S-02 2021 Fuel Reports -Tanks 1 -4.pdf

PDF 6 MB Posted

Attached to
Z2DA--693-20-109 Replace Underground Storage Tanks Federal contract opportunity
Solicitation number
36C24421B0011
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

About this file

This document contains four underground storage tank inspection reports for the Wilkes-Barre VA Medical Center and a related federal contract opportunity notice. The inspection reports document the condition of four underground diesel fuel tanks - Tanks 1 through 4 - at the Medical Center prior to planned cleaning. Each report provides details on the tank identification and capacity, inspection date, inspecting technicians, customer point of contact, and visual observations of the fuel and tank components.

The related federal contract opportunity is a solicitation to replace the underground storage tank system at the Wilkes-Barre VA Medical Center. The scope of work includes removing and replacing the four existing underground fuel tanks, associated piping, mechanical and electrical equipment, controls and monitoring systems. Ancillary work includes earthwork, utilities, concrete and exterior improvements. The project size is estimated between $1 million to $5 million and work must be completed within 272 calendar days of the notice to proceed. The solicitation is set aside solely for service-disabled veteran-owned small businesses and questions should be directed to the specified contracting officer by April 12, 2021.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--693-20-109 Replace Underground Storage Tanks, newest first.
File Type Posted
S02 Amendment 3 Project 693-20-109 02.docx DOCX document
36C24421B0011 0003.docx DOCX document
S02 SafetyHealthDuringConstruction 18S-15-346.pdf PDF
S02 Existing Leak Detect Monit Alarm Sys Plan.pdf PDF
S02 PROJECT SITE PHOTOGRAPH 1.pdf PDF
S02 Price Sheet with Bid Deduct.docx DOCX document
36C24421B0011 0002.docx DOCX document
36C24421B0011 0001.docx DOCX document
S04 UST Sign-in.pdf PDF
P09 Replace USTs Specs.pdf PDF
P09 DWGs.pdf PDF
36C24421B0011.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Industrial Tank Maintenance Field Report

CONTAMINANTS FOUND:PARTS CONDITION:

_____None _____Bulk Water _____Suspended Water _____Micro-organisms _____Sediments _____Rust _____Sludge

THIS TANK PASSES THE ASTM D975 "CLEAR &

BRIGHT" VISUAL INSPECTION.

*Lab Report will determine fuel parameters based on ASTM D975 Specifications

THIS TANK DOES NOT PASS ASTM D975 "CLEAR & BRIGHT"

VISUAL INSPECTION

*Tank cleaning is recommended based on Visual Fuel Inspection ONLY. Lab Report will determine fuel parameters based on ASTM D975 Specifications

COMMENTS:

SERVICE TECHNICIAN:______________________________________________DATE:__________________

877-252-6396 (Toll Free) 843-225-1777843-377-0412 (Fax) 4310 Amsterdam St., N. Charleston, SC 29418 www.petroleumrecoveryservices.com

VISUAL FUEL RATING:

____Pre-Clean ____Post Clean____Pre-Clean ____Post Clean

_____TBD by Lab Analysis _____Good _____Watch Closely _____Advanced Aging _____Bad-Not Recommended _____Severe-Do Not Use

GROUP NAME: ___________________________________________ DATE:______________________ CUSTOMER:___________________________________________________SVC MARKET _____________________

FACILITY:___________________________________________________________________________________________

ADDRESS:__________________________________________________________________________________________

CONTACT:___________________________________________PHONE:______________________________________

EMAIL:_______________________________________________CELL: ________________________________________

Unit Id :_____________________ Type : ______ Capacity :___________Material:____________

Last Tank Cleaning:_________________

FUEL SAMPLE TAKEN:

_____Annual/Pre-Clean _____ Post Clean _____ None

SERVICES PERFORMED:

____ Maintenance ____ STI 001 Inspection ____ Tank Cleaning ____ Bottom Sweep ____ Pre-clean Lab Analysis ____ Post-clean Lab Analysis Fuel Treatment:

_____HydroClean

_____ILFC 1032

_____Biocide Predator 6000 _____None

ExteriorTank Condition:

Good Bad

Recommend Inspection

Good Bad N/A -Fill Cap

Good

Bad N/A - VentGood

Bad

N/A -Fill PortGood Bad N/A -SumpGood Bad N/A - Spill BucketGood Bad N/A - GaugeBadGood N/A - Gaskets

Fuel Level:______

See STI 001 Report

Diesel

Ron Palmer & Sean Dix 03/09/2021

Wilkes Barre VAMC Wilkes Barre VA Medical Center

Hank O’Hop (570) 830-7026 henry.ohop@va.gov

03/09/2021

1111 East End Blvd, Wilkes-Barre, PA 18711

Photo shows a before cleaning sample.

Tank 1 30,000UST 30,000UST

_____None _____Bulk Water _____Suspended Water _____Micro-organisms _____Sediments _____Rust _____Sludge

THIS TANK PASSES THE ASTM D975 "CLEAR &

BRIGHT" VISUAL INSPECTION.

*Lab Report will determine fuel parameters based on ASTM D975 Specifications

THIS TANK DOES NOT PASS ASTM D975 "CLEAR & BRIGHT"

VISUAL INSPECTION

*Tank cleaning is recommended based on Visual Fuel Inspection ONLY. Lab Report will determine fuel parameters based on ASTM D975 Specifications

COMMENTS:

SERVICE TECHNICIAN:______________________________________________DATE:__________________

877-252-6396 (Toll Free) 843-225-1777843-377-0412 (Fax) 4310 Amsterdam St., N. Charleston, SC 29418 www.petroleumrecoveryservices.com

VISUAL FUEL RATING:

____Pre-Clean ____Post Clean____Pre-Clean ____Post Clean

_____TBD by Lab Analysis _____Good _____Watch Closely _____Advanced Aging

FACILITY:___________________________________________________________________________________________

ADDRESS:__________________________________________________________________________________________

CONTACT:___________________________________________PHONE:______________________________________

EMAIL:_______________________________________________CELL: ________________________________________

Unit Id :_____________________ Type : ______ Capacity :___________Material:____________

Last Tank Cleaning:_________________

FUEL SAMPLE TAKEN:

_____Annual/Pre-Clean _____ Post Clean _____ None

SERVICES PERFORMED:

____ Maintenance ____ STI 001 Inspection ____ Tank Cleaning ____ Bottom Sweep ____ Pre-clean Lab Analysis ____ Post-clean Lab Analysis Fuel Treatment:

_____HydroClean

_____ILFC 1032

_____Biocide Predator 6000 _____None

ExteriorTank Condition:

Good Bad

Recommend Inspection

Good Bad N/A -Fill Cap

Good

Bad N/A - VentGood

Bad

N/A -Fill PortGood Bad N/A -SumpGood Bad N/A - Spill BucketGood Bad N/A - GaugeBadGood N/A - Gaskets

Fuel Level:______

See STI 001 Report

Diesel

Ron Palmer & Sean Dix 03/09/2021

03/09/2021

Wilkes Barre VAMC Wilkes Barre VA Medical Center

Hank O’Hop henry.ohop@va.gov

(570) 830-7026

1111 East End Blvd, Wilkes-Barre, PA 18711

Tank 2 30,000USTUST

_____None _____Bulk Water _____Suspended Water _____Micro-organisms _____Sediments _____Rust _____Sludge

THIS TANK PASSES THE ASTM D975 "CLEAR &

BRIGHT" VISUAL INSPECTION.

*Lab Report will determine fuel parameters based on ASTM D975 Specifications

THIS TANK DOES NOT PASS ASTM D975 "CLEAR & BRIGHT"

VISUAL INSPECTION

*Tank cleaning is recommended based on Visual Fuel Inspection ONLY. Lab Report will determine fuel parameters based on ASTM D975 Specifications

COMMENTS:

SERVICE TECHNICIAN:______________________________________________DATE:__________________

877-252-6396 (Toll Free) 843-225-1777843-377-0412 (Fax) 4310 Amsterdam St., N. Charleston, SC 29418 www.petroleumrecoveryservices.com

VISUAL FUEL RATING:

____Pre-Clean ____Post Clean____Pre-Clean ____Post Clean

_____TBD by Lab Analysis _____Good _____Watch Closely _____Advanced Aging

FACILITY:___________________________________________________________________________________________

ADDRESS:__________________________________________________________________________________________

CONTACT:___________________________________________PHONE:______________________________________

EMAIL:_______________________________________________CELL: ________________________________________

Unit Id :_____________________ Type : ______ Capacity :___________Material:____________

Last Tank Cleaning:_________________

FUEL SAMPLE TAKEN:

_____Annual/Pre-Clean _____ Post Clean _____ None

SERVICES PERFORMED:

____ Maintenance ____ STI 001 Inspection ____ Tank Cleaning ____ Bottom Sweep ____ Pre-clean Lab Analysis ____ Post-clean Lab Analysis Fuel Treatment:

_____HydroClean

_____ILFC 1032

_____Biocide Predator 6000 _____None

ExteriorTank Condition:

Good Bad

Recommend Inspection

Good Bad N/A -Fill Cap

Good

Bad N/A - VentGood

Bad

N/A -Fill PortGood Bad N/A -SumpGood Bad N/A - Spill BucketGood Bad N/A - GaugeBadGood N/A - Gaskets

Fuel Level:______

See STI 001 Report

Diesel

Ron Palmer & Sean Dix 03/09/2021

03/09/2021

Wilkes Barre VAMC Wilkes Barre VA Medical Center

Hank O’Hop henry.ohop@va.gov

(570) 830-7026

1111 East End Blvd, Wilkes-Barre, PA 18711

Tank 3 30,000USTUST

_____None _____Bulk Water _____Suspended Water _____Micro-organisms _____Sediments _____Rust _____Sludge

THIS TANK PASSES THE ASTM D975 "CLEAR &

BRIGHT" VISUAL INSPECTION.

*Lab Report will determine fuel parameters based on ASTM D975 Specifications

THIS TANK DOES NOT PASS ASTM D975 "CLEAR & BRIGHT"

VISUAL INSPECTION

*Tank cleaning is recommended based on Visual Fuel Inspection ONLY. Lab Report will determine fuel parameters based on ASTM D975 Specifications

COMMENTS:

SERVICE TECHNICIAN:______________________________________________DATE:__________________

877-252-6396 (Toll Free) 843-225-1777843-377-0412 (Fax) 4310 Amsterdam St., N. Charleston, SC 29418 www.petroleumrecoveryservices.com

VISUAL FUEL RATING:

____Pre-Clean ____Post Clean____Pre-Clean ____Post Clean

_____TBD by Lab Analysis _____Good _____Watch Closely _____Advanced Aging

FACILITY:___________________________________________________________________________________________

ADDRESS:__________________________________________________________________________________________

CONTACT:___________________________________________PHONE:______________________________________

EMAIL:_______________________________________________CELL: ________________________________________

Unit Id :_____________________ Type : ______ Capacity :___________Material:____________

Last Tank Cleaning:_________________

FUEL SAMPLE TAKEN:

_____Annual/Pre-Clean _____ Post Clean _____ None

SERVICES PERFORMED:

____ Maintenance ____ STI 001 Inspection ____ Tank Cleaning ____ Bottom Sweep ____ Pre-clean Lab Analysis ____ Post-clean Lab Analysis Fuel Treatment:

_____HydroClean

_____ILFC 1032

_____Biocide Predator 6000 _____None

ExteriorTank Condition:

Good Bad

Recommend Inspection

Good Bad N/A -Fill Cap

Good

Bad N/A - VentGood

Bad

N/A -Fill PortGood Bad N/A -SumpGood Bad N/A - Spill BucketGood Bad N/A - GaugeBadGood N/A - Gaskets

Fuel Level:______

See STI 001 Report

Diesel

Ron Palmer & Sean Dix 03/09/2021

03/09/2021

Wilkes Barre VAMC Wilkes Barre VA Medical Center

Hank O’Hop henry.ohop@va.gov

(570) 830-7026

1111 East End Blvd, Wilkes-Barre, PA 18711

Tank 4 30,000USTUST

2021 Fuel Reports - Wilkes Barre VA Medical Center - Tank 1 (Pre-Clean)
2021 Fuel Reports - Wilkes Barre VA Medical Center - Tank 2 (Pre-Clean)
2021 Fuel Reports - Wilkes Barre VA Medical Center - Tank 3 (Pre-Clean)
2021 Fuel Reports - Wilkes Barre VA Medical Center - Tank 4 (Pre-Clean)

File details come from the government source that posted it. Updated .