V
2-1-56V
2-1-57V
2-1-58V
2-1-59V
2-1-60V
2-1-61V
2-1-62V
2-1-63V
2-1-64V
2-1-65V
2-1-66V
2-1-67V
2-1-68V
2-1-69V
2-1-70V
2-1-71C
2-1-72V
1-1-73V
1-1-74V
1-1-75V
1-1-76V
1-1-77V
1-1-78V
1-1-79V
1-1-80V
1-1-81V
1-1-82V
2-1-43V
1-1-84C
1-1-85V
1-1-86V
GENERAL NOTES
1. BOXES SHALL HAVE PIPE CONNECTIONS ON SAME SIDE AND BE FOR SOLDERED FITTINGS.
2. COIL AND BOX SIZE MAY BE INCREASED TO MEET REQUIRED CONDITIONS; BUT SHALL NOT BE DECREASED FROM SIZE SHOWN.
3. BOXES SHALL BE SET FOR MAXIMUM CFM SHOWN ON PLANS.
4. DUCT CONNECTIONS TO BOXES SHALL BE SAME SIZE AS BOX INLET UNLESS SHOWN OTHERWISE.
5. MAXIMUM WATER PRESSURE DROP SHALL BE 4 FEET.
6. VARIABLE VOLUME BOXES SHALL OPERATE DOWN TO 50% OF MAXIMUM FLOW.
7. CONSTANT VOLUME BOXES SHALL BE THE SAME BOX USED FOR VARIABLE VOLUME BOX EXCEPT CFM SHALL BE LOCKED AT CAPACITY SHOWN. BOX SHALL NOT OPERATE AS
VARIABLE VOLUME.
8. CONTROLS SHALL BE DDC PROVIDED BY CONTROLS CONTRACTOR AND INSTALLED BY BOX MANUFACTURER.
9. BASIS OF DESIGN SHALL BE SINGLE DUCT VARIABLE VOLUME TERMINAL UNIT.
10. MAXIMUM NC LEVEL OF 30 ON ALL BOXES. PROVIDE SOUND ATTENUATOR AS REQUIRED.
11. PROVIDE DIFFERENTIAL AIRFLOW SWITCH.
12. "HC" DEPICTS TERMINAL BOXES THAT SHALL BE SUPPLIED WITH HIGH CAPACITY COILS.
REHEAT
ROWS
WATER
RUNOUT
SIZE
UNIT SIZE
AIR
RUNOUT
SIZE
ROOM NUMBER AND NAME
MIN.MAX.
WATER
PRESSURE
DROP(FT)
L.W.T.
(°F)
E.W.T.
(°F)MBHGPM
MINIMUM
OPERATING
PD (in.wg)
HEATING
L.A.T.
(°F)
E.A.T.
(°F)
CFMTERMINAL
NO.
GENERAL NOTES
1. BOXES SHALL HAVE PIPE CONNECTIONS ON SAME SIDE AND BE FOR SOLDERED FITTINGS.
2. COIL AND BOX SIZE MAY BE INCREASED TO MEET REQUIRED CONDITIONS; BUT SHALL NOT BE DECREASED FROM SIZE SHOWN.
3. BOXES SHALL BE SET FOR MAXIMUM CFM SHOWN ON PLANS.
4. DUCT CONNECTIONS TO BOXES SHALL BE SAME SIZE AS BOX INLET UNLESS SHOWN OTHERWISE.
5. MAXIMUM WATER PRESSURE DROP SHALL BE 4 FEET.
6. VARIABLE VOLUME BOXES SHALL OPERATE DOWN TO 50% OF MAXIMUM FLOW.
7. CONSTANT VOLUME BOXES SHALL BE THE SAME BOX USED FOR VARIABLE VOLUME BOX EXCEPT CFM SHALL BE LOCKED AT CAPACITY SHOWN. BOX SHALL NOT OPERATE AS
VARIABLE VOLUME.
8. CONTROLS SHALL BE DDC PROVIDED BY CONTROLS CONTRACTOR AND INSTALLED BY BOX MANUFACTURER.
9. BASIS OF DESIGN SHALL BE SINGLE DUCT VARIABLE VOLUME TERMINAL UNITS.
10. MAXIMUM NC LEVEL OF 30 ON ALL BOXES. PROVIDE SOUND ATTENUATOR AS REQUIRED.
11. PROVIDE DIFFERENTIAL AIRFLOW SWITCH.
12. "HC" DEPICTS TERMINAL BOXES THAT SHALL BE SUPPLIED WITH HIGH CAPACITY COILS.
REHEAT
ROWS
WATER
RUNOUT
SIZE
UNIT SIZE
AIR
RUNOUT
SIZE
ROOM NUMBER AND NAME
MIN.MAX.
WATER
PRESSURE
DROP(FT)
L.W.T.
(°F)
E.W.T.
(°F)MBHGPM
MINIMUM
OPERATING
PD (in.wg)
HEATING
L.A.T.
(°F)
E.A.T.
(°F)
CFMTERMINAL
NO.
0.04
0.01
0.13
0.13
0.07
0.1
0.1
0.11
0.11
0.1
0.03
0.1
0.11
0.11
0.08
0.06
0.06
0.16
0.11
0.11
0.07
0.09
0.09
0.07
0.28
0.08
0.04
0.03
0.09
0.78
1.53
1.56
0.76
1.42
1.98
2.05
0.97
0.4
0.67
2.95
3.48
3.83
0.49
0.93
0.73
1.15
2.07
1.45
0.82
0.89
0.91
1.78
3.78
0.49
0.45
0.41
0.91
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
5.72
14.91
15.21
7.39
13.81
19.33
19.99
9.46
5.22
5.92
21.57
33.96
27.99
4.77
7.67
7.09
14.08
20.15
14.13
8.00
8.68
8.84
12.97
46.1
4.77
4.43
3.95
8.84
0.31
1.56
1.61
0.39
0.60
1.38
3.16
0.57
0.1
0.24
4.38
2.45
2.65
0.15
0.4
0.36
0.25
3.2
1.43
0.44
0.5
0.51
1.47
2.82
0.15
0.13
0.11
0.51
3/4"
TELECOM C114
STAFF WORK AREA C117, OFFICE AT (2)C113
LIBRARY C119, DEN C120
ELEC C124
OFFICE SW B167, OFFICE SW B166
CORRIDOR C101
FAMILY ROOM B150
FAMILY ROOM B151
PEDS FAMILY ROOM B152
CONFERENCE B160
WAITING B146
OFFICE PA B125, EXAM B124
CORRIDOR B103
EXAM B141
STAFF WORK AREA B126
MEDS B127
RECEPTION B145, SHOWER B144
VESTIBULE A131
PANTRY B116, KITCHEN B114
DINING B117
DINING B117
CORRIDOR B101, CORRIDOR B102
OFFICE DR B140
CORRIDOR A101
TELECOM A115
NURSE MGR B106, OFFICE B107
LIBRARY A119, DEN A120
STAFF WORK AREA A114
OFFICE AT (2) A112
0.13
0.1
0.12
0.1
0.11
0.1
0.02
0.01
0.12
0.14
0.03
0.09
0.09
0.11
0.1
0.12
0.12
0.09
1.03
0.92
1.38
2.03
0.31
0.6
0.65
0.55
1.35
0.50
2.02
1.98
1.00
1.48
1.35
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
1 HC
10.04
9.00
9.00
9.00
9.75
13.48
19.83
19.5
2.99
5.89
6.37
5.38
13.15
4.92
19.66
19.33
9.61
14.45
13.15
0.62
0.53
0.53
0.53
0.6
1.33
3.12
3.04
0.07
0.2
0.23
0.18
1.28
0.15
3.08
0.58
1.48
1.28
CORRIDOR A148
LAUNDRY A135
LIVING ROOM A134, NUTRITION A133
GROUP B109
REC B108
OFFICE MANAGER B123
SMALL GROUP B122
VESTIBULE B121
ADMIT NURSE B118, OFFICE B120
BREAK B113
GROUP B110
GROUP B154
GROUP B153
CORRIDOR B105
WOMENS LOUNGE B138
CODE SUPPY B129
ELEC B130
CORRIDOR 148
STAFF BREAK B157, STORAGE B156
FITNESS CENTER B155
CORRIDOR C167
OFFICE 151
LIVING ROOM C134, LAUNDRY C135
NUTRITION C133
1 HC
1 HC
1 HC
1 HC
360 180 180 8 8 0.1 0.9255
360 180 180 8 8 0.1 0.9255
300 150 150 8 8 0.07 0.82 1 HC 8.00 0.4418055
300 150 150 8 8 0.07 0.82 1 HC 8.00 0.4418055
750 375 375 12 12 0.11 2 1 HC 19.5 3.0418055
1-1-90V
1-1-87V
1-1-88V
1-1-89V
1-1-91V
1-1-92V
1-1-93V NOT USED
745 375 375 12 12 0.1 2 1 HC 19.5 160 3.0418055
300 150 150 8 8 55 0.07 0.82 1 HC 8.00 180 160 0.44
300 150 150 8 8 55 0.07 0.82 1 HC 8.00 180 160 0.44
300 150 150 8 8 55 0.07 0.82 1 HC 8.00 180 160 0.44
300 150 150 8 8 55 0.07 0.82 1 HC 8.00 180 160 0.44
205 205 8 8 55 0.12 1.00 1 HC 9.75 180 160
300 150 150 8 8 55 0.07 0.82 1 HC 8.00 180 160 0.44
340 170 170 8 8 55 0.08 0.79 1 7.67 180 160 0.41
205 100 100 6 6 55 0.08 0.49 1 4.77 180 160 0.15
200 100 100 6 6 55 0.08 0.49 1 4.77 180 160 0.15
570 285 285 10 10 0.11 1.47 1 HC 14.45 1.4618055
605 300 300 10 10 0.12 1.51 1 HC 14.76 1.5318055
300 150 150 8 8 55 0.07 0.82 1 HC 8.00 180 0.44
750 375 375 12 12 0.11 2.00 1 HC 19.5 3.0418055
300 150 150 8 8 55 0.07 0.82 1 HC 8.00 180 0.44
380 180 180 8 8 0.1 0.92 1 HC 9.00 0.5318055
470 235 235 8 8 0.15 1.09 10.60 0.6818055 1 HC
300 150 150 8 8 55 0.07 0.82 1 HC 8.00 180 0.44
255 130 130 6 6 55 0.13 0.58 1 5.63 180 0.19
270 135 135 6 6 55 0.16 0.70 1HC 6.50 180 0.24
360 180 180 8 8 0.1 0.92 1 HC 9.00 0.5318055
360 180 180 8 8 0.1 0.92 1 HC 9.00 0.5318055
640 320 320 10 10 55 0.14 1.57 1 HC 15.36 180 1.63
195 100 100 6 6 55 0.07 0.49 1 4.77 180 0.15
2-1-44V
2-1-45V
2-1-46V
550 275 275 10 10 0.11 1.43 1 HC 13.97 160 1.41
CORRIDOR C121
VESTIBULE C131, CLEAN LINEN C149
55 180
300 150 150 8 8 55 0.07 0.82 1 HC 8.00 180 160 0.44
345 175 175 8 8 55 0.09 0.91 1 HC 8.84 180 160 0.51
N/A N/A N/A N/A N/A N/A N/A N/A55
N/A N/A N/A N/A N/A N/A N/A N/A55
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
14 14 0.11 3.83 1 27.99 160 2.6518055
2-1-94V OFFICE C152225 115 115 6 6 0.11 0.60 1HC 5.89 0.2018055 3/4"
RESIDENT ROOM A108, RESIDENT
BATHROOM A110
RESIDENT ROOM A102, RESIDENT
BATHROOM A104, RESIDENT ROOM A106
RESIDENT ROOM A103, RESIDENT
BATHROOM A105, RESIDENT ROOM A107
RESIDENT ROOM A109, RESIDENT
BATHROOM A111, RESIDENT ROOM A113
STORAGE B163, OFFICE SW B164,
OFFICE SW B165
RESIDENT ROOM C108, RESIDENT
BATHROOM C110, RESIDENT ROOM C112
RESIDENT ROOM C106, RESIDENT
BATHROOM C104, RESIDENT ROOM C102
RESIDENT ROOM C103, RESIDENT
BATHROOM C105, RESIDENT ROOM C107
RESIDENT ROOM C109, RESIDENT
BATHROOM C111
SOILED UTILITY & LINEN C122, CLEAN
SUPPLY C123
RESIDENT ROOM C126, RESIDENT
BATHROOM C128, RESIDENT ROOM C130
RESIDENT ROOM C129, RESIDENT
BATHROOM C127, RESIDENT ROOM C125
RESIDENT ROOM C154, RESIDENT
BATHROOM C153
RESIDENT ROOM C156, RESIDENT
BATHROOM C158, RESIDENT ROOM C160
RESIDENT ROOM C162, RESIDENT
BATHROOM C164, RESIDENT ROOM C166
RESIDENT ROOM C165, RESIDENT
BATHROOM C163, RESIDENT ROOM C161
RESIDENT ROOM C159, RESIDENT
BATHROOM C157, RESIDENT ROOM C155
RESIDENT ROOM C140, RESIDENT
BATHROOM C138
RESIDENT ROOM C142, RESIDENT
BATHROOM C144, RESIDENT ROOM C146
RESIDENT ROOM C147, RESIDENT
BATHROOM C145, RESIDENT ROOM C143
RESIDENT ROOM C141, RESIDENT
BATHROOM C139, RESIDENT ROOM C137
RESIDENT ROOM A137, RESIDENT
BATHROOM A139, RESIDENT ROOM A141
RESIDENT ROOM A143, RESIDENT
BATHROOM A145, RESIDENT ROOM A147
RESIDENT ROOM A146, RESIDENT
BATHROOM A144, RESIDENT ROOM A142
RESIDENT ROOM A140, RESIDENT
BATHROOM A138
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
100 160
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
ELEC A124200 100 - 6 6 55 0.08 - - - - - - --
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100
Charlotte, NC 28212 704 531 3000
704 531 3001 FAX
Firm License Number: F-0674
This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.
It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.
It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.
Project
Salisbury, NC City, State
VA Contract Number
Drawn By
Checked By
Seal / Signature
Sheet Title
Date
Sheet Number
Architect of Record
5960 Fairview Road Suite 500 Charlotte, NC 28210
887.3500
887.3507 fax
Issued For
December 29, 2015
CONSTRUCTION
COLEJENEST & STONE, P.A.
200 South Tryon Street, Suite 1400 Charlotte, North Carolina 28202
704.376.1555 PHONE
704.376.7851 FAX
CIVIL/LANDSCAPING:
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212
704.531.3000 PHONE
MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:
Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031
704.987.9114 PHONE
704.987.9938 FAX
STRUCTURAL:
Program Manager
13620 Reese Blvd.
Suite 100
Huntersville, NC 28078
401.2040
401.2067 fax
CE PROJ # 3132
VAMC Salisbury Building 11 - Additions & Renovations
VA246-12-C-0089
M-002A
MECHANICAL -
SCHEDULES
SMN
SERVICES LOCATION CFM
FAN SCHEDULE
STARTER DISC. SW.
EF-1
FAN NO. FAN RPM
EXTERNAL
STATIC PRESS.
IN W.G. FAN WHEEL TYPE
MOTOR
HP/VOLT/PHASE
DRIVE
TYPE
FAN TYPE CONTROL SWITCH &
INTERLOCK TYPE
EF-2
NOT USED
NOT USED
GROUND FLOOR EXHAUST ROOF 1,680 1,614 1.5 BELT ROOF MOUNTED CENTRIFUGAL CONSTANTBACKWARD INCLINED 1 / 208V / 3øEF-3
NOTES:
1. PROVIDE BACKDRAFT DAMPER, BIRD SCREEN AND ROOF CURB (FOR ROOF MOUNTED FANS).
2. PROVIDE VIBRATION ISOLATORS, SEE SPECIFICATIONS.
3. COORDINATE HEIGHT OF ROOF CURB WITH ROOFING CONTRACTOR
4. BASIS OF DESIGN PER FAN: EF-1 AND EF-2 - GREENHECK TBI-CA-5L20-75, EF-3 - GREENHECK GB-141-10, EF-4 AND EF-5 - FANTECH FR-140.
HEAT TRANSFER PACKAGE SCHEDULE
UNIT
NUMBER
MINIMUM
CAPACITY
BTU/HR
TUBE SIDE
E.W.T. °F
HTP-1
SHELL SIDE PUMPS
L.W.T. °F MAX. P.D.
PSI
GPM
MINIMUM
STEAM PSI. &
#/HR. GPM FT. HEAD HP
LOCATION REMARKS
1,200,000 160 180 120 1.4 15/1,221 (2) @ 120 55' EACH 3 CRAWLSPACE
NOTES:
HEAT
EXCHANGER
MODEL NO.
WS-1002-200-1
PUMP SIZE
EC ECSYMBOL SIZE TYPE
111-250 CFM 10"x6"
0-110 CFM 8"x4"
251-480 CFM 14"x8"
481-650 CFM 18"x10"
651-835 CFM 18"x12"
836-1400 CFM 24"x18"
CFM
A
CFM
B
CFM
C
CFM
D
CFM
E
CFM
F
SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
226-450 CFM 12"x10"
0-225 CFM 10"x6"
451-700 CFM 18"x12"
701-900 CFM 24"x12"
901-1180 CFM 30"x12"
1181-1350 CFM 36"x12"
SYMBOL CFM RANGE & MODULE SIZE
SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
CFM
CFM
CFM
CFM
CFM
CFM
TYPE
SYMBOL SIZE TYPE
111-250 CFM 10"x8"
0-110 CFM 8"x4"
251-480 CFM 14"x10"
481-650 CFM 18"x12"
651-835 CFM 20"x14"
836-1400 CFM 24"x18"
LOUVERED RETURN SIDEWALL
CFM
CFM
CFM
CFM
CFM
CFM
SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
SYMBOL REGISTER SIZE 24"x24" TYPE
136-210 CFM 8" ROUND NECK
0-135 CFM 6" ROUND NECK
211-325 CFM 10" ROUND NECK
326-475 CFM 12" ROUND NECK
651-840 CFM 16" ROUND NECK
841-2000 CFM 22"x22" NECK
476-650 CFM 14" ROUND NECK
CFM
A
CFM
B
CFM
C
CFM
D
CFM
E
CFM
F
CFM
G
NOTES:
1. SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
2. REGISTERS LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH
SURFACE MOUNTED FRAMES.
SYMBOL REGISTER SIZE 24"x24" TYPE
136-210 CFM 8" ROUND NECK
0-135 CFM 6" ROUND NECK
PERFORATED FACE RETURN AIR
211-325 CFM 10" ROUND NECK
326-475 CFM 12" ROUND NECK
651-840 CFM 16" ROUND NECK
841-2000 CFM 22"x22" NECK
476-650 CFM 14" ROUND NECK
CFM
CFM
CFM
CFM
CFM
CFM
CFM
NOTES:
1. SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
2. GRILLES LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE
MOUNTED FRAMES.
12"x12" REGISTER
CFM
H
0-135 CFM 6"� NECK
SYMBOL
CFM RANGE, FACE SIZE, & NECK SIZE
TYPE
136-210 CFM 9"x9" FACE 8" NECK
0-135 CFM 6"x6" FACE 6"� NECK
LOUVERED FACE DIRECTIONAL
211-325 CFM 12"x12" FACE 10" NECK
326-475 CFM 12"x12" FACE 12" NECK
476-650 CFM 15"x15" FACE 14" NECK
CFM
CFM
CFM
CFM
CFM
CFM
CFM
650-840 CFM 18"x18" FACE 16" NECK
841-1125 CFM 18"X18" FACE & NECK
NOTES:
1. SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
2. DIFFUSERS LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE
MOUNTED FRAMES.
3. PROVIDE ROUND NECK ADAPTER.
TYPICAL MODULE SIZE - 24"x24"
STEAM PRESSURE REDUCING VALVE STATION (CRAWL SPACE)
NOTES
1. PROVIDE ORIFICE TYPE FLOW METER UPSTREAM OF PIPE FLOW AS
REQUIRED.
2. GATE VALVES SHOULD BE FULLY OPEN TO PROVIDE UNRESTRICTED FLOW.
3. PROVIDE PILOT OPERATED REGULATORS.
4. PROVIDE DRIP PAN ELBOW FROM SRV-1A. OUTLET SIZE OF SRV-1A SHALL MATCH INLET OF DRIP PAN ELBOW.
5. SIZING VARIES BY MANUFACTURER. PERFORMACE SHALL BE VERIFIED.
PRV-#
ENTERING
PRESSURE
(psi)
LEAVING
PRESSURE
(psi)
STEAM CAPACITY
(LBS/HR)
VALVE
SIZE
(in)
PRESSURE REDUCING VALVES
PRV-1A 100 15 1,060 1-1/4"
SRV-#
DISCHARGE
PRESSURE
(psi)
ACTUAL STEAM
FLOW (LBS/HR) INLET/OUTLET SIZES
SRV-1A 20 3,375
2"INLET/3" OUTLET
PRV-1B 100 15 2,120 1-1/2"
PORT
TYPE
NORMAL
FULL
STRAINER
MEDIUM
PRESSURE
TRAP PRV-1B
2"
10 PIPE
DIAMETERS
MINIMUM
PRESSURE SENSING LINES
REDUCED STEAM
PRESSURE SUPPLY
TO EQUIPMENT.
PITCH DN.
STEAM
SUPPLY
TO LPC
SAFETY RELIEF
VALVE - SRV-1A
PRV-1A
PRESSURE REDUCING VALVE STATION SCHEDULE
SAFETY RELIEF VALVE
11/4"
11/2"
11/2" 11/2"
21/2"
4"
21/2"21/2"
(SEE NOTE 5)
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE RETURN AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE RETURN AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE RETURN AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE RETURN AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE RETURN AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE RETURN AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE EXHAUST AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE EXHAUST AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE EXHAUST AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE EXHAUST AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE EXHAUST AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE EXHAUST AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE EXHAUST AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
PERFORATED FACE EXHAUST AIR
CEILING DIFFUSER (STEEL
CONSTRUCTION)
DIFFUSERS (STEEL
CONSTRUCTION)
LOUVERED FACE DIRECTIONAL
DIFFUSERS (STEEL
CONSTRUCTION)
LOUVERED FACE DIRECTIONAL
DIFFUSERS (STEEL
CONSTRUCTION)
LOUVERED FACE DIRECTIONAL
DIFFUSERS (STEEL
CONSTRUCTION)
LOUVERED FACE DIRECTIONAL
DIFFUSERS (STEEL
CONSTRUCTION)
LOUVERED FACE DIRECTIONAL
DIFFUSERS (STEEL
CONSTRUCTION)
LOUVERED FACE DIRECTIONAL
DIFFUSERS (STEEL
CONSTRUCTION)
FIXED LOUVER (45° DEFLECTION)
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED RETURN SIDEWALL
FIXED LOUVER (45° DEFLECTION)
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED RETURN SIDEWALL
FIXED LOUVER (45° DEFLECTION)
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED RETURN SIDEWALL
FIXED LOUVER (45° DEFLECTION)
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED RETURN SIDEWALL
FIXED LOUVER (45° DEFLECTION)
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED RETURN SIDEWALL
FIXED LOUVER (45° DEFLECTION)
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED EXHAUST SIDEWALL
FIXED LOUVER (45° DEFLECTION)
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED EXHAUST SIDEWALL
FIXED LOUVER (45° DEFLECTION)
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED EXHAUST SIDEWALL
FIXED LOUVER (45° DEFLECTION)
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED EXHAUST SIDEWALL
FIXED LOUVER (45° DEFLECTION)
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED EXHAUST SIDEWALL
FIXED LOUVER (45° DEFLECTION)
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED EXHAUST SIDEWALL
FIXED LOUVER (45° DEFLECTION)
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED SUPPLY SIDEWALL
DOUBLE DEFLECTION
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED SUPPLY SIDEWALL
DOUBLE DEFLECTION
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED SUPPLY SIDEWALL
DOUBLE DEFLECTION
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED SUPPLY SIDEWALL
DOUBLE DEFLECTION
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED SUPPLY SIDEWALL
DOUBLE DEFLECTION
3/4" SPACING (STEEL
CONSTRUCTION)
LOUVERED SUPPLY SIDEWALL
DOUBLE DEFLECTION
3/4" SPACING (STEEL
CONSTRUCTION)
3"x11/2"x8"
NOT USEDEF-4
CRAWL SPACE EXHAUST CRAWL SPACE 3 115 2,850 0.6 DIRECT INLINE EXHAUST FAN INTERLOCKED WITH HUMIDISTATFORWARD CURVE 61W / 115V / 1 øEF-5 N/A EC
1. PACKAGE TO INCLUDE DUPLEX PACKAGED CONDENSATE PUMPS (2 @ 1
3HP), AIR SEPARATOR WITH STRAINER, HIGH CAPACITY AUTOMATIC AIR VENT, STEAM CONTROL VALVE, COMBINATION
PRV AND PRV WITH FAST FILL 3
4" MAKE UP LINE, STEAM TRAP, STEAM PRESSURE RELIEF VALVE, BLADDER TYPE EXPANSION TANK, CONTROL PANEL WITH VFD'S AND DISCONNECTS.
PITCH
DOWN
STEAM PRESSURE REDUCING VALVE STATION (CRAWL SPACE)
NOTES
1. PROVIDE ORIFICE TYPE FLOW METER UPSTREAM OF PIPE FLOW AS
REQUIRED.
2. GATE VALVES SHOULD BE FULLY OPEN TO PROVIDE UNRESTRICTED FLOW.
3. PROVIDE PILOT OPERATED REGULATORS.
4. PROVIDE DRIP PAN ELBOW FROM SRV-1A. OUTLET SIZE OF SRV-1A SHALL MATCH INLET OF DRIP PAN ELBOW.
5. SIZING VARIES BY MANUFACTURER. PERFORMACE SHALL BE VERIFIED.
PRV-#
ENTERING
PRESSURE
(psi)
LEAVING
PRESSURE
(psi)
STEAM CAPACITY
(LBS/HR)
VALVE
SIZE
(in)
PRESSURE REDUCING VALVES
PRV-2A 100 15 1,200 1-1/4"
SRV-#
DISCHARGE
PRESSURE
(psi)
ACTUAL STEAM
FLOW (LBS/HR) INLET/OUTLET SIZES
SRV-2A 20 4,000
2"INLET/3" OUTLET
PRV-2B 100 15 2,500 1-1/2"
PORT
TYPE
NORMAL
FULL
STRAINER
MEDIUM
PRESSURE
TRAP PRV-2B
2"
10 PIPE
DIAMETERS
MINIMUM
PRESSURE SENSING LINES
REDUCED STEAM
PRESSURE SUPPLY
TO EQUIPMENT.
PITCH DN.
STEAM
SUPPLY
TO LPC
SAFETY RELIEF
VALVE - SRV-2A
PRV-2A
PITCH
DOWN
PRESSURE REDUCING VALVE STATION SCHEDULE
SAFETY RELIEF VALVE
11/4"
11/2"
11/2" 11/2"
21/2"
4"
21/2"21/2"
(SEE NOTE 5)
EF-6
EF-7
1ST FLOOR GENERAL EXHAUST ROOF 750 1,990 0.5 BELT CONSTANT EC ECBACKWARD INCLINED 1_ 3 /115V/1ø
1ST FLOOR GENERAL EXHAUST ROOF 1,435 1,227 0.7 BELT CONSTANTBACKWARD INCLINED 1_
2 /115V/1øEF-8 EC EC
1ST FLOOR GENERAL EXHAUST ROOF 140 1,221 0.5 BELT1_
4 /115V/1øEF-9 EC
1ST FLOOR GENERAL EXHAUST ROOF 410 1,397 0.5 BELT1_
4 /115V/1øEF-10 EC
EF-11
EF-12
1ST FLOOR GENERAL EXHAUST ROOF 960 1,131 0.5 BELT CONSTANT EC EC
EC EC
BACKWARD INCLINED 1_
4 /115V/1ø
1ST FLOOR GENERAL EXHAUST ROOF 1,430 1,083 0.4 BELT CONSTANTBACKWARD INCLINED 1_
3 /115V/1ø
1ST FLOOR GENERAL EXHAUST ROOF 760 2,009 0.5 BELT ROOF MOUNTED CENTRIFUGAL CONSTANTBACKWARD INCLINED 1_ 3 /115V/1øEF-13 EC EC
1ST FLOOR GENERAL EXHAUST ROOF 810 2,231 0.7 BELT1_
2 /115V/1øEF-14 EC
1ST FLOOR GENERAL EXHAUST ROOF 685 2,007 0.7 BELT CONSTANTBACKWARD INCLINED 1_
3 /115V/1ø EC EC
1ST FLOOR GENERAL EXHAUST ROOF 680 1,704 0.3 BELT ROOF MOUNTED CENTRIFUGAL CONSTANTBACKWARD INCLINED 1_ 4 /115V/1øEF-15 EC EC
1ST FLOOR GENERAL EXHAUST ROOF 1,265 1,089 0.6 BELT1_
2 /115V/1øEF-16 ECROOF MOUNTED CENTRIFUGAL
ROOF MOUNTED CENTRIFUGAL
ROOF MOUNTED CENTRIFUGAL
ROOF MOUNTED CENTRIFUGAL
ROOF MOUNTED CENTRIFUGAL
ROOF MOUNTED CENTRIFUGAL
ROOF MOUNTED CENTRIFUGAL
ROOF MOUNTED CENTRIFUGAL
ROOF MOUNTED CENTRIFUGAL
BACKWARD INCLINED
BACKWARD INCLINED
BACKWARD INCLINED
BACKWARD INCLINED CONSTANT
CONSTANT
CONSTANT
CONSTANT EC
EC
EC
EC
MODEL
GREENHECK GB-141-10
FANTECH FR-140
GREENHECK GB-101HP-3
GREENHECK GB-101HP-3
GREENHECK GB-161HP-5
GREENHECK G-097-VG
GREENHECK GB-101HP-4
GREENHECK GB-121-4
GREENHECK GB-161HP-3
GREENHECK GB-101HP-3
GREENHECK GB-101HP-5
GREENHECK GB-101HP-4
GREENHECK GB-161HP-5
SIDEWALL EXHAUST REGISTER
SIDEWALL SUPPLY REGISTER
SIDEWALL RETURN REGISTER
PERFORATED EXHAUST REGISTERS
PERFORATED RETURN REGISTERS
LOUVERED SUPPLY DIFFUSER
NTS
NTS
M
P
DPT
T
TO
SPACE
MERV 15
FILTER
SAF VFD
COOLING COIL
MERV 8
PRE-FILTER
LOW LIMIT
TEMP SWITCH
HIGH DISCHARGE
PRESSURE SWITCH
T
DISCHARGE AIR TEMP
SENSOR
ECONOMIZER
DAMPER
T
MIXED AIR
TEMP
SENSOR
SP
HEATING
COIL
H
FS
MECONOMIZER
OUTSIDE AIR
DAMPER
H
HUMIDITY HIGH LIMIT
SENSOR
DPT
AFMS-1
HUMIDITY
SENSOR
LEGEND
AFMS - AIR FLOW MONITORING STATION
DD - DUCT DETECTOR
FS - FIRE STAT
P - HIGH DISCHARGE PRESSURE SWITCH
VFD - VARIABLE FREQUENCY DRIVE
DPS - DIFFERENTIAL PRESSURE SENSOR
H - HUMIDITY SENSOR
SP - STATIC PRESSURE SENSOR
T - TEMPERATURE SENSOR
GEAF - GENERAL EXHAUST AIR FAN
HXEAF - HEAT EXCHANGER EXHAUST AIR FAN
HXOAF - HEAT EXCHANGER OUTSIDE AIR FAN
SAF - SUPPLY AIR FAN
RAF - RETURN AIR FAN
SUPPLY
AIR FANPOWERED
EXHAUST FAN
RETURN AIR
OUTSIDE AIR DAMPER
PRE-FILTERS SECTION
HEATING COIL
COOLING COIL
ACCESS/DISCHARGE AIR PLENUM
AIR DIFFUSER FINAL FILTER SECTION
SUPPLY AIR DAMPERACCESS SECTIONACCESS SECTION
(ECONOMIZER DAMPER
ON OPPOSITE SIDE OF UNIT)
EXHAUST AIR
DAMPER
ECONOMIZER
MEAF VFD
AFMS-2
T
H
DD
M
FROM SPACE
OUTSIDE AIR
RETURN AIR DAMPER
AFMS-3
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100
Charlotte, NC 28212 704 531 3000
704 531 3001 FAX
Firm License Number: F-0674
This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.
It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.
It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.
Project
Salisbury, NC City, State
VA Contract Number
Drawn By
Checked By
Seal / Signature
Sheet Title
Date
Sheet Number
Architect of Record
5960 Fairview Road Suite 500 Charlotte, NC 28210
887.3500
887.3507 fax
Issued For
December 29, 2015
CONSTRUCTION
COLEJENEST & STONE, P.A.
200 South Tryon Street, Suite 1400 Charlotte, North Carolina 28202
704.376.1555 PHONE
704.376.7851 FAX
CIVIL/LANDSCAPING:
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212
704.531.3000 PHONE
MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:
Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031
704.987.9114 PHONE
704.987.9938 FAX
STRUCTURAL:
Program Manager
13620 Reese Blvd.
Suite 100
Huntersville, NC 28078
401.2040
401.2067 fax
CE PROJ # 3132
VAMC Salisbury Building 11 - Additions & Renovations
VA246-12-C-0089
M-002B
MECHANICAL -
SCHEDULES
SMN
DN
NTS
A
B
J
S
NOTES:
1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR…