36C24419B0007-0003005.pdf

PDF 15 KB Posted

Attached to
Renovate Building 1, Ground Floor East & 3rd Floor Project No. 542-15-204
Solicitation number
36C24419B0007
Issued by

About this file

36C24419B0007 0003 089000.pdf

View the file

Other files

File Type Posted
36C24419B0007-0005011.pdf PDF
36C24419B0007-0005007.pdf PDF
36C24419B0007-0005002.pdf PDF
36C24419B0007-0005010.pdf PDF
36C24419B0007-0005000.docx DOCX document
36C24419B0007-0005008.pdf PDF
36C24419B0007-0005003.pdf PDF
36C24419B0007-0005009.pdf PDF
36C24419B0007-0005006.pdf PDF
36C24419B0007-0005005.pdf PDF
36C24419B0007-0005004.pdf PDF
36C24419B0007-0005001.pdf PDF
36C24419B0007-0004000.docx DOCX document
36C24419B0007-0003012.pdf PDF
36C24419B0007-0003000.docx DOCX document
36C24419B0007-0003008.pdf PDF
36C24419B0007-0003015.pdf PDF
36C24419B0007-0003009.pdf PDF
36C24419B0007-0003016.pdf PDF
36C24419B0007-0003013.pdf PDF
36C24419B0007-0003010.pdf PDF
36C24419B0007-0003003.pdf PDF
36C24419B0007-0003004.pdf PDF
36C24419B0007-0003002.pdf PDF
36C24419B0007-0003011.pdf PDF
36C24419B0007-0003006.pdf PDF
36C24419B0007-0003007.pdf PDF
36C24419B0007-0003001.pdf PDF
36C24419B0007-0003017.pdf PDF
36C24419B0007-0003014.pdf PDF
36C24419B0007-0002000.docx DOCX document
36C24419B0007-0002002.pdf PDF
36C24419B0007-0002001.pdf PDF
36C24419B0007-0001000.docx DOCX document
Final_Drawings_01072019.pdf PDF
Final_Specification_01072019.pdf PDF
GOVERNMENT_FURNISHED_PROPERTY.pdf PDF
36C24419B0007.docx DOCX document
36C24419B0007_1.docx DOCX document
Show all 39

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RENOVATE BUILDING 1, GROUND FLOOR EAST & 3RD FLOOR 02-19

VA MEDICAL CENTER, COATESVILLE, PA

Project# 542-15-204

542-15-204 08 90 00

SECTION 08 90 00

LOUVERS AND VENTS

PART 1 - GENERAL

1.1 DESCRIPTION

This section specifies fixed and operable wall louvers, door louvers and wall vents.

1.2 RELATED WORK

A. Louvers in steel doors: Section 08 11 13, HOLLOW METAL DOORS AND FRAMES.

1.3 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Shop Drawings:

Each type, showing material, finish, size of members, operating devices, method of assembly, and installation and anchorage details.

C. Manufacturer's Literature and Data:

Each type of louver and vent.

1.4 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B. The Master Painters Institute (MPI):

Approved Product List – September 2011

C. American Society for Testing and Materials (ASTM):

A167-99(R2009)..........Stainless and Heat-Resisting Chromium - Nickel

Steel Plate, Sheet, and Strip

A1008/A1008M-10.........Steel, Sheet, Carbon, Cold Rolled, Structural, and High Strength Low-Alloy with Improved

Formability

B209/B209M-03(R2007)....Aluminum and Aluminum Alloy, Sheet and Plate

B221-08.................Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes

B221M-07................Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire Shapes, and Tubes

D. National Association of Architectural Metal Manufacturers (NAAMM):

AMP 500-06..............Metal Finishes Manual

E. National Fire Protection Association (NFPA):

Project# 542-15-204

542-15-204 08 90 00

90A-09..................Installation of Air Conditioning and Ventilating

Systems

G. American Architectural Manufacturers Association (AAMA):

2605-11.................High Performance Organic Coatings on

Architectural Extrusions and Panels

H. Air Movement and Control Association, Inc. (AMCA):

500-L-07................Testing Louvers

PART 2 - PRODUCTS

2.1 MATERIALS

A. Aluminum, Extruded: ASTM B221/B221M.

B. Stainless Steel: ASTM A167, Type 302B.

C. Carbon Steel: ASTM A1008/A1008M.

D. Aluminum, Plate and Sheet: ASTM B209/B209M.

E. Fasteners: Fasteners for securing louvers and wall vents to adjoining construction, except as otherwise specified or shown, shall be toggle or expansion bolts, of size and type as required for each specific type of installation and service condition.

1. Where type, size, or spacing of fasteners is not shown or specified, submit shop drawings showing proposed fasteners, and method of installation.

2. Fasteners for louvers, louver frames, and wire guards shall be of stainless steel or aluminum.

F. Inorganic Zinc Primer: MPI No. 19.

2.2 EXTERIOR WALL LOUVERS

A. General:

1. Provide fixed and operable type louvers of size and design shown.

2. Heads, sills and jamb sections shall have formed caulking slots or be designed to retain caulking. Head sections shall have exterior drip lip, and sill sections an integral water stop.

3. Furnish louvers with sill extension or separate sill as shown.

4. Frame shall be mechanically fastened or welded construction with welds dressed smooth and flush.

B. Performance Characteristics:

1. Weather louvers shall have a minimum of 50 percent free area.

2. Louvers shall bear AMCA certified rating seals for air performance and water penetration ratings.

C. Aluminum Louvers:

Project# 542-15-204

542-15-204 08 90 00

1. General: Frames, blades, sills and mullions (sliding interlocking type); 2 mm (0.081-inch) thick extruded aluminum. Blades shall be or drainable type and have reinforcing bosses.

2. Louvers, fixed: Make frame sizes 13 mm (1/2-inch) smaller than openings. Single louvers frames shall not exceed 1700 mm (66 inches) wide. When openings exceed 1700 mm (66 inches), provide twin louvers separated by mullion members.

3. Louvers, operable: Louver frame opening sizes, single louver sizes and mullion requirements shall be as specified for fixed louvers.

a. Blades: Attach blades to frame with aluminum pivot pins through nylon bearings. Fasten each blade to stainless steel operation arms that are connected to minimum 3 mm (1/8-inch) thick stainless steel operating bar arranged for simultaneous operation of blades.

b. Spring/chain operation: Exposed operator activated by spring attached to operating bar and mounted on frame. Control of louver shall be by pull chain of required length to be operable from floor. Provide pulleys and brackets as required.

2.3 CLOSURE ANGLES AND CLOSURE PLATES

A. Fabricate from 2 mm (0.074-inch) thick stainless steel or aluminum.

B. Provide continuous closure angles and closure plates on inside head, jambs and sill of exterior wall louvers.

C. Secure angles and plates to louver frames with screws, and to masonry or concrete with fasteners as specified.

2.4 WIRE GUARDS

A. Provide wire guards on outside of all exterior louvers, except on exhaust air louvers.

B. Fabricate frames from 2 mm (0.081-inch) thick extruded or sheet aluminum designed to retain wire mesh.

C. Wire mesh shall be woven from not less than 1.6 mm (0.063-inch) diameter aluminum wire in 13 mm (1/2-inch) square mesh.

D. Miter corners and join by concealed corner clips or locks extending about 57 mm (2-1/4 inches) into rails and stiles. Equip wire guards over four feet in height with a mid-rail constructed as specified for frame components.

E. Fasten frames to outside of louvers with aluminum or stainless steel devices designed to allow removal and replacement without damage to the wire guard or the louver.

Project# 542-15-204

542-15-204 08 90 00

2.5 EXTERIOR DOOR LOUVERS

A. Fabricate of 1.6 mm (0.063-inch) thick extruded aluminum. Miter frames at corners and join by concealed corner brackets.

B. Equip louvers on outside with wire guards, except omit wire guards for louvers in doors located completely below enclosed areaways.

2.6 INTERIOR DOOR LOUVERS

A. Fabricate louvers for interior doors 1.6 mm (0.063-inch) thick extruded aluminum.

B. Make louvers sight-proof type with stationary blades,

2.7 WALL VENTS

A. Fabricate exterior wall vents from either 4.7 mm (0.187-inch) thick aluminum plate of 6 mm (1/4-inch) thick cast iron, perforated in diamond lattice pattern, with not over 19 mm (3/4-inch) openings.

B. Vents shall have aluminum screen frame with aluminum alloy insect screening mounted on back of vent by means of 19 mm x 5 mm (3/4-inch by

3/16-inch) top and bottom bars screwed to grille.

C. Vent Frames In Masonry: Fabricate of 45 mm x 30 mm x 5 mm (1-3/4 inch by

1-1/4 inch by 3/16-inch) steel angles bolted with 6 mm (1/4-inch) diameter expansion bolts at jambs.

2.7 AIR INTAKE VENTS

A. Fabricate exterior louvered wall ventilators for fresh air intake for air conditioning units from extruded aluminum, ASTM B221. Form with integral horizontal louvers and frame, with drip extending beyond face of wall and integral water stops.

B. Provide 0.8 m (0.032-inch) thick aluminum sleeves in cavity walls where shown.

2.8 FINISH

A. In accordance with NAAMM Metal Finishes Manual: AMP 500-505

B. Aluminum Louvers Air Intake Vents:

1. Anodized finish

a. AA-C22A42 Chemically etched medium matte, with integrally colored anodic coating, Class I Architectural, 0.7 mils thick.

NOTE: AA-C22A44 Chemically etched medium matte, with electronically deposited metallic compound, Class I

Architectural, 0.7 mils thick may be provided as an option for AA-C22A42 color anodic coating. Dyes will not be accepted.

Project# 542-15-204

542-15-204 08 90 00

C. Aluminum Wall Vents: Sand blasted satin finish.

2.9 PROTECTION

A. Provide protection for aluminum against galvanic action wherever dissimilar materials are in contact, by painting the contact surfaces of the dissimilar material with a heavy coat of bituminous paint (complete coverage), or by separating the contact surfaces with a performed synthetic rubber tape having pressure sensitive adhesive coating on one side.

B. Isolate the aluminum from plaster, concrete and masonry by coating aluminum with zinc-chromate primer.

C. Protect finished surfaces from damage during fabrication, erection, and after completion of the work. Strippable plastic coating on colored anodized.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Set work accurately, in alignment and where shown. Items shall be plumb, level, free of rack and twist, and set parallel or perpendicular as required to line and plane of surface.

B. Furnish setting drawings and instructions for installation of anchors and for the positioning of items having anchors to be built into masonry construction. Provide temporary bracing for such items until masonry is set.

C. Provide anchoring devices and fasteners as shown and as necessary for securing louvers to building construction as specified. Power actuated drive pins may be used, except for removal items and where members would be deformed or substrate damaged by their use.

D. Generally, set wall louvers in masonry walls during progress of the work. If wall louvers are not delivered to job in time for installation in prepared openings, make provision for later installation. Set in cast-in-place concrete in prepared openings.

3.2 CLEANING AND ADJUSTING

A. After installation, all exposed prefinished and plated items and all items fabricated from stainless steel and aluminum shall be cleaned as recommended by the manufacturer and protected from damage until completion of the project.

B. All movable parts, including hardware, shall be cleaned and adjusted to operate as designed without binding or deformation of the members, so as

Project# 542-15-204

542-15-204 08 90 00 to be centered in the opening of frame, and where applicable, to have all contact surfaces fit tight and even without forcing or warping the components

- - - E N D - - -