S-02 2021 Fuel Reports -Tanks 1 -4.pdf
PDF 6 MB Posted
- Attached to
- Z2DA--693-20-109 Replace Underground Storage Tanks Federal contract opportunity
- Solicitation number
- 36C24421B0011
About this file
This document contains four underground storage tank inspection reports for the Wilkes-Barre VA Medical Center and a related federal contract opportunity notice. The inspection reports document the condition of four underground diesel fuel tanks - Tanks 1 through 4 - at the Medical Center prior to planned cleaning. Each report provides details on the tank identification and capacity, inspection date, inspecting technicians, customer point of contact, and visual observations of the fuel and tank components.
The related federal contract opportunity is a solicitation to replace the underground storage tank system at the Wilkes-Barre VA Medical Center. The scope of work includes removing and replacing the four existing underground fuel tanks, associated piping, mechanical and electrical equipment, controls and monitoring systems. Ancillary work includes earthwork, utilities, concrete and exterior improvements. The project size is estimated between $1 million to $5 million and work must be completed within 272 calendar days of the notice to proceed. The solicitation is set aside solely for service-disabled veteran-owned small businesses and questions should be directed to the specified contracting officer by April 12, 2021.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S02 Amendment 3 Project 693-20-109 02.docx | DOCX document | |
| 36C24421B0011 0003.docx | DOCX document | |
| S02 SafetyHealthDuringConstruction 18S-15-346.pdf | ||
| S02 Existing Leak Detect Monit Alarm Sys Plan.pdf | ||
| S02 PROJECT SITE PHOTOGRAPH 1.pdf | ||
| S02 Price Sheet with Bid Deduct.docx | DOCX document | |
| 36C24421B0011 0002.docx | DOCX document | |
| 36C24421B0011 0001.docx | DOCX document | |
| S04 UST Sign-in.pdf | ||
| P09 Replace USTs Specs.pdf | ||
| P09 DWGs.pdf | ||
| 36C24421B0011.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Industrial Tank Maintenance Field Report
CONTAMINANTS FOUND:PARTS CONDITION:
_____None _____Bulk Water _____Suspended Water _____Micro-organisms _____Sediments _____Rust _____Sludge
THIS TANK PASSES THE ASTM D975 "CLEAR &
BRIGHT" VISUAL INSPECTION.
*Lab Report will determine fuel parameters based on ASTM D975 Specifications
THIS TANK DOES NOT PASS ASTM D975 "CLEAR & BRIGHT"
VISUAL INSPECTION
*Tank cleaning is recommended based on Visual Fuel Inspection ONLY. Lab Report will determine fuel parameters based on ASTM D975 Specifications
COMMENTS:
SERVICE TECHNICIAN:______________________________________________DATE:__________________
877-252-6396 (Toll Free) 843-225-1777843-377-0412 (Fax) 4310 Amsterdam St., N. Charleston, SC 29418 www.petroleumrecoveryservices.com
VISUAL FUEL RATING:
____Pre-Clean ____Post Clean____Pre-Clean ____Post Clean
_____TBD by Lab Analysis _____Good _____Watch Closely _____Advanced Aging _____Bad-Not Recommended _____Severe-Do Not Use
GROUP NAME: ___________________________________________ DATE:______________________ CUSTOMER:___________________________________________________SVC MARKET _____________________
FACILITY:___________________________________________________________________________________________
ADDRESS:__________________________________________________________________________________________
CONTACT:___________________________________________PHONE:______________________________________
EMAIL:_______________________________________________CELL: ________________________________________
Unit Id :_____________________ Type : ______ Capacity :___________Material:____________
Last Tank Cleaning:_________________
FUEL SAMPLE TAKEN:
_____Annual/Pre-Clean _____ Post Clean _____ None
SERVICES PERFORMED:
____ Maintenance ____ STI 001 Inspection ____ Tank Cleaning ____ Bottom Sweep ____ Pre-clean Lab Analysis ____ Post-clean Lab Analysis Fuel Treatment:
_____HydroClean
_____ILFC 1032
_____Biocide Predator 6000 _____None
ExteriorTank Condition:
Good Bad
Recommend Inspection
Good Bad N/A -Fill Cap
Good
Bad N/A - VentGood
Bad
N/A -Fill PortGood Bad N/A -SumpGood Bad N/A - Spill BucketGood Bad N/A - GaugeBadGood N/A - Gaskets
Fuel Level:______
See STI 001 Report
Diesel
Ron Palmer & Sean Dix 03/09/2021
Wilkes Barre VAMC Wilkes Barre VA Medical Center
Hank O’Hop (570) 830-7026 henry.ohop@va.gov
03/09/2021
1111 East End Blvd, Wilkes-Barre, PA 18711
Photo shows a before cleaning sample.
Tank 1 30,000UST 30,000UST
_____None _____Bulk Water _____Suspended Water _____Micro-organisms _____Sediments _____Rust _____Sludge
THIS TANK PASSES THE ASTM D975 "CLEAR &
BRIGHT" VISUAL INSPECTION.
*Lab Report will determine fuel parameters based on ASTM D975 Specifications
THIS TANK DOES NOT PASS ASTM D975 "CLEAR & BRIGHT"
VISUAL INSPECTION
*Tank cleaning is recommended based on Visual Fuel Inspection ONLY. Lab Report will determine fuel parameters based on ASTM D975 Specifications
COMMENTS:
SERVICE TECHNICIAN:______________________________________________DATE:__________________
877-252-6396 (Toll Free) 843-225-1777843-377-0412 (Fax) 4310 Amsterdam St., N. Charleston, SC 29418 www.petroleumrecoveryservices.com
VISUAL FUEL RATING:
____Pre-Clean ____Post Clean____Pre-Clean ____Post Clean
_____TBD by Lab Analysis _____Good _____Watch Closely _____Advanced Aging
FACILITY:___________________________________________________________________________________________
ADDRESS:__________________________________________________________________________________________
CONTACT:___________________________________________PHONE:______________________________________
EMAIL:_______________________________________________CELL: ________________________________________
Unit Id :_____________________ Type : ______ Capacity :___________Material:____________
Last Tank Cleaning:_________________
FUEL SAMPLE TAKEN:
_____Annual/Pre-Clean _____ Post Clean _____ None
SERVICES PERFORMED:
____ Maintenance ____ STI 001 Inspection ____ Tank Cleaning ____ Bottom Sweep ____ Pre-clean Lab Analysis ____ Post-clean Lab Analysis Fuel Treatment:
_____HydroClean
_____ILFC 1032
_____Biocide Predator 6000 _____None
ExteriorTank Condition:
Good Bad
Recommend Inspection
Good Bad N/A -Fill Cap
Good
Bad N/A - VentGood
Bad
N/A -Fill PortGood Bad N/A -SumpGood Bad N/A - Spill BucketGood Bad N/A - GaugeBadGood N/A - Gaskets
Fuel Level:______
See STI 001 Report
Diesel
Ron Palmer & Sean Dix 03/09/2021
03/09/2021
Wilkes Barre VAMC Wilkes Barre VA Medical Center
Hank O’Hop henry.ohop@va.gov
(570) 830-7026
1111 East End Blvd, Wilkes-Barre, PA 18711
Tank 2 30,000USTUST
_____None _____Bulk Water _____Suspended Water _____Micro-organisms _____Sediments _____Rust _____Sludge
THIS TANK PASSES THE ASTM D975 "CLEAR &
BRIGHT" VISUAL INSPECTION.
*Lab Report will determine fuel parameters based on ASTM D975 Specifications
THIS TANK DOES NOT PASS ASTM D975 "CLEAR & BRIGHT"
VISUAL INSPECTION
*Tank cleaning is recommended based on Visual Fuel Inspection ONLY. Lab Report will determine fuel parameters based on ASTM D975 Specifications
COMMENTS:
SERVICE TECHNICIAN:______________________________________________DATE:__________________
877-252-6396 (Toll Free) 843-225-1777843-377-0412 (Fax) 4310 Amsterdam St., N. Charleston, SC 29418 www.petroleumrecoveryservices.com
VISUAL FUEL RATING:
____Pre-Clean ____Post Clean____Pre-Clean ____Post Clean
_____TBD by Lab Analysis _____Good _____Watch Closely _____Advanced Aging
FACILITY:___________________________________________________________________________________________
ADDRESS:__________________________________________________________________________________________
CONTACT:___________________________________________PHONE:______________________________________
EMAIL:_______________________________________________CELL: ________________________________________
Unit Id :_____________________ Type : ______ Capacity :___________Material:____________
Last Tank Cleaning:_________________
FUEL SAMPLE TAKEN:
_____Annual/Pre-Clean _____ Post Clean _____ None
SERVICES PERFORMED:
____ Maintenance ____ STI 001 Inspection ____ Tank Cleaning ____ Bottom Sweep ____ Pre-clean Lab Analysis ____ Post-clean Lab Analysis Fuel Treatment:
_____HydroClean
_____ILFC 1032
_____Biocide Predator 6000 _____None
ExteriorTank Condition:
Good Bad
Recommend Inspection
Good Bad N/A -Fill Cap
Good
Bad N/A - VentGood
Bad
N/A -Fill PortGood Bad N/A -SumpGood Bad N/A - Spill BucketGood Bad N/A - GaugeBadGood N/A - Gaskets
Fuel Level:______
See STI 001 Report
Diesel
Ron Palmer & Sean Dix 03/09/2021
03/09/2021
Wilkes Barre VAMC Wilkes Barre VA Medical Center
Hank O’Hop henry.ohop@va.gov
(570) 830-7026
1111 East End Blvd, Wilkes-Barre, PA 18711
Tank 3 30,000USTUST
_____None _____Bulk Water _____Suspended Water _____Micro-organisms _____Sediments _____Rust _____Sludge
THIS TANK PASSES THE ASTM D975 "CLEAR &
BRIGHT" VISUAL INSPECTION.
*Lab Report will determine fuel parameters based on ASTM D975 Specifications
THIS TANK DOES NOT PASS ASTM D975 "CLEAR & BRIGHT"
VISUAL INSPECTION
*Tank cleaning is recommended based on Visual Fuel Inspection ONLY. Lab Report will determine fuel parameters based on ASTM D975 Specifications
COMMENTS:
SERVICE TECHNICIAN:______________________________________________DATE:__________________
877-252-6396 (Toll Free) 843-225-1777843-377-0412 (Fax) 4310 Amsterdam St., N. Charleston, SC 29418 www.petroleumrecoveryservices.com
VISUAL FUEL RATING:
____Pre-Clean ____Post Clean____Pre-Clean ____Post Clean
_____TBD by Lab Analysis _____Good _____Watch Closely _____Advanced Aging
FACILITY:___________________________________________________________________________________________
ADDRESS:__________________________________________________________________________________________
CONTACT:___________________________________________PHONE:______________________________________
EMAIL:_______________________________________________CELL: ________________________________________
Unit Id :_____________________ Type : ______ Capacity :___________Material:____________
Last Tank Cleaning:_________________
FUEL SAMPLE TAKEN:
_____Annual/Pre-Clean _____ Post Clean _____ None
SERVICES PERFORMED:
____ Maintenance ____ STI 001 Inspection ____ Tank Cleaning ____ Bottom Sweep ____ Pre-clean Lab Analysis ____ Post-clean Lab Analysis Fuel Treatment:
_____HydroClean
_____ILFC 1032
_____Biocide Predator 6000 _____None
ExteriorTank Condition:
Good Bad
Recommend Inspection
Good Bad N/A -Fill Cap
Good
Bad N/A - VentGood
Bad
N/A -Fill PortGood Bad N/A -SumpGood Bad N/A - Spill BucketGood Bad N/A - GaugeBadGood N/A - Gaskets
Fuel Level:______
See STI 001 Report
Diesel
Ron Palmer & Sean Dix 03/09/2021
03/09/2021
Wilkes Barre VAMC Wilkes Barre VA Medical Center
Hank O’Hop henry.ohop@va.gov
(570) 830-7026
1111 East End Blvd, Wilkes-Barre, PA 18711
Tank 4 30,000USTUST
| 2021 Fuel Reports - Wilkes Barre VA Medical Center - Tank 1 (Pre-Clean) |
| 2021 Fuel Reports - Wilkes Barre VA Medical Center - Tank 2 (Pre-Clean) |
| 2021 Fuel Reports - Wilkes Barre VA Medical Center - Tank 3 (Pre-Clean) |
| 2021 Fuel Reports - Wilkes Barre VA Medical Center - Tank 4 (Pre-Clean) |
File details come from the government source that posted it. Updated .