Damarc Quality Inspection Services, LLC Doc ID:

SS-1

Summary Sheet

7/10/2012

Rev. 0

Facility: Clarksburg VAMC Address: 1 Medical Center Drive

Clarksburg, WV 26301

Reviewed By:

Date:

Date of inspection: 8-20-2016 Contact: Joshua Johnston Contact Phone #: 304-623-3461 x:3774 Contact Email: Joshua.Johnston@va.gov Inspected By: Pat Kearney

Boiler/Building/ Jurisdiction #

NB #

Inspection Type

Remarks/Cost A B C D E Emissions

1 Cond. Tank-1 61 PO:540-C53112 2 Cond. Tank-2 2089 PO:540-C53112 3 DA Tank-1 3187 PO: 540-P64460

Damarc Quality Inspection Services LLC Tank Inspection Diagram VA Medical Center

CLARKSBURG,WV COND. TK NB 61

VA MED CTR CLARKSBURG,WV

INTERNAL NEAR SIDE (SOUTH)

.263

.263

.262

CLARKSBURG,WV COND. TK#2 NB 2089

.208

.208

.227

INSPECTION REPORT

REV. 8 3/10/2015

DAMARC QUALITY INSPECTION

SERVICES

2195 59th Street Somerset, WI 54025

PHONE: 866-361-4321

FAX: 715-247-2055

TYPE OF INSPECTION

A. INTERNAL AND EXTERNAL

B. INTERNAL AND EXTERNAL

WITH HYDROSTATIC TEST

C. EXTERNAL UNDER OPERATION

D. HYDROSTATIC TEST ONLY

E. EXPANSION TANK

DATE OF INSPECTION

8-20-2016

CONTRACT NUMBER

RECOMMENDATIONS

NO YES (PLEASE EXPLAIN IN

SECTION VII)

UNSCHEDULED INSPECTION

( IF YES, EXPLAIN IN SECTION VII)

SECTION I IDENTIFICATION

INSTITUTION NAME AND ADDRESS

VA MED CTR CLARKSBURG 1 MED CTR DR. CLARKSBURG,WV 26301

EMAIL(S) WHERE REPORTS ARE TO BE SENT

JOSHUA.JOHNSTON@VA.GOV

TYPE OF PLANT

STM HTG

POINT OF CONTACT

JOSH LOHNSTON

TELEPHONE #

304-623-3461 X3560

BUILDING NUMBER

POWER HOUSE

BOILER TYPE

COND TK

BOILER NUMBER

#1

NB NUMBER

NB 61

BOILER HORSEPOWER

N/A

BOILER CAPACITY

N/A

MANUFACTURED BY

GEORGE MARKER

YEAR BUILT

YEAR INSTALLED

FIRING EQUIPMENT

N/A

FUEL

N/A

WORKING PRESSURE

PRESSURE ALLOWED

SAFETY VALVE SETTING

N/A

PRESSURE OBSERVED

SECTION II – STATEMENT OF POST ENGINEER

REPAIRS MADE SINCE LAST INSPECTION

NONE

SECTION III – INTERNAL INSPECTION (TYPES A AND B ONLY)

DESCRIBE INSPECTION FULLY (STATE LOCATION OF ANY SCALE, GREASE, OIL, OR OTHER DEPOSITS; ANY CORROSION, PITTING, GROOVING, CRACKS OR LAMINATIONS; ANY EVIDENCE OF OVERHEATING, SUCH AS BULGING OR WARPING; ANY BROKEN OR LOOSE RIVETS OR STRAYS, ETC.)

N/A

SECTION IV EXTERNAL INSPECTION (TYPES A, B, C, AND D)

CONDITION OF SEAMS, TUBE ENDS, PIPE CONNECTIONS, ETC. (DESCRIBE FULLY AND STATE LOCATION OF ANY CORROSION, LEAKAGE, EROSION, EVIDENCE OF OVERHEATING, SOOT OR OTHER DESTRUCTIVE ACCUMULATIONS, ETC)

No leaks on valves, piping, etc.

SEAMS ARE IN GOOD CONDITION

NO EXTERNAL SIGNS OF CORROSION, OR OVERHEATING.

SETTING, LINNINGS, BAFFLES AND BOILER SUPPORTS

GOOD

SECTION V – INSPECTION OF SAFETY DEVICES

SAFETY VALVES

SIZE (NO. AND DIAMETER)

SET AT (LBS)

N/A

CONDITION AND HOW TESTED (TOTAL SAFETY RELEIF VALVE CAPACITY)

N/A

PRESSURE

GAGES

STATE CORRECTION (IF MADE) STATE REASON (IF NOT TESTED)

GOOD

OTHER

APPLIANCES

WATER COLUMNS, GAGE GLASSES, GAGE COCKS, BLOW OFF PIPE AND VALVE OR COCKS, FEED PIPE, ETC

GOOD

REGULATORS FEED WATER, DAMPER, COMBUSTION, ETC.

SECTION VI – STATEMENT OF INSPECTOR (BOILER NUMBER NB 61 )

WAS BOILER PREPARED FOR THOROUGH EXAMINATION? (IF NO, STATE IN SECTIONS VII WHAT WAS NOT PREPARED AND WHY)

YES NO

WAS BOILER ENTERED FOR THE INSPECTION? (IF NO, EXPLAIN REASON IN SECTION VII)

YES NO

SECTION VII - REMARKS

LIST DEFICIENCIES TO BE CORRECTED AND REPAIRS TO BE MADE ( USE SUPPLEMENTARY SHEET, IF NECESSARY)

NONE AT THIS TIME

NAME AND TITLE OF INSPECTOR

SIGNATURE OF INSPECTOR

PATRICK KEARNEY NB10111

SECTION VIII – ACTION TAKEN ON RECOMMENDATIONS

NAME GRADE AND TITLE OF OFFICE IN CHARGE

SIGNATURE OF OFFICER IN CHARGE

B. INTERNAL AND EXTERNAL

WITH HYDROSTATIC TEST

C. EXTERNAL UNDER OPERATION

SECTION VII)

UNSCHEDULED INSPECTION

( IF YES, EXPLAIN IN SECTION VII)

SECTION I IDENTIFICATION

TYPE OF PLANT

STM HTG

POINT OF CONTACT

JOSH LOHNSTON

TELEPHONE #

304-623-3461 X3560

BUILDING NUMBER

POWER HOUSE

BOILER TYPE

COND TK

BOILER NUMBER

#2

NB NUMBER

NB 2089

BOILER HORSEPOWER

N/A

BOILER CAPACITY

N/A

MANUFACTURED BY

GEORGE MARKER

YEAR BUILT

YEAR INSTALLED

FIRING EQUIPMENT

N/A

FUEL

N/A

SAFETY VALVE SETTING

N/A

NONE

SECTION III – INTERNAL INSPECTION (TYPES A AND B ONLY)

DESCRIBE INSPECTION FULLY (STATE LOCATION OF ANY SCALE, GREASE, OIL, OR OTHER DEPOSITS; ANY CORROSION, PITTING, GROOVING, CRACKS OR LAMINATIONS; ANY EVIDENCE OF OVERHEATING, SUCH AS BULGING OR WARPING; ANY BROKEN OR LOOSE RIVETS OR STRAYS, ETC.)

CONDITION OF SEAMS, TUBE ENDS, PIPE CONNECTIONS, ETC. (DESCRIBE FULLY AND STATE LOCATION OF ANY CORROSION, LEAKAGE, EROSION, EVIDENCE OF OVERHEATING, SOOT OR OTHER DESTRUCTIVE ACCUMULATIONS, ETC)

No leaks on valves, piping, etc.

SEAMS ARE IN GOOD CONDITION

SET AT (LBS)

N/A

CONDITION AND HOW TESTED (TOTAL SAFETY RELEIF VALVE CAPACITY)

N/A

PRESSURE

GAGES

STATE CORRECTION (IF MADE) STATE REASON (IF NOT TESTED)

GOOD

OTHER

APPLIANCES

WATER COLUMNS, GAGE GLASSES, GAGE COCKS, BLOW OFF PIPE AND VALVE OR COCKS, FEED PIPE, ETC

GOOD

SECTION VI – STATEMENT OF INSPECTOR (BOILER NUMBER NB 2089 )

WAS BOILER PREPARED FOR THOROUGH EXAMINATION? (IF NO, STATE IN SECTIONS VII WHAT WAS NOT PREPARED AND WHY)

YES NO

WAS BOILER ENTERED FOR THE INSPECTION? (IF NO, EXPLAIN REASON IN SECTION VII)

YES NO

SECTION VII - REMARKS

DAMARC

“Quality Inspection Services” LLC Client: CLARKSBURG VA

MED CTR

Date:

8-20-216

Procedure: BIC-WFMT

Project: DA Tank Acceptance Standard: ASME VIII, No Cracks

Location: DAYTON VA MED

CTR

Component /Identification:

DA Tank

NB 3187 YR: 1986

Surface Condition:

As Welded X Ground Other

Material:

STEEL

Examination Method:

Wet Fluorescent

MT Equipment Mfg.:

MAGNAFLUX

Model:

Y-1

Serial No.:

Calibration Date

Current:

AC x DC ___ Halfwave _____

Ampere Turns/ Current Level:

Prod/Yoke Spacing:

6”

Head Shot, Coil, Central Conductor, Yoke:

HAND

Area of Examination: Inside Diameter of accessible weldments

Field Indicator (Pie Gage):

Yes

Particles: Demagnetization:

Yes ____ No ___X__

Identification Examination Results

Accept Reject Cause for Rejection

Circular Seams X Longitudinal Seams A X Nozzle and attachment welds X

Remarks: ________________________________________________________________________

Examined By: PATRICK KEARNEY Level: _____2_________ Date: 8-1-2016

Reviewed By: ____________________________ Level: ______________ Date: ____________\

CLARKSBURG,WV DA-TANK NB 3187

.293

.293

.293 .293

.293 .293

.323

.323 .323

.323 .323

B. INTERNAL AND EXTERNAL

WITH HYDROSTATIC TEST

C. EXTERNAL UNDER OPERATION

SECTION VII)

UNSCHEDULED INSPECTION

( IF YES, EXPLAIN IN SECTION VII)

SECTION I IDENTIFICATION

TYPE OF PLANT

STM HTG

POINT OF CONTACT

JOSH LOHNSTON

TELEPHONE #

304-623-3461 X3560

BUILDING NUMBER

POWER HOUSE

BOILER TYPE

DA TK

BOILER NUMBER

#1

NB NUMBER

NB3187

BOILER HORSEPOWER

N/A

BOILER CAPACITY

MANUFACTURED BY

YEAR BUILT

YEAR INSTALLED

FIRING EQUIPMENT

N/A

FUEL

N/A

SAFETY VALVE SETTING

N/A

NONE

SECTION III – INTERNAL INSPECTION (TYPES A AND B ONLY)

DESCRIBE INSPECTION FULLY (STATE LOCATION OF ANY SCALE, GREASE, OIL, OR OTHER DEPOSITS; ANY CORROSION, PITTING, GROOVING, CRACKS OR LAMINATIONS; ANY EVIDENCE OF OVERHEATING, SUCH AS BULGING OR WARPING; ANY BROKEN OR LOOSE RIVETS OR STRAYS, ETC.)

NO SIGNS OF SCALE,CORROSION, PITTING, OR LAMINATION, NO EVIDENCE OF OVERHEATING, ALL STAYS AND SUPPORTS ARE IN GOOD

CONDITION,

CONDITION OF SEAMS, TUBE ENDS, PIPE CONNECTIONS, ETC. (DESCRIBE FULLY AND STATE LOCATION OF ANY CORROSION, LEAKAGE, EROSION, EVIDENCE OF OVERHEATING, SOOT OR OTHER DESTRUCTIVE ACCUMULATIONS, ETC)

No leaks on valves, piping, etc.

,SEAMS ARE IN GOOD CONDITION

1X2"

SET AT (LBS)

CONDITION AND HOW TESTED (TOTAL SAFETY RELEIF VALVE CAPACITY)

GOOD-VENDER TESTED 1143 LB/HR

PRESSURE

GAGES

STATE CORRECTION (IF MADE) STATE REASON (IF NOT TESTED)

GOOD

OTHER

APPLIANCES

WATER COLUMNS, GAGE GLASSES, GAGE COCKS, BLOW OFF PIPE AND VALVE OR COCKS, FEED PIPE, ETC

GOOD

SECTION VI – STATEMENT OF INSPECTOR (BOILER NUMBER NB 3187 )

WAS BOILER PREPARED FOR THOROUGH EXAMINATION? (IF NO, STATE IN SECTIONS VII WHAT WAS NOT PREPARED AND WHY)

YES NO

WAS BOILER ENTERED FOR THE INSPECTION? (IF NO, EXPLAIN REASON IN SECTION VII)

YES NO

SECTION VII - REMARKS

SS-1 SUMMARY SHEET 7-10-2012
Tank-CON TK#1 CLARKSBURG 2016
Tank-CON TK#2 CLARKSBURG 2016
VA CLARKSBURG COND TK#1A 8-2016
VA CLARKSBURG COND TK#2 8-2016
Mag CLARKSBURG 2016
Tank-DA VA CLARKSBURG 2016
VA CLARKSBURG DA TK 8-16