This document is a Questions & Answers file for a VA Medical Center fire pump testing solicitation (Solicitation Number: 36C24425Q0284). The solicitation is a Service-disabled Veteran-owned Small Business Set-Aside for annual fire pump testing at the Lebanon VA Medical Center, with a NAICS Code of 561621 and a business size standard of $25 million. Key details include a base contract plus 4-year options, to be awarded on a Lowest Price Technically Acceptable (LPTA) basis. Vendors must submit quotes via email with separate sections for administrative/regulatory, technical, and pricing information, including past performance narratives demonstrating fire pump testing experience within the last five years. The solicitation requires SAM registration, compliance with 13 CFR 125.6 subcontractor rules, and adherence to the Service Contract Act Wage Determination 2015-4231 v.27. The final date for submitting questions is 03/11/2025 at 2:00 pm, with quotes to be evaluated for technical compliance and best value to the government.

View the file

Other files

File Type Posted
Inspection Report_Lebanon.pdf PDF
36C24425Q0284 0001.docx DOCX document
36C24425Q0284.docx DOCX document
S02 36C24425Q0284 Final.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions & Answers

1.More information is required in order to accurately quote the fire alarm inspection, testing, maintenance & monitoring for this solicitation.
a.Please provide the previous inspection reports.
Prior inspection report is attached.
b.Please provide the device counts for all building.
See SOW, Section B: General Requirements.
2.Please confirm whether a NICET IV certification will be added as a requirement to the solicitation, to ensure the fire alarm system meets all required local, national, government, and industry standards, codes, and regulations.
The above is only applicable for fire alarm testing. This requirement is for fire pump testing only.