20074.AST1.IS.STI.12.20.pdf

PDF 4 MB Posted

Attached to
R425--IH, Safety & Environmental Service Contract Federal contract opportunity
Solicitation number
36C24522Q0263
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 5

View the file

Other files for this federal contract opportunity

Other files attached to R425--IH, Safety & Environmental Service Contract, newest first.
File Type Posted
LUC Template - VRP - 2020.07.20_Draft Martinsburg VAMC_Sept102021.pdf PDF
Exhibit C LUC Inspection Form 2020.05.15_Draft Martinsburg VAMC.docx DOCX document
Annual Inspection Certification AST 1.pdf PDF
QA from SOL 36C24522Q0263.pdf PDF
Updated Schedule.pdf PDF
36C24522Q0263 0002.docx DOCX document
36C24522Q0263_2.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA Medical Center Martinsburg, WV

Report No.: 20074.AST1.IS.STI.12.20

Inspector : Ryan Peterson

Employer : TechKnowServ

Inspection Date : 12/02/2020

IN-SERVICE

Inspection Report For

AST 1

Diesel Fuel

A Standard STI inspection was completed on Tank AST 1 in the VA Medical Center facility located at Martinsburg, WV on 12/02/2020 to meet the required 3 year and annual inspection set fourth in the West Virginia Code:

CHAPTER 22. ENVIRONMENTAL RESOURCES.ARTICLE 30. The inspection was conducted in accordance with client and state regulated criterion for NDE which included visual examinations. The tank was built to API 650 specification for AST tanks for storing Diesel Fuel. This inspection was conducted in accordance with requirements standards established by W.Va. Code 22-30 and the steel tank institute SP-001 6th edition . The following is a detailed report of the inspection including findings and recommendations.

Inspector Signature API Certification No. 80187 STI Certification No. AC 44269

Jayfish Media Group, LLC

TABLE OF CONTENTS

1.0 EXECUTIVE SUMMARY

2.0 VESSEL DATA

3.0 INSPECTION RESULTS

3.1 Foundation

3.2 Shell

3.3 Nozzles

3.4 Roof

3.5 Floor

3.6 Ancillary Equipment

3.7 Other

4.0 RECOMMENDATIONS

4.1 Foundation

4.2 Shell

4.3 Nozzles

4.4 Roof

4.5 Floor

4.6 Ancillary Equipment

4.7 Other

4.8 Next Inspections

5.0 ULTRASONIC THICKNESS (UT) MEASUREMENTS

5.1 Results Summary

5.2 Recommendations

APPENDICIES APPENDIX A Thickness Measurement Record

APPENDIX B Mechanical Integrity Calculation

APPENDIX C Inspection Drawings

APPENDIX D Inspection Checklist

APPENDIX E Inspection Photographs

APPENDIX F NDE Records and Certifications

1.0 EXECUTIVE SUMMARY

The tank AST 1 diesel fuel storage tank was found to meet or exceed the minimum code requirements of STI SP-001 and the West Virginia code and regulations. This tank is built to API 650 code standards.

The tank has some minor issues with coating failure that should be managed at customer discretion.

The tank foundation and containment have areas with cracking and spalling which needs to be properly sealed to ensure no product can escape the containment in the event of a release.

The tank bottom-to-foundation seal has failed in areas and should be repaired to ensure protection against water seepage beneath the bottom of the tank floor and to help protect against tank floor bottom side corrosion.

Thickness measurements were taken and locations identified in this report.

The UT examination shows no significant wall loss deeming the tank structurally sound.

Tank AST 1 diesel fuel storage tank is found to be fit for continued service.

Please refer to the results and recommendation sections of this report for other minor discrepancies and recommendations that were identified during the course of this inspection.

Required Next Inspections per State Regulations :

Annual UT Thickness: Site Tracked External: 12/02/2023 Internal: Site Tracked

A Standard STI inspection was completed on Tank AST 1 in the VA Medical Center facility located at Martinsburg, WV on 12/02/2020 to meet the required annual and 3 year and annual inspection interval set forth in the West Virginia Code: CHAPTER 22. ENVIRONMENTAL RESOURCES.ARTICLE 30 for level 1, and to collect data in order to evaluate the mechanical integrity and fitness for continued service of the tank.

2.0 TANK DATA

Equip. ID: AST 1 Product: Diesel Fuel

City/State: Martinsburg, WV Gallons: 75,000

Client: VA Medical Center Specific Gravity: 0.88

State ID: 002-00000185 Fill Height (ft): 23.0

Inspection Date: 12/02/2020 Corr. Allow.(Ca): 0.000

Type Inspection: IN-SERVICE Joint Eff.: 0.85

Test Methods: VT and UT Plate Spec: Unknown

Manufacturer: Convault Inc. Roof/Head 1 t (inch): 0.203

Year Built: 1972 Bttm/Head 2 t (inch):

Const. Code: API-650 Course 1 t (inch): 0.250

Diameter/Width(ft): 24.0 Course 2 t (inch): 0.203

Height (ft): 23.0 Course 3 t (inch): 0.203

Length(ft):

Shell Const: Butt Welded

Roof Type: Fixed/Cone

Foundation: Concrete Pad

Insulation Type: None

Insul.Tk.(in):

3.0 INSPECTION RESULTS

The following results are the summarization of a field checklist that was utilized during the inspection of AST 1

3.1 Foundation:

3.1.1 The foundation is constructed of a concrete pad. The concrete containment structure appears to meet the capacity requirements recommended by NFPA 30.

3.1.2 The concrete containment walls and floor have cracking throughout.

3.1.3 The concrete foundation has some cracking and spalling throughout.

3.1.4 The tank bottom-to-foundation sealant has failed in some areas.

3.2 Shell:

3.2.1 No deformation or significant wall loss was found on the tank shell courses. The tank shell has some minor issues with coating failure but is in overall satisfactory condition.

3.3 Nozzles:

3.3.1 Tank nozzles appear to be in satisfactory mechanical condition with the appropriate, required, valves and instrumentation for venting.

3.4 Roof:

3.4.1 Tank roof is of a fixed cone design and found to be in satisfactory condition.

3.4.2 The tank roof has minor areas of coating failure.

3.5 Floor:

3.5.1 N/A

3.6 Ancillary Equipment:

3.6.1 Tank is properly grounded.

3.7 Other:

3.7.1 The tank access stairway has minor coating failure.

4.0 RECOMMENDATIONS

4.1 Foundation:

4.1.1 The concrete containment and foundation should be properly sealed to ensure adequate containing capabilities in the event of a release.

4.1.2 The bottom-to-foundation gap should be properly sealed to protect against water seepage beneath the bottom of the tank floor and to help protect against tank floor bottom side corrosion.

4.2 Shell:

4.2.1 Consideration should be given to the cleaning and re-coating the tanks external surface.

4.3 Nozzles:

4.3.1 Clean and recoat nozzles as needed.

4.4 Roof:

4.4.1 Clean and re-coat tank roof and components as needed to ensure proper against surface oxidation.

4.5 Floor:

4.5.1 None

4.6 Ancillary Equipment:

4.6.1 None

4.7 Other:

4.7.1 Consideration should be given to the cleaning and re-coating of the access stairs as needed.

4.8 Next Inspections:

4.8.1 Next internal inspection is due by:

4.8.2 Next External inspection is due by: 12/02/2023

4.8.3 Next UT inspection is due by:

5.0 ULTRASONIC THICKNESS (UT) MEASUREMENTS

5.1 Results Summary:

5.1.1 UT examination was performed on all the accessible tank and components to reveal no significant wall loss at the time of inspection.

5.2 Recommendations:

5.2.1 Thickness measurements should be taken during next scheduled inspection to monitor corrosion rates and tank integrity.

APPENDIX A

Thickness Measurement Record

1) Component TML Record

2) Nozzle TML Record

AST Storage Tank Evaluation

AST Component Inspection Data Report No Client Inspector Vessel Date

20074.AST1.IS.STI.12.20 VA Medical Center Ryan Peterson AST 1 12/02/2020

Component Thickness Measurements in (inch)

CML Component Location tml-1 tml-2 tml-3 tml-4 tml-5 tml-6 Minimum 001 Shell Crs 1 Chime N-SE 0.260 0.251 0.258 0.252 0.251

002 Shell Crs 1 Chime S-NW 0.253 0.255 0.251 0.257 0.251

003 Shell Crs 1 North Drop

BMT 0.254 0.258 0.261 0.254

004 Shell Crs 1 East Drop

BMT 0.256 0.259 0.263 0.256

005 Shell Crs 1 South Drop

BMT 0.251 0.257 0.252 0.251

006 Shell Crs 1 West Drop

BMT 0.254 0.254 0.253 0.253

007 Shell Crs 2 Stair Drop 0.202 0.212 0.206 0.206 0.203 0.199 0.199

008 Shell Crs 3 Stair Drop 0.205 0.216 0.214 0.206 0.216 0.209 0.205

009 Roof N-S 0.200 0.199 0.192 0.194 0.195 0.195 0.192

010 Roof E-W 0.195 0.191 0.207 0.193 0.194 0.196 0.191

API-653 STORAGE TANK EVALUATION

Nozzle Inspection Data

20074.AST1.IS.STI.1

2.20 VA Medical Center Ryan Peterson AST 1 12/02/2020

Nozzle Thickness Measurements in (inch)

Components with Vert. Axis: tml-1 N., tml-2 E., tml-3 S., tml-4 W. (Drawing N.)

Component with Horz. Axis:tml-1 Top, tml-2 Side, tml-3 Bttm., tml-4 Side (Clock Wise)

CML # Comp. ID Size Location Service tml-1 tml-2 tml-3 tml-4 Minimum 011 24" MW 24.000 A Manway 0.382 0.377 0.377 0.390 0.377

012 2" Cplg 2.000 B Return

013 2" Cplg 2.000 C Supply

014 4" Nozzle 4.000 D Product 0.321 0.330 0.311 0.313 0.311

015 3" Nozzle 3.000 E Drain 0.264 0.237 0.254 0.256 0.237

016 6" Nozzle 6.000 F Vent 0.352 0.339 0.335 0.335 0.335

017 24" E.V. 24.000 G E.V. 0.258 0.266 0.271 0.262 0.258

018 6" Nozzle 6.000 0 Gauge Hatch 0.337 0.335 0.329 0.339 0.329

APPENDIX B

Mechanical Integrity Calculation

1) Component Life Calculations

2) Nozzle RL Calculations

Date 12/02/2020

COMPONENT REMAINING LIFE EVALUATION

Report No Client Initials Tank No Temp (degF)

20074.AST1.IS.STI

.12.20 VA Medical Center Ryan Peterson AST 1 100

Minimum Thickness Determinations: Component tmin may be determined by any of the following as relative:

1) Components calculated per original design Ca as follows: tnom - Ca = t

2) Pipe components calculated per ASME B31.3, para. 304 as follows: PD/2(SE+PY) = t

3) PV cyl. components calculated per ASME Sect VIII, UG 27 as follows: PR/SE-0.6P = t

4) Components calculated per original code of construction, (ASME, API, et.)

Component Remaining Life Calculations:

Where:

Ca = Remaining corrosion allowance of the component under consideration, in inch.

Cr = Corrosion rate of the component under consideration, in inch/Yr.

tact = Minimum thickness measurement of the component under consideration, as recorded at the time of inspection, in inch.

tmin = minimum required thickness of component, at the maximum allowable loading , in inch.

tprev = previous thickness measurement of the component under consideration, as recorded at last inspection or nominal thickness if no previous thickness measurements, in inch.

RL = Estimated remaining life of the component under consideration, in year.

Y = Time span between thickness readings or age of the component if nominal thickness is used for tprev, in year.

CML Comp. Disc Age (year) Size (inch) t prev (inch) t act (inch) t min (inch) Ca (inch) Cr (inch/Yr) RL (year)

001 Shell Crs 1 48 0.000 0.250 0.251 0.125 0.126 0.00000 >20

002 Shell Crs 1 48 0.000 0.250 0.251 0.125 0.126 0.00000 >20

003 Shell Crs 1 48 0.000 0.250 0.254 0.125 0.129 0.00000 >20

004 Shell Crs 1 48 0.000 0.250 0.256 0.125 0.131 0.00000 >20

005 Shell Crs 1 48 0.000 0.250 0.251 0.125 0.126 0.00000 >20

006 Shell Crs 1 48 0.000 0.250 0.253 0.125 0.128 0.00000 >20

007 Shell Crs 2 48 0.000 0.203 0.199 0.101 0.098 0.00008 1176

008 Shell Crs 3 48 0.000 0.203 0.205 0.101 0.104 0.00000 >20

009 Roof 48 0.000 0.203 0.192 0.101 0.091 0.00023 397

010 Roof 48 0.000 0.203 0.191 0.101 0.090 0.00025 360

AST STORAGE TANK EVALUATION

Nozzle/Pipe Remaining Life Calculations

20074.AST1.IS.STI.1

2.20 VA Medical Center Ryan Peterson AST 1 12/02/2020

Minimum Thickness Determinations:

a) The following pipe minimum thicknesses are based on the current in-house engineering standards, which take into consideration, pressures, structural integrity and localized corrosion allowance.

Size (inch) <2 3 4 6 8 10 12 >12 tmin (inch) 0.080 0.100 0.100 0.125 0.125 0.156 0.188 0.188

Nozzle Remaining Life Calculations:

CML Age (year)

Comp.Disc.

(inch)

Size (inch) tprev (inch) tact (inch) tmin (inch)

Ca (inch)

Cr (inch/Yr)

RL

(year)

011 48 24" MW 24.000 0.375 0.377 0.188 0.189 0.00000 >20

012 48 2" Cplg 2.000 0.080 013 48 2" Cplg 2.000 0.080 014 48 4" Nozzle 4.000 0.337 0.311 0.169 0.142 0.00054 262 015 48 3" Nozzle 3.000 0.250 0.237 0.125 0.112 0.00027 414 016 48 6" Nozzle 6.000 0.337 0.335 0.169 0.166 0.00004 >20 017 48 24" E.V. 24.000 0.250 0.258 0.125 0.133 0.00000 >20 018 48 6" Nozzle 6.000 0.337 0.329 0.169 0.160 0.00017 960

APPENDIX C

Inspection Drawings

1) Shell Layout Drawings

2) Roof Layout Drawings

APPENDIX D

Inspection Checklist

1) STI Checklist

AST INSPECTION CHECKLIST(S)

Inspector: Ryan Peterson

Cert No: 80187

Company:

VA Medical

Center Tank: AST 1 Report No:

20074.AST1.IS.S

TI.12.20

Date: 12/02/2020

STEEL TANK INSTITUTE SP001 INSPECTION CHECKLIST

TANK CONFIGURATION: TANK HAS CRDM? AST CATEGORY

AST in contact with ground no 2 or 3

Elevated tank with spill control and with no part of AST in contact with ground No 1

Vertical tank with RPB and spill control yes 1

Vertical tank with double bottom and spill control No 1

Vertical tank with RPB under tank and spill control yes 1

Double-wall AST No 1

AST with secondary containment dike/berm No 1

TANK ID AFFIXED TO TANK: YES PRODUCT: Diesel Fuel___________

NAMEPLATE: YES READABLE: YES AST CATEGORY 1__________

MFG: Fisher Tank Co. CAPACITY:_75,000 Gallons_ YR Built: 1972_ CODE: API 650__

DOT LABEL: YES GROUND: YES

TYPE: Single Wall Vert Cylinder CONCERTE PAD: YES

CONTAINMENT CONDITION: CONCRETE Satisfactory

SPOTTED COATING FAILURE W/ SURFACE O2 (RUST): NA

CRACKS IN CONTAINMENT BASIN: YES WALLS: YES

FOUNDATION CONDITION: CONCRETE PAD Satisfactory

CRACKS IN CONCRETE / ASPHALT: NO

SHELL &HEADS CONDITION: Satisfactory ACCESSIBLE: Yes SPOTTED COATING FAILURE W/ SURFACE O2 (RUST): Yes

NOZZLE CONDITION: CS Satisfactory

SPOTTED COATING FAILURE W/ SURFACE O2 (RUST): YES

ANTI-SYPHON VALVE REQUIRED: YES PRESENT: YES

SHEAR VALVE REQUIRED: NO PRESENT: NO

EXPANSION VALVE REQUIRED NO INSTALLED CORRECTLY NA

FILL BASIN REQUIRED: NO PRESENT: NO

ISOLATION VALVE REQUIRED: YES PRESENT: YES

LEVEL IND. TYPE: ATG , Digital Indicator

HIGH LEVEL ALARM -OR- PUMP HIGH LEVEL CUTOUT SWITCH: YES

PRESS/TEMP INDICATORS: Digital HAS CERT STICKER: NA

GLASS BROKE : NO

ACCESS: STEPS

SPOTTED COATING FAILURE W/ SURFACE O2 (RUST): YES

NORMAL VENT EMERGENCY VENT

SIZE 6” 24”

CAPACITY 246,130 CFH 1,736,450 CFH

MAKE Fisher Tank Co. Fisher Tank Co.

HEIGHT 24’ 24’

VENT TO OUTSIDE YES YES

VESSEL LAYOUT DRAWINGS

1 Record Following Data a._X__Roof or Head and skirt lengths and type (especially head to shell joint config.)

b._X__Shell lines of support (Head Tangents, Braces, Jacket Closures, etc.).

c._X__Foundation support member dimensions and orientation.

d._X__Inside/Outside diameter.

e._X__Tank component nominal thicknesses.

f.___Nozzle layouts, size and use.

UT THICKNESS READINGS

1 Measure and Record Vessel Part Thicknesses a._X__Roof/Heads - (4) locations minimum, (1) in each quadrant and for roofs - an X pattern

(6) per leg.

b._X__Shell - (12) locations, (3) in each quadrant for each course.

c.___Jacket - As required (at least (4) locations).

d._X__Nozzles - (4) locations, (1) in each quadrant for 2 inches and greater, (1) location for nozzles less than 2 inches.

E.___Floor - If ultrasonic testing equipment that is capable of scanning the tank (i.e MFE) is not practical, use equipment that tests individual points. In this case, take UTT measurements of at least 15 points per each 12 inches x 12 inches (0.3 meters x 0.3 meters) square area of the shell that is in contact with the ground.

UT RESULTS: GENERAL GUIDE

CAT 2 &3 - UT Meas. less than 0.75 x Nominal Thickness - reference SP001 para 10.2.2 or

10.2.3 respectively CAT 1 - UT Meas. less than 0.50 x Nominal Thickness - reference SP001 para 10.2.4

APPENDIX E

Inspection Photographs

1) Photo Files

REPORT-20074.AST1.IS.STI.12.20 INSPECTION PHOTOGRAPHS

Tank ID Label with NFPA Diamond

Tank I.D. Label

Tank Containment Sump

Cracks in Tank Containment Floor

Cracking in Containment Walls

Tank Concrete Foundation with Cracks and Openings

Tank Bottom-to-Foundation Sealant Failing

Tank Data Plate

Tank with Areas of Coating Failure

Tank Grounding Cable

Tank ATG

Tank Access Stairs with Minor Coating Failure

General Condition of Tank Roof

Tank Vent Screen Intact

APPENDIX F

NDE Records and Certifications

1) Annual Inspection Certification

2) UT Calibration Report

3) NDE Tech Certification

4) STI Certification

5) API 653 Certification

ANNUAL INSPECTION CERTIFICATION

Aboveground Storage Tank

Is Fit for Service

V.7.22.2016

☐ I am a qualified individual as described in WV CSR 47‐63‐5.2 and I have performed a tank evaluation on the above AST system. I certify the tank system meets applicable standards established by WV CSR 47‐63.

☐ I am the tank owner, operator, or qualified representative of the tank owner or operator, and have performed a tank evaluation on the above AST system. I certify there is no obvious change to the tank system that would cause this tank to become not‐fit for service since it was certified by a PE, API or STI inspector on

_______________________ (date). This certification meets the requirements set in WV CSR 47‐63‐5.2.b.3 to certify annual inspections in intervening years between the evaluations required by a PE, API or STI inspector.

In accordance with the WV CSR 47‐63‐5.2, I have documented all deficiencies and/or changes in the tank system found during the inspection, in writing, and provided my recommendations, including a proposed schedule, for abating the deficiencies and submitted them with this form.

I certify that I have personally examined and/or am familiar with the inspection performed on the AST system listed above, including its associated equipment, leak detection system and secondary containment structure, and that based on my direct knowledge that the AST listed above is Fit for Service.

Signature of Certifying Individual Date Signed

P.E. Registration #, STI Certification # or Registration/Certification Expiration Date API

Certification # (if applicable) (if applicable)

AST Facility Name

Address

City, State, Zip

Tank Owner Name

Telephone Number

Email Address

Certifying Individual

Address

City, State, Zip

Telephone Number

Email Address

Facility’s/Owner’s Tank ID

DEP Issued Tank Label

DEP Determined Tank Level Level 1 tank ☐ Level 2 tank ☐

ULTRASONIC THICKNESS CALIBRATION REPORT

Client: VA Martinsburg, WV Job #: N/A

Contact: Robert Moore Job Site: Martinsburg, WV

Address: 510 Butler Ave Procedure:

Martinsburg, WV 25405 Part ID #: AST 1, and 2

Phone: 304-263-0811 x3412 Drawing #:

Job Description: AST STI SP001 Annual Inspection Code:

TEST ITEM INFORMATION

Item: AST Material: Carbon Steel

Specs (size): See Drawing Nominal t: See report

Coating t: Paint Temperature: 40° F

Surface Condition:

Good Additional Info:

Insp. Pattern: See Report

EQUIPMENT PARAMETERS

UT Unit Mfgr Model S/N Calibration Due Date

Olympus 45 MG 130152606 9/21

Transducer Mfgr Type Freq Angle Size S/N

Parametircs

NDT

D7096-3N 7.5mHz Straight ¼” 1251825

Cable Mfgr Type Length S/N

Olympus N/A 5 ft N/A

Couplant Mfgr Type Batch Number

N/A Ultrasonic N/A

Calib. Block Material S/N Step # Thickness Range

1018 Steel N/A 6 0.1”.-0.6”

INITIAL CALIBRATION

Reference Level Gain

Thin Step Thick Step Settings Time Tech

Thickness Amplitude Thickness Amplitude Velocity Zero

0.10” 60db 0.6” 60db N/A N/A 8:00 MJK

SUBSEQUENT CALIBRATIONS

Calibrations to be performed at intervals not to exceed every 8 hrs, and if there is a chance in shift, couplant, personnel, search unit or cables.

Time

Technician

CERTIFICATION

Notes:

Conducted By

Print: Thomas Hay UT Level Date

Signature:

III 12/02/20

AST Facility Name: Veterans Affairs Medical Center
Address: 510 Butler Avenuew
City State Zip: Martinsburg, WV 25405
Tank Owner Name: Veterans Affairs Medical Center
Telephone Number: (304) 263-0811 x 3412
Email Address: Robert.Moore10@va.gov
Certifying Individual: Ryan Peterson - STI, API 653
Address_2: 498 Meckley Drive
City State Zip_2: State College, PA 16803
Telephone Number_2: (814) 237-0144
Email Address_2: jayfishcontracting@gmail.com
FacilitysOwners Tank ID: AST 1
DEP Issued Tank Label: 002-00000185
Check Box1: Yes
Check Box12: Yes
Check Box11: Off
Check Box13: Off
certify annual inspections in intervening years between the evaluations required by a PE API or STI inspector:
Date Signed: 12/2/2020
PE Registration STI Certification or: STI # AC 44269 API 653 # 80187
RegistrationCertification Expiration Date API: STI - May 10th, 2023 / API 653 March 31st 2021