Damarc Quality Inspection Services, LLC Doc ID:
SS-1
Summary Sheet
7/10/2012
Rev. 0
Facility: Clarksburg VAMC Address: 1 Medical Center Drive
Clarksburg, WV 26301
Reviewed By:
Date:
Date of inspection: 8-20-2016 Contact: Joshua Johnston Contact Phone #: 304-623-3461 x:3774 Contact Email: Joshua.Johnston@va.gov Inspected By: Pat Kearney
Boiler/Building/ Jurisdiction #
NB #
Inspection Type
Remarks/Cost A B C D E Emissions
1 Cond. Tank-1 61 PO:540-C53112 2 Cond. Tank-2 2089 PO:540-C53112 3 DA Tank-1 3187 PO: 540-P64460
Damarc Quality Inspection Services LLC Tank Inspection Diagram VA Medical Center
CLARKSBURG,WV COND. TK NB 61
VA MED CTR CLARKSBURG,WV
INTERNAL NEAR SIDE (SOUTH)
.263
.263
.262
CLARKSBURG,WV COND. TK#2 NB 2089
.208
.208
.227
INSPECTION REPORT
REV. 8 3/10/2015
DAMARC QUALITY INSPECTION
SERVICES
2195 59th Street Somerset, WI 54025
PHONE: 866-361-4321
FAX: 715-247-2055
TYPE OF INSPECTION
A. INTERNAL AND EXTERNAL
B. INTERNAL AND EXTERNAL
WITH HYDROSTATIC TEST
C. EXTERNAL UNDER OPERATION
D. HYDROSTATIC TEST ONLY
E. EXPANSION TANK
DATE OF INSPECTION
8-20-2016
CONTRACT NUMBER
RECOMMENDATIONS
NO YES (PLEASE EXPLAIN IN
SECTION VII)
UNSCHEDULED INSPECTION
( IF YES, EXPLAIN IN SECTION VII)
SECTION I IDENTIFICATION
INSTITUTION NAME AND ADDRESS
VA MED CTR CLARKSBURG 1 MED CTR DR. CLARKSBURG,WV 26301
EMAIL(S) WHERE REPORTS ARE TO BE SENT
JOSHUA.JOHNSTON@VA.GOV
TYPE OF PLANT
STM HTG
POINT OF CONTACT
JOSH LOHNSTON
TELEPHONE #
304-623-3461 X3560
BUILDING NUMBER
POWER HOUSE
BOILER TYPE
COND TK
BOILER NUMBER
#1
NB NUMBER
NB 61
BOILER HORSEPOWER
N/A
BOILER CAPACITY
N/A
MANUFACTURED BY
GEORGE MARKER
YEAR BUILT
YEAR INSTALLED
FIRING EQUIPMENT
N/A
FUEL
N/A
WORKING PRESSURE
PRESSURE ALLOWED
SAFETY VALVE SETTING
N/A
PRESSURE OBSERVED
SECTION II – STATEMENT OF POST ENGINEER
REPAIRS MADE SINCE LAST INSPECTION
NONE
SECTION III – INTERNAL INSPECTION (TYPES A AND B ONLY)
DESCRIBE INSPECTION FULLY (STATE LOCATION OF ANY SCALE, GREASE, OIL, OR OTHER DEPOSITS; ANY CORROSION, PITTING, GROOVING, CRACKS OR LAMINATIONS; ANY EVIDENCE OF OVERHEATING, SUCH AS BULGING OR WARPING; ANY BROKEN OR LOOSE RIVETS OR STRAYS, ETC.)
N/A
SECTION IV EXTERNAL INSPECTION (TYPES A, B, C, AND D)
CONDITION OF SEAMS, TUBE ENDS, PIPE CONNECTIONS, ETC. (DESCRIBE FULLY AND STATE LOCATION OF ANY CORROSION, LEAKAGE, EROSION, EVIDENCE OF OVERHEATING, SOOT OR OTHER DESTRUCTIVE ACCUMULATIONS, ETC)
No leaks on valves, piping, etc.
SEAMS ARE IN GOOD CONDITION
NO EXTERNAL SIGNS OF CORROSION, OR OVERHEATING.
SETTING, LINNINGS, BAFFLES AND BOILER SUPPORTS
GOOD
SECTION V – INSPECTION OF SAFETY DEVICES
SAFETY VALVES
SIZE (NO. AND DIAMETER)
SET AT (LBS)
N/A
CONDITION AND HOW TESTED (TOTAL SAFETY RELEIF VALVE CAPACITY)
N/A
PRESSURE
GAGES
STATE CORRECTION (IF MADE) STATE REASON (IF NOT TESTED)
GOOD
OTHER
APPLIANCES
WATER COLUMNS, GAGE GLASSES, GAGE COCKS, BLOW OFF PIPE AND VALVE OR COCKS, FEED PIPE, ETC
GOOD
REGULATORS FEED WATER, DAMPER, COMBUSTION, ETC.
SECTION VI – STATEMENT OF INSPECTOR (BOILER NUMBER NB 61 )
WAS BOILER PREPARED FOR THOROUGH EXAMINATION? (IF NO, STATE IN SECTIONS VII WHAT WAS NOT PREPARED AND WHY)
YES NO
WAS BOILER ENTERED FOR THE INSPECTION? (IF NO, EXPLAIN REASON IN SECTION VII)
YES NO
SECTION VII - REMARKS
LIST DEFICIENCIES TO BE CORRECTED AND REPAIRS TO BE MADE ( USE SUPPLEMENTARY SHEET, IF NECESSARY)
NONE AT THIS TIME
NAME AND TITLE OF INSPECTOR
SIGNATURE OF INSPECTOR
PATRICK KEARNEY NB10111
SECTION VIII – ACTION TAKEN ON RECOMMENDATIONS
NAME GRADE AND TITLE OF OFFICE IN CHARGE
SIGNATURE OF OFFICER IN CHARGE
B. INTERNAL AND EXTERNAL
WITH HYDROSTATIC TEST
C. EXTERNAL UNDER OPERATION
SECTION VII)
UNSCHEDULED INSPECTION
( IF YES, EXPLAIN IN SECTION VII)
SECTION I IDENTIFICATION
TYPE OF PLANT
STM HTG
POINT OF CONTACT
JOSH LOHNSTON
TELEPHONE #
304-623-3461 X3560
BUILDING NUMBER
POWER HOUSE
BOILER TYPE
COND TK
BOILER NUMBER
#2
NB NUMBER
NB 2089
BOILER HORSEPOWER
N/A
BOILER CAPACITY
N/A
MANUFACTURED BY
GEORGE MARKER
YEAR BUILT
YEAR INSTALLED
FIRING EQUIPMENT
N/A
FUEL
N/A
SAFETY VALVE SETTING
N/A
NONE
SECTION III – INTERNAL INSPECTION (TYPES A AND B ONLY)
DESCRIBE INSPECTION FULLY (STATE LOCATION OF ANY SCALE, GREASE, OIL, OR OTHER DEPOSITS; ANY CORROSION, PITTING, GROOVING, CRACKS OR LAMINATIONS; ANY EVIDENCE OF OVERHEATING, SUCH AS BULGING OR WARPING; ANY BROKEN OR LOOSE RIVETS OR STRAYS, ETC.)
CONDITION OF SEAMS, TUBE ENDS, PIPE CONNECTIONS, ETC. (DESCRIBE FULLY AND STATE LOCATION OF ANY CORROSION, LEAKAGE, EROSION, EVIDENCE OF OVERHEATING, SOOT OR OTHER DESTRUCTIVE ACCUMULATIONS, ETC)
No leaks on valves, piping, etc.
SEAMS ARE IN GOOD CONDITION
SET AT (LBS)
N/A
CONDITION AND HOW TESTED (TOTAL SAFETY RELEIF VALVE CAPACITY)
N/A
PRESSURE
GAGES
STATE CORRECTION (IF MADE) STATE REASON (IF NOT TESTED)
GOOD
OTHER
APPLIANCES
WATER COLUMNS, GAGE GLASSES, GAGE COCKS, BLOW OFF PIPE AND VALVE OR COCKS, FEED PIPE, ETC
GOOD
SECTION VI – STATEMENT OF INSPECTOR (BOILER NUMBER NB 2089 )
WAS BOILER PREPARED FOR THOROUGH EXAMINATION? (IF NO, STATE IN SECTIONS VII WHAT WAS NOT PREPARED AND WHY)
YES NO
WAS BOILER ENTERED FOR THE INSPECTION? (IF NO, EXPLAIN REASON IN SECTION VII)
YES NO
SECTION VII - REMARKS
DAMARC
“Quality Inspection Services” LLC Client: CLARKSBURG VA
MED CTR
Date:
8-20-216
Procedure: BIC-WFMT
Project: DA Tank Acceptance Standard: ASME VIII, No Cracks
Location: DAYTON VA MED
CTR
Component /Identification:
DA Tank
NB 3187 YR: 1986
Surface Condition:
As Welded X Ground Other
Material:
STEEL
Examination Method:
Wet Fluorescent
MT Equipment Mfg.:
MAGNAFLUX
Model:
Y-1
Serial No.:
Calibration Date
Current:
AC x DC ___ Halfwave _____
Ampere Turns/ Current Level:
Prod/Yoke Spacing:
6”
Head Shot, Coil, Central Conductor, Yoke:
HAND
Area of Examination: Inside Diameter of accessible weldments
Field Indicator (Pie Gage):
Yes
Particles: Demagnetization:
Yes ____ No ___X__
Identification Examination Results
Accept Reject Cause for Rejection
Circular Seams X Longitudinal Seams A X Nozzle and attachment welds X
Remarks: ________________________________________________________________________
Examined By: PATRICK KEARNEY Level: _____2_________ Date: 8-1-2016
Reviewed By: ____________________________ Level: ______________ Date: ____________\
CLARKSBURG,WV DA-TANK NB 3187
.293
.293
.293 .293
.293 .293
.323
.323 .323
.323 .323
B. INTERNAL AND EXTERNAL
WITH HYDROSTATIC TEST
C. EXTERNAL UNDER OPERATION
SECTION VII)
UNSCHEDULED INSPECTION
( IF YES, EXPLAIN IN SECTION VII)
SECTION I IDENTIFICATION
TYPE OF PLANT
STM HTG
POINT OF CONTACT
JOSH LOHNSTON
TELEPHONE #
304-623-3461 X3560
BUILDING NUMBER
POWER HOUSE
BOILER TYPE
DA TK
BOILER NUMBER
#1
NB NUMBER
NB3187
BOILER HORSEPOWER
N/A
BOILER CAPACITY
MANUFACTURED BY
YEAR BUILT
YEAR INSTALLED
FIRING EQUIPMENT
N/A
FUEL
N/A
SAFETY VALVE SETTING
N/A
NONE
SECTION III – INTERNAL INSPECTION (TYPES A AND B ONLY)
DESCRIBE INSPECTION FULLY (STATE LOCATION OF ANY SCALE, GREASE, OIL, OR OTHER DEPOSITS; ANY CORROSION, PITTING, GROOVING, CRACKS OR LAMINATIONS; ANY EVIDENCE OF OVERHEATING, SUCH AS BULGING OR WARPING; ANY BROKEN OR LOOSE RIVETS OR STRAYS, ETC.)
NO SIGNS OF SCALE,CORROSION, PITTING, OR LAMINATION, NO EVIDENCE OF OVERHEATING, ALL STAYS AND SUPPORTS ARE IN GOOD
CONDITION,
CONDITION OF SEAMS, TUBE ENDS, PIPE CONNECTIONS, ETC. (DESCRIBE FULLY AND STATE LOCATION OF ANY CORROSION, LEAKAGE, EROSION, EVIDENCE OF OVERHEATING, SOOT OR OTHER DESTRUCTIVE ACCUMULATIONS, ETC)
No leaks on valves, piping, etc.
,SEAMS ARE IN GOOD CONDITION
1X2"
SET AT (LBS)
CONDITION AND HOW TESTED (TOTAL SAFETY RELEIF VALVE CAPACITY)
GOOD-VENDER TESTED 1143 LB/HR
PRESSURE
GAGES
STATE CORRECTION (IF MADE) STATE REASON (IF NOT TESTED)
GOOD
OTHER
APPLIANCES
WATER COLUMNS, GAGE GLASSES, GAGE COCKS, BLOW OFF PIPE AND VALVE OR COCKS, FEED PIPE, ETC
GOOD
SECTION VI – STATEMENT OF INSPECTOR (BOILER NUMBER NB 3187 )
WAS BOILER PREPARED FOR THOROUGH EXAMINATION? (IF NO, STATE IN SECTIONS VII WHAT WAS NOT PREPARED AND WHY)
YES NO
WAS BOILER ENTERED FOR THE INSPECTION? (IF NO, EXPLAIN REASON IN SECTION VII)
YES NO
SECTION VII - REMARKS
| SS-1 SUMMARY SHEET 7-10-2012 |
| Tank-CON TK#1 CLARKSBURG 2016 |
| Tank-CON TK#2 CLARKSBURG 2016 |
| VA CLARKSBURG COND TK#1A 8-2016 |
| VA CLARKSBURG COND TK#2 8-2016 |
| Mag CLARKSBURG 2016 |
| Tank-DA VA CLARKSBURG 2016 |
| VA CLARKSBURG DA TK 8-16 |