This notice announces an upcoming Request for Proposal for construction services related to a Retro-Commissioning Mechanical Corrections project located at the Lebanon VA Medical Center. The single firm-fixed price contract will have a period of performance of 545 calendar days from receipt of the Notice to Proceed. The solicitation will be issued according to FAR Subpart 15 procedures and is set aside as 100% for Service-Disabled Veteran Owned Small Businesses. The North American Industry Classification System code is 236220 with an annual revenue size standard of $39.5 million. The estimated construction cost is between $1 million to $2 million. The solicitation will be posted on October 28, 2020 at Contracting Opportunities. All questions must be submitted in writing to the specified email by the specified date. A pre-bid conference will be held approximately one week after posting at a location specified in the solicitation. Respondents must be registered in SAM and verified in CVE at the time of proposal submission according to VAAR Subpart 819.7003(b).
View the file
Other files for this federal contract opportunity
Show all 35
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Achieving swift results
Appendix C
Individual Building Model Overviews
(with and without markup)
AC-4-18 42°F
56°F
481700 BTU/H
68.8 GPM
P-1-18
VSD
488.4 GPM
117.4 FT
(100%)
P-2-18
VSD
0 GPM
0 FT
(0%)
AC-4-22 42°F
52°F
53000 BTU/H
10.6 GPM
P-1-22
VSD
102.8 GPM
117.9 FT
P-2-22
VSD
0 GPM
0 FT
(100/0%)
AHU-1 AHU-2 AHU-3
P-1-2 P-2-2
AC-1-102 44°F
58°F
587300 BTU/H
83.9 GPM
AC-1-1 44°F
58°F
875400 BTU/H
125 GPM
AC-2-144°F
58°F
686000 BTU/H
98 GPM
AC-3-1 44°F
58°F
418900 BTU/H
59.8 GPM
AC-4-1 44°F
58°F
486300 BTU/H
69.4 GPM
AC-11-144°F
56°F
425000 BTU/H
70.8 GPMAC-12-144°F
57°F
104000 BTU/H
16 GPM
AC-6-144°F
58°F
393000 BTU/H
56.1 GPM
AC-9-1 44°F
58°F
227160 BTU/H
32.4 GPM
AC-7-144°F
58°F
523400 BTU/H
74.7 GPM
AC-8-144°F
58°F
410400 BTU/H
58.6 GPM
AC-5-144°F
58°F
202900 BTU/H
29 GPM
AC-14-144°F
58°F
116000 BTU/H
16.6 GPM
CWP 1-1
VSD
1257.4 GPM
250.3 FT
CWP 2-1
VSD
0 GPM
0 FT
(0%)
RTU-3-101 44°F
54°F
90000 BTU/H
18 GPM
AC-1-1942°F
56°F
217000 BTU/H
31 GPM
AC-2-19 42°F
56°F
171000 BTU/H
24.4 GPM
AC-4-1942°F
56°F
92400 BTU/H
13.2 GPM
P-1-19
VSD
82.9 GPM
64.5 FT
P-2-19
VSD
0 GPM
0 FT
(100/0%)
AC-24-1 42°F
52°F
147930 BTU/H
29.6 GPM
24-AHU-1 42°F
52°F
114400 BTU/H
22.9 GPM
CH-1
95°F
85°F
10940200 BTU/H
911.7 TONS
1666.2 GPM
(46.91%)
42°F
55.1°F
CT-1
14600300 BTU/H
2936.6 GPM
(53.382%)
95°F
85°F
P-3
0 GPM
0 FT
(100/0%)
P-5
5501.1 GPM
50.3 FT
P-6
0 GPM
0 FT
(100/0%)
P-4
5501.1 GPM
53.8 FT
P-2
3332.5 GPM
215.6 FT
P-1
3332.5 GPM
216.5 FT
CT-2
14600300 BTU/H
2936.6 GPM
(53.382%)
95°F
85°F
CT-3
14600300 BTU/H
2936.6 GPM
(53.382%)
95°F
85°F
CH-2
95°F
85°F
10940200 BTU/H
911.7 TONS
1666.2 GPM
(46.91%)
42°F
55.1°F
AC-1-17 42°F
56°F
962300 BTU/H
137.4 GPM
AC-2-17 42°F
56°F
632600 BTU/H
90.3 GPM
AC-3-1742°F
56°F
505400 BTU/H
72.2 GPM
AC-4-17 42°F
56°F
256600 BTU/H
36.6 GPM
AC-5-1742°F
56°F
166610 BTU/H
23.8 GPM
RTU-1-1742°F
52°F
RTU-2-1742°F
52°F
P-1-17
VSD
796.4 GPM
82.1 FT
P-2-17
VSD
0 GPM
0 FT
(0%)
106-AC-1
50°F
42°F
259000 BTU/H
64.7 GPM
FM A
FM B
FM C
FM D
FM E
FM F
CHILLER #3CHILLER #2CHILLER #1
HX
TRANSFERSOURCE
PUMP 1 PUMP 2 PUMP 3 PUMP 4
PUMP 5
PUMP 6
TS-IT-01 TS-IT-03 TS-IT-05 TS-IT-07 TS-IT-09 TS-IT-11 TS-IT-13 TS-IT-15
TS-IT-02 TS-IT-04 TS-IT-06 TS-IT-08 TS-IT-10 TS-IT-12 TS-IT-14 TS-IT-16
P-1-136
47.3 GPM
30.7 FT
P-2-136
0 GPM
0 FT
(0%)
AC-1-13642°F
56°F
331100 BTU/H
47.3 GPM
RTU-1-101 44°F
58°F
316000 BTU/H
45.1 GPM
RTU-2-101 44°F
58°F
680000 BTU/H
97.1 GPM
UNIT
RTU-4-2342°F
52°F
100000 BTU/H
20 GPM
RTU-3-2342°F
56°F
100000 BTU/H
14.3 GPM
RTU-1-23 42°F
52°F
100000 BTU/H
20 GPM
RTU-2-23 42°F
54°F
100000 BTU/H
16.7 GPM
CHP-1
71 GPM
37.2 FT
VSD
CHP-2
0 GPM
0 FT
(0%)
VSD
?°F
40°F
1-CH-1
0 BTU/H
0 TONS
0 GPM
AHU-4AHU-5
AC-3-1842°F
56°F
423100 BTU/H
60.4 GPM
AC-1-18 42°F
56°F
980100 BTU/H
140 GPM
AC-2-1842°F
56°F
1372100 BTU/H
196 GPM
AC-5-1842°F
56°F
161980 BTU/H
23.1 GPM
AHU-1-10342°F
52°F
875000 BTU/H
174.9 GPM
AHU-2-10342°F
62°F
600000 BTU/H
60 GPM
AHU-3-10342°F
65°F
554000 BTU/H
48.2 GPM
AHU-4-10342°F
62°F
284000 BTU/H
28.4 GPM
AC-3-1942°F
56°F
100300 BTU/H
14.3 GPM
CV-AC-5-17
CV-AC-1-17 CV-AC-3-17
CV-AC-2-17
CV-AC-4-17
CV-RTU-2-17 CV-RTU-1-17
V-1 V-2
V-3
V-4
V-5
V-6 V-7
STR-1
STR-2
STR-3 STR-4
STR-5
STR-6
STR-7
BLDG 17 DP SENSOR
CV-RTU-1-23
V-8
STR-8
CV-RTU-4-23
V-9
STR-9
CV-AC-4-18
BV-AC-4-18
STR-10
V-10
CV-AC-3-18
BV-AC-3-18
STR-11
V-11
CV-AC-1-18
CV-AC-5-18STR-12
V-12
CV-AC-2-18
STR-13
V-13
BV-AC-1-18
STR-14
BV-AC-2-18
STR-15
CV-15
V-14
JTP-1 JTP-2
CV-16
V-15
V-16
FM-1
CV-17
FM-2
SENF-1
STR-16
V-17
CV-RTU-3-23
STR-17
V-18
CV-RTU-2-23
BV-5
FM-3
BV-6
CV-20
FM-4
CKV-1CKV-2
V-19
V-20
JTP-3JTP-4
JTP-5JTP-6
JTP-7JTP-8
AC-5-22 42°F
52°F
60000 BTU/H
12 GPM
AC-3-22 42°F
52°F
275000 BTU/H
55 GPM
CV-AC-3-22 CV-AC-4-22
STR-18 STR-19
V-21
V-22
CV-23
CV-AC-1-136
STR-20
V-23
FM-5
FM-6
CV-25
JTP-9
BV-7
ASU-P1 ASU-P2
GRND FLR WING
117100 BTU/H
23.4 GPM54°F
44°F
GRND FLR WING
150000 BTU/H
30 GPM
54°F
44°F
RM125Q
13800 BTU/H
2.8 GPM
54°F 44°F
RM125A
8500 BTU/H
1.7 GPM
54°F 44°F
1ST FLR WING
66400 BTU/H
13.3 GPM
54°F
44°F 1ST FLR WING
175000 BTU/H
35 GPM
54°F
44°F
2ND FLR WING
176200 BTU/H
35.2 GPM
54°F
44°F
2ND FLR WING
155100 BTU/H
31 GPM54°F
44°F
3RD FLR WING
133100 BTU/H
26.6 GPM54°F
44°F
3RD FLR WING
120100 BTU/H
24 GPM
54°F
44°F
5TH FLR WING
134600 BTU/H
26.9 GPM
54°F
44°F
5TH FLOOR WING
146100 BTU/H
29.2 GPM
54°F 44°F
4TH FLR WING
129700 BTU/H
25.9 GPM
54°F
44°F
C58
8800 BTU/H
1.8 GPM
54°F44°F
CV-AC-12-1
CV-AC-4-1
CV-AC-9-1 CV-AC-5-1
CV-AC-1-1
CV-AC-3-1
CV-AC-6-1
CV-AC-2-1
CV-AC-11-1
CV-AC-7-1
CV-AC-8-1
CV-AC-14-1
CV-AC-1-102
STR-21
STR-22
STR-23
STR-24
STR-25 STR-26
STR-27
STR-28
STR-29
STR-30
STR-31
STR-32
STR-33
STR-34
STR-35
CV-RTU-1-101
CV-RTU-2-101
STR-36
STR-37 STR-38
STR-39
STR-40
STR-41
STR-42
STR-43
STR-44
STR-45
STR-46
CV-C58
CV-GRND FLR WING
CV-GRND FLR WING
CV-1ST FLR WING
CV-RM125A
CV-RM125Q
CV-1ST FLR WING
AHU-3N-10442°F
52°F
584000 BTU/H
116.8 GPM
AHU-5-10442°F
52°F
818000 BTU/H
163.5 GPM
CHWP-1-104
VSD
756.7 GPM
89.2 FT
CHWP-2-104
VSD
0 GPM
0 FT
(0%)
4TH FLOOR WING
453500 BTU/H
90.7 GPM
52°F
42°F
3RD FLOOR WING
419200 BTU/H
83.8 GPM52°F
42°F
5TH FLOOR WING
190100 BTU/H
38 GPM
52°F
42°F
2ND FLOOR WING
149200 BTU/H
29.8 GPM
52°F
42°F
FCU-1
12800 BTU/H
2.6 GPM
52°F
42°F
FCU-2
35130 BTU/H
7 GPM
52°F
42°F
FCU-3
35130 BTU/H
7 GPM
52°F
42°F
FCU-4
35130 BTU/H
7 GPM
52°F
42°F
P-1
76.1 GPM
37.3 FT
VSD
P-2
76.1 GPM
37.3 FT
VSD
CV-FCU-4
CV-FCU-2
CV-FCU-3
CV-FCU-1
CV-AC-24-1
CV-24-AHU-1
STR-47
STR-48
STR-49
STR-50
STR-51
STR-52
STR-53
STR-54
STR-55
STR-56
CV-AC-1-19 CV-AC-2-19
CV-AC-4-19
CV-AC-3-19
V-24 V-25
V-26
V-27
V-28
V-29
CV-AC-5-22
STR-57 V-30
JTP-10 JTP-11
JTP-12JTP-13
CV-59
CKV-3
V-31
V-32
CV-60
JTP-14 JTP-15
JTP-16 JTP-17
JTP-18 JTP-19
V-33
JTP-20
JTP-21
JTP-22
JTP-23
V-34 V-35
CV-61 CV-62
JTP-24 JTP-25
JTP-26 JTP-27
JTP-28
JTP-29
4TH FLOOR WING
384500 BTU/H
76.9 GPM
52°F
42°F
AH-1 42°F
54°F
390100 BTU/H
65 GPM
AH-242°F
54°F
311100 BTU/H
51.8 GPM
CV-RTU-3-101
STR-58
V-36
V-37 V-38
CV-AHU-4-103
CV-AHU-3N-104CV-AHU-3-103
CV-AHU-5-104
CV-AHU-2-103
STR-59
STR-60STR-61
STR-62
STR-63
JTP-30
JTP-31
JTP-32
V-39 V-40
JTP-33
JTP-34
JTP-35
JTP-36
JTP-37
V-41
V-42
V-43
V-44
V-45
V-46
V-47
V-48
V-49 V-50
V-51
V-52
V-53
V-54
V-55
V-56
JTP-38 JTP-39
JTP-40 JTP-41
JTP-42JTP-43JTP-44JTP-45
CV-5TH FLOOR WING
JTP-46JTP-47
CV-5TH FLR WING
STR-64
JTP-48 JTP-49
STR-65
CV-4TH FLR WING
CV-3RD FLR WING
CV-2ND FLR WING
STR-66
CV-2ND FLR WING
JTP-50JTP-51
JTP-52
JTP-53
CV-75
CV-AH-1 CV-AH-2
STR-67
STR-68
STR-69
CV-2ND FLOOR WING
CV-3RD FLOOR WINGSTR-70
STR-71
STR-72
CV-4TH FLOOR WING
CV-4TH FLOOR WING
CV-AHU-1-103
STR-73
ONCOLOGY AHU42°F
52°F
825000 BTU/H
164.9 GPM
CV-ONCOLOGY AHU
STR-74
FUTURE ROOF LOAD FUTURE ROOF LOAD
JTP-54 JTP-55 JTP-56 JTP-57
SENF-2
SENF-3
SENF-4
CV-84
CV-85
V-57
V-58
UNIT
CH-1
CH-2
P-3-2
FCU-1
0 BTU/H
0 GPM
?°F
?°F
AHU?°F
?°F
0 BTU/H
0 GPM
V-59
V-60
V-61
V-62
LEVEL 1 FCU
42000 BTU/H
8.4 GPM
52°F
42°F
LEVEL 1 FCU
42000 BTU/H
8.4 GPM
52°F
42°F
LEVEL 1 FCU
42000 BTU/H
8.4 GPM
52°F
42°F
12"6'
12"7.5'
8" 8'
8"
6'
6"
20'
10"
10'
12"5'
10"17' 10"
17'
18" 8'
12"
8'
10"17' 10"17' 12"
20'
14"
20'
12"
12'
12"14'
10"8'
12"15'
14"12'
CHWR12"60'
2"
18'
2"
25'
4" 28.5'4"
11'
4"150'
3"
16.5'
3"
5'
C H W R
6"15'
C H W R
6"265'
C H W S
6"15'
C H W S
6" 265'
6"
48'
2.5"25'
2.5"55'
2.5" 25'
6"6'
6"
9'
6"
20'
6"
6'
8"
6'
8" 12'
3"
5'
3" 56.5'
3"109'
3"45.5' 4" 24'
3"50'
4"150'
6"
20'
4"150'
3" 45.5'
4"24'
6"
10'
3"50'
CHWR
3"120'
1.25"
35'
3"25'
CHWS
3"120'
1.25" 35'
3"25'
4"
8'
6" 6'
2.5"
40'
3"
50' 2.5"100'
3"50'
CHWS
12"
550'
756.7 GPM
CHWR CHWR
12"
550'
756.7 GPM
C H W S
CHWS
12"250'
2575.7 GPM
CHWS
8"130'
3"56.5'
C H W R
CHWR
12"250'
2986.8 GPM
C H W S
3"130'
CHWR
8"
130'
CHWS
8"170'
CHWR
8"
170'
2"40'
2"40'
C H W S
6"400' C H W R
6"
400'
C H W R
3"130'
3"
6'
2.5"
40'
2.5" 20'
2"0'
2.5"
40'
2.5"
40'
2.5"
20'
2.5"
20'
2.5"20'
4"
150'
C H W R
CHWR
4"100'
C H W S
CHWS
4"100'
1.5"50' 1.5"
50'
1.5"20'
CHWR
2"
50'
6"
33'
CHWR
6"
30'
2.5"
100'
2" 110'
2"15'
6"
12'
4"60'
3"
12'
2"28'
6"
12'
CHWS
2"190'
2.5"160'
6"
6'
6"
6'
C H W S
6"
100'
CHWS
2"155'
CHWS
CHWS
2.5" 490'
6"
8'
8"5'
CHWS5"70'
CHWS
12"
200'
1257.4 GPM
CHWS
C H W S
C H W S
8"
575'
6"15'
CHWS
C H W S
C H W S
4"200'
2.5"30'
6"25'
C H W S
3"
30'
3"
24'
CHWS
2"155'
3"
24'
CHWS
1.25"
150'
0.75"50'
4"12'
CHWR
12"
200'
2053.8 GPM
3"
15'
4"
12'
2.5"100'
6"
12'
CHWR
2"190'
6"
12'
6"8'
2.5"160'
6"
6'
6"
6'
C H W R
6"
100'
8"30'
CHWR
CHWR
2.5"
490'
CHWR0.75"50'
CHWR
1.25"150'
6"25'
C H W R
3"
30'
2.5" 66'
4"60'CHWR
2"110'
3"
24'
2" 15'
2.5"45'
2"
20'
CHWR
3"30'
2.5"
20' 2"
28'
2"80'
8"5'
3"
60'
6"
8'
3"
25'
3"25'
2"20' 3"
30'
2.5"
45'
2.5"
20'
2"80'
3"
70'
4"
40'
6"15'
2.5"30'
CHWS
1.5"180'
2"155'
2"30'
2"30'
CHWR
2"155'
CHWR
2"155'
CHWR
1.5"180'
12"8'
12"15'
3"110'
1.5"
20'
3" 15'
1.5"
20'
2.5"30'
2"80'
2"0'
2"
80'
2"30'
2.5"65'
1.5"20'
4"24' 4"
24'
3"11'3"11'
6"
150'
6" 150'
6"
20'
4"11' 4"11'
4"11' 4"
11'
2.5"100'
3" 100'
3" 100'
3"50'
2.5" 20'
3"50'
C H W S
6"45' C H W R
6"
45'
6"
210' 6"
210'
6"30'
4"
22'
4"22'
1.5"
50'
1.5"
30'
CHWS
2"150'
4"
11'
CHWR
2"150'
4"
10'
4"
10'
4"
10'
4"
10'
4"
10'
4"
10'
6"
10'
6"20'
CHWS2.5"130' CHWS2.5"100'
4"
40'
2"100' 2"
100'
3"
70'
12"30'
C H W S
C H W S
C H W R
C H W R
12"5'
12"15'
12"15'
8"
0'
C H W S
CHWS
2"
65'
C H W R
2"65'
C H W S
C H W S
6"
120'
C H W R
C H W R
6"
120'
C H W R
C H W R
CHWR
8"575'
C H W S
CHWS
3"100'
C H W R
CHWR
3"
100'
C H W R
C H W R
CHWR
4"
200'
C H W R
3"
100'
C H W S
3"100'
3"110'
3"15'
3" 12' 3"
12'
3"
14'
3"12'
3"
14'
2" 10'
2.5"
66'
3"
24'
1.5"100'
1.5"100'
CHWS
1.75"155'
CHWR
1.75"155'
2"155'
2.5"190'
2.5"190'
3"60'
CHWR
5"70'
CHWR
2.5"130'
CHWR
2.5" 100'
2"
145'
2"145'
CHWR
3"150'
CHWS
3"150'
CHWS
3"150' CHWS
3" 150'
CHWR
3" 150'CHWR
3"150'
12"
30' 12"60'
12"
0'
12" 30'
12"60'
4"0'
4"90'
4"90'
3"25'
12"30'
3"25'
12"30'
2.5"0'
6"25'
6"
25'
2.5"
0'
8"
15'
8"30'
8"30'
8"15'
2.5"0'
2.5"0'
10"25'
10"25'
0"
0'
0"0'
Bldg 18 (Outpatient)
Bldg 23 (Admin)
Bldg 22 (Education)
Bldg 22 Ice Storage Plant
Bldg 2 (Admin)
Bldg 104 (Hospital)
Bldg 102 (Rehab)
Bldg 1 (Main)
Bldg 101 (Hospital)
Bldg 19 (Police/Admin)
Bldg 24 (YMCA)
Bldg 7 (Laundry)
Bldg 6 (Warehouse)
Bldg 136 (IT)
Bldg 17 (Amb Care)
Bldg 106 (Chapel)
For clarity in the model, Alares did not include all valves, strainers, air separators, and/or other contributors to the pressure drop near the chillers and pumps, so they are not included in the calculated pump heads.
New SPS unit serves Bldg 1.
Unit is not online yet.
Connects Bldgs 1/101.
No information provided.
New unit serves corridor.
Unit is not online yet.
Connects Bldgs 1/104.
No information provided.
20 HP motors on pumps sharpie note on pump covering:
GPM 318 TDH 105
Imp Dia 11.50"
Basement
Rooftop
First Floor
Penthouse
Basement
Sub-basement
Basement
1st Floor
2nd Floor
3rd Floor
4th Floor
5th Floor
Attic
Attic
Basement
1st Floor
2nd Floor
3rd Floor
4th Floor
5th Floor
Penthouse
5th Floor
4th Floor
3rd Floor
2nd Floor
1st Floor
Basement
Ground Floor
6th Floor
2nd Floor, Roof
6th Floor, Roof6th Floor, Roof
Rooftop
The main laundry AHU has been removed.
Lone FCU assumed negligible to overall model.
Project No. 37-5345 Drawing 106-H2
First Floor
Second Floor
Third Floor
There are two separate CHW systems in the building;
- A Building CHW System that serves all the chilled water devices, consisting of 2 air-cooled chillers w/ 2 primary pumps and 1 backup
- A 30 ton CHW system that consists of 1 air-cooled chiller and two constant volume pumps which serves the data center, IT closets and elevator equip. room
Campus CHW system is only available to be used by the 30-ton system in the event of failure
Used recommended model diameters for piping as could not confirm actual sizes (8")
Assumed 100,000 BTUH and a 10 degF delta T for all four units.
CHW pumps were rated for
82 GPM
Offices served by split system.
The AHU serves the chapel.
Bldg 10 (Chiller Plant)
1st Floor Roof
First Floor
Second Floor
Third Floor
Roof
1st Floor
Air Cooled Chiller Pumps
MAIN RISERAC-7 + AC-8 RISER
B102 CHW LINE
AC-1-14 + GRND FLR FCU LINE
ASSUMED LOAD OF 175,000 BTUH
AS NO UPDATED VALUES AVAILABLE.
Proj. No. 595-04-131 has a CHW Riser which shows a flow of 38.5 GPM for this floor
AC-6 + AC-3 RISER
6th Floor
Drawings used:
Construct ICU Med Surge Unit 595-335 Surgery.ED.Endo 595-390
Renovate 1-2B Bed Unit 595-10-105
Drawings used for FCU sizing in Bldg 17:
5th floor - 595-02-107 Relocate Dental 4th floor - 595-433 Ambulatory Care Improvements 3rd floor - 595-433 Ambulatory Care Improvements 2nd floor - 595-060 Construct Ambulatory Care 1st floor - 595-060 Construct Ambulatory Care
Mechanical Space
First Floor
Assumed 60,000 BTUH for AHU-5 as no other information was available.
This is a former lab unit.
This is the combined load of 28 FCUs located on this wing. Largest pipe size and furthest pipe distance was used
Penthouse
Basement
Roof
Roof
Pump Design Values:
GPM = 337
TDH = 75
Design Pump Values GPM = 606 per pump TDH = 105 per pump
Pump Design Values:
GPM = 600 per pump
TDH = 95 per pump
Pump Design Values:
GPM = 1950 per pump TDH = 145 per pump
Air Cooled Chiller appears not to be working during Alares site visits. For purpose of model this chiller was not connected to the overall system
Capacity = 134.6 tons EWT = 53.1 degF LWT = 40 degF
GPM = 246
Possible issue with pressure for this system.
This issue is most likely arising with the air cooled chiller system not being in operation and some possible issues with pipe sizes on 6th floor
Future load 350 GPM Future Load 700 GPM
Rated GPM = 246
TDH = 135
Equipped w/ VFD, 15 HP motor
Combination of 7 loads totaling 66,400 BTUH
Combination of 18 loads totaling 176,200 BTUH
Combination of 12 loads totaling 155,100 BTUH
Combination of 22 loads totaling 120,100 BTUH
Combination of 15 loads totaling 133,100 BTUH
Combination of 18 loads totaling 129,700 BTUH
ASSUMED LOAD OF 150,000 BTUH
AS NO UPDATED VALUES AVAILABLE.
Proj. No. 595-04-131 has a CHW Riser which shows a flow of 39.8 GPM for this floor
Combination of 20 loads totaling 146,100 BTUH
Combination of 18 loads totaling 134,600 BTUH
Possible relocation for Differential Pressure Sensor
Possible piping size increase needed.
Currently 2.5", model recommends increasing to 4"
Possible piping size increases needed Currently 3-4", model recommends increasing to 5"
Possible piping size increases needed Currently 1.25", model recommends increasing to 2"
Possible piping size increases needed Currently 2", model recommends increasing to 3"
Possible piping size increases needed Currently 4", model recommends increasing to 6"
Possible piping size increases needed Currently 2.5", model recommends increasing to 4"
Possible piping size increases needed Currently 2", model recommends increasing to 3"
Possible piping size increases needed Currently 2.5", model recommends increasing to 3"
Pumps installed here along with FCUs 1-4 and 24-AHU-1 are under construction and are part of the new renovations at Bldg. 24 (Project No. 595-13-106)
No details available on CHW to this building.
Assumed negligible to overall model.
Representative of the pipe vault which is located north of Building 2.
See report appendices detailing connections for this area.
Ice Storage Plant supply and return lines only shown here as illustration. Unable to tie into working model.
The Ice Storage Plant is only for illustration within the model. It is not connected to the chiller plant output and overall loads.
Consists of 3 RTAC air-cooled chillers upstream of ice storage tanks, 2 variable secondary loop manifolded pumps, and pump skid with:
4 variable primary flow manifolded N+1 pumps, chiller min. flow bypass valve and heat exchanger
These future loads were noted from Project 595-390, and are shown on M-701R6 Chilled Water Schematic for Bldg. 104.
Basement
No values inputted as no drawing information available and unable to confirm if these units are supplied by the campus CHW
BLDG 101 LINE
Secondary Chilled Water Pump Control (Bldgs 1, 2, 17, 18, 19 & 22) 595-03-101, HVAC Deficiencies Chilled Water System Corrections, H1, 15 October 2003
1. Each secondary CHW pump shall be sequenced in an alternating lead/standby arrangement.
2. On a call from ECC for CHW flow, lead secondary CHW pump shall energize. The pump speed shall vary to maintain a system differential setpoint as sensed by the differential pressure sensor located in the building secondary system. The differential pressure sensor shall be located out in the building secondary CHW loop shall send a signal to VFD controller based on the differential pressure across SCWS and SCWR piping. The remote transmitter shall be located in the secondary loop where the greatest pressure is required.
3. Pump speed shall not reduce below 30% (adj.). When the speed falls to 30%, bypass valve V-2 shall slowly modulate to maintain the DPS setpoint.
4. CHW control valve V-1 shall modulate to maintain a CHW temp of 44 degF (adj.) as sensed by temperature sensor T-1.
5. Other temperature sensors shall indicate chilled water temperature on operators terminal.
Ice Storage Plant System General Operation Description 595-11-131, Thermal Storage for Chiller Plant, MI-001, 07/18/2016
1. Ice on pipe internal melt VPF (variable-primary flow):
Three (3) RTAC air-cooled chillers upstream of ice storage tanks, two (2) variable secondary loop manifolded pumps, and pump skid with: four (4) variable primary flow manifolded N+1 pumps, chiller minimum flow bypass valve, heat exchanger
2. Operation narrative:
The existing chilled water plant will remain the primary cooling entity in the system. It will be controlled via the existing Tracer Summit system with new supervisory control via the new Tracer ES system. The existing plant's system will be re-commissioned to operate against the original design criteria, and will be ported to the Tracer ES system to provide a single-seat graphics, dashboards and reports for both plant's operations.
3. Normal operation:
The load of the central plant will be monitored at all times. During adjustable daytime operation windows, the central plant will call for an ice plant cooling contribution to the facility in order to either reduce the central cooling plant from two-chiller to one-chiller operation, from a full load to a more efficient part-load status, or to totally supplant a single chiller at low part load operation. The logic to make the determination of when and at what setpoints these transitions will take place will be addressable from the web-based graphical interface. Trane will work with the engineer and owner through the commissioning period to clarify the setpoints, timing, and mode transition triggers to maximize the operational benefits of the mode transfers.
4. Emergency operation:
The variable temperature and flows of the ice plant to the heat exchanger will allow various rates of load shaving to be performed on the return water flow to the central plant. The level of load impact and target central plant return water temperatures will likewise be calculated by the Tracer ES system. The target resultant is a reduced net energy cost and a reduction in peak loads.
Central Chiller Plant Operation 595-15-203, Chiller Replacement, M-801, 10-06-2017
1. Chiller
a. Chillers 10-CH-1 and 10-CH-2 are to be on a lead-lag control to have approximate equal run time. Each week, the lead chiller designation shall change.
b. Upon the chilled water plant being enabled and the centrifugal chillers being active by the above mode control table, the evaporator chilled water isolation valve (ZC-1 or ZC-3, to match lead chiller) shall be commanded to open.
c. After the primary chilled water pump has started and is under differential pressure speed control, the chiller start cycle shall continue. The lead condenser water pump shall start and the cooling towers shall be started as described below.
d. After the chiller controller has established the condenser water and chilled water flow, the chiller shall start under its self-contained control system.
e. A single chiller shall be allowed to run for the first five minutes after initiation of the central chiller plant. After this period, the lag chiller shall be turned on based on distribution water flow of the plant as measured by FT-1.
f. When flow FT-1 exceeds 1,350 gpm, the lag chilled water pump shall be added as described in the primary chilled water pump control.
g. When the lag water pump is under differential pressure control and the lag chiller isolation valves are open, the startup sequence for the chiller shall continue.
h. The lag condenser water pump and an additional cooling tower shall be energized.
i. After the lag chiller controller has established the condenser water and chilled water flow, the chiller shall start under its self-contained control system.
2. Cooling Towers
a. The number of closed circuit cooling towers (each tower has multiple cells) is as follows:
i. One chiller operating - two towers
ii. Two chillers operating - three towers
b. Upon tower start up: the condenser water flow isolation valve shall open; the tower circulation pumps shall energize and the fans of the tower shall be controlled as described below.
c. Cooling tower fan control:
i. When the cooling tower basin temperature rises to 2 degrees F above the current tower leaving water setpoint, the cooling tower lead tower fan shall be turned on at minimum speed and the control loop shall be enabled.
1. The cooling tower fan speed shall be modulated to maintain the desired cooling tower leaving water temperature.
2. When the operating fan(s) are operating at 40 percent speed an additional fan shall be enabled and controlled at the same speed as the operating fans until all active cooling tower cell fans are enabled.
3. When operating fans are running at minimum speed of 30% full speed and the tower supply water temperature is 5 degrees F below the current tower leaving water setpoint, the most lag tower fan shall be turned off.
4. Cooling tower fans shall have 5 minute minimum on and off time delays.
5. Cooling tower fan sequence shall be rotated on a 7 day basis to equalize fan run time.
d. Cooling tower leaving water setpoint optimization
i. The chiller plant control system shall calculate the optimal tower setpoint at any chiller(s) load and ambient wet bulb. The chiller plant control system shall provide as an output a leaving tower water temperature setpoint.
ii. Optimal performance is defined as the lowest total kW input consumed by both chiller(s) plus cooling tower(s) while maintaining chilled water setpoint.
iii. As part of the BMS/ATC contractor's letter of specification compliance (to be submitted 10 days prior to the scheduled bid date), provide optimal setpoint and estimated chiller + tower power (kW) for the following load and ambient conditions:
1. Chiller Load 100% Full Load, Wet Bulb 78 deg F, Tower Setpoint -- deg F, Chiller + Tower Power - kW
2. Chiller Load 75% Full Load, Wet Bulb 74 deg F, Tower Setpoint -- deg F, Chiller + Tower Power - kW
3. Chiller Load 50% Full Load, Wet Bulb 70 deg F, Tower Setpoint -- deg F, Chiller + Tower Power - kW
4. Chiller Load 50% Full Load, Wet Bulb 60 deg F, Tower Setpoint -- deg F, Chiller + Tower Power - kW
5. Chiller Load 25% Full Load, Wet Bulb 66 deg F, Tower Setpoint -- deg F, Chiller + Tower Power - kW
iv. At all times the tower leaving setpoint shall be limited within the high and low values specific to the chiller(s) being supplied as specified by the chiller manufacturer.
e. The chiller plant control system shall include a chiller/cooling tower optimization routine. As a minimum, the following chiller and tower characteristics shall be used in the optimization routine.
i. Chiller type (per chiller)
ii. Chiller full load efficiency (kW/ton)
iii. Chiller part load performance (kW/ton) (efficiencies from 100-10% in 10% increments)
iv. Chiller condenser water flow rate
v. Tower type (per tower)
vi. Tower approach temperature
vii. Tower range
viii. Actual instantaneous chiller tons
Notes from site visits:
Did not see V-4, V-5, or V-6 in field.
Flow meter (FM) IDs came from Alares;
FMs are not labeled in the field.
CHW flow meter IDs on front-end:
FM-1, FM-2, and FM-3
CW flow meter IDs on front-end:
FM-4, FM-5, and FM-6
Mechanical Room
Exterior
Mechanical Room
BTU/H for AC-9-1 comes from Alares' latest design (Previous BTU/H from latest available drawing set was 208,260 BTU)
Estimate total cooling load of FCUs on Level 1
Estimate total cooling load of FCUs on Level 2
Estimate total cooling load of FCUs on Level 3
481700 BTU/H
68.8 GPM
P-1-18
VSD
488.4 GPM
117.4 FT
(100%)
P-2-18
VSD
0 GPM
0 FT
(0%)
AC-4-22 42°F
52°F
53000 BTU/H
10.6 GPM
P-1-22
VSD
102.8 GPM
117.9 FT
P-2-22
VSD
0 GPM
0 FT
(100/0%)
AHU-1 AHU-2 AHU-3
P-1-2 P-2-2
AC-1-102 44°F
58°F
587300 BTU/H
83.9 GPM
AC-1-1 44°F
58°F
875400 BTU/H
125 GPM
AC-2-144°F
58°F
686000 BTU/H
98 GPM
AC-3-1 44°F
58°F
418900 BTU/H
59.8 GPM
AC-4-1 44°F
58°F
486300 BTU/H
69.4 GPM
AC-11-144°F
56°F
425000 BTU/H
70.8 GPMAC-12-144°F
57°F
104000 BTU/H
16 GPM
AC-6-144°F
58°F
393000 BTU/H
56.1 GPM
AC-9-1 44°F
58°F
227160 BTU/H
32.4 GPM
AC-7-144°F
58°F
523400 BTU/H
74.7 GPM
AC-8-144°F
58°F
410400 BTU/H
58.6 GPM
AC-5-144°F
58°F
202900 BTU/H
29 GPM
AC-14-144°F
58°F
116000 BTU/H
16.6 GPM
CWP 1-1
VSD
1257.4 GPM
250.3 FT
CWP 2-1
VSD
0 GPM
0 FT
(0%)
RTU-3-101 44°F
54°F
90000 BTU/H
18 GPM
AC-1-1942°F
56°F
217000 BTU/H
31 GPM
AC-2-19 42°F
56°F
171000 BTU/H
24.4 GPM
AC-4-1942°F
56°F
92400 BTU/H
13.2 GPM
P-1-19
VSD
82.9 GPM
64.5 FT
P-2-19
VSD
0 GPM
0 FT
(100/0%)
AC-24-1 42°F
52°F
147930 BTU/H
29.6 GPM
24-AHU-1 42°F
52°F
114400 BTU/H
22.9 GPM
CH-1
95°F
85°F
10940200 BTU/H
911.7 TONS
1666.2 GPM
(46.91%)
42°F
55.1°F
CT-1
14600300 BTU/H
2936.6 GPM
(53.382%)
95°F
85°F
P-3
0 GPM
0 FT
(100/0%)
P-5
5501.1 GPM
50.3 FT
P-6
0 GPM
0 FT
(100/0%)
P-4
5501.1 GPM
53.8 FT
P-2
3332.5 GPM
215.6 FT
P-1
3332.5 GPM
216.5 FT
CT-2
14600300 BTU/H
2936.6 GPM
(53.382%)
95°F
85°F
CT-3
14600300 BTU/H
2936.6 GPM
(53.382%)
95°F
85°F
CH-2
95°F
85°F
10940200 BTU/H
911.7 TONS
1666.2 GPM
(46.91%)
42°F
55.1°F
AC-1-17 42°F
56°F
962300 BTU/H
137.4 GPM
AC-2-17 42°F
56°F
632600 BTU/H
90.3 GPM
AC-3-1742°F
56°F
505400 BTU/H
72.2 GPM
AC-4-17 42°F
56°F
256600 BTU/H
36.6 GPM
AC-5-1742°F
56°F
166610 BTU/H
23.8 GPM
RTU-1-1742°F
52°F
RTU-2-1742°F
52°F
P-1-17
VSD
796.4 GPM
82.1 FT
P-2-17
VSD
0 GPM
0 FT
(0%)
106-AC-1
50°F
42°F
259000 BTU/H
64.7 GPM
FM A
FM B
FM C
FM D
FM E
FM F
CHILLER #3CHILLER #2CHILLER #1
HX
TRANSFERSOURCE
PUMP 1 PUMP 2 PUMP 3 PUMP 4
PUMP 5
PUMP 6
TS-IT-01 TS-IT-03 TS-IT-05 TS-IT-07 TS-IT-09 TS-IT-11 TS-IT-13 TS-IT-15
TS-IT-02 TS-IT-04 TS-IT-06 TS-IT-08 TS-IT-10 TS-IT-12 TS-IT-14 TS-IT-16
P-1-136
47.3 GPM
30.7 FT
P-2-136
0 GPM
0 FT
(0%)
AC-1-13642°F
56°F
331100 BTU/H
47.3 GPM
RTU-1-101 44°F
58°F
316000 BTU/H
45.1 GPM
RTU-2-101 44°F
58°F
680000 BTU/H
97.1 GPM
UNIT
RTU-4-2342°F
52°F
100000 BTU/H
20 GPM
RTU-3-2342°F
56°F
100000 BTU/H
14.3 GPM
RTU-1-23 42°F
52°F
100000 BTU/H
20 GPM
RTU-2-23 42°F
54°F
100000 BTU/H
16.7 GPM
CHP-1
71 GPM
37.2 FT
VSD
CHP-2
0 GPM
0 FT
(0%)
VSD
?°F
40°F
1-CH-1
0 BTU/H
0 TONS
0 GPM
AHU-4AHU-5
AC-3-1842°F
56°F
423100 BTU/H
60.4 GPM
AC-1-18 42°F
56°F
980100 BTU/H
140 GPM
AC-2-1842°F
56°F
1372100 BTU/H
196 GPM
AC-5-1842°F
56°F
161980 BTU/H
23.1 GPM
AHU-1-10342°F
52°F
875000 BTU/H
174.9 GPM
AHU-2-10342°F
62°F
600000 BTU/H
60 GPM
AHU-3-10342°F
65°F
554000 BTU/H
48.2 GPM
AHU-4-10342°F
62°F
284000 BTU/H
28.4 GPM
AC-3-1942°F
56°F
100300 BTU/H
14.3 GPM
CV-AC-5-17
CV-AC-1-17 CV-AC-3-17
CV-AC-2-17
CV-AC-4-17
CV-RTU-2-17 CV-RTU-1-17
V-1 V-2
V-3
V-4
V-5
V-6 V-7
STR-1
STR-2
STR-3 STR-4
STR-5
STR-6
STR-7
BLDG 17 DP SENSOR
CV-RTU-1-23
V-8
STR-8
CV-RTU-4-23
V-9
STR-9
CV-AC-4-18
BV-AC-4-18
STR-10
V-10
CV-AC-3-18
BV-AC-3-18
STR-11
V-11
CV-AC-1-18
CV-AC-5-18STR-12
V-12
CV-AC-2-18
STR-13
V-13
BV-AC-1-18
STR-14
BV-AC-2-18
STR-15
CV-15
V-14
JTP-1 JTP-2
CV-16
V-15
V-16
FM-1
CV-17
FM-2
SENF-1
STR-16
V-17
CV-RTU-3-23
STR-17
V-18
CV-RTU-2-23
BV-5
FM-3
BV-6
CV-20
FM-4
CKV-1CKV-2
V-19
V-20
JTP-3JTP-4
JTP-5JTP-6
JTP-7JTP-8
AC-5-22 42°F
52°F
60000 BTU/H
12 GPM
AC-3-22 42°F
52°F
275000 BTU/H
55 GPM
CV-AC-3-22 CV-AC-4-22
STR-18 STR-19
V-21
V-22
CV-23
CV-AC-1-136
STR-20
V-23
FM-5
FM-6
CV-25
JTP-9
BV-7
ASU-P1 ASU-P2
GRND FLR WING
117100 BTU/H
23.4 GPM54°F
44°F
GRND FLR WING
150000 BTU/H
30 GPM
54°F
44°F
RM125Q
13800 BTU/H
2.8 GPM
54°F 44°F
RM125A
8500 BTU/H
1.7 GPM
54°F 44°F
1ST FLR WING
66400 BTU/H
13.3 GPM
54°F
44°F 1ST FLR WING
175000 BTU/H
35 GPM
54°F
44°F
2ND FLR WING
176200 BTU/H
35.2 GPM
54°F
44°F
2ND FLR WING
155100 BTU/H
31 GPM54°F
44°F
3RD FLR WING
133100 BTU/H
26.6 GPM54°F
44°F
3RD FLR WING
120100 BTU/H
24 GPM
54°F
44°F
5TH FLR WING
134600 BTU/H
26.9 GPM
54°F
44°F
5TH FLOOR WING
146100 BTU/H
29.2 GPM
54°F 44°F
4TH FLR WING
129700 BTU/H
25.9 GPM
54°F
44°F
C58
8800 BTU/H
1.8 GPM
54°F44°F
CV-AC-12-1
CV-AC-4-1
CV-AC-9-1 CV-AC-5-1
CV-AC-1-1
CV-AC-3-1
CV-AC-6-1
CV-AC-2-1
CV-AC-11-1
CV-AC-7-1
CV-AC-8-1
CV-AC-14-1
CV-AC-1-102
STR-21
STR-22
STR-23
STR-24
STR-25 STR-26
STR-27
STR-28
STR-29
STR-30
STR-31
STR-32
STR-33
STR-34
STR-35
CV-RTU-1-101
CV-RTU-2-101
STR-36
STR-37 STR-38
STR-39
STR-40
STR-41
STR-42
STR-43
STR-44
STR-45
STR-46
CV-C58
CV-GRND FLR WING
CV-GRND FLR WING
CV-1ST FLR WING
CV-RM125A
CV-RM125Q
CV-1ST FLR WING
AHU-3N-10442°F
52°F
584000 BTU/H
116.8 GPM
AHU-5-10442°F
52°F
818000 BTU/H
163.5 GPM
CHWP-1-104
VSD
756.7 GPM
89.2 FT
CHWP-2-104
VSD
0 GPM
0 FT
(0%)
4TH FLOOR WING
453500 BTU/H
90.7 GPM
52°F
42°F
3RD FLOOR WING
419200 BTU/H
83.8 GPM52°F
42°F
5TH FLOOR WING
190100 BTU/H
38 GPM
52°F
42°F
2ND FLOOR WING
149200 BTU/H
29.8 GPM
52°F
42°F
FCU-1
12800 BTU/H
2.6 GPM
52°F
42°F
FCU-2
35130 BTU/H
7 GPM
52°F
42°F
FCU-3
35130 BTU/H
7 GPM
52°F
42°F
FCU-4
35130 BTU/H
7 GPM
52°F
42°F
P-1
76.1 GPM
37.3 FT
VSD
P-2
76.1 GPM
37.3 FT
VSD
CV-FCU-4
CV-FCU-2
CV-FCU-3
CV-FCU-1
CV-AC-24-1
CV-24-AHU-1
STR-47
STR-48
STR-49
STR-50
STR-51
STR-52
STR-53
STR-54
STR-55
STR-56
CV-AC-1-19 CV-AC-2-19
CV-AC-4-19
CV-AC-3-19
V-24 V-25
V-26
V-27
V-28
V-29
CV-AC-5-22
STR-57 V-30
JTP-10 JTP-11
JTP-12JTP-13
CV-59
CKV-3
V-31
V-32
CV-60
JTP-14 JTP-15
JTP-16 JTP-17
JTP-18 JTP-19
V-33
JTP-20
JTP-21
JTP-22
JTP-23
V-34 V-35
CV-61 CV-62
JTP-24 JTP-25
JTP-26 JTP-27
JTP-28
JTP-29
4TH FLOOR WING
384500 BTU/H
76.9 GPM
52°F
42°F
AH-1 42°F
54°F
390100 BTU/H
65 GPM
AH-242°F
54°F
311100 BTU/H
51.8 GPM
CV-RTU-3-101
STR-58
V-36
V-37 V-38
CV-AHU-4-103
CV-AHU-3N-104CV-AHU-3-103
CV-AHU-5-104
CV-AHU-2-103
STR-59
STR-60STR-61
STR-62
STR-63
JTP-30
JTP-31
JTP-32
V-39 V-40
JTP-33
JTP-34
JTP-35
JTP-36
JTP-37
V-41
V-42
V-43
V-44
V-45
V-46
V-47
V-48
V-49 V-50
V-51
V-52
V-53
V-54
V-55
V-56
JTP-38 JTP-39
JTP-40 JTP-41
JTP-42JTP-43JTP-44JTP-45
CV-5TH FLOOR WING
JTP-46JTP-47
CV-5TH FLR WING
STR-64
JTP-48 JTP-49
STR-65
CV-4TH FLR WING
CV-3RD FLR WING
CV-2ND FLR WING
STR-66
CV-2ND FLR WING
JTP-50JTP-51
JTP-52
JTP-53
CV-75
CV-AH-1 CV-AH-2
STR-67
STR-68
STR-69
CV-2ND FLOOR WING
CV-3RD FLOOR WINGSTR-70
STR-71
STR-72
CV-4TH FLOOR WING
CV-4TH FLOOR WING
CV-AHU-1-103
STR-73
ONCOLOGY AHU42°F
52°F
825000 BTU/H
164.9 GPM
CV-ONCOLOGY AHU
STR-74
FUTURE ROOF LOAD FUTURE ROOF LOAD
JTP-54 JTP-55 JTP-56 JTP-57
SENF-2
SENF-3
SENF-4
CV-84
CV-85
V-57
V-58
UNIT
CH-1
CH-2
P-3-2
FCU-1
0 BTU/H
0 GPM
?°F
?°F
AHU?°F
?°F
0 BTU/H
0 GPM
V-59
V-60
V-61
V-62
LEVEL 1 FCU
42000 BTU/H
8.4 GPM
52°F
42°F
LEVEL 1 FCU
42000 BTU/H
8.4 GPM
52°F
42°F
LEVEL 1 FCU
42000 BTU/H
8.4 GPM
52°F
42°F
12"6'
12"7.5'
8" 8'
8"
6'
6"
20'
10"
10'
12"5'
10"17' 10"
17'
18" 8'
12"
8'
10"17' 10"17' 12"
20'
14"
20'
12"
12'
12"14'
10"8'
12"15'
14"12'
CHWR12"60'
2"
18'
2"
25'
4" 28.5'4"
11'
4"150'
3"
16.5'
3"
5'
C H W R
6"15'
C H W R
6"265'
C H W S
6"15'
C H W S
6" 265'
6"
48'
2.5"25'
2.5"55'
2.5" 25'
6"6'
6"
9'
6"
20'
6"
6'
8"
6'
8" 12'
3"
5'
3" 56.5'
3"109'
3"45.5' 4" 24'
3"50'
4"150'
6"
20'
4"150'
3" 45.5'
4"24'
6"
10'
3"50'
CHWR
3"120'
1.25"
35'
3"25'
CHWS
3"120'
1.25" 35'
3"25'
4"
8'
6" 6'
2.5"
40'
3"
50' 2.5"100'
3"50'
CHWS
12"
550'
756.7 GPM
CHWR CHWR
12"
550'
756.7 GPM
C H W S
CHWS
12"250'
2575.7 GPM
CHWS
8"130'
3"56.5'
C H W R
CHWR
12"250'
2986.8 GPM
C H W S
3"130'
CHWR
8"
130'
CHWS
8"170'
CHWR
8"
170'
2"40'
2"40'
C H W S
6"400' C H W R
6"
400'
C H W R
3"130'
3"
6'
2.5"
40'
2.5" 20'
2"0'
2.5"
40'
2.5"
40'
2.5"
20'
2.5"
20'
2.5"20'
4"
150'
C H W R
CHWR
4"100'
C H W S
CHWS
4"100'
1.5"50' 1.5"
50'
1.5"20'
CHWR
2"
50'
6"
33'
CHWR
6"
30'
2.5"
100'
2" 110'
2"15'
6"
12'
4"60'
3"
12'
2"28'
6"
12'
CHWS
2"190'
2.5"160'
6"
6'
6"
6'
C H W S
6"
100'
CHWS
2"155'
CHWS
CHWS
2.5" 490'
6"
8'
8"5'
CHWS5"70'
CHWS
12"
200'
1257.4 GPM
CHWS
C H W S
C H W S
8"
575'
6"15'
CHWS
C H W S
C H W S
4"200'
2.5"30'
6"25'
C H W S
3"
30'
3"
24'
CHWS
2"155'
3"
24'
CHWS
1.25"
150'
0.75"50'
4"12'
CHWR
12"
200'
2053.8 GPM
3"
15'
4"
12'
2.5"100'
6"
12'
CHWR
2"190'
6"
12'
6"8'
2.5"160'
6"
6'
6"
6'
C H W R
6"
100'
8"30'
CHWR
CHWR
2.5"
490'
CHWR0.75"50'
CHWR
1.25"150'
6"25'
C H W R
3"
30'
2.5" 66'
4"60'CHWR
2"110'
3"
24'
2" 15'
2.5"45'
2"
20'
CHWR
3"30'
2.5"
20' 2"
28'
2"80'
8"5'
3"
60'
6"
8'
3"
25'
3"25'
2"20' 3"
30'
2.5"
45'
2.5"
20'
2"80'
3"
70'
4"
40'
6"15'
2.5"30'
CHWS1.5"180'
2"155'
2"30'
2"30'
CHWR
2"155'
CHWR
2"155'
CHWR
1.5"180'
12"8'
12"15'
3"110'
1.5"
20'
3" 15'
1.5"
20'
2.5"30'
2"80'
2"0'
2"
80'
2"30'
2.5"65'
1.5"20'
4"24' 4"
24'
3"11'3"11'
6"
150'
6" 150'
6"
20'
4"11' 4"11'
4"11' 4"
11'
2.5"100'
3" 100'
3" 100'
3"50'
2.5" 20'
3"50'
C H W S
6"45' C H W R
6"
45'
6"
210' 6"
210'
6"30'
4"
22'
4"22'
1.5"
50'
1.5"
30'
CHWS
2"150'
4"
11'
CHWR
2"150'
4"
10'
4"
10'
4"
10'
4"
10'
4"
10'
4"
10'
6"
10'
6"20'
CHWS2.5"130' CHWS2.5"100'
4"
40'
2"100' 2"
100'
3"
70'
12"30'
C H W S
C H W S
C H W R
C H W R
12"5'
12"15'
12"15'
8"
0'
C H W S
CHWS
2"
65'
C H W R
2"65'
C H W S
C H W S
6"
120'
C H W R
C H W R
6"
120'
C H W R
C H W R
CHWR
8"575'
C H W S
CHWS
3"100'
C H W R
CHWR
3"
100'
C H W R
C H W R
CHWR
4"
200'
C H W R
3"
100'
C H W S
3"100'
3"110'
3"15'
3" 12' 3"
12'
3"
14'
3"12'
3"
14'
2" 10'
2.5"
66'
3"
24'
1.5"100'
1.5"100'
CHWS
1.75"155'
CHWR
1.75"155'
2"155'
2.5"190'
2.5"190'
3"60'
CHWR
5"70'
CHWR
2.5"130'
CHWR
2.5" 100'
2"
145'
2"145'
CHWR
3"150'
CHWS
3"150'
CHWS
3"150' CHWS
3" 150'
CHWR
3" 150'CHWR
3"150'
12"
30' 12"60'
12"
0'
12" 30'
12"60'
4"0'
4"90'
4"90'
3"25'
12"30'
3"25'
12"30'
2.5"0'
6"25'
6"
25'
2.5"
0'
8"
15'
8"30'
8"30'
8"15'
2.5"0'
2.5"0'
10"25'
10"25'
0"
0'
0"0'
Bldg 18 (Outpatient)
Bldg 23 (Admin)
Bldg 22 (Education)
Bldg 22 Ice Storage Plant
Bldg 2 (Admin)
Bldg 104 (Hospital)
Bldg 102 (Rehab)
Bldg 1 (Main)
Bldg 101 (Hospital)
Bldg 19 (Police/Admin)
Bldg 24 (YMCA)
Bldg 7 (Laundry)
Bldg 6 (Warehouse)
Bldg 136 (IT)
Bldg 17 (Amb Care)
Bldg 106 (Chapel)
For clarity in the model, Alares did not include all valves, strainers, air separators, and/or other contributors to the pressure drop near the chillers and pumps, so they are not included in the calculated pump heads.
New SPS unit serves Bldg 1.
Unit is not online yet.
Connects Bldgs 1/101.
No information provided.
New unit serves corridor.
Unit is not online yet.
Connects Bldgs 1/104.
No information provided.
20 HP motors on pumps sharpie note on pump covering:
GPM 318 TDH 105
Imp Dia 11.50"
Basement
Rooftop
First Floor
Penthouse
Basement
Sub-basement
Basement
1st Floor
2nd Floor
3rd Floor
4th Floor
5th Floor
Attic
Attic
Basement
1st Floor
2nd Floor
3rd Floor
4th Floor
5th Floor
Penthouse
5th Floor
4th Floor
3rd Floor
2nd Floor
1st Floor
Basement
Ground Floor
6th Floor
2nd Floor, Roof
6th Floor, Roof6th Floor, Roof
Rooftop
The main laundry AHU has been removed.
Lone FCU assumed negligible to overall model.
Project No. 37-5345 Drawing 106-H2
First Floor
Second Floor
Third Floor
There are two separate CHW systems in the building;
- A Building CHW System that serves all the chilled water devices, consisting of 2 air-cooled chillers w/ 2 primary pumps and 1 backup
- A 30 ton CHW system that consists of 1 air-cooled chiller and two constant volume pumps which serves the data center, IT closets and elevator equip. room
Campus CHW system is only available to be used by the 30-ton system in the event of failure
Used recommended model diameters for piping as could not confirm actual sizes (8")
Assumed 100,000 BTUH and a 10 degF delta T for all four units.
CHW pumps were rated for
82 GPM
Offices served by split system.
The AHU serves the chapel.
Bldg 10 (Chiller Plant)
1st Floor Roof
First Floor
Second Floor
Third Floor
Roof
1st Floor
Air Cooled Chiller Pumps
MAIN RISERAC-7 + AC-8 RISER
B102 CHW LINE
AC-1-14 + GRND FLR FCU LINE
ASSUMED LOAD OF 175,000 BTUH
AS NO UPDATED VALUES AVAILABLE.
Proj. No. 595-04-131 has a CHW Riser which shows a flow of 38.5 GPM for this floor
AC-6 + AC-3 RISER
6th Floor
Drawings used:
Construct ICU Med Surge Unit 595-335 Surgery.ED.Endo 595-390
Renovate 1-2B Bed Unit 595-10-105
Drawings used for FCU sizing in Bldg 17:
5th floor - 595-02-107 Relocate Dental 4th floor - 595-433 Ambulatory Care Improvements 3rd floor - 595-433 Ambulatory Care Improvements 2nd floor - 595-060 Construct Ambulatory Care 1st floor - 595-060 Construct Ambulatory Care
Mechanical Space
First Floor
Assumed 60,000 BTUH for AHU-5 as no other information was available.
This is a former lab unit.
This is the combined load of 28 FCUs located on this wing. Largest pipe size and furthest pipe distance was used
Penthouse
Basement
Roof
Roof
Pump Design Values:
GPM = 337
TDH = 75
Design Pump Values GPM = 606 per pump TDH = 105 per pump
Pump Design Values:
GPM = 600 per pump
TDH = 95 per pump
Pump Design Values:
GPM = 1950 per pump TDH = 145 per pump
Air Cooled Chiller appears not to be working during Alares site visits. For purpose of model this chiller was not connected to the overall system
Capacity = 134.6 tons EWT = 53.1 degF LWT = 40 degF
GPM = 246
Future load 350 GPM Future Load 700 GPM
Rated GPM = 246
TDH = 135
Equipped w/ VFD, 15 HP motor
Combination of 7 loads totaling 66,400 BTUH
Combination of 18 loads totaling 176,200 BTUH
Combination of 12 loads totaling 155,100 BTUH
Combination of 22 loads totaling 120,100 BTUH
Combination of 15 loads totaling 133,100 BTUH
Combination of 18 loads totaling 129,700 BTUH
ASSUMED LOAD OF 150,000 BTUH
AS NO UPDATED VALUES AVAILABLE.
Proj. No. 595-04-131 has a CHW Riser which shows a flow of 39.8 GPM for this floor
Combination of 20 loads totaling 146,100 BTUH
Combination of 18 loads totaling 134,600 BTUH
Pumps installed here along with FCUs 1-4 and 24-AHU-1 are under construction and are part of the new renovations at Bldg. 24 (Project No. 595-13-106)
No details available on CHW to this building.
Assumed negligible to overall model.
The Ice Storage Plant is only for illustration within the model. It is not connected to the chiller plant output and overall loads.
Consists of 3 RTAC air-cooled chillers upstream of ice storage tanks, 2 variable secondary loop manifolded pumps, and pump skid with:
4 variable primary flow manifolded N+1 pumps, chiller min. flow bypass valve and heat exchanger
These future loads were noted from Project 595-390, and are shown on M-701R6 Chilled Water Schematic for Bldg. 104.
Basement
No values inputted as no drawing information available and unable to confirm if these units are supplied by the campus CHW
BLDG 101 LINE
Notes from site visits:
Did not see V-4, V-5, or V-6 in field.
Flow meter (FM) IDs came from Alares;
FMs are not labeled in the field.
CHW flow meter IDs on front-end:
FM-1, FM-2, and FM-3
CW flow meter IDs on front-end:
FM-4, FM-5, and FM-6
Mechanical Room
Exterior
Mechanical Room
BTU/H for AC-9-1 comes from Alares' latest design (Previous BTU/H from latest available drawing set was 208,260 BTU)
Estimate total cooling load of FCUs on Level 1
Estimate total cooling load of FCUs on Level 2
Estimate total cooling load of FCUs on Level 3
481700 BTU/H
68.8 GPM
P-1-18
VSD
488.4 GPM
117.4 FT
(100%)
P-2-18
VSD
0 GPM
0 FT
(0%)
AC-4-22 42°F
52°F
53000 BTU/H
10.6 GPM
P-1-22
VSD
102.8 GPM
117.9 FT
P-2-22
VSD
0 GPM
0 FT
(100/0%)
AHU-1 AHU-2 AHU-3
P-1-2 P-2-2
AC-1-102 44°F
58°F
587300 BTU/H
83.9 GPM
AC-1-1 44°F
58°F
875400 BTU/H
125 GPM
AC-2-144°F
58°F
686000 BTU/H
98 GPM
AC-3-1 44°F
58°F
418900 BTU/H
59.8 GPM
AC-4-1 44°F
58°F
486300 BTU/H
69.4 GPM
AC-11-144°F
56°F
425000 BTU/H
70.8 GPMAC-12-144°F
57°F
104000 BTU/H
16 GPM
AC-6-144°F
58°F
393000 BTU/H
56.1 GPM
AC-9-1 44°F
58°F
227160 BTU/H
32.4 GPM
AC-7-144°F
58°F
523400 BTU/H
74.7 GPM
AC-8-144°F
58°F
410400 BTU/H
58.6 GPM
AC-5-144°F
58°F
202900 BTU/H
29 GPM
AC-14-144°F
58°F
116000 BTU/H
16.6 GPM
CWP 1-1
VSD
1257.4 GPM
250.3 FT
CWP 2-1
VSD
0 GPM
0 FT
(0%)
RTU-3-101 44°F
54°F
90000 BTU/H
18 GPM
AC-1-1942°F
56°F
217000 BTU/H
31 GPM
AC-2-19 42°F
56°F
171000 BTU/H
24.4 GPM
AC-4-1942°F
56°F
92400 BTU/H
13.2 GPM
P-1-19
VSD
82.9 GPM
64.5 FT
P-2-19
VSD
0 GPM
0 FT
(100/0%)
AC-24-1 42°F
52°F
147930 BTU/H
29.6 GPM
24-AHU-1 42°F
52°F
114400 BTU/H
22.9 GPM
CH-1
95°F
85°F
10940200 BTU/H
911.7 TONS
1666.2 GPM
(46.91%)
42°F
55.1°F
CT-1
14600300 BTU/H
2936.6 GPM
(53.382%)
95°F
85°F
P-3
0 GPM
0 FT
(100/0%)
P-5
5501.1 GPM
50.3 FT
P-6
0 GPM
0 FT
(100/0%)
P-4
5501.1 GPM
53.8 FT
P-2
3332.5 GPM
215.6 FT
P-1
3332.5 GPM
216.5 FT
CT-2
14600300 BTU/H
2936.6 GPM
(53.382%)
95°F
85°F
CT-3
14600300 BTU/H
2936.6 GPM
(53.382%)
95°F
85°F
CH-2
95°F
85°F
10940200 BTU/H
911.7 TONS
1666.2 GPM
(46.91%)
42°F
55.1°F
AC-1-17 42°F
56°F
962300 BTU/H
137.4 GPM
AC-2-17 42°F
56°F
632600 BTU/H
90.3 GPM
AC-3-1742°F
56°F
505400 BTU/H
72.2 GPM
AC-4-17 42°F
56°F
256600 BTU/H
36.6 GPM
AC-5-1742°F
56°F
166610 BTU/H
23.8 GPM
RTU-1-1742°F
52°F
RTU-2-1742°F
52°F
P-1-17
VSD
796.4 GPM
82.1 FT
P-2-17
VSD
0 GPM
0 FT
(0%)
106-AC-1
50°F
42°F
259000 BTU/H
64.7 GPM
FM A
FM B
FM C
FM D
FM E
FM F
CHILLER #3CHILLER #2CHILLER #1
HX
TRANSFERSOURCE
PUMP 1 PUMP 2 PUMP 3 PUMP 4
PUMP 5
PUMP 6
TS-IT-01 TS-IT-03 TS-IT-05 TS-IT-07 TS-IT-09 TS-IT-11 TS-IT-13 TS-IT-15
TS-IT-02 TS-IT-04 TS-IT-06 TS-IT-08 TS-IT-10 TS-IT-12 TS-IT-14 TS-IT-16
P-1-136
47.3 GPM
30.7 FT
P-2-136
0 GPM
0 FT
(0%)
AC-1-13642°F
56°F
331100 BTU/H
47.3 GPM
RTU-1-101 44°F
58°F
316000 BTU/H
45.1 GPM
RTU-2-101 44°F
58°F
680000 BTU/H
97.1 GPM
UNIT
RTU-4-2342°F
52°F
100000 BTU/H
20 GPM
RTU-3-2342°F
56°F
100000 BTU/H
14.3 GPM
RTU-1-23 42°F
52°F
100000 BTU/H
20 GPM
RTU-2-23 42°F
54°F
100000 BTU/H
16.7 GPM
CHP-1
71 GPM
37.2 FT
VSD
CHP-2
0 GPM
0 FT
(0%)
VSD
?°F
40°F
1-CH-1
0 BTU/H
0 TONS
0 GPM
AHU-4AHU-5
AC-3-1842°F
56°F
423100 BTU/H
60.4 GPM
AC-1-18 42°F
56°F
980100 BTU/H
140 GPM
AC-2-1842°F
56°F
1372100 BTU/H
196 GPM
AC-5-1842°F
56°F
161980 BTU/H
23.1 GPM
AHU-1-10342°F
52°F
875000 BTU/H
174.9 GPM
AHU-2-10342°F
62°F
600000 BTU/H
60 GPM
AHU-3-10342°F
65°F
554000 BTU/H
48.2 GPM
AHU-4-10342°F
62°F
284000 BTU/H
28.4 GPM
AC-3-1942°F
56°F
100300 BTU/H
14.3 GPM
CV-AC-5-17
CV-AC-1-17 CV-AC-3-17
CV-AC-2-17
CV-AC-4-17
CV-RTU-2-17 CV-RTU-1-17
V-1 V-2
V-3
V-4
V-5
V-6 V-7
STR-1
STR-2
STR-3 STR-4
STR-5
STR-6
STR-7
BLDG 17 DP SENSOR
CV-RTU-1-23
V-8
STR-8
CV-RTU-4-23
V-9
STR-9
CV-AC-4-18
BV-AC-4-18
STR-10
V-10
CV-AC-3-18
BV-AC-3-18
STR-11
V-11
CV-AC-1-18
CV-AC-5-18STR-12
V-12
CV-AC-2-18
STR-13
V-13
BV-AC-1-18
STR-14
BV-AC-2-18
STR-15
CV-15
V-14
JTP-1 JTP-2
CV-16
V-15
V-16
FM-1
CV-17
FM-2
SENF-1
STR-16
V-17
CV-RTU-3-23
STR-17
V-18
CV-RTU-2-23
BV-5
FM-3
BV-6
CV-20
FM-4
CKV-1CKV-2
V-19
V-20
JTP-3JTP-4
JTP-5JTP-6
JTP-7JTP-8
AC-5-22 42°F
52°F
60000 BTU/H
12 GPM
AC-3-22 42°F
52°F
275000 BTU/H
55 GPM
CV-AC-3-22 CV-AC-4-22
STR-18 STR-19
V-21
V-22
CV-23
CV-AC-1-136
STR-20
V-23
FM-5
FM-6
CV-25
JTP-9
BV-7
ASU-P1 ASU-P2
GRND FLR WING
117100 BTU/H
23.4 GPM54°F
44°F
GRND FLR WING
150000 BTU/H
30 GPM
54°F
44°F
RM125Q
13800 BTU/H
2.8 GPM
54°F 44°F
RM125A
8500 BTU/H
1.7 GPM
54°F 44°F
1ST FLR WING
66400 BTU/H
13.3 GPM
54°F
44°F 1ST FLR WING
175000 BTU/H
35 GPM
54°F
44°F
2ND FLR WING
176200 BTU/H
35.2 GPM
54°F
44°F
2ND FLR WING
155100 BTU/H
31 GPM54°F
44°F
3RD FLR WING
133100 BTU/H
26.6 GPM54°F
44°F
3RD FLR WING
120100 BTU/H
24 GPM
54°F
44°F
5TH FLR WING
134600 BTU/H
26.9 GPM
54°F
44°F
5TH FLOOR WING
146100 BTU/H
29.2 GPM
54°F 44°F
4TH FLR WING
129700 BTU/H
25.9 GPM
54°F
44°F
C58
8800 BTU/H
1.8 GPM
54°F44°F
CV-AC-12-1
CV-AC-4-1
CV-AC-9-1 CV-AC-5-1
CV-AC-1-1
CV-AC-3-1
CV-AC-6-1
CV-AC-2-1
CV-AC-11-1
CV-AC-7-1
CV-AC-8-1
CV-AC-14-1
CV-AC-1-102
STR-21
STR-22
STR-23
STR-24
STR-25 STR-26
STR-27
STR-28
STR-29
STR-30
STR-31
STR-32
STR-33
STR-34
STR-35
CV-RTU-1-101
CV-RTU-2-101
STR-36
STR-37 STR-38
STR-39
STR-40
STR-41
STR-42
STR-43
STR-44
STR-45
STR-46
CV-C58
CV-GRND FLR WING
CV-GRND FLR WING
CV-1ST FLR WING
CV-RM125A
CV-RM125Q
CV-1ST FLR WING
AHU-3N-10442°F
52°F
584000 BTU/H
116.8 GPM
AHU-5-10442°F
52°F
818000 BTU/H
163.5 GPM
CHWP-1-104
VSD
756.7 GPM
89.2 FT
CHWP-2-104
VSD
0 GPM
0 FT
(0%)
4TH FLOOR WING
453500 BTU/H
90.7 GPM
52°F
42°F
3RD FLOOR WING
419200 BTU/H
83.8 GPM52°F
42°F
5TH FLOOR WING
190100 BTU/H
38 GPM
52°F
42°F
2ND FLOOR WING
149200 BTU/H
29.8 GPM
52°F
42°F
FCU-1
12800 BTU/H
2.6 GPM
52°F
42°F
FCU-2
35130 BTU/H
7 GPM
52°F
42°F
FCU-3
35130 BTU/H
7 GPM
52°F
42°F
FCU-4
35130 BTU/H
7 GPM
52°F
42°F
P-1
76.1 GPM
37.3 FT
VSD
P-2
76.1 GPM
37.3 FT
VSD
CV-FCU-4
CV-FCU-2
CV-FCU-3
CV-FCU-1
CV-AC-24-1
CV-24-AHU-1
STR-47
STR-48
STR-49
STR-50
STR-51
STR-52
STR-53
STR-54
STR-55
STR-56
CV-AC-1-19 CV-AC-2-19
CV-AC-4-19
CV-AC-3-19
V-24 V-25
V-26
V-27
V-28
V-29
CV-AC-5-22
STR-57 V-30
JTP-10 JTP-11
JTP-12JTP-13
CV-59
CKV-3
V-31
V-32
CV-60
JTP-14 JTP-15
JTP-16 JTP-17
JTP-18 JTP-19
V-33
JTP-20
JTP-21
JTP-22
JTP-23
V-34 V-35
CV-61 CV-62
JTP-24 JTP-25
JTP-26 JTP-27
JTP-28
JTP-29
4TH FLOOR WING
384500 BTU/H
76.9 GPM
52°F
42°F
AH-1 42°F
54°F
390100 BTU/H
65 GPM
AH-242°F
54°F
311100 BTU/H
51.8 GPM
CV-RTU-3-101
STR-58
V-36
V-37 V-38
CV-AHU-4-103
CV-AHU-3N-104CV-AHU-3-103
CV-AHU-5-104
CV-AHU-2-103
STR-59
STR-60STR-61
STR-62
STR-63
JTP-30
JTP-31
JTP-32
V-39 V-40
JTP-33
JTP-34
JTP-35
JTP-36
JTP-37
V-41
V-42
V-43
V-44
V-45
V-46
V-47
V-48
V-49 V-50
V-51
V-52
V-53
V-54
V-55
V-56
JTP-38 JTP-39
JTP-40 JTP-41
JTP-42JTP-43JTP-44JTP-45
CV-5TH FLOOR WING
JTP-46JTP-47
CV-5TH FLR WING
STR-64
JTP-48 JTP-49
STR-65
CV-4TH FLR WING
CV-3RD FLR WING
CV-2ND FLR WING
STR-66
CV-2ND FLR WING
JTP-50JTP-51
JTP-52
JTP-53
CV-75
CV-AH-1 CV-AH-2
STR-67
STR-68
STR-69
CV-2ND FLOOR WING
CV-3RD FLOOR WINGSTR-70
STR-71
STR-72
CV-4TH FLOOR WING
CV-4TH FLOOR WING
CV-AHU-1-103
STR-73
ONCOLOGY AHU42°F
52°F
825000 BTU/H
164.9 GPM
CV-ONCOLOGY AHU
STR-74
FUTURE ROOF LOAD FUTURE ROOF LOAD
JTP-54 JTP-55 JTP-56 JTP-57
SENF-2
SENF-3
SENF-4
CV-84
CV-85
V-57
V-58
UNIT
CH-1
CH-2
P-3-2
FCU-1
0 BTU/H
0 GPM
?°F
?°F
AHU?°F
?°F
0 BTU/H
0 GPM
V-59
V-60
V-61
V-62
LEVEL 1 FCU
42000 BTU/H
8.4 GPM
52°F
42°F
LEVEL 1 FCU
42000 BTU/H
8.4 GPM
52°F
42°F
LEVEL 1 FCU
42000 BTU/H
8.4 GPM
52°F
42°F
12"6'
12"7.5'
8" 8'
8"
6'
6"
20'
10"
10'
12"5'
10"17' 10"
17'
18" 8'
12"
8'
10"17' 10"17' 12"
20'
14"
20'
12"
12'
12"14'
10"8'
12"15'
14"12'
CHWR12"60'
2"
18'
2"
25'
4" 28.5'4"
11'
4"150'
3"
16.5'
3"
5'
C H W R
6"15'
C H W R
6"265'
C H W S
6"15'
C H W S
6" 265'
6"
48'
2.5"25'
2.5"55'
2.5" 25'
6"6'
6"
9'
6"
20'
6"
6'
8"
6'
8" 12'
3"
5'
3" 56.5'
3"109'
3"45.5' 4" 24'
3"50'
4"150'
6"
20'
4"150'
3" 45.5'
4"24'
6"
10'
3"50'
CHWR
3"120'
1.25"
35'
3"25'
CHWS
3"120'
1.25" 35'
3"25'
4"
8'
6" 6'
2.5"
40'
3"
50' 2.5"100'
3"50'
CHWS
12"
550'
756.7 GPM
CHWR CHWR
12"
550'
756.7 GPM
C H W S
CHWS
12"250'
2575.7 GPM
CHWS
8"130'
3"56.5'
C H W R
CHWR
12"250'
2986.8 GPM
C H W S
3"130'
CHWR
8"
130'
CHWS
8"170'
CHWR
8"
170'
2"40'
2"40'
C H W S
6"400' C H W R
6"
400'
C H W R
3"130'
3"
6'
2.5"
40'
2.5" 20'
2"0'
2.5"
40'
2.5"
40'
2.5"
20'
2.5"
20'
2.5"20'
4"
150'
C H W R
CHWR
4"100'
C H W S
CHWS
4"100'
1.5"50' 1.5"
50'
1.5"20'
CHWR
2"
50'
6"
33'
CHWR
6"
30'
2.5"
100'
2" 110'
2"15'
6"
12'
4"60'
3"
12'
2"28'
6"
12'
CHWS
2"190'
2.5"160'
6"
6'
6"
6'
C H W S
6"
100'
CHWS
2"155'
CHWS
CHWS
2.5" 490'
6"
8'
8"5'
CHWS5"70'
CHWS
12"
200'
1257.4 GPM
CHWS
C H W S
C H W S
8"
575'
6"15'
CHWS
C H W S
C H W S
4"200'
2.5"30'
6"25'
C H W S
3"
30'
3"
24'
CHWS
2"155'
3"
24'
CHWS
1.25"
150'
0.75"50'
4"12'
CHWR
12"
200'
2053.8 GPM
3"
15'
4"
12'
2.5"100'
6"
12'
CHWR
2"190'
6"
12'
6"8'
2.5"160'
6"
6'
6"
6'
C H W R
6"
100'
8"30'
CHWR
CHWR
2.5"
490'
CHWR0.75"50'
CHWR
1.25"150'
6"25'
C H W R
3"
30'
2.5" 66'
4"60'CHWR
2"110'
3"
24'
2" 15'
2.5"45'
2"
20'
CHWR
3"30'
2.5"
20' 2"
28'
2"80'
8"5'
3"
60'
6"
8'
3"
25'
3"25'
2"20' 3"
30'
2.5"
45'
2.5"
20'
2"80'
3"
70'
4"
40'
6"15'
2.5"30'
CHWS
1.5"180'
2"155'
2"30'
2"30'
CHWR
2"155'
CHWR
2"155'
CHWR
1.5"180'
12"8'
12"15'
3"110'
1.5"
20'
3" 15'
1.5"
20'
2.5"30'
2"80'
2"0'
2"
80'
2"30'
2.5"65'
1.5"20'
4"24' 4"
24'
3"11'3"11'
6"
150'
6" 150'
6"
20'
4"11' 4"11'
4"11' 4"
11'
2.5"100'
3" 100'
3" 100'
3"50'
2.5" 20'
3"50'
C H W S
6"45' C H W R
6"
45'
6"
210' 6"
210'
6"30'
4"
22'
4"22'
1.5"
50'
1.5"
30'
CHWS
2"150'
4"
11'
CHWR
2"150'
4"
10'
4"
10'
4"
10'
4"
10'
4"
10'
4"
10'
6"
10'
6"20'
CHWS2.5"130' CHWS2.5"100'
4"
40'
2"100' 2"
100'
3"
70'
12"30'
C H W S
C H W S
C H W R
C H W R
12"5'
12"15'
12"15'
8"
0'
C H W S
CHWS
2"
65'
C H W R
2"65'
C H W S
C H W S
6"
120'
C H W R
C H W R
6"
120'
C H W R
C H W R
CHWR
8"575'
C H W S
CHWS
3"100'
C H W R
CHWR
3"
100'
C H W R
C H W R
CHWR
4"
200'
C H W R
3"
100'
C H W S
3"100'
3"110'
3"15'
3" 12' 3"
12'
3"
14'
3"12'
3"
14'
2" 10'
2.5"
66'
3"
24'
1.5"100'
1.5"100'
CHWS
1.75"155'
CHWR
1.75"155'
2"155'
2.5"190'
2.5"190'
3"60'
CHWR
5"70'
CHWR
2.5"130'
CHWR
2.5" 100'
2"
145'
2"145'
CHWR
3"150'
CHWS
3"150'
CHWS
3"150' CHWS
3" 150'
CHWR
3" 150'CHWR
3"150'
12"
30' 12"60'
12"
0'
12" 30'
12"60'
4"0'
4"90'
4"90'
3"25'
12"30'
3"25'
12"30'
2.5"0'
6"25'
6"
25'
2.5"
0'
8"
15'
8"30'
8"30'
8"15'
2.5"0'
2.5"0'
10"25'
10"25'
0"
0'
0"0'
Bldg 18 (Outpatient)
Bldg 23 (Admin)
Bldg 22 (Education)
Bldg 22 Ice Storage Plant
Bldg 2 (Admin)
Bldg 104 (Hospital)
Bldg 102 (Rehab)
Bldg 1 (Main)
Bldg 101 (Hospital)
Bldg 19 (Police/Admin)
Bldg 24 (YMCA)
Bldg 7 (Laundry)
Bldg 6 (Warehouse)
Bldg 136 (IT)
Bldg 17 (Amb Care)
Bldg 106 (Chapel)
For clarity in the model, Alares did not include all valves, strainers, air separators, and/or other contributors to the pressure drop near the chillers and pumps, so they are not included in the calculated pump heads.
New SPS unit serves Bldg 1.
Unit is not online yet.
Connects Bldgs 1/101.
No information provided.
New unit serves corridor.
Unit is not online yet.
Connects Bldgs 1/104.
No information provided.
20 HP motors on pumps sharpie note on pump covering:
GPM 318 TDH 105
Imp Dia 11.50"
Basement
Rooftop
First Floor
Penthouse
Basement
Sub-basement
Basement
1st Floor
2nd Floor
3rd Floor
4th Floor
5th Floor
Attic
Attic
Basement
1st Floor
2nd Floor
3rd Floor
4th Floor
5th Floor
Penthouse
5th Floor
4th Floor
3rd Floor
2nd Floor
1st Floor
Basement
Ground Floor
6th Floor
2nd Floor, Roof
6th Floor, Roof6th Floor, Roof
Rooftop
The main laundry AHU has been removed.
Lone FCU assumed negligible to overall model.
Project No. 37-5345 Drawing 106-H2
First Floor
Second Floor
Third Floor
There are two separate CHW systems in the building;
- A Building CHW System that serves all the chilled water devices, consisting of 2 air-cooled chillers w/ 2 primary pumps and 1 backup
- A 30 ton CHW system that consists of 1 air-cooled chiller and two constant volume pumps which serves the data center, IT closets and elevator equip. room
Campus CHW system is only available to be used by the 30-ton system in the event of failure
Used recommended model diameters for piping as could not confirm actual sizes (8")
Assumed 100,000 BTUH and a 10 degF delta T for all four units.
CHW pumps were rated for
82 GPM
Offices served by split system.
The AHU serves the chapel.
Bldg 10 (Chiller Plant)
1st Floor Roof
First Floor
Second Floor
Third Floor
Roof
1st Floor
Air Cooled Chiller Pumps
MAIN RISERAC-7 + AC-8 RISER
B102 CHW LINE
AC-1-14 + GRND FLR FCU LINE
ASSUMED LOAD OF 175,000 BTUH
AS NO UPDATED VALUES AVAILABLE.
Proj. No. 595-04-131 has a CHW Riser which shows a flow of 38.5 GPM for this floor
AC-6 + AC-3 RISER
6th Floor
Drawings used:
Construct ICU Med Surge Unit 595-335 Surgery.ED.Endo 595-390
Renovate 1-2B Bed Unit 595-10-105
Drawings used for FCU sizing in Bldg 17:
5th floor - 595-02-107 Relocate Dental 4th floor - 595-433 Ambulatory Care Improvements 3rd floor - 595-433 Ambulatory Care Improvements 2nd floor - 595-060 Construct Ambulatory Care 1st floor - 595-060 Construct Ambulatory Care
Mechanical Space
First Floor
Assumed 60,000 BTUH for AHU-5 as no other information was available.
This is a former lab unit.
This is the combined load of 28 FCUs located on this wing. Largest pipe size and furthest pipe distance was used
Penthouse
Basement
Roof
Roof
Pump Design Values:
GPM = 337
TDH = 75
Design Pump Values GPM = 606 per pump TDH = 105 per pump
Pump Design Values:
GPM = 600 per pump
TDH = 95 per pump
Pump Design Values:
GPM = 1950 per pump TDH = 145 per pump
Air Cooled Chiller appears not to be working during Alares site visits. For purpose of model this chiller was not connected to the overall system
Capacity = 134.6 tons EWT = 53.1 degF LWT = 40 degF
GPM = 246
Possible issue with pressure for this system.
This issue is most likely arising with the air cooled chiller system not being in operation and some possible issues with pipe sizes on 6th floor
Future load 350 GPM Future Load 700 GPM
Rated GPM = 246
TDH = 135
Equipped w/ VFD, 15 HP motor
Combination of 7 loads totaling 66,400 BTUH
Combination of 18 loads totaling 176,200 BTUH
Combination of 12 loads totaling 155,100 BTUH
Combination of 22 loads totaling 120,100 BTUH
Combination of 15 loads totaling 133,100 BTUH
Combination of 18 loads totaling 129,700 BTUH
ASSUMED LOAD OF 150,000 BTUH
AS NO UPDATED VALUES AVAILABLE.
Proj. No. 595-04-131 has a CHW Riser which shows a flow of 39.8 GPM for this floor
Combination of 20 loads totaling 146,100 BTUH
Combination of 18 loads totaling 134,600 BTUH
Possible relocation for Differential Pressure Sensor
Possible piping size increase needed.
Currently 2.5", model recommends increasing to 4"
Possible piping size increases needed Currently 3-4", model recommends increasing to 5"
Possible piping size increases needed Currently 1.25", model recommends increasing to 2"
Possible piping size increases needed Currently 2", model recommends increasing to 3"
Possible piping size increases needed Currently 4", model recommends increasing to 6"
Possible piping size increases needed Currently 2.5", model recommends increasing to 4"
Possible piping size increases needed Currently 2", model recommends increasing to 3"
Possible piping size increases needed Currently 2.5", model recommends increasing to 3"
Pumps installed here along with FCUs 1-4 and 24-AHU-1 are under construction and are part of the new renovations at Bldg. 24 (Project No. 595-13-106)