The scope of work encompasses monthly operational testing (minimum 30 continuous minutes under facility load with 10-second load transfer requirement), supplemental load bank testing as required by NFPA 110 Section 8.4.2 (2 hours annually at 75% nameplate rating), and triennial 4-hour load tests (first 3 hours at 30% nameplate kW, final hour at 75%). The contractor must provide emergency repair services with a maximum 2-hour on-site response time, available 24/7/365, and submit all reports to Facilities Management Service within 72 hours in audit-ready format. All documentation must comply with NFPA 110 standards and include specific technical data (kW/amperage, frequency, exhaust temperatures, battery diagnostics via conductance or specific gravity readings). The facility maintains five generators: three in Building 17 (Caterpillar SR-4 1000 kva, Caterpillar C32 1250 kva, Kato 500SS9D 625 kva), one portable Kohler 128 kva unit in the parking garage, and one portable Baldor 225 kva unit in the grounds. Contractors must be EGSA-certified or factory-trained, comply with NFPA 70E safety standards, and maintain records for three years. The contract structure consists of a base year plus four option years, with responses due by March 20, 2026 at 10:00 AM ET to Bill Pratt at Billie.Pratt@va.gov. This notice is for market research purposes only and does not constitute a binding solicitation.

View the file

Other files

File Type Posted
36C24526Q0352.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SUBJECT* Sources Sought Notice Need a contractor for Generator Testing Services Louis A Johnson VA Medical Center 36C24526Q0352

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE* 21902

SOLICITATION NUMBER* 36C24526Q0352

RESPONSE DATE/TIME/ZONE 03-20-2026 10:00 EASTERN TIME, NEW YORK, USA

ARCHIVE 30 DAYS AFTER THE RESPONSE DATE

RECOVERY ACT FUNDS N

SET-ASIDE

PRODUCT SERVICE CODE* J049

NAICS CODE* 811310

CONTRACTING OFFICE ADDRESS Department of Veterans Affairs

VISN 5 Contracting Satellite office

361 Boiler House Rd Perry Point MD 21902

POINT OF CONTACT* Contracting Officer Bill Pratt Billie.Pratt@va.gov 410-642-2411

PLACE OF PERFORMANCE

ADDRESS Department of Veterans Affairs

Louis A. Johnson VA Medical Center

1 Medical Center Drive Clarksburg WV

POSTAL CODE 26301

COUNTRY USA

ADDITIONAL INFORMATION

AGENCY’S URL https://www.va.gov

URL DESCRIPTION VA

AGENCY CONTACT’S EMAIL ADDRESS billie.pratt@va.gov

EMAIL DESCRIPTION NCO 5

Summary:

Department of Veterans Affairs, Veterans Health Administration, Network Contracting Office 5, is issuing this request for sources sought notice in order to identify vendors that are interested in and capable of providing contractor services. For a contractor to provide Generator Testing Services for the Louis A Johnson VA Medical Center. Review last page for details on how to respond to this Sources Sought notice.

Scope of work:

Location of work:

Louis A Johnson VA Medical Center 1 Medical Ctr Dr, Clarksburg, WV 26301 Base plus Four (4) Option Year contract. This ensures the Louis A. Johnson VAMC maintains continuous compliance with the most recent VHA-adopted NFPA 110 and is fully prepared for The Joint Commission (TJC) and OIG inspections.

1.0 Contract Structure

Base Year: [Dates]

Option Years 1-4: To be exercised annually.

Emergency Coverage: 24/7/365 On-call availability.

2.0 Scope of Work

The contractor shall provide all labor, materials, and equipment to perform monthly, annual, and triennial testing, as well as emergency repair services.

2.1 Monthly Operational Test

Duration: Minimum 30 continuous minutes under facility load.

Time-to-Transfer: Must reach operating voltage/frequency and transfer load within 10 seconds.

ATS Rotation: Contractor shall rotate the initiating Automatic Transfer Switch (ATS) monthly to ensure all switches are cycled annually.

2.2 Supplemental Load Bank Testing (As Required)

In accordance with the most recent NFPA 110, Section 8.4.2, if a generator fails to reach the required 30% of the nameplate kW rating or the manufacturer’s recommended exhaust gas temperature during the monthly run:

Requirement: The contractor shall provide a portable load bank.

Procedure: The unit shall be exercised for 2 hours annually at a load increasing to at least 75% of the nameplate rating.

2.3 Triennial (36-Month) 4-Hour Run

Once every 36 months, the contractor shall conduct a continuous 4-hour load test:

First 3 Hours: Minimum 30% of nameplate kW.

Final Hour: Minimum 75% of nameplate kW (utilizing a load bank if facility load is insufficient).

3.0 Emergency Response & Repair

Response Time: The contractor shall provide emergency repair services with a maximum 2-hour on-site response time from the initial call by the M&O Supervisor or Engineering Staff.

Availability: This requirement applies 24 hours a day, 7 days a week, including holidays.

Reporting: Any emergency repair must result in a "Return to Service" report documenting the root cause and the specific NFPA 110 re-test performed to verify system readiness.

4.0 TJC & OIG Documentation Standards

All reports must be "Audit-Ready" and submitted to the Facilities Management Service (FMS) within 72 hours.

Specific Data: Reports must include exact kW/Amperage, Hz, and exhaust temperatures.

Battery Diagnostics: Conductance or specific gravity readings are mandatory for each battery cell/unit.

Certification: A signed attestation that the test met the most recent VHA/NFPA 110 performance criteria.

5.0 Contractor Qualifications & Safety

Certification: Technicians must be EGSA-certified or factory-trained on VAMC-specific assets.

Safety: All work must comply with the most recent NFPA 70E standards. The contractor is responsible for all Arc Flash PPE and for establishing a safe working perimeter.

6.0 Record Management.

. Documentation Requirements:

1. Date of test

2. Start and end time.

3. Total run duration.

4. Generator identification number/location.

5. Load percentage or kW output.

6. Voltage and frequency readings.

7. Oil pressure and coolant temperature readings.

8. Fuel level.

9. Battery condition.

10. Following NFPA 110.

7.0 Record Retention.

1. Generator test records shall be maintained for a minimum of three (3) years.

2. Records may be maintained electronically or in hard copy available to the facility when requested.

8.0 Generator Description.

GENSET #1 GENSET #2 GENSET #3

Manufacturer/Make/Year: Caterpillar Caterpillar Kato

Model No: SR-4 C32 500SS9D

Serial/Order No: 6NA01031 G1G00044 7319

Load Rating:

(Emergency/Standby/Prime)

1000 kva 1250 kva 625KVA

Power Factor: .8 .8 .8

Frequency: 60 Hertz 60 Hertz 60 hertz

Load in Amperage: 1000 amps 1000 amps 87

Output Voltage: 480 480 volts 4160 volts

Phase: 3-phase 3-phase 3-phase

Building: Bld 17 Bld 17 Bld 17

Location (Area/Room): Generator room Generator Rm Generator Rm

GENSET #4 GENSET #5 (portable)

Manufacturer/Make/Year: Kohler Baldor

Model No: 100RE0ZJF TS225-3J

Serial/Order No: 3346GMJL0001 P1205240012

Load Rating:

(Emergency/Standby/Prime)

128 kva 225 kva

Power Factor: .8 .8

Frequency: 60 Hertz 60 Hertz

Load in Amperage: 153 amps 625 amps

Output Voltage: 480 480 volts

Phase: 3-phase 3-phase

Building: Parking Garage Grounds

Location (Area/Room): Parking Garage Grounds (portable)

Please respond to this RFI/Sources Sought 36C24526Q0352 with your:

1. Business name (including Unique Entity ID (SAM.gov)

2. Business type, socio-economic status (e.g., Veteran-Owned, Woman-Owned, Disadvantaged Small Business, 8(a), etc.), and

3. Person of contact (including telephone number & email address).

4. Capability statement and summary of previous experience providing these types of services for the Veterans Health Administration or other similar facilities.

5. Available contract vehicles (GSA FSS, etc.) for use by Department of VA (include applicable NAICS)

6. Brief Summary of categories of services that your company can/cannot provide.

7. Certification(s) / Licenses for meeting the local requirements to provide these services at the DC VAMC (if applicable)

8. Confirmation that your organization has the capability & expertise to meet the performance requirements while complying with applicable limitations in subcontracting by responding to the questions below with your response:

a. Do you intend to self-perform this effort?

b. If you are located outside the immediate area, how will you self-perform?

c. Or do you intend to subcontract work under this contract?

d. If you intend to subcontract work under this contract, how will you ensure compliance with the limitations on subcontracting?

Response Instructions:

Responses must be submitted NLT 10:00 AM (ET) 03-20-2026, Responses to the information requested above must be submitted via email to Bill Pratt at Billie.Pratt@va.gov.

Respond: 36C24526Q0352 – Sources Sought Notice | Company Name

This request for information/sources sought notice is for planning purposes ONLY and does not constitute a solicitation, responses to this notice are not offers and cannot be accepted by the Government to form a binding contract. The results of this market research will assist in the development of (1) the requirement, and (2) the acquisition strategy (e.g., SDVOSB/SDVOSB set-aside, small business set-aside, full and open.