Questions From Solicitors (003).pdf

PDF 86 KB Posted

Attached to
J045--Drum Door Resurfacing and Replacement
Solicitation number
36C24423Q0046
Issued by

About this file

This document contains a combined synopsis and solicitation for drum door resurfacing and replacement services at a Veterans Affairs medical center. The solicitation number is 36C24423Q0046 and seeks bids from SDVOSB contractors for drum door resurfacing and replacement on three boilers at the Coatesville, PA VAMC between November 22, 2022 and February 21, 2023. The NAICS code is 238220 and the wage determination is 2015-5791 Rev 20. The point of contact is Keisiha Davenport and questions are due by November 1st. Bids are due by November 3rd and the solicitation incorporates FAR and VAAR clauses.

View the file

Other files

File Type Posted
BLR 3 useful life oct 2020 9.pdf PDF
BLR 3 useful life oct 2020 24.pdf PDF
Image.jpeg JPEG file
Questions From Solicitors (003).pdf PDF
BLR 3 useful life oct 2020 25.pdf PDF
36C24423Q0046 0001_1.docx DOCX document
36C24423Q0046 0001.pdf PDF
Boiler 3 manufacturers data report.pdf PDF
Boiler 1 manufacturers data report.pdf PDF
Boiler 2 manufacturers data report.pdf PDF
WD 2015-5791 COATESVILLE REV 20 DATED 6-27-22.pdf PDF
36C24423Q0046_1.docx DOCX document
36C24423Q0046final.docx DOCX document
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Contractor Questions – 36C24423Q0046

1. Will all (4) boilers be available at the same time for this work? If not, can you please explain how boiler shutdowns will be staged?

One boiler will be available at a time. When a completed boilers drum sealing has been verified, the next boiler will be made available. The next boiler will already be cooled but will need to be drained, and locked out, which could take several hours.

2. With there being (4) boilers, I would like to confirm that there is a total of (12) manhole surfaces/doors and not (16) manhole surfaces/doors.

12 Manholes doors only

3. Will the contractor need to provide and erect scaffolding to access the steam drum surfaces?

The steam drums are 9-10’ above the operating floor with no platforms present.

4. Who is the manufacturer and what is the model number of the boilers?

E. Keeler water tube boilers. One 40000#/hr and two 20000#/hr boilers

5. Can you please provide a legible picture of each boiler’s National Board Plate?

Manufacturer’s data sheets are attached.

6. Is there any information regarding the last known or current condition of the manhole surfaces?

Useful life testing has recommended resurfacing the mating surfaces of the drums due to age and pitting.

7. Will any weld build up on the manhole surfaces be required prior to machining?

There may be some build up required. We are able to get the doors to seal using specialized gasketing.

8. Will there be any internals to be removed to gain access to the confined spa.

I am not sure what space is needed for the milling equipment, it is possible the contract will need to remove some trays in the steam drum.

9. The scope of work mentions 4 boilers. Can you clarify if there are 3 or 4 boilers?

If there are 4 boilers can you share the data report for the fourth boiler?

Only three boilers, one has been taken out of service.

10. Can you confirm that a bond is not required for solicitation notice

36C24423Q0046?

No bond is required.