About this file

36C24519Q0587 36C24519Q0587_1.docx

View the file

Other files

File Type Posted
36C24520C0025-000.docx DOCX document
36C24519Q0587-004.doc DOC document
36C24519Q0587-003.docx DOCX document
36C24519Q0587-004.doc DOC document
36C24519Q0587-001.docx DOCX document
36C24519Q0587-000.docx DOCX document
36C24519Q0587-002.docx DOCX document
36C24519Q0587-002.docx DOCX document
36C24519Q0587-001.docx DOCX document
36C24519Q0587-000.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FedBizOpps Amendment to a Previous Combined Solicitation

CLASSIFICATION CODE

SUBJECT

CONTRACTING OFFICE'S

ZIP-CODE

SOLICITATION NUMBER

BASE NOTICE TYPE

RESPONSE

DATE (MM-DD-YYYY)

ARCHIVE

DAYS AFTER THE RESPONSE DATE

RECOVERY ACT FUNDS

SET-ASIDE

NAICS CODE

CONTRACTING OFFICE

ADDRESS

POINT OF CONTACT

(POC Information Automatically Filled from User Profile Unless Entered)

DESCRIPTION

See Attachment

AGENCY'S URL

URL DESCRIPTION

AGENCY CONTACT'S EMAIL

ADDRESS

EMAIL DESCRIPTION

ADDRESS

POSTAL CODE

COUNTRY

ADDITIONAL INFORMATION

GENERAL INFORMATION

PLACE OF PERFORMANCE

* = Required Field FedBizOpps Amendment to a Previous Combined Solicitation Rev. March 2010 H

AMENDMENT TO SOLICITATION 36C24519Q0587

This is to answer the submitted questions and also to provide attached Past Performace Questionnaire (PPQ).

25405 36C24519Q0587 09-19-2019 N 221310 Department of Veterans Affairs Network Contracting Office 5 (NCO 5) 90C

NCO 5

510 Butler Avenue Martinsburg WV 25405 Phillip.Duba@va.gov Beckley VA Medical Centeer 200 Veterans Drive Beckley, WV 25801 Phillip.Duba@va.gov Questions for Solicitation 36C24519Q0587

1) Does the facility have an existing WMP for the potable water system?

-Yes.

2) Please confirm that the risk assessment, flow diagrams, and WMP formation is only for the utility cooling water system?

-No potable and non-potable water as described in the statement of work.

3) Which laboratory is currently providing the required legionella testing?

-Phigenics.

4) Is the facility utilizing any other data management system currently other than the VA legionella data archive spreadsheet system?

-No.

5) Describe the current water purification arrangement – for example: filter, softener, SDI or RO, etc.

-Boiler plant has a water softener and SPD utilizes a RO system.

6) Who provides the ongoing maintenance and servicing of this equipment?

-Inhouse staff.

7) Is the facility currently conducting the required AAMI testing particularly the TIR 34 testing?

-No

8) Legionella lab analysis is typically a 10-14 day window of time. Will this be sufficient or does the result have to be within 10 days?

-10 days from time the sample is received at the lab.

See attached document: PPQ 36C24519Q0587.