This is a Statement of Work (SOW) for preventive maintenance and cleaning services on 41 direct expansion (DX) HVAC and refrigeration units located across 14 locations at the Louis A. Johnson Veterans Medical Center in Clarksburg, West Virginia. The equipment inventory ranges from 1.5-ton ductless mini-splits to a 273-ton air-cooled chiller and includes condensing units, packaged rooftop units, precision cooling/CRAC units, and multiple refrigerant types (R-410A, R-134A, R-22, R-407C, R-404A). The contract is structured as a firm-fixed-price/time-and-materials arrangement with a not-to-exceed cost basis for multiple contract line items, covering a base year plus three option years. The Department of Veterans Affairs' contract officer is Keysha Gorman (Keysha.Gorman74@va.gov, 410-637-1509), and capability statements are due May 18, 2026, at 8:00 AM Eastern Time.
The SOW is currently issued as a Request for Information (RFI) pre-solicitation notice; responses are not binding offers and do not constitute a solicitation under FAR 15.201(e). Responders must include business size and SAM UEI Number with their capability statements. Services must comply with manufacturer instructions for use and a comprehensive regulatory baseline including NFPA 70E-2024, NFPA 70B-2023, NFPA 99-2024, ASHRAE 170-2025, ASHRAE 180-2018, The Joint Commission EC.02.05.01/.02, VHA Directives 1028 and 1061(4), VA PG-18-10, and EPA AIM Act requirements. Primary objectives include maintaining all units in peak operating condition with full regulatory compliance, sustaining TJC compliance through documentation of ventilation parameters, supporting the facility's electrical maintenance program, managing regulated refrigerants per EPA Section 608 standards, and inspecting and cleaning condensate drain systems and humidifier sections per Legionella prevention protocols. The NAICS code is 238220 (Plumbing, Heating & AC Services), and the product service code is J045.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK | HVAC / DX PM Services — 41 Units | LAJ VAMC | Document No. LAJ-ENG-SOW-HVAC-PM-2026-001 Rev.1 FOR OFFICIAL USE ONLY – PRE-AWARD SENSITIVE
| SUBJECT* |
| PREVENTIVE MAINTENANCE & CLEANING- 41 DX HVAC |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 21201 |
| SOLICITATION NUMBER* |
| 36C24526Q0514 |
| RESPONSE DATE/TIME/ZONE |
| 05-18-2026 8am EASTERN TIME, NEW YORK, USA |
| ARCHIVE |
| 30 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
| SET-ASIDE |
| SBA |
| PRODUCT SERVICE CODE* |
| J045 |
| NAICS CODE* |
| 561210 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
VAMC
10 N Greene St Baltimore MD 21201
POINT OF CONTACT*
Contract Officer Keysha Gorman Keysha.Gorman74@va.gov 410-637-1509
PLACE OF PERFORMANCE
| ADDRESS |
| Louis A. Johnson Veterans Medical Center |
1 Medical Center Drive
Clarksburg, WV
| POSTAL CODE |
| 26301-4155 |
| COUNTRY |
| USA |
ADDITIONAL INFORMATION
| AGENCY’S URL |
| https://www.va.gov/clarksburg-health-care/locations/louis-a- |
| URL DESCRIPTION |
| Veterans Affairs Hospital |
| AGENCY CONTACT’S EMAIL ADDRESS |
| Keysha.Gorman74@va.gov |
| EMAIL DESCRIPTION |
| Keysha Gorman |
Sources Sought Notice Sources Sought Notice
DESCRIPTION
| *= Required Field |
| Sources Sought Notice |
Sources Sought Notice
DISCLAIMER
This RFI is issued solely for information and planning purposes only and does not constitute a solicitation. All information received in response to this RFI that is marked as proprietary will be handled accordingly. In accordance with FAR 15.201(e), responses to this notice are not offers and cannot be accepted by the Government to form a binding contract. Responders are solely responsible for all expenses associated with responding to this RFI.
Submit your capability statement by May 18, 2026, to Keysha.Gorman74@va.gov. For your information to be accepted, include in your information business size and SAM’s UEI Number.
This action is for a base plus three option year contract.
Page 1 of Page 1 of
STATEMENT OF WORK & IGCE
Preventive Maintenance & Cleaning — 41 DX HVAC Units | IAW Manufacturers' IFU
Mini-Splits • Condensing Units • Packaged RTUs • Precision Cooling / CRAC • Air-Cooled Chillers Refrigerants: R-410A · R-134A · R-22 · R-407C · R-404A | 1.5 Ton – ~273 Ton | 41 Units | 14 Locations
Regulatory Baseline: NFPA 70E-2024 • NFPA 70B-2023 • NFPA 99-2024 • ASHRAE 170-2025 • ASHRAE 180-2018 • TJC EC.02.05.01/.02 • VHA Dir. 1028 / 1061(4) • VA PG-18-10 (Rev. 3/1/2024) • EPA AIM Act
| Document No. |
| LAJ-ENG-SOW-HVAC-PM-2026-001 |
| Solicitation # |
| [TBD at Award] |
| Prepared By |
| Deputy Chief Engineer, FMS |
| Rev. Date |
| March 2026 |
| Total Units |
| 41 DX Units / 14 Locations |
| Contract Type |
| FFP / T&M NTE / Cost (CLINs) |
| Period of Perf. |
| Base Year + 3 Option Years |
| NAICS |
| 238220 – Plumbing, Heating & AC |
SECTION 1 — PURPOSE, SCOPE & REGULATORY FOUNDATION
1.1 Purpose
This Statement of Work (SOW) establishes performance requirements for a qualified mechanical contractor to provide preventive maintenance (PM), cleaning, inspection, and regulatory-compliance services for forty-one (41) direct expansion (DX) HVAC and refrigeration units at the Louis A. Johnson (LAJ) VA Medical Center, Clarksburg, West Virginia (VISN 5 / NCO 5). The equipment inventory spans 14 locations and ranges in capacity from 1.5-ton ductless mini-splits to a 273-ton York YVAA air-cooled chiller. Services shall be performed in strict accordance with each unit's manufacturer Instructions for Use (IFU), the applicable codes and standards cited in Section 1.2, VHA Directives, VA Technical Information Library (TIL) publications, and The Joint Commission (TJC) Environment of Care requirements. This SOW is performance-based: the Contractor is responsible for achieving the outcomes defined herein and shall exercise professional judgment within the boundaries established by the IFU and applicable standards.
1.2 Regulatory Foundation — Current Editions (as of Award Date) The Contractor's program shall be governed by the most current editions of all applicable standards. The following hierarchy of authority applies. In cases of conflict, the more stringent requirement governs.
1. VA/VHA Directives and VA CFM Technical Information Library (TIL) publications — highest authority for VA medical facilities.
1. The Joint Commission (TJC) Hospital Accreditation Standards — EC.02.05.01 (Utility Systems) and EC.02.05.02 (Water Management Program); non-compliance constitutes a TJC finding reportable to facility leadership.
1. NFPA codes and standards — mandatory reference for healthcare occupancies under NFPA 99-2024, NFPA 101-2021, NFPA 110-2022, NFPA 70E-2024, NFPA 70B-2023, NFPA 90A-2024, NFPA 90B-2024.
1. ASHRAE standards — ASHRAE 170-2025 (ventilation), ASHRAE 180-2018 (HVAC PM), ASHRAE 15-2022 (refrigeration safety), ASHRAE 34-2022 (refrigerant classification), ASHRAE 188-2021 (Legionella risk management).
1. EPA regulations — 40 CFR Part 82 Subpart F (Section 608), AIM Act / 40 CFR Part 84 (HFC phasedown and Technology Transitions).
1. OSHA standards — 29 CFR 1910.147 (LOTO), 29 CFR 1910.134 (respiratory protection), 29 CFR 1910 Subpart S (electrical safety).
1. Manufacturer IFU / O&M manuals — minimum PM task baseline; manufacturer requirements shall not be waived without written COR approval.
1.3 Objectives
1. Maintain all 41 DX units in peak operating condition and full regulatory compliance throughout the period of performance (POP).
1. Sustain TJC EC.02.05.01 compliance: verify and document ventilation pressure relationships, ACH, filtration efficiency, temperature, and humidity per ASHRAE 170-2025 for all units serving patient-care areas.
1. Support the facility's NFPA 70B-2023 Electrical Maintenance Program (EMP) through proper documentation of all electrical PM findings, Equipment Condition Assessments (ECAs), and corrective actions.
1. Manage all regulated refrigerants (R-410A, R-134A, R-22, R-407C, R-404A) in full compliance with EPA Section 608 and AIM Act provisions; provide written advisory to COR on any legacy refrigerant unit requiring > 1 lb addition per service visit.
1. Support facility compliance with VHA Directive 1061(4) — Legionella Prevention: inspect, clean, and treat condensate drain systems and humidifier sections of CRAC/precision cooling units at every PM visit.
1. Document all PM activities in the format required by ASHRAE 180-2018, TJC EC.02.05.01, and the facility's Utility Systems Management Plan (USMP).